Instrument Transformer Basics. Kent Jones, P.E. Line Power Manufacturing

Similar documents
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

0.84" x 2.00" Z-TRAUQ INC. Tel.: (450) Fax: (450) z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP.

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21,

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X

Z-TRAUQ INC. Tel.: (450) Fax: (450)

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

Current Transformers

CT Application Guide for the 489 Generator Management Relay

Type SA-1 Generator Differential Relay

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Current Transformers Ratio / Polarity / Types

rpsa FIRE PROTECTION ENGINEERS

VOLTAGE REGULATOR AND PARALLEL OPERATION

Experiment NO.3 Series and parallel connection

Kuhlman Electric Corporation Volt Instrument Transformers

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

Insulation Resistance Testing of Low Voltage Cables in the Field

Ducoterra Radiant Heating Panel Installation Manual

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Beware of Simplistic Voltage Drop Calculations. By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

GenTech Practice Questions

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

Current & Instrument Transformers

User Guide. Model Insulation Tester / Megohmmeter

Manual Ranging MultiMeter

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

CURRENT TRANSFORMERS INSTALLATION GUIDE

Chapter 24. Three-Phase Voltage Generation

ELECTRICAL CIRCUITS. Electrical Circuits

T Substation Maintenance and Commissioning Test Equipment

7 FUNCTION DIGITAL MULTIMETER

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

Short Circuit Current Calculations

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

How Much Voltage Drop Is Acceptable?

ANALOG AND DIGITAL METERS ANALOG VS. DIGITAL METERS VOLTMETERS ANALOG AND DIGITAL

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY

Power over Ethernet plus Isolation requirements. David Law 3Com

What is a multimeter?

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

DIRECT CURRENT GENERATORS

Seven function digital multimeter

Transformer circuit calculations

Voltage Detection and Indication by Electric Field Measurement

Tamura Closed Loop Hall Effect Current Sensors

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

COOL-01, Cooling Fan Operation and Troubleshooting

WINDING RESISTANCE TESTING

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Understanding Insulation Resistance Testing

Using Current Transformers with the 78M661x

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Introduction. Harmonics and IEEE 519 Page 1 of 19

W03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören

How To Get A Power Line Extension

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Measurement of Power in single and 3-Phase Circuits. by : N.K.Bhati

Solid State Timers Type F

EVALUATING WAVE FILES TO DETERMINE THE SEVERITY OF THE ULTRASONIC EMISSIONS

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Fault location on power cables. Fault location on power cables

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

CHAPTER 2 EXAMPLES AND TABLES

Instrument Transformers. Technical Information and Application Guide

DC Circuits (Combination of resistances)

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

Electrical Predictive and Preventative Maintenance

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

Experiment #5, Series and Parallel Circuits, Kirchhoff s Laws

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Radiant Temperature Sensor TY7321

High Voltage Power Supplies for Analytical Instrumentation

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

User's Guide. True RMS Industrial Multimeter

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

People s Physics Book


Electrical Safety Tester Verification

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Parallel Circuits Charles Lang

Resistors. Some substances are insulators. A battery will not make detectible current flow through them.

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

AC Generators. Basic Generator

Single Phase Soft Starter

Fig. 1 Analogue Multimeter Fig.2 Digital Multimeter

Chapter 11. Inductors ISU EE. C.Y. Lee

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Transcription:

Kent Jones, P.E. Line Power Manufacturing

What is an Instrument Transformer? Current Transformer (Sometimes called CTs) It is simply a device unused to measure current by producing a smaller current that is proportional to the current that is to measured. Current transformers are always connected in series. I.e. the main current carrying conductor must pass through it.

What is an instrument transformer? Voltage Transformer (Sometimes called Potential Transformers, VTs, or PTs) It is simply a device unused to measure voltage by producing a smaller voltage that is proportional to the voltage that is to measured. Voltage transformers are always connected in parallel. I.e. the transformer must be connected phase to phase or phase to Neutral.

Understanding the terminology Reading the Label Right sizing Do s and Don ts Checking it Out Inspecting

The Rule Book: IEEE C57.13 2008 Standard Requirements for Instrument Transformers

Understanding the Terminology Turns Ratio (Also called TTR, TR, or Ratio) Current Transformer TR= Primary Current/ Secondary Current Example: What is the TR of a CT marked 600:5? TR=600/5= 120 Voltage Transformer TR= Primary Voltage/ Secondary Voltage Example: What is the TR of a PT marked 13200:120? TR=13200/120=110 Example: What is the TR of a PT marked 110:1? TR= 110/1=110

Understanding the Terminology Polarity The Primary Terminals of an instrument transformer is marked H1 and H2. The secondary side is marked X1 and X2. The rule is that whenever the AC wave shape of the H1 is high, then the X1 will also be high. Some transformers use dots in lieu of characters. In this case H1 and X1 are marked with a dot. H2 and X2 have no marking.

Polarity

Polarity- A multi-ratio

Understanding the Terminology CT Rating Factor (RF) The RF is the number of times the name plate current that can pass through the CT without over heating. Typical values are 1.0, 1.33, 1.5, 2.0, 3.0 or 4.0 Example: A CT is marked 1200:5, RF=2.0 This CT can be applied at 1200*2.0= 2400 amps continuously without over heating!

Understanding the Terminology Current Transformer Metering accuracy Expressed in a form like: 0.3 B 1.8 The first number is the accuracy class. This is usually 0.3%, 0.6%, 1.2%, or 2.4% The second number this the maximum burden (load) that you can put on the transformer and still get the accuracy percent!

Understanding the Terminology Current Transformer Metering accuracy The IEEE C57.13 standard burdens: Burden Designation Impedance (Ohms) VA @ 5 amps Power Factor Metering B0.1 0.1 2.5 0.9 B0.2 0.2 5 0.9 B0.5 0.5 12.5 0.9 B0.9 0.9 22.5 0.9 B1.8 1.8 45 0.9

Understanding the Terminology Voltage Transformer Metering accuracy The IEEE C57.13 standard burdens: Burden Burden Power Designation (VA) Factor W 12.5 0.10 X 25 0.70 M 35 0.20 Y 75 0.85 Z 200 0.85 ZZ 400 0.85

Understanding the Terminology Current Transformer Relay accuracy Expressed in a form like: C50 or T50 Where the number represents the maximum amount of voltage that the CT can produce at 20 times over current with no more than a 10% error in transformation.

Understanding the Terminology Selecting a CT Both of these CTs are rated 600:5 How do you decide which one is right for you?

Understanding the Terminology Current Transformer Relay accuracy Example: A 600:5 CT is rated C20, 0.3 B 0.9. Can it produce enough voltage to trip a relay 50 feet away if connected to the relay with #14 awg. wire? The voltage required is the sum of the voltage drop in the wire plus the relay burden (but most electronic relays have near zero burden), so lets look a the wire resistance: Wire resistance= 50* 2*.0025 ohms/ ft =.25 ohms Required voltage= I*R= 5*20*.25= 25 volts 25 volts > 20 volts

Understanding the Terminology Current Transformer Relay accuracy Example: A 600:5 CT is rated C20. Can it produce enough voltage to trip a relay 50 feet away if connected to the relay with #14 awg. wire? 25 volts > 20 volts, so this CT is to small!! How could this be fixed?

Understanding the Terminology Current Transformer Relay accuracy Aside: CT accuracy can more accurately be determined with the use on a CT Excitation curve.

Understanding the Terminology Current Transformer Metering Accuracy Example: A 600:5 CT is rated C20, 0.3 B 0.9. Can it produce enough voltage to meter 50 feet away if connected to the relay with #14 awg. Wire? The voltage required is the sum of the voltage drop in the wire plus the relay burden (but most electronic relays have near zero burden), so lets look a the wire resistance: Wire resistance= 50* 2*.0025 ohms/ ft = 0.25 ohms

Understanding the Terminology Current Transformer Metering Accuracy Example: A 600:5 CT is rated C20, 0.3 B 0.9. Can it produce enough voltage to meter 50 feet away if connected to the relay with #14 awg. Wire? Since 0.25 ohms < 0.9 ohms Even with the addition of a small meter burden, the CTs will perform fine.

Reading The Label Actual Transformer Label INSTRUMENT TRANSFOMERS,INC. CURRENT TRANSFORMER RATIO 1200:5 A. CAT 623-122MR RF 1.33 ACC CLASS C100 50-400 HZ 600V INS CLASS 10kV BIL

Reading The Label Actual Transformer Label INSTRUMENT TRANSFOMERS,INC. CURRENT TRANSFORMER RATIO 400:5 A. CAT 115-401 RF 2.0 ACC CLASS 0.3B0.9 C50 50-400 HZ 600V INS CLASS 10kV BIL

Reading The Label Actual Transformer Label INSTRUMENT TRANSFOMERS,INC. VOLTAGE TRANSFORMER PRI 2400V. 20:1 BIL 60kV 60 HZ 0.3Y 750VA @ 30 DEG C PTG3-2-60-SD0331

Reading The Label Transformer Label INSTRUMENT TRANSFOMERS,INC. VOLTAGE TRANSFORMER PRI 12000V. 100:1 BIL 110kV 60 HZ 0.3WXMYZ 1.2ZZ 1200VA @ 30 DEG C PTG5-2-110-SDXXXXXFF

Do s and Don ts Never open circuit a current transformer secondary while the primary is energized CTs are intended to be proportional current devices. Very high voltages can result from open circuiting the secondary circuit of an energized CT. Even very small primary currents can cause damage

Do s and Don ts Never short circuit the secondary of an energized VT VTs are intended to be used as proportional voltage devices. Damaging current will result from short circuiting the secondary circuit of an energized VT.

Checking Instrument Transformers Is my transformer good? The Rule Book: ANSI/ NETA MTS- STANDARD FOR MAINTENANCE TESTING SPECIFICATIONS

Checking Instrument Transformers Is my transformer good? Test number #1- Physical Observation Sight Do you see any damage? Burn marks Cracks Blown fuse (PT only) Sound Does it rattle? Smell If you suspect a recent event, sniff the CT or PT. An internally shorted transformer can produce a lot of heat that can burn insulation. And, by all means, do not re-energize a transformer that does not pass the sniff test- even if it tests good! Caution: Don t sniff test PVC dipped CTs

Checking Instrument Transformers Is my PT good? Test #2 Continuity test to look for broken internal wires Measure the resistance from X1 to X2 and H1 to H2. You should always see some resistance, but the H1 to H2 might be high on medium voltage transformers. The resistance from X1 to X2 should always be less than H1 to H2! If you can t measure resistance the PT is bad, don t do any more testing!

Checking Instrument Transformers Is my CT good? Test #2 Continuity test to look for broken internal wires Measure the resistance from X1 to X2. Make sure all leads and shorting wires are removed form the terminals. If resistance can t be measured or it shows very high, the CT is bad. All 5 amp secondary CTs have a low secondary resistance. The exact value can be found on the manufactures specification sheet. If you can t measure resistance the CT is bad, don t do any more testing!

Checking Instrument Transformers Is my CT good? Test #3 (the ratio test) Buy a small bench top Variac (A variable voltage output transformer) and a small 120:12v transformer. Connect the transformer so that you have a variable 0-12 volt power source. 1. Connect the variac leads to the X1 and X2 terminals of the CT and very slowly raise the voltage Rules of thumb: Apply no more than ½ the relay class on a relay class CT I.e. if the relay class is C50, then apply no more than 50/2=25 volts Apply no more than 5 * burden class on a metering CT I.e. if the burden is B0.5, then apply no more than 0.5*5=2.5volt 2. Loop a wire through the CT window one or more times and measure the voltage. The voltage measured should be: V(X1 to X2) * # of loops / Turns ratio

Checking Instrument Transformers Is my PT good? Test #3 (Ratio test) 1. Remove all wires from the PT terminals. 2. Connect your variac across the H1 and H2 terminals. STOP: NEVER connect the variac across the X1 to X2 terminals. Very high voltage may be present across H1 and H2 if this is done! 3. Slowly raise the voltage on the variac to about 50 volts maximum. You don t need more! 4. Measure voltage across H1 to H2, and then across X1 to X2. 5. V(H1 to H2)/ V(X1 to X2) should equal the Transformer Turns Ratio

Checking Instrument Transformers Is my Instrument Transformer good? Test #4 (the insulation test) Perform insulation resistance testing per NETA/ ANSI MTS Insulation resistance test levels and test values are recorded in Table 100.1 of the NETA/ANSI MTS standard. For example 1000v rated equipment should be tested with 1000VDC and 100 Megohms should be the lowest acceptable resistance.

Inspecting Instrument Transformers In theory, instrument transformers require little service, but. Keep them Clean Wipe them clean when you inspect them with a clean dry cloth. If you have transformers on medium voltage systems, look for treeing. (Treeing is carbon tracks that forms on the surface of the transformer due to partial discharge and/or corona.) Clean it off!! The tracks will only grow larger, and can eventually break down.

Questions?