Table 1 (All Classes in 1 Table) This revision combines the Delta and the Wye-Connected Tables from Revision 8 into the new Revision 9

Similar documents
Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Unified requirements for systems with voltages above 1 kv up to 15 kv

DS 600. A contact free flux gate based current measurement sensor 600A rms

INTERNATIONAL STANDARD

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

0.84" x 2.00" Z-TRAUQ INC. Tel.: (450) Fax: (450) z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP.

SANS : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation

Transformer Design & Design Parameters

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

THE VALUE OF POWER FACTOR TESTING

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

SURGE PROTECTIVE DEVICES

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

Medium voltage insulator

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

Presentation of the France Transfo factories

MIT510/2, MIT520/2 and MIT1020/2

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

ACCURACY OF POTENTIALTRANSFORMERS

PC software icos Advanced

HV glass suspension insulator U70BS and U70BL type Ball and socket type Standard profile

Three-phase AC circuits

ENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613

7CURRENT TRANSFORMERS

Testing of Power Transformers. Routine tests, Type tests and Special tests

Transformer Bushings for GIS

Medium-voltage Transformers

HV reed relays K-551H, K-552H K-553H, K-554H, K-555H, K-556H form A contact (normally open) for PCBs

The standards mentioned in this document

Shunt Capacitor Bank Fundamentals and Protection

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

AMIS. Automated Metering and Information System. Integration of meters from other manufacturers

Definition AC Power Distribution

Step Voltage Regulators

Z-TRAUQ INC. Tel.: (450) Fax: (450)

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

CATALOGUE SURGE PROTECTION LOW VOLTAGE

Earth Fault Detection Basics in Theory

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

English version. Voltage characteristics of electricity supplied by public distribution systems

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

Relés e Contatores de Estado Sólido SIRIUS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Pilot-wire differential relay for lines with two or more terminals

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

TRANSRADIO SenderSysteme Berlin

Checking Capacitor Banks for Failed Capacitors

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Hyperlinks are Inactive

TRANSFORMER: THREE PHASE

EVALUATION OF CURRENTS AND CHARGE IN SURGE PROTECTIVE DEVICES IN LOW-VOLTAGE DISTRIBUTION NETWORKS DUE TO DIRECT LIGHTNING STRIKES

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Redline. Comfort functions. Surge Arresters. SurgeGuard. Functions. Applications. Standards. Features. Marking. plug-in

The following table shows approximate percentage wise the

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

INTERNATIONAL STANDARD

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Medium-voltage transformers

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Unit 33 Three-Phase Motors

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G

Power Meter Series 700

CONTENTS.

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Pluggable interface relays CR-P Pcb relays

Safety automation solutions

WINDING RESISTANCE TESTING

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Power Transformers Small, Medium & Large

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Low Voltage Products. Switches Automatic Transfer Switches

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

This section applies to the design and installation of transformers.

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

8. TESTING POWER TRANSFORMERS

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

Good EMC Design Principles: cable routing

Chapter 14: Inductor design

SECTION SUBSTATION TRANSFORMERS

Automated test systems for distribution transformers Part II. Detailed analysis of the test system features EVENTS ABSTRACT KEYWORDS

Service Power Technologies. Retrofitting A future-oriented concept in lifecycle management

Multi-tap Transformers

T Substation Maintenance and Commissioning Test Equipment

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

Transformers. Special transformers Reactors products

GUIDE FOR TESTING POWER TRANSFORMERS

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

Understanding the Alternator

T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

Intelligent maintenance decisions with ABB TrafoAssetManagement TM proactive services

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Transcription:

Max in kv Table 1 (All Classes in 1 Table) From C57.12.00 Table 7 in kv Nominal 2V (V, in kv) Delta Gr Y Imp Y 3 Induced Test, in kv Dist. & Class I Class 2, >72.5 kv Basic Insulation Level, in kv Neutral BIL, in kv One Hour Enhanced 7200 cy Min. Alternates GrY Impedance Distribution and Class I Power Transformers, =69 kv Nominal 1.5 1.2 10 10 10 1.4 30 45 30 30 3.5 2.5 15 15 15 2.9 45 60 45 45 6.9 5 19 19 19 5.8 60 75 60 60 11 8.7 26 26 26 10 75 95 75 75 17.2 15 34 26 26 17.3 95 110 125 75 75 26 25 50 26 34 28.9 125 150 75 95 38 34.5 70 26 50 39.8 150 200 75 125 72.5 69 140 34 95 79.7 250 350 400 95 200 Class II Power Transformers, > 72.5 kv Nominal 120 115 173 34* 95* N/A 105 120 350 450 550 110 250 145 138 207 34* 95* N/A 125 145 450 550 650 110 250 166 161 242 34* 95* N/A 145 170 550 650 750 850 110 350* 244 230 345 34* 95* N/A 210 240 750 825 900 110 350* 362 345 518 34* 95* N/A 315 360 1050 1175 110* 350* 550 500 N/A 34* 95* N/A 475 550 1425 1550 1675 110* 350* 765 735 N/A 34* 95* N/A 750 850 1950 2050 110* 350* 800 765 N/A 34* 95* N/A 795 885 1950 2050 110* 350* 1.* Insulation level to conform with service requirements but never less than the level shown. 2. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 3. Front-of-wave Impulse levels must be specified prior to design of the transformer. 4. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 5. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage 6. All test levels are line to ground. 7. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for 8. Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal 9. Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal 10. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 11. s greater than Maximum shall use the next higher voltage class test levels. 12. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 13. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kv and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. 14. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals.

This example shows Table 1 split into two tables by transformer class: Table 1a (Distribution and Class 1) Max (kv) Nominal From C57.12.00 Table 7 (kv) (kv) Delta Gr Y Imp Y Induced Test in kv 2V Distribution Transformers 3 Basic Insulation Level (kv) Neutral BIL (kv) Min. Alternates GrY Impedance 1.5 1.2 10 10 10 1.4 30 30 30 3.5 2.5 15 15 15 2.9 45 45 45 6.9 5 19 19 19 5.8 60 60 60 11 8.7 26 26 26 10 75 75 75 17.2 15 34 26 26 17.3 95 75 75 26 25 50 26 34 28.9 125 150 75 95 38 34.5 70 26 50 39.8 125 150 200 75 125 Class I Power Transformers, =69 kv Nominal 1.5 1.2 10 10 10 1.4 30 45 30 30 3.5 2.5 15 15 15 2.9 45 60 45 45 6.9 5 19 19 19 5.8 60 75 60 60 11 8.7 26 26 26 10 75 95 75 75 17.2 15 34 26 26 17.3 95 110 75 75 26 25 50 26 34 28.9 150 75 95 38 34.5 70 26 50 39.8 200 75 125 1.* Insulation level to conform with service requirements but never less than the level shown. 15. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 16. Front-of-wave Impulse levels must be specified prior to design of the transformer. 17. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 18. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage 19. All test levels are line to ground. 20. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for 21. Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal 22. Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal 23. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 24. s greater than Maximum shall use the next higher voltage class test levels. 25. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 26. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kv and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. 27. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals.

Max (kv) Table 1b (Class II Transformers) Induced Test (kv) From C57.12.00 Table 7 (kv) Class 1 Class 2, >72.5 kv Basic Insulation Level (kv) Neutral BIL (kv) Nominal (kv) Delta Gr Y Imp Y =69 kv One Hour Class II Power Transformers, > 72.5 kv Nominal Enhanced 7200 cy. Min Alternates GrY Impedance 120 115 173 34* 95* N/A 105 120 350 450 550 110 250 145 138 207 34* 95* N/A 125 145 450 550 650 110 250 166 161 242 34* 95* N/A 145 170 550 650 750 850 110 350* 244 230 345 34* 95* N/A 210 240 750 825 900 110 350* 362 345 518 34* 95* N/A 315 360 1050 1175 110* 350* 550 500 N/A 34* 95* N/A 475 550 1425 1550 1675 110* 350* 765 735 N/A 34* 95* N/A 750 850 1950 2050 110* 350* 800 765 N/A 34* 95* N/A 795 885 1950 2050 110* 350* 1.* Insulation level to conform with service requirements but never less than the level shown. 2. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 3. Front-of-wave Impulse levels must be specified prior to design of the transformer. 4. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 5. The Insulation levels for Class 1 and Class 2 transformers shall be selected from this table for both the high-voltage and lowvoltage windings. 6. All test levels are line to ground. 7. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for 8. Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal 9. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 10. s greater than Maximum shall use the next higher voltage class test levels. 11. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 12. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals.

Table 2 High Frequency Test Tables BIL Chopped Wave Front Of Wave Switching Impulse 1.2 X 50 µ-sec 1.1*BIL 30 33 1.0 45 50 1.5 60 66 1.5 75 83 1.5 95 105 1.8 165 0.5 110 120 2.0 195 0.5 125 138 2.3 220 0.5 150 165 3.0 260 0.5 200 220 3.0 345 0.5 250 275 3.0 435 0.5 0.83*BIL 350 385 3.0 580 0.58 280 450 495 3.0 N/A unless specified 375 550 605 3.0 N/A unless specified 460 650 715 3.0 N/A unless specified 540 750 825 3.0 N/A unless specified 620 825 900 3.0 N/A unless specified 685 900 990 3.0 N/A unless specified 745 1050 1155 3.0 N/A unless specified 870 1175 1290 3.0 N/A unless specified 975 1300 1430 3.0 N/A unless specified 1080 1425 1570 3.0 N/A unless specified 1180 1550 1705 3.0 N/A unless specified 1290 1675 1845 3.0 N/A unless specified 1390 1800 1980 3.0 N/A unless specified 1550 1950 2145 3.0 N/A unless specified 1620 2050 2255 3.0 N/A unless specified 1700 1. Front-of-Wave tests must be specified prior to the design of the transformer. 2. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 3. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage 4. Phase to ground specified Switching impulse levels are not always possible for low voltage windings.

Table 1b Max (V) Nominal From C57.12.00 Induced Test Table 7 2V Basic Insulation Level Neutral BIL (V) Delta Gr Y Imp Y 3 Min. Alternates GrY Impedance Distribution Transformers 1.5 1.2 10 10 10 1.4 30 30 30 3.5 2.5 15 15 15 2.9 45 45 45 6.9 5 19 19 19 5.8 60 60 60 11 8.7 26 26 26 10 75 75 75 17.2 15 34 26 26 17.3 95 75 75 26 25 50 26 34 28.9 125 150 75 95 38 34.5 70 26 50 39.8 125 150 200 75 125 Class I Power Transformers, < or = 69 kv Nominal 1.5 1.2 10 10 10 1.4 30 45 30 30 3.5 2.5 15 15 15 2.9 45 60 45 45 6.9 5 19 19 19 5.8 60 75 60 60 11 8.7 26 26 26 10 75 95 75 75 17.2 15 34 26 26 17.3 95 110 75 75 26 25 50 26 34 28.9 150 75 95 38 34.5 70 26 50 39.8 200 75 125 1. Insulation level to conform with service requirements but never less than the level shown. 13. The BIL serves both as a test level for the full wave lightning impulse tests and as the primary identity of a set of coordinated insulation levels. 14. Front-of-wave Impulse levels must be specified prior to design of the transformer. 15. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 16. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage 17. All test levels are line to ground. 18. The applied test levels are not applicable to wye-connected windings unless they have been specified to be suitable for 19. Phase-to-Phase Induced test levels for 3 phase Distribution Transformers shall be not less than 2.0 times nominal 20. Phase-to-Phase Induced test levels for 3 phase Class I Power Transformers shall be not less than 1.65 times nominal 21. When specified, Y-Y connected transformers using a common solidly grounded neutral may use a neutral bushing sellected in accordance with the requirements of the low voltage winding. 22. s greater than Maximum shall use the next higher voltage class test levels. 23. Neutral BIL shall be a minimum of 2.5 times neutral applied potential test level. 24. Single phase distribution and power transformers and regulating transformers for voltage ratings between terminals of 8.7 kv and below are designed for both Y and Delta connection so that a single line of transformers serves for the higher than needed for their voltage rating. 25. For Series windings in transformers, such as regulating transformers, the test values to ground shall be determined by the BIL of the series windings rather than the rated voltage between terminals.

Table 2 High Frequency Test Tables BIL Chopped Wave Front Of Wave Switching Impulse 1.2 X 50 µ-sec 1.1*BIL 30 33 1.0 45 50 1.5 60 66 1.5 75 83 1.5 95 105 1.8 165 0.5 110 120 2.0 195 0.5 125 138 2.3 220 0.5 150 165 3.0 260 0.5 200 220 3.0 345 0.5 250 275 3.0 435 0.5 0.83*BIL 350 385 3.0 580 0.58 280 450 495 3.0 N/A unless specified 375 550 605 3.0 N/A unless specified 460 650 715 3.0 N/A unless specified 540 750 825 3.0 N/A unless specified 620 825 900 3.0 N/A unless specified 685 900 990 3.0 N/A unless specified 745 1050 1155 3.0 N/A unless specified 870 1175 1290 3.0 N/A unless specified 975 1300 1430 3.0 N/A unless specified 1080 1425 1570 3.0 N/A unless specified 1180 1550 1705 3.0 N/A unless specified 1290 1675 1845 3.0 N/A unless specified 1390 1950 2145 3.0 N/A unless specified 1550 1950 2145 3.0 N/A unless specified 1620 2050 2255 3.0 N/A unless specified 1700 1. Front-of-Wave tests must be specified prior to the design of the transformer. 5. Front-of-wave tests are not recommended on low voltage or tertiary windings that are not exposed to lightning. 6. The Insulation levels for Distribution, Class 1 and Class 2 transformers shall be selected from this table for both the highvoltage 7. Phase to ground specified Switching impulse levels are not always possible for low voltage windings.