Chapter 2. Chapter 2 provides information to help you:

Similar documents
Using installed Fieldbus Wiring to carry Ethernet Communications

Configuring SMC-Flex for Communications over Remote I/O Network using 20-COMM-R Card This document is intended to be used for reference purposes only.

Allen-Bradley/Rockwell

FIELDPOINT BUS EXTENDER CABLE

SECTION PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL Summary. A. Section Includes:

LDG DTS-4/4R Desktop Coaxial Switch / Remote

BACnet Automation Interface Module (Network Version)

Contents. Document information

Model 201 Wiegand Touchpad Reader Installation Guide

Series Six Plus Programmable Controller

Backup Scanner Module

EMBEDDED ACCESS CONTROL Hardware Installation Guide

Switch board datasheet EB

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

How to Install a Motherboard

KVM Cable Length Best Practices Guide

Rack & Stack 123 TM. Enterprise Education Government Telecommunications Service Providers Tel:

HSG Engineering Tech Bulletin

Operation and Installation Manual

Fire Pump Controllers Remote Alarm Panels

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference :

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

EDI Distributor Control Interface Wiring and Setup Instructions

ALARMS-xx. Remote Alarm Unit Setup Guide RESET ALL

RACEAIR REMOTE PAGER SYSTEM

HP UPS R1500 Generation 3

TC Grounding and Bonding for Telecommunications Systems

MACHINEMATE. CNC SYSTEM Hardware SPECIFICATION

Express5800/120Ed. Rack Mount Kit Installation Procedures PN:

Extender for HDMI Long Range. GTV-HDMI-CAT5LR. User Manual

Research RF Sputtering Packages

User manual Compact Web PLC WP240 series IEC-line

LocoNet, the Digitrax Difference

PART 1 - INTRODUCTION...

UniStream CPU-for-Panel

BLUE RIBBON CORP. BC001 Birdcage Installation Manual

Advantium 2 Plus Alarm

Attention statements help you to: identify a hazard avoid the hazard recognize the consequences

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

FLEX I/O High-Density Analog Modules

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

3500/93 System Display

FLEX I/O Isolated Analog Modules

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Cisco Model EPC2100 EuroDOCSIS 2.0 Cable Modem

Fire Fighter Phone System Installation Instructions

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Modular I/O System Analog and Digital Interface Modules

TELIKOU Intercom System. TM-200 Main Station. Instruction Manual

Job Aid Pre-Installation Information S8500 Media Server

Rack mounted telephone- and leased line modem for industrial applications

Setting Up and Testing the MAX Hardware

Model 5511 Filler Controller User s Manual Version 1.1 October 2011

Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies.

LDG DTS-6/6R Desktop Coaxial Switch / Remote

Contents. : AEOS Blue cabling and technical aspects. NEDAP N.V. IDEAS Information Bulletin No: H032. Date : 12 January 2016

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Data Highway/Data Highway Plus/ Data Highway II/Data Highway 485 Cable Installation Manual

RS232C < - > RS485 CONVERTER S MANUAL. Model: LD15U. Phone: / 97 / 98 (M)

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

Installation instructions for Series NRX INCOM communications adapter module

ECR Shelf System Installation Guide Centralized Rack Mount Call Recording

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

8 Channel Status Input Panel model SIP-8

This Datasheet for the IC697CPM790. GMR Redundancy CPU, 486, 2K Triplex (voted) I/O.

IBS IP I/O Gateway. Data Sheet INTERBUS-S. Coupling Module for Two InterBus-S Lines

Access control designed simply for you

Application/Connection Examples

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

Raritan AMS Series Intelligent Electronic Asset Management

Access Server Rack Cabinet Compatibility Guide

Wireless LAN Outdoor Bridge Solution

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY

THE INPUT/OUTPUT SYSTEM. Key Points

Provides one channel for Ethernet over existing

Series LC6D/LC6C. To power supply PLC. LC6C dedicated teaching box P.971. Options P.973

USB to RS-422/485 Serial Adapter

PanelView Standard Operator Terminals

Model CFA-24 Transparent Cable Farm Automation Switch

Provides one channel for Ethernet over existing

FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc rd Street San Francisco, CA Phone:

Text String Activation

PTU Series Transducer Digital Display Indicator User s Manual

BUILDING INSTRUCTIONS

Unidirectional Transmitter/ Receiver Units Introduction

Allen-Bradley/Rockwell

Telebyte 209 Short Haul Modem

INSTALLATION INSTRUCTIONS

PCAN-MicroMod Evaluation Test and Development Environment for the PCAN-MicroMod. User Manual. Document version ( )

Cisco Model DPC3010 DOCSIS 3.0 8x4 Cable Modem

Product Specifications

Specifying a Variable Frequency Drive s

L5354 ControlNet Communications Interface

Allen-Bradley HP AC Line Filter Kit

NSI DIGITAL DIMMING SYSTEM DDS 9800 DIMMER PACKS

Electronic Control Devices The European Product Catalogue 2007

40.3. Control Relays and Timers

Transcription:

Chapter 2 Chapter 2 provides information to help you: set the module configuration switches mount the remote I/O module connect the remote I/O cable connect the termination resistor connect the SCANport link connect the power supply Read this chapter completely before you attempt to install or configure your remote I/O communications module. Double check all connections and option selections before you apply power. Important: Switch selections take effect only on power up. If you change selections after power is applied, cycle the power to use the new settings. This publication describes switches as being either on or off. If the switch assembly has the word OPEN printed on it, the word OPEN corresponds to OFF (O). When you change the adapter board configurations, keep in mind the addressing conventions of the type of processor that you are using. In all cases, each remote I/O device must have a unique address that the processor can recognize. Important: This adapter is not compatible with complementary I/O configurations because the adapter uses both output and input image words for proper drive control.! ATTENTION: When you make changes to the switch settings, use a blunt, pointed instrument such as a ball point pen. Do not use a pencil because the lead (graphite) of the pencil may damage the switch assembly. ATTENTION: Failure to check connections and switch settings for compatibility with your application when configuring the communications module, could result in personal injury and/or equipment damage due to unintended or undesirable operation of the drive or process equipment.

2 2 Set switch SW3 first. The settings on this switch determine how the SCANport device uses the data contained in the programmable controller I/O image table. SW3 also establishes the minimum rack size that this communications module requires. The switches are labeled in the same orientation as they appear on the board. Table 2.A, SW3 Image Table Map, and Figure 2.2, SW3 Flowchart, are included to help you set the DIP switches properly. It may also be helpful to color in the final switch settings in Figure 2.1 as a visual record of your SW3 settings. Chapter 3 contains several examples of how to fill in the worksheet and set these DIP switches. J1 ➀➁ ➀ ➁

2 3 ➀ ➀ How to use Table 2.A: 1. Use Figure 2.2 to set DIP switch SW3 and fill out Table 2.A. 2. Use minimum rack size shown in Table 2.A to set DIP switch SW2-1 and SW2-2.

2 4

2 5 Switch SW2 determines Rack Size, Last State, Rack Fault, and Bit Rate Selections as shown in Figure 2.3. The switches are labeled in the same orientation as they appear on the board. J1 ➂ ➄ ➅ ➄ ➅ ➃ ➁ ➀ ➄ ➅ ➀ ➁ ➂ ➃

2 6

2 7 Switch SW1 controls starting quarter and rack address options as shown in Figure 2 7. Note: When using a PLC-2 family processor, you need to offset the value of the rack number by one. The PLC-2 cannot have a remote I/O rack numbered zero. Therefore, add a value of one to the Rack No value in Table 2.B when writing your PLC code.

2 8

2 9 The remote I/O communications module can be provided in three mounting configurations: Open Style board factory installed in a drive (not available for all drives) Open Style board as a separate kit Enclosed style for panel mount or DIN rail mount This section provides mounting information for the Enclosed style and the Open style kit. J1 Install the board with the component side facing you.

2 10 J1 Install the board with the component side facing you.

2 11 ÉÉ ÉÉ ÉÉ ÉÉ DIN RAIL ÍÍÍÍ ÍÍÍÍ ÍÍÍÍ ÍÍÍÍ Note: The enclosure requires clearance at the top and bottom for proper cooling. Additional space will be required if access to DIP switches is desired without having to remove the device. All dimensions in millimeters and (inches)

2 12 You must connect remote I/O communications module cables as shown in the example in Figure 2.11. Refer to Table 2.C for cable guidelines. 1 2..

2 13 Twinaxial cable used for remote I/O (RIO) and Data Highway+ (DH+ TM ) communications represents a communications transmission line in which certain characteristics exist. The following are some general guidelines that must be adhered to in order to obtain the best results. Cable Type Only 1770-CD Belden #9463 is approved for RIO and DH+ installations. All other cable types or manufacturers, no matter how similar, are untested. Using other cable types is strictly at your own risk. Important: The transmission rate determines the maximum cable length. Connections Connect all three conductors, blue, clear, and shield, at each wiring point. No additional ground connections should be made to the shield. Important: DO NOT use star type connections. Only two cables may be connected at any wiring point on a series connection application. These are general rules and certain deviations may be warranted because diverse installation and environmental concerns could change the requirements.

2 14 You must terminate both ends of a remote I/O link to ensure proper operation. This termination is required only at the ends of the physical cable. Each remote I/O network should have exactly two termination resistors installed. Use Table 2.D and Figure 2.12 and Figure 2.13 to determine the proper termination for your particular link. Termination resistor R3 is located on the board, and the J2 jumper selects this resistor. Important: The following products (Table 2.E) cannot be on a link using 82-Ohm termination resistors.

2 15 ±

2 16 SCANport cables are available in either Male to Male or Male to Female configuration. You can connect cables of up to 10 meters (33 feet) from the master to the SCANport device (A in Figure 2.14). If you use a port expander as shown in Figure 2.14, subtract the cable length from the master to the port expander from the cable length used to connect the device to the expander (B1+ C = maximum 10 meters). An Allen-Bradley SCANport link cable is used to make the connection between the communications module and the drive (Figure 2.14). 2 3 4 5 Important: The maximum cable distance between any two master devices cannot exceed 10 meters (33 feet) of cable. For example, B1 + C = maximum of 10 meters or B1 + B2 = maximum of 10 meters. Refer to the product manual for connection information. On larger horsepower 1336 PLUS and 1336 FORCE drives with an open remote I/O module mounted in the drive, you do not need a separate SCANport cable connection.

2 17 An Allen-Bradley SCANport cable is used to connect the communications adapter and an SMP 3. See the cable requirements on page 2 16 for details on cable length. An Allen-Bradley Bulletin 1202 SCANport cable is required to connect the communications adapter and the SMC Dialog Plus controller.

2 18 The Enclosed remote I/O is powered from a separate 24V dc or 115V ac power supply (Figure 2.17). With the open style remote I/O board mounted in the drive, no separate power supply connections are required.