Psychrometrics James F. Thompson

Similar documents
HVAC Made Easy - Overview of Psychrometrics

How do I measure the amount of water vapor in the air?

UNIT 6a TEST REVIEW. 1. A weather instrument is shown below.

How To Understand And Understand Psychrometrics

Temperature and Humidity

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Akton Psychrometric Chart Tutorial and Examples

Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside.

CONDENSATION. Section Break (Next Page)

THE PSYCHROMETRIC CHART AND ITS USE

THE HUMIDITY/MOISTURE HANDBOOK

Greenhouse Cooling. Why is Cooling Needed?

Environment-Laboratory Ambient Conditions

ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE

Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2

Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives

Fog and Cloud Development. Bows and Flows of Angel Hair

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Page 1. Weather Unit Exam Pre-Test Questions

Humidity, Condensation, Clouds, and Fog. Water in the Atmosphere

In this experiment, we will use three properties to identify a liquid substance: solubility, density and boiling point..

THIRD GRADE WEATHER 1 WEEK LESSON PLANS AND ACTIVITIES

Name: Date: LAB: Dew Point and Cloud Formation Adapted from Exploration in Earth Science, The Physical Setting, United Publishing Company, Inc.

Wet Bulb Temperature and Its Impact on Building Performance

Physical Properties of a Pure Substance, Water

PHYSICAL SEPARATION TECHNIQUES. Introduction

Soil Suction. Total Suction

Humidity the story for teachers

Determination of Moisture Content

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

2. The map below shows high-pressure and low-pressure weather systems in the United States.

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Simplifying Humidity Measurement with Single-Chip Relative Humidity and Temperature Sensor ICs

Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010

Principles of Frost Protection (Short version Quick Answer FP005)

MOLECULAR WEIGHT BY BOILING POINT ELEVATION

Evaporative Cooling. Terminology. Date: February 28, Concepts

The Rotronic Humidity Handbook

ASHRAE Climatic Data Activities. Dru Crawley Didier Thevenard

The HVAC Process: Changing the Properties of Air

Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2

Relative Humidity Sensors, Transmitters and Calibration Products Relative Humidity Measurement and Calibration

SECOND GRADE 1 WEEK LESSON PLANS AND ACTIVITIES

ULT Freezer Performance Testing Emerson Design Services Network Project #

UNIT IV--TEMPERATURE-MOISTURE RELATIONSHIP

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

A beginner s guide to humidity measurement

How is Dew Point Measured Reliably?

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH%

Characteristics of Evaporators

Environmental Data Center Management and Monitoring

Energy Recovery Ventilation Equipment

Distillation Experiment

Evaporative Cooling System for Aquacultural Production 1

1. The Determination of Boiling Point

HAY MOISTURE & WEATHER:

Evolution of the Thermometer

To measure the solubility of a salt in water over a range of temperatures and to construct a graph representing the salt solubility.

Postharvest Sample Questions

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

AIR CONDITIONING TECHNOLOGY

Evaporative Cooling for Residential and Light-Commercial

Principles of Frost Protection (Long version Quick Answer FP005)

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

FROST / FREEZE PROTECTION

Psychrometrics - The Study Of Air-Water Vapor Mixtures

CONDENSATION - THE BASICS

Laboratory Exercise: Calibration of a Thermometer

Performance Rating of Room Fan- Coils

Infrared Thermometer Calibration A Complete Guide

Name: OBJECTIVES Correctly define: WEATHER BASICS: STATION MODELS: MOISTURE: PRESSURE AND WIND: Weather

Principles of Rice Drying How does rice dry?

Refrigeration Manual. Part 3 - The Refrigeration Load

By Tom Brooke PE, CEM

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

Thermal environments. Tel

(Walter Glogowski, Chaz Shapiro & Reid Sherman) INTRODUCTION

Natatorium Building Enclosure Deterioration Due to Moisture Migration

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Refrigeration and Air Conditioning with Psychrometry

ph Measurement and Control

J3.4 DESIGN TEMPERATURES FOR HEATING AND COOLING APPLICATIONS IN NORTHERN COLORADO -- AN UPDATE

Accurate Air Flow Measurement in Electronics Cooling

Case study Realistic and best uncertainties with humidity instruments

Partner: Jack 17 November Determination of the Molar Mass of Volatile Liquids

Super Heated Steam Drying of Wood on Industrial Scale

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

Measurement and Calibration

ES 106 Laboratory # 2 HEAT AND TEMPERATURE

The Development of a Frost-Less Heat Pump

User's Guide. Digital Psychrometer. Model RH390. F C WBT Dew Point MAX MIN

Partnerships Implementing Engineering Education Worcester Polytechnic Institute Worcester Public Schools

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Optimum Solar Orientation: Miami, Florida

Chapter 18 Temperature, Heat, and the First Law of Thermodynamics. Problems: 8, 11, 13, 17, 21, 27, 29, 37, 39, 41, 47, 51, 57

WEATHER THEORY Temperature, Pressure And Moisture

Why and How we Use Capacity Control

We will study the temperature-pressure diagram of nitrogen, in particular the triple point.

Professional Thermohygrometer

Transcription:

Psychrometrics James F. Thompson Psychrometrics is the measurement of the heat and water vapor properties of air. Commonly used psychrometric variables are temperature, relative humidity, dew-point temperature, and wet-bulb temperature. Psychrometric Chart The psychrometric chart describes the relationships between these variables. Figure 1 is a psychrometric chart in customary units which describes the relationship between the variables. Temperature, sometimes called dry-bulb temperature after the unwetted thermometer in a psychrometer, is the horizontal axis of the chart. The vertical axis is the moisture content of the air, called humidity ratio (sometimes called mixing ratio or absolute humidity). The units of humidity ratio are mass of water vapor per mass of dry air. Under typical California conditions, the humidity ratio of outside air varies between 0.004 and 0.015 lb/lb. Even though water vapor represents only 0.4 to 1.5 percent of the weight of the air, this small amount of water vapor plays a very significant role in rice drying and storage. The maximum amount of water vapor that air can hold at a specific temperature is given by the leftmost, upward-curved line in the psychrometric chart. Notice that air holds more water vapor at increasing temperatures. As a rule of thumb, the maximum amount of water that the air can hold doubles for every 20 F increase in temperature. This line is also called the 100 percent relative humidity line. A corresponding 50 percent relative humidity line is approximated by the points that represent the humidity ratio when the air contains one-half of its maximum water content. The other relative humidity lines are formed in a similar manner. Notice that relative humidity without some other psychrometric variable does not determine a specific air condition on the chart. For instance, 80 percent relative humidity at 32 F has much lower humidity ratio than air with 80 percent relative humidity at 68 F. If a mass of air is cooled without changing its moisture content, it loses capacity to hold moisture. If cooled enough, it becomes saturated (has 100 percent relative humidity) and if cooled further, begins to lose water in the form of dew or frost. The temperature at which condensation begins to form is called the dew point temperature if it is above 32 F or the frost point temperature if it is below 32 F. Another commonly used psychrometric variable is wet-bulb temperature. On

the chart this is represented by lines that slope diagonally upward from right to left. These lines represent the temperature of a thermometer covered with water-soaked gauze. In practice, wet-bulb lines are used to determine the exact point on the psychrometric chart that represents the air conditions in a given location as measured by a psychrometer. The intersection of the diagonal wet-bulb temperature line (equal to the temperature of a wet-bulb thermometer) and the vertical dry-bulb temperature line defines the temperature and humidity conditions of air. Psychrometric charts and calculators are based on a specific atmospheric pressure, usually a typical sea-level condition. Precise calculations of psychrometric variables require an adjustment for barometric pressures different from those listed on a standard chart. Consult the ASHRAE Handbook listed in the references for more information on this. Most field measurements do not require adjustment for atmospheric pressure. Measuring Psychrometric Variables All psychrometric properties of air are determined by measuring two psychrometric variables (three, if barometric pressure is considered). For example, if wet- and dry-bulb temperatures are measured, then relative humidity, vapor pressure, dew point, and so on can be determined with the aid of a psychrometric chart. Many variables can be measured to determine the psychrometric state of air, but dry-bulb temperature, wet-bulb temperature, dew point temperature, and relative humidity are most commonly measured. Dry-bulb temperature Dry-bulb temperature can be simply and inexpensively measured by an alcohol-in-glass thermometer. The thermometer should be marked in divisions of at most 0.5 F if it is used in conjunction with a wet-bulb thermometer. The thermometer should be shielded from radiant heat sources such as motors, lights, external walls, and people. This can be done by placing the thermometer where it cannot "see" the warm object or by protecting it with a radiant heat shield assembly. Hand-held thermistor, resistance bulb, or thermocouple thermometers can also be used. They are more expensive than a glass thermometer but are not necessarily more accurate. These instruments can be purchased with a sharp probe allowing them to be used for measuring product pulp temperature. Inexpensive alcohol-in-glass and bimetallic dial thermometers are not recommended unless their calibrations have been checked against a calibrated thermometer. In field situations, an ice-water mixture is an easy way to check calibration at 32 F. Wet-bulb temperature Use of a wet-bulb thermometer in conjunction with a dry-bulb thermometer

is a common method for determining the state point on the psychrometric chart. The wet-bulb thermometer is basically an ordinary glass thermometer (although electronic temperature sensing elements can also be used) with a wetted cotton wick secured around the bulb. Air is forced over the wick, causing it to cool to the wet-bulb temperature. The wet- and dry-bulb temperatures together determine the state point of the air on the psychrometric chart, allowing all other variables to be determined. An accurate wet-bulb temperature reading depends on 1) sensitivity and accuracy of the thermometer, 2) maintenance of an adequate air speed past the wick, 3) shielding of the thermometer from radiation, 4) use of distilled or deionized water to wet the wick, and 5) use of a cotton wick. The thermometer sensitivity required to determine an accurate humidity varies according to the temperature range of the air. More sensitivity is needed at low than at high temperatures. For example, at 150 F a 1 F error in wet-bulb temperature reading results in a 2.6 percent error in relative humidity determination, but at 32 F that same error results in a 10.5 percent error in relative humidity. In most cases, absolute calibration of the wet- and dry-bulb thermometer is not as important as ensuring that they read the same at a given temperature. For example, if both thermometers read 1 F low, this will result in less than a 1.3 percent error in relative humidity at dry-bulb temperatures between 65 C and 32 F (at a 50C difference between dry- and wet-bulb temperatures). Before wetting the wick of the wet-bulb thermometer, operate both thermometers long enough to determine if there is any difference between their readings. If there is a difference, assume that one is correct and adjust the reading of the other accordingly when determining relative humidity. The rate of evaporation from the wick is a function of air speed past it. A minimum air speed of about 500 feet per minute is required for accurate readings. An air speed much below this will result in an erroneously high wet-bulb reading. Wet-bulb devices that do not provide a guaranteed air flow cannot be relied on to give an accurate reading. As with the dry-bulb thermometer, sources of radiant heat such as motors, lights, and so on can affect the wet-bulb thermometer. The reading must be taken in an area protected from these sources of radiation or thermometers must be shielded from radiant energy. A buildup of salts from impure water or contaminants in the air affects the rate of water evaporation from the wick and results in erroneous data. Distilled or deionized water should be used to moisten the wick and the wick should be replaced if there is any sign of contamination. The wick material should not have been treated with chemicals such as sizing compounds that affect the water evaporation rate.

Special care must be taken when using a wet-bulb thermometer when the wet-bulb temperature is near freezing. Most humidity tables and calculators are based on a frozen wick at wet-bulb temperatures below 32 F. At temperatures below 32 F, touch the wick with a piece of clean ice or another cold object to induce freezing, because distilled water can be cooled below 32 F without freezing. The psychrometric chart or calculator must use frost-bulb, not wet-bulb temperatures, below 32 F to be accurate with this method. Under most conditions wet-bulb temperature data are not reliable when the relative humidity is below 20 percent or the wet-bulb temperature is above 212 F. At low humidities, the wet-bulb temperature is much lower than the dry-bulb temperature and it is difficult for the wet-bulb thermometer to be cooled completely because of heat transferred by the glass or metal stem. Water boils above 212 F, so wet-bulb temperatures above that cannot be measured with a wet-bulb thermometer. In general, properly designed and operated wet- and dry-bulb psychrometers can operate with an accuracy of less than 2 percent of the actual relative humidity. Improper operation greatly increases the error. Relative humidity Direct relative humidity measurement usually uses an electric sensing element or a mechanical system. Electric hygrometers are based on substances whose electrical properties change as a function of their moisture content. As the humidity of the air around the sensor increases, its moisture increases, proportionally affecting the sensor's electrical properties. These devices are more expensive than wet- and dry-bulb psychrometers, but their accuracy is not as severely affected by incorrect operation. An accuracy of less than 2 percent of the actual humidity is often obtainable. Sensors lose their calibration if allowed to become contaminated, and some lose calibration if water condenses on them. Most sensors have a limited life. Mechanical hygrometers usually employ human hairs as a sensing element. Hair changes in length in proportion to the humidity of the air. The response to changes in relative humidity is slow and is not dependable at very high relative humidities. These devices are acceptable as an indicator of a general range of humidity but are not suitable for accurate measurements. Dew point indicators Two types of dew point sensors are commonly used today: a saturated salt system and a condensation dew point method. The saturated salt system operates at dew points between 10 to 100 F) with an error of less than ± 2 F. The system costs less than the condensation system, is not significantly affected by contaminating ions, and has a response time of

about 4 minutes. The condensation type is very accurate over a wide range of dew point temperatures (less than ± 1 F from -100 to 212 F). A condensation dew point hygrometer can be expensive. References 1. ASHRAE. 1986. ASHRAE handbook, fundamentals. Am. Soc. Heating, Refrigeration and Air Conditioning Engineers. Atlanta, GA. 2. Gaffney, J. J. 1978. Humidity: Basic principles and measurement techniques. HortScience 13(5): 551-55. 3. Wexler, A., and W. G. Brombacher. 1951. Methods of measuring humidity and testing hygrometers. National Bureau of Standards, Circ. 512. Sample Psychrometric Calculations 1. A wet-bulb thermometer reads 60 F and a dry-bulb thermometer reads 72 F. What is the relative humidity? Solution: The diagonal 60 F wet-bulb (wb) line and the vertical 72 F dry-bulb (db) line intersect at point A. Point A falls on the 50 percent relative humidity (rh) line. 2. What is the dew point temperature of the air in problem 1? Solution: If the air represented by point A is cooled without changing its moisture content, it will follow a horizontal line until it reaches 52 F. At that temperature, it has 100 percent relative humidity, and any further cooling will cause water to condense out of the air (dew forms). The dewpoint (dpt) temperature is 52 F. 3. What is the humidity ratio of the air in problem 1? Solution: Find the humidity ratio of the air represented by point A by reading horizontally across to the vertical axis of the psychrometric chart. The humidity ratio (w) is 0.0084 lb/lb. 4. If the air in problem 1 is heated to 120 F, what will be its relative humidity? Solution: Heating is represented by moving horizontally to the right from the initial temperature conditions. The horizontal line intersects the vertical 120 F line at about 12% rh. On calm, clear nights the air cools by radiation, following a horizontal line to the left. If the air cooled to 52 F (and 100% rh), it would still produce the same rh after heating to 120 F. If it cooled to less than 52 F, it would cause dew fall and the air would have less moisture content. If this air (even though its relative humidity is 100%) were heated to 120 F it would have less than 12% rh.