ELECTRICAL SYMBOL LIST

Similar documents
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

B. Related Sections: 1. Section Raceway and Boxes for Electrical Systems.

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

BASIC NEC CODE RULES AND DESIGN PRACTICE

Top Commercial / Residential Electrical Requirements *

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

NEC 2014 Code Changes

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.

SECTION COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

Line Loss WSDOT Winter 2008 BZA

Residential Electrical Inspection. Checklist

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

AMERBRITE UNDERWATER WHITE LED POOL LAMP

A. Shop Drawing submittals shall include, but not be limited to, the following:

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Commercial/Industrial Electricity

SECTION ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

Instructions & Safety Information Models A220-20D and A220-20L Version 2

How To Get A Power Line Extension

City of Riverside Building & Safety Division Phone: (951)

How To Power A Power Supply On A Powerline From A Power Source To A Power Box

Residential Electrical Inspection. Checklist

Phase-Adaptive Power Module

Utility Distribution Systems

Cable/Conduit Conversion

Switching Power Module

Element D Services Electrical

Exhibit C Design Review Guidelines

Arc Fault Circuit Interrupters Frequently Asked Questions

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION LOW VOLTAGE LIGHTING CONTROLS

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

Questions and Answers for Heating and A/C Contractors

Residential Electrical Inspection Checklist

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4

GENERAL WIRING RULES FOR HOUSES

Electrical Design TABLE OF CONTENTS FOREWORD BASIC ELEMENTS OF ELECTRICITY... 2 Electricity works much like water Ohm s Law

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

SECTION FIRE ALARM AND DETECTION SYSTEM

Electrical Grounding. Appendix C

POWER DISTRIBUTION. Power and Undercarpet Products POWER AND UNDERCARPET PRODUCTS. Chapter Summary

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

COUNTY OF LOS ANGELES BUILDING AND SAFETY DIVISION ELECTRICAL CODE FEE SCHEDULE (Title 27 of the County of Los Angeles Code, Ord No.

Three-Phase Electric Power Distribution for Computer Data Centers

CHAPTER 2 EXAMPLES AND TABLES

Multiple Meter Installation Amperes Per Position -Single Phase, Self-contained

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS

PHOTOVOLTAIC ARRAY WIRING HANDBOOK FOR STANDARD NOMINAL 6, 12, 24, AND 48 VOLT SYSTEMS. (for SX-60 series or smaller and MSX-120 solar modules)

SECTION SIGNAL WIRE AND CABLE

INSTALLATION GUIDE LOW VOLTAGE TRANSFORMER

Electrical Code Regulation

For Models #6-5001, #6-7501, # & #10-12K1

EcoSystem Dimming Power Module for 3-wire Lutron Dimming Ballasts. EcoSystem One-Line. EcoSystem C5-BMJ-16A. EcoSystemR Dimming Module

The Pennsylvania State University Physical Security Office. Intrusion Alarm. Performance Specification

Engineers Edge, LLC PDH & Professional Training

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

Electrical Contractors. and the. New Jersey. Rehabilitation Code

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

Hyperlinks are Inactive

8146/5 Series Breaker Panelboards

INSPECTION GUDELINES

LANTANA LUMINAIRE HI-LUME 1% ECOSYSTEM LED DRIVER L3DA4U1UMN-XXXXX

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

ELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES

Electrical Practices for Construction Work

Building Permit Application

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

Electric Service Guide for Commercial Construction

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

C. Conform to requirements of Americans with Disabilities Act (ADA).

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide

Wiring for Health Care Facilities NEC Article 517

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering

SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment

Installation Manual Version 7.3 IMPORTANT:

Transcription:

NOTE: This is a standard symbol list and not all items listed may be used. ELECTRICAL SYMBOL LIST GENERAL ELECTRICAL NOTES A. DO NOT COMMENCE INSTALLATION OF ELECTRICAL SYSTEMS AND EQUIPMENT WITHOUT RELATED SHOP DRAWING APPROVALS. Abbreviations EXISTING A AMPERES, AMBER AIC AVAILABLE INTERRUPTING CAPACITY AWG AMERICAN WIRE GAUGE C CONDUIT, CLOSE, CONTROL J Connections / Equipment OR J J General JUNCTION BOX WALL-MOUNTED JUNCTION BOX DEMOLISH B. ELECTRICAL CIRCUITS SHALL BE INTERRUPTED ONLY WITH PRIOR WRITTEN CONSENT. SUCH INTERRUPTIONS SHALL BE PRECEDED BY ALL POSSIBLE PREPARATIONS BY THE CONTRACTOR WHICH ARE NECESSARY TO KEEP THE ELECTRICAL CIRCUITS OFF FOR A MINIMUM PERIOD IN AN EXPEDITIOUS MANNER PURSUANT WITH GOOD WORKMANSHIP. THIS INCLUDES CIRCUIT TRACING TO IDENTIFY THE ELECTRICAL LOAD BEING SERVED AND THE ORIGIN OF THE CIRCUIT. C. COORDINATE WITH OWNER SO THAT WORK CAN BE SCHEDULED NOT TO INTERRUPT OPERATIONS, NORMAL ACTIVITIES, BUILDING ACCESS, ACCESS TO DIFFERENT AREAS. THE OWNER WILL COOPERATE TO THE BEST OF THEIR ABILITY TO ASSIST IN A COORDINATED SCHEDULE, BUT WILL REMAIN THE FINAL AUTHORITY AS TO TIME OF WORK PERMITTED. D. COORDINATE THE EXACT LOCATION OF EXISTING UTILITIES AND EQUIPMENT PRIOR TO COMMENCEMENT OF WORK. COMPENSATE THE OWNER FOR DAMAGES CAUSED BY THE FAILURE TO LOCATE AND PRESERVE UTILITIES. REPLACE DAMAGED ITEMS WITH NEW MATERIAL TO MATCH EXISTING. 204-0380 Jason Lau CB CLG COORD CU DIM DWG CIRCUIT BREAKER CEILING COORDINATE COPPER DIMENSION DRAWING X X EXISTING WORK NEW WORK DETAIL NUMBER AND SHEET LOCATION KEYED NOTE E. REMOVE EXISTING LUMINAIRES, SWITCHES, RECEPTACLES, AND OTHER ELECTRICAL EQUIPMENT AND DEVICES AND ASSOCIATED WIRING FROM WALLS, CEILINGS, FLOORS, AND OTHER SURFACES SCHEDULED FOR REMODELING, RELOCATION, OR DEMOLITION UNLESS SHOWN AS RETAINED OR RELOCATED ON DRAWINGS. F. MAINTAIN ELECTRICAL CONTINUITY OF EXISTING SYSTEMS. REMOVE OR RELOCATE ELECTRICAL BOXES, CONDUIT, WIRING, EQUIPMENT, LUMINAIRES, AND THE LIKE, AS REQUIRED IN REMOVED OR REMODELED AREAS IN THE EXISTING CONSTRUCTION AFFECTED BY THIS WORK. G. REMOVE AND RESTORE WIRING WHICH SERVES USABLE EXISTING OUTLETS CLEAR OF THE CONSTRUCTION OR DEMOLITION. EA EL FT G, GND GFCI GFI HT EACH ELEVATION FOOT, FEET GROUND GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT INTERRUPTER HEIGHT Miscellaneous #0 B-27,29,3. BRANCH CIRCUIT WIRING. ARROW INDICATES HOME RUN TO PANEL WITH CIRCUITS AS NOTED. WIRE SIZE IS #2 AWG MINIMUM UNLESS NOTED OTHERWISE. SHORT TICK MARKS INDICATE PHASE CONDUCTORS. LONG TICK MARKS INDICATE NEUTRAL CONDUCTORS. A SINGLE CURVED TICK MARK INDICATES INSULATED GREEN GROUND CONDUCTOR. SECOND CURVED TICK MARK INDICATES "ISOLATED GROUND" (GREEN INSULATION WITH YELLOW STRIPE) CONDUCTOR. BRANCH PANEL H. IF EXISTING JUNCTION BOXES WILL BE MADE INACCESSIBLE, OR IF ABANDONED OUTLETS SERVE AS FEED THROUGH BOXES FOR OTHER EXISTING ELECTRICAL EQUIPMENT WHICH IS BEING RETAINED, PROVIDE NEW CONDUIT AND WIRE TO BYPASS THE ABANDONED OUTLETS. I. IF EXISTING CONDUITS PASS THROUGH PARTITIONS OR CEILING WHICH ARE BEING REMOVED OR REMODELED, PROVIDE NEW CONDUIT AND WIRE TO REROUTE CLEAR OF THE CONSTRUCTION OR DEMOLITION AND MAINTAIN SERVICE TO THE EXISTING LOAD. J. CONCEALED CONDUIT LOCATED IN CONCRETE WALLS OR HARDBOARD CEILING SPACES MAY BE ABANDONED IN PLACE. REMOVE CONDUCTORS AND TAG ABANDONED CONDUITS WITH CORRESPONDING SYSTEM AND TERMINATION POINT. CUT AND CAP ABANDONED CONDUIT. DO NOT EXTEND STUBS ABOVE FINISHED FLOOR. K. EXTEND CIRCUITING AND DEVICES IN EXISTING WALLS TO BE FURRED OUT. L. PROVIDE TEMPORARY SUPPORT FOR ELECTRICAL SYSTEMS THAT REMAIN IN PLACE. IN KVA KW INCH, INCHES KILOVOLT AMPERES KILOWATT FLUSH WALL MOUNTED BRANCH PANEL GROUNDING POINT M. VERIFY EXACT LOCATION AND NUMBER OF EXISTING ELECTRICAL OUTLETS AND LUMINAIRES IN THE FIELD. LOCATIONS OF ITEMS SHOWN ON DRAWINGS AS EXISTING ARE PARTIALLY BASED ON RECORD AND OTHER DRAWINGS WHICH MAY CONTAIN ERRORS. VERIFY THE ACCURACY OF THE INFORMATION SHOWN PRIOR TO BIDDING AND PROVIDE SUCH LABOR AND MATERIAL AS IS NECESSARY TO ACCOMPLISH THE INTENT OF THE CONTRACT DOCUMENTS. LED MIN MT, MTD N/A LIGHT EMITTING DIODE MINIMUM MOUNT, MOUNTED NOT APPLICABLE Raceways CONDUIT CONCEALED IN WALL OR CEILING SPACE CONDUIT ROUTED BELOW FLOOR / GRADE N. REMOVE ABANDONED WIRING TO LEAVE SITE CLEAN. O. EXISTING LIGHTING WHICH IS TO REMAIN OR BE RELOCATED IS TO BE RELAMPED, REBALLASTED, AND CLEANED. LEAVE ALL LUMINAIRES IN PROPER WORKING ORDER. REPLACE DAMAGED OR BROKEN LENS AND/OR COMPONENTS. P. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS WHICH REMAIN ACTIVE. MODIFY INSTALLATION OR PROVIDE ACCESS PANEL AS APPROPRIATE. NEC NEMA NATIONAL ELECTRIC CODE NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION CONDUIT/WIRING CONTINUATION Q. WHERE DRAWINGS INDICATE EXISTING ELECTRICAL EQUIPMENT OR DEVICES TO BE RELOCATED AND/OR REUSED, REFURBISH THEM. THOROUGHLY CLEAN SUCH ITEMS. NOTIFY ARCHITECT OF ANY DEFECTS IN SUCH INSTALLATIONS. REPAIR ANY DAMAGE CAUSED BY DEMOLITION OR CONSTRUCTION PERFORMED UNDER THIS CONTRACT. NTS OC REQD NOT TO SCALE ON CENTER REQUIRED CONDUIT/WIRING STUBBED OUT WITH END CAP OR INSULATED PLASTIC BUSHING Switches and Receptacles R. PROVIDE UPDATED PANEL SCHEDULES AND DIRECTORIES THAT IDENTIFY EXISTING CIRCUITS AND NUMBER OF SPARE CIRCUITS AVAILABLE UPON COMPLETION OF DEMOLITION WORK. S. OFFER REMOVED LUMINAIRES, WIRING DEVICES, PANELBOARDS AND EQUIPMENT TO THE OWNER. IF OWNER CHOOSES TO RETAIN THESE ITEMS, RETURN SUCH ITEMS TO OWNER. CAREFULLY REMOVE AND DISPOSE OF ITEMS REJECTED BY OWNER FROM PROJECT SITE AND IN A LEGAL MANNER. RM S SHT TYP ROOM SWITCH SHEET TYPICAL SPECIAL PURPOSE RECEPTACLE. LETTER CODE DENOTES RECEPTACLE CONFIGURATION LX-XXR = NEMA CONFIGURATION TWIST-LOCK RECEPTACLE X-XXR = NEMA CONFIGURATION STRAIGHT BLADE RECEPTACLE P = PENDANT MOUNT WITH CORD GRIPS. VERIFY PENDANT LENGTH X = COORDINATE RECEPTACLE CONFIGURATION WITH EQUIPMENT BEING SUPPLIED T. RECONNECT EXISTING LUMINAIRES NOT SHOWN ON DRAWINGS AND AFFECTED DUE TO DEMOLITION TO NEAREST AVAILABLE EXISTING LIGHTING CIRCUIT ABLE TO TAKE THE ADDITIONAL LOAD. U. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. V. DRAWINGS AND SPECIFICATIONS COMPLIMENT EACH OTHER. REQUIREMENT BY EITHER INFERS REQUIREMENT BY BOTH. UL UNDERWRITERS LABORATORIES W. CONNECT EQUIPMENT AND DEVICES FURNISHED UNDER OTHER DIVISIONS OF THIS CONTRACT, BY OWNER OR BY OTHER CONTRACTS. UON V UNLESS OTHERWISE NOTED VOLTS, VOLTAGE X. UNLESS OTHERWISE NOTED, PROVIDE CONCEALED AND FLUSH MOUNTED INSTALLATION OF DEVICES AND EQUIPMENT IN AREAS. Y. PROVIDE SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN 20 VOLT, MULTI-WIRE CIRCUITS. W/ W/O WITH WITHOUT Z. FOR 20 VOLT, 20 AMP CIRCUITS, WHERE CIRCUIT DISTANCE FROM PANELBOARD TO FARTHEST DEVICE/FIXTURE EXCEEDS 7 FEET, PROVIDE #0 SIZE CONDUCTOR. AA. RUN ELECTRICAL CONDUIT CONCEALED AND PARALLEL TO BUILDING LINES. VERIFY WITH ARCHITECT. AB. RECEPTACLE OUTLETS SHALL COMPLY WITH CEC SECTION 20.7. AC. LIGHTS, SWITCHES AND CONTROL MECHANISMS SHALL COMPLY WITH CEC SECTION 404. AD. AE. BRACE ELECTRICAL EQUIPMENT TO RESIST A HORIZONTAL FORCE THAT ACT IN ANY DIRECTION. COMPLY WITH TITLE 24 REQUIREMENTS. INSTALL COMPLETE SYSTEM OF CONDUCTORS IN RACEWAY SYSTEM THROUGHOUT BUILDING FOR FEEDERS, BRANCH CIRCUITS, ETC. SHEET INDEX E0. SYMBOL LIST AND GENERAL NOTES - ELECTRICAL E2. FLOOR PLAN - LIGHTING E2.2 LIGHTING CONTROL FLOOR PLANS NO SCALE Sept. 9, 204

GENERAL SHEET NOTES A. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF LUMINAIRES AND LIGHTING CONTROLS WITH THEATRICAL LIGHTING CONSULTANT PRIOR TO INSTALLATION. B. REFER TO THEATRICAL LIGHTING CONSULTANT DRAWINGS FOR ADDITIONAL INFORMATION AND LIGHTING CONTROL REQUIREMENTS. C. REFER TO THEATRICAL LIGHTING CONSULTANT DRAWINGS FOR LUMINAIRE SCHEDULE AND SYMBOLS. D. EXISTING LUMINAIRES AND LIGHTING CONTROLS NOT SHOWN ON PLAN SHALL REMAIN, U.O.N. 204-0380 Jason Lau 3 6 SHEET KEYNOTES DISCONNECT AND REUSE EXISTING LIGHTING CIRCUIT AS PART OF LED LUMINAIRE REPLACEMENT. LUMINAIRES TO BE RECONNECTED BACK TO EXISTING DIMMER RACK. 2 DISCONNECT AND REMOVE EXISTING LUMINAIRES AND PROVIDE NEMA L-20R RECEPTACLE FOR CONNECTION TO NEW REPLACEMENT TYPE LUMINAIRES. REUSE EXISTING JUNCTION BOX AND CIRCUIT FOR NEW RECEPTACLE. 4 6 3 RELAMP/REPAIR EXISTING FLUORESCENT LUMINAIRES TO REMAIN. 4 REMOVE EXISTING LAMPS AND ABANDON FLUORESCENT LUMINAIRES IN PLACE. REPLACE EXISTING INCANDESCENT LAMP WITH LED RETROFIT LAMP IN EXISTING DOWNLIGHT. 6 ADD ALTERNATE: DISCONNECT AND REMOVE EXISTING FLUORESCENT LUMINAIRES WITH NEW TYPE 'D' LUMINAIRES. RECONNECT COMPLETE TO EXISTING LIGHTING CIRCUIT AS REQUIRED TO PLACE BACK INTO SERVICE. (TYP.) (TYP.) 2 (TYP. OF 9) 4 6 3 6 (TYP.) 4 6 3 6 FLOOR PLAN - LIGHTING 0 4' 8' 6' SCALE: /8"='-0" /8" = '-0" Sept. 9, 204

GENERAL SHEET NOTES A. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF LIGHTING CONTROLS WITH THEATRICAL LIGHTING CONSULTANT PRIOR TO INSTALLATION. B. REFER TO THEATRICAL LIGHTING CONSULTANT DRAWINGS FOR ADDITIONAL INFORMATION AND LIGHTING CONTROL REQUIREMENTS. SHEET KEYNOTES 204-0380 Jason Lau DISCONNECT AND REMOVE EXISTING RACK-MOUNTED HOUSE LIGHT CONTROL STATION AND WORKLIGHT CONTROL STATION AND REPLACE WITH NEW STAGE MANAGER'S PANEL WORKLIGHT/HOUSE LIGHT CONTROL PANEL. RECONNECT COMPLETE BACK TO EXISTING CIRCUIT TO PLACE BACK INTO SERVICE. 2 DISCONNECT AND REMOVE EXISTING HOUSE LIGHT SLIDER CONTROL STATION AND REPLACE WITH NEW HOUSE LIGHT MASTER STATION 'HLM'. PROVIDE NEW SURFACE BACK BOX AS REQUIRED. RECONNECT COMPLETE BACK TO EXISTING CIRCUIT TO PLACE BACK INTO SERVICE. 3 DISCONNECT AND REMOVE EXISTING WORK LIGHT CONTROL STATION AND REPLACE WITH NEW WORKLIGHT CONTROL STATION 'WL'. REUSE EXISTING BACK BOX. RECONNECT COMPLETE BACK TO EXISTING CIRCUIT TO PLACE BACK INTO SERVICE. 4 DISCONNECT AND REMOVE EXISTING HOUSE LIGHT CONTROL STATION AND REPLACE WITH NEW HOUSE LIGHT CONTROL STATION 'HL'. REUSE EXISTING BACK BOX AND LOCKING COVER. RECONNECT COMPLETE BACK TO EXISTING CIRCUIT TO PLACE BACK INTO SERVICE. DISCONNECT AND REMOVE EXISTING ETC UNISON ER-4 EXTERNAL PROCESSING RACK AND REPLACE WITH NEW ETC UNISON ERn2 EXTERNAL PROCESSING RACK WITH 4-PORT NETWORK SWITCH. RECONNECT COMPLETE BACK TO EXISTING CIRCUIT TO PLACE BACK INTO SERVICE. 2 3 4 LIGHTING CONTROL PLAN - MAIN LEVEL 0 4' 8' 6' 2 LIGHTING CONTROL PLAN - ELECTRICAL ROOM 0 4' 8' 6' /8" = '-0" Sept. 9, 204 SCALE: /8"='-0" SCALE: /8"='-0"

NOTE: This is a standard symbol list and not all items listed may be used. ELECTRICAL SYMBOL LIST GENERAL ELECTRICAL NOTES A. DO NOT COMMENCE INSTALLATION OF ELECTRICAL SYSTEMS AND EQUIPMENT WITHOUT RELATED SHOP DRAWING APPROVALS. Abbreviations EXISTING A AMPERES, AMBER AIC AVAILABLE INTERRUPTING CAPACITY AWG AMERICAN WIRE GAUGE C CONDUIT, CLOSE, CONTROL CB CIRCUIT BREAKER CLG CEILING COORD COORDINATE CU COPPER DIM DIMENSION DWG DRAWING J Connections / Equipment OR J J General X X JUNCTION BOX WALL-MOUNTED JUNCTION BOX DEMOLISH EXISTING WORK NEW WORK DETAIL NUMBER AND SHEET LOCATION KEYED NOTE B. ELECTRICAL CIRCUITS SHALL BE INTERRUPTED ONLY WITH PRIOR WRITTEN CONSENT. SUCH INTERRUPTIONS SHALL BE PRECEDED BY ALL POSSIBLE PREPARATIONS BY THE CONTRACTOR WHICH ARE NECESSARY TO KEEP THE ELECTRICAL CIRCUITS OFF FOR A MINIMUM PERIOD IN AN EXPEDITIOUS MANNER PURSUANT WITH GOOD WORKMANSHIP. THIS INCLUDES CIRCUIT TRACING TO IDENTIFY THE ELECTRICAL LOAD BEING SERVED AND THE ORIGIN OF THE CIRCUIT. C. COORDINATE WITH OWNER SO THAT WORK CAN BE SCHEDULED NOT TO INTERRUPT OPERATIONS, NORMAL ACTIVITIES, BUILDING ACCESS, ACCESS TO DIFFERENT AREAS. THE OWNER WILL COOPERATE TO THE BEST OF THEIR ABILITY TO ASSIST IN A COORDINATED SCHEDULE, BUT WILL REMAIN THE FINAL AUTHORITY AS TO TIME OF WORK PERMITTED. D. COORDINATE THE EXACT LOCATION OF EXISTING UTILITIES AND EQUIPMENT PRIOR TO COMMENCEMENT OF WORK. COMPENSATE THE OWNER FOR DAMAGES CAUSED BY THE FAILURE TO LOCATE AND PRESERVE UTILITIES. REPLACE DAMAGED ITEMS WITH NEW MATERIAL TO MATCH EXISTING. E. REMOVE EXISTING LUMINAIRES, SWITCHES, RECEPTACLES, AND OTHER ELECTRICAL EQUIPMENT AND DEVICES AND ASSOCIATED WIRING FROM WALLS, CEILINGS, FLOORS, AND OTHER SURFACES SCHEDULED FOR REMODELING, RELOCATION, OR DEMOLITION UNLESS SHOWN AS RETAINED OR RELOCATED ON DRAWINGS. F. MAINTAIN ELECTRICAL CONTINUITY OF EXISTING SYSTEMS. REMOVE OR RELOCATE ELECTRICAL BOXES, CONDUIT, WIRING, EQUIPMENT, LUMINAIRES, AND THE LIKE, AS REQUIRED IN REMOVED OR REMODELED AREAS IN THE EXISTING CONSTRUCTION AFFECTED BY THIS WORK. G. REMOVE AND RESTORE WIRING WHICH SERVES USABLE EXISTING OUTLETS CLEAR OF THE CONSTRUCTION OR DEMOLITION. 204-0380 Jason Lau EA EL FT G, GND GFCI GFI HT EACH ELEVATION FOOT, FEET GROUND GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT INTERRUPTER HEIGHT Miscellaneous #0 B-27,29,3. BRANCH CIRCUIT WIRING. ARROW INDICATES HOME RUN TO PANEL WITH CIRCUITS AS NOTED. WIRE SIZE IS #2 AWG MINIMUM UNLESS NOTED OTHERWISE. SHORT TICK MARKS INDICATE PHASE CONDUCTORS. LONG TICK MARKS INDICATE NEUTRAL CONDUCTORS. A SINGLE CURVED TICK MARK INDICATES INSULATED GREEN GROUND CONDUCTOR. SECOND CURVED TICK MARK INDICATES "ISOLATED GROUND" (GREEN INSULATION WITH YELLOW STRIPE) CONDUCTOR. BRANCH PANEL H. IF EXISTING JUNCTION BOXES WILL BE MADE INACCESSIBLE, OR IF ABANDONED OUTLETS SERVE AS FEED THROUGH BOXES FOR OTHER EXISTING ELECTRICAL EQUIPMENT WHICH IS BEING RETAINED, PROVIDE NEW CONDUIT AND WIRE TO BYPASS THE ABANDONED OUTLETS. I. IF EXISTING CONDUITS PASS THROUGH PARTITIONS OR CEILING WHICH ARE BEING REMOVED OR REMODELED, PROVIDE NEW CONDUIT AND WIRE TO REROUTE CLEAR OF THE CONSTRUCTION OR DEMOLITION AND MAINTAIN SERVICE TO THE EXISTING LOAD. J. CONCEALED CONDUIT LOCATED IN CONCRETE WALLS OR HARDBOARD CEILING SPACES MAY BE ABANDONED IN PLACE. REMOVE CONDUCTORS AND TAG ABANDONED CONDUITS WITH CORRESPONDING SYSTEM AND TERMINATION POINT. CUT AND CAP ABANDONED CONDUIT. DO NOT EXTEND STUBS ABOVE FINISHED FLOOR. K. EXTEND CIRCUITING AND DEVICES IN EXISTING WALLS TO BE FURRED OUT. L. PROVIDE TEMPORARY SUPPORT FOR ELECTRICAL SYSTEMS THAT REMAIN IN PLACE. IN KVA KW INCH, INCHES KILOVOLT AMPERES KILOWATT FLUSH WALL MOUNTED BRANCH PANEL GROUNDING POINT M. VERIFY EXACT LOCATION AND NUMBER OF EXISTING ELECTRICAL OUTLETS AND LUMINAIRES IN THE FIELD. LOCATIONS OF ITEMS SHOWN ON DRAWINGS AS EXISTING ARE PARTIALLY BASED ON RECORD AND OTHER DRAWINGS WHICH MAY CONTAIN ERRORS. VERIFY THE ACCURACY OF THE INFORMATION SHOWN PRIOR TO BIDDING AND PROVIDE SUCH LABOR AND MATERIAL AS IS NECESSARY TO ACCOMPLISH THE INTENT OF THE CONTRACT DOCUMENTS. LED MIN MT, MTD N/A LIGHT EMITTING DIODE MINIMUM MOUNT, MOUNTED NOT APPLICABLE Raceways CONDUIT CONCEALED IN WALL OR CEILING SPACE CONDUIT ROUTED BELOW FLOOR / GRADE N. REMOVE ABANDONED WIRING TO LEAVE SITE CLEAN. O. EXISTING LIGHTING WHICH IS TO REMAIN OR BE RELOCATED IS TO BE RELAMPED, REBALLASTED, AND CLEANED. LEAVE ALL LUMINAIRES IN PROPER WORKING ORDER. REPLACE DAMAGED OR BROKEN LENS AND/OR COMPONENTS. P. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS WHICH REMAIN ACTIVE. MODIFY INSTALLATION OR PROVIDE ACCESS PANEL AS APPROPRIATE. NEC NEMA NATIONAL ELECTRIC CODE NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION CONDUIT/WIRING CONTINUATION Q. WHERE DRAWINGS INDICATE EXISTING ELECTRICAL EQUIPMENT OR DEVICES TO BE RELOCATED AND/OR REUSED, REFURBISH THEM. THOROUGHLY CLEAN SUCH ITEMS. NOTIFY ARCHITECT OF ANY DEFECTS IN SUCH INSTALLATIONS. REPAIR ANY DAMAGE CAUSED BY DEMOLITION OR CONSTRUCTION PERFORMED UNDER THIS CONTRACT. NTS OC REQD NOT TO SCALE ON CENTER REQUIRED CONDUIT/WIRING STUBBED OUT WITH END CAP OR INSULATED PLASTIC BUSHING Switches and Receptacles R. PROVIDE UPDATED PANEL SCHEDULES AND DIRECTORIES THAT IDENTIFY EXISTING CIRCUITS AND NUMBER OF SPARE CIRCUITS AVAILABLE UPON COMPLETION OF DEMOLITION WORK. S. OFFER REMOVED LUMINAIRES, WIRING DEVICES, PANELBOARDS AND EQUIPMENT TO THE OWNER. IF OWNER CHOOSES TO RETAIN THESE ITEMS, RETURN SUCH ITEMS TO OWNER. CAREFULLY REMOVE AND DISPOSE OF ITEMS REJECTED BY OWNER FROM PROJECT SITE AND IN A LEGAL MANNER. RM S SHT TYP ROOM SWITCH SHEET TYPICAL DUPLEX RECEPTACLE T. RECONNECT EXISTING LUMINAIRES NOT SHOWN ON DRAWINGS AND AFFECTED DUE TO DEMOLITION TO NEAREST AVAILABLE EXISTING LIGHTING CIRCUIT ABLE TO TAKE THE ADDITIONAL LOAD. U. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. V. DRAWINGS AND SPECIFICATIONS COMPLIMENT EACH OTHER. REQUIREMENT BY EITHER INFERS REQUIREMENT BY BOTH. UL UNDERWRITERS LABORATORIES W. CONNECT EQUIPMENT AND DEVICES FURNISHED UNDER OTHER DIVISIONS OF THIS CONTRACT, BY OWNER OR BY OTHER CONTRACTS. UON V UNLESS OTHERWISE NOTED VOLTS, VOLTAGE X. UNLESS OTHERWISE NOTED, PROVIDE CONCEALED AND FLUSH MOUNTED INSTALLATION OF DEVICES AND EQUIPMENT IN AREAS. Y. PROVIDE SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN 20 VOLT, MULTI-WIRE CIRCUITS. W/ W/O WITH WITHOUT Z. FOR 20 VOLT, 20 AMP CIRCUITS, WHERE CIRCUIT DISTANCE FROM PANELBOARD TO FARTHEST DEVICE/FIXTURE EXCEEDS 7 FEET, PROVIDE #0 SIZE CONDUCTOR. AA. RUN ELECTRICAL CONDUIT CONCEALED AND PARALLEL TO BUILDING LINES. VERIFY WITH ARCHITECT. AB. RECEPTACLE OUTLETS SHALL COMPLY WITH CEC SECTION 20.7. AC. LIGHTS, SWITCHES AND CONTROL MECHANISMS SHALL COMPLY WITH CEC SECTION 404. AD. AE. BRACE ELECTRICAL EQUIPMENT TO RESIST A HORIZONTAL FORCE THAT ACT IN ANY DIRECTION. COMPLY WITH TITLE 24 REQUIREMENTS. INSTALL COMPLETE SYSTEM OF CONDUCTORS IN RACEWAY SYSTEM THROUGHOUT BUILDING FOR FEEDERS, BRANCH CIRCUITS, ETC. SHEET INDEX E0. SYMBOL LIST AND GENERAL NOTES - ELECTRICAL E2. FLOOR PLAN - LIGHTING E2.2 LIGHTING CONTROL FLOOR PLANS NO SCALE Sept. 9, 204

GENERAL SHEET NOTES A. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF LUMINAIRES AND LIGHTING CONTROLS WITH THEATRICAL LIGHTING CONSULTANT PRIOR TO INSTALLATION. B. REFER TO THEATRICAL LIGHTING CONSULTANT DRAWINGS FOR ADDITIONAL INFORMATION AND LIGHTING CONTROL REQUIREMENTS. C. REFER TO THEATRICAL LIGHTING CONSULTANT DRAWINGS FOR LUMINAIRE SCHEDULE AND SYMBOLS. D. EXISTING LUMINAIRES AND LIGHTING CONTROLS NOT SHOWN ON PLAN SHALL REMAIN, U.O.N. 204-0380 Jason Lau SHEET KEYNOTES DISCONNECT AND REUSE EXISTING LIGHTING CIRCUIT AS PART OF LED LUMINAIRE REPLACEMENT. LUMINAIRES TO BE RECONNECTED BACK TO EXISTING DIMMER RACK. (TYPICAL) (TYPICAL) FLOOR PLAN - LIGHTING 0 2' 4' 8' AS NOTED Sept. 9, 204 SCALE: /4"='-0"

GENERAL SHEET NOTES A. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF EQUIPMENTS AND LIGHTING CONTROLS WITH THEATRICAL LIGHTING CONSULTANT PRIOR TO INSTALLATION. B. REFER TO THEATRICAL LIGHTING CONSULTANT DRAWINGS FOR ADDITIONAL INFORMATION AND LIGHTING CONTROL REQUIREMENTS. C. EXISTING EQUIPMENTS AND LIGHTING CONTROLS NOT SHOWN ON PLAN SHALL REMAIN, U.O.N. 204-0380 Jason Lau SHEET KEYNOTES 4 DISCONNECT AND REMOVE EXISTING UNISON SINGLE-GANG 0-BUTTON SNAPSHOT STATION AND REPLACE WITH NEW STATION 'S'. RECONNECT COMPLETE BACK TO EXISTING CIRCUIT TO PLACE BACK INTO SERVICE. 2 DISCONNECT AND REMOVE EXISTING UNISON SINGLE-GANG -BUTTON HOUSE/WORKLIGHT STATION AND REPLACE WITH NEW STATION 'HL'. RECONNECT COMPLETE BACK TO EXISTING CIRCUIT TO PLACE BACK INTO SERVICE. 3 DISCONNECT AND REMOVE EXISTING HOUSE LIGHT KEYSWITCH CONTROL STATION AND REPLACE WITH NEW STATION 'HLK'. RECONNECT COMPLETE BACK TO EXISTING CIRCUIT TO PLACE BACK INTO SERVICE. PANEL '3RBB' 4 EXISTING ETC UNISON ER-4 DR2 WALL MOUNTED DIMMER RACK TO REMAIN. INSTALL NEW ETC UNISON PARADIGM ERn2 SIGNAL PROCESSOR RACK WITH SMALL 4-PORT NETWORK SWITCH. INTERCEPT AND EXTEND EXISTING CIRCUIT '3RBB-.' TO NEW RACK AND CONNECT COMPLETE AS REQUIRED TO PLACE INTO SERVICE. 4 THEATER BASEMENT LEVEL ELECTRICAL ROOM PLAN 0 2' 4' 8' SCALE: /4"='-0" 3 2 2 2 3 THEATER MAIN LEVEL STAGE PLAN 0 4' 8' 6' 2 CONTROL ROOM PLAN 0 4' 8' 6' THEATER MAIN LEVEL AUDITORIUM PLAN 0 4' 8' 6' AS NOTED Sept. 9, 204 SCALE: /8"='-0" SCALE: /8"='-0" SCALE: /8"='-0"