EXSULATION S5000 Mineral Wool Slab Non Combustible EIFS DSC5001 Exsulation S5000 System Installation Details
Exsulation S5000 DETAIL Table of Contents NOTE EXS.0.0.01 EXS.0.0.02A EXS.0.0.02B EXS.0.0.03 EXS.0.0.04 EXS.0.0.05 EXS.0.0.06 EXS.0.0.07 EXS.0.0.08 EXS.0.0.09 EXS.0.0.10 EXS.0.0.11 EXS.0.0.12 EXS.0.0.13 EXS.0.0.14 EXS.0.0.15 EXS.0.0.16A EXS.0.0.16B EXS.0.0.17 EXS.0.0.18 EXS.0.0.19 EXS.0.0.20 EXS.0.0.21 EXS.0.0.22 EXS.0.0.23 EXS.0.0.24 EXS.0.0.25 NORMAL AND HIGH IMPACT FOUNDATION WITH DRAINAGE STRIP - APPLICATION SEQUENCE FOUNDATION WITH DRAINAGE STRIP - EXTENDED 2D VIEW MECHANICAL FIXING PATTERNS HEAD/SILL HEAD/SILL FOR SELF FLASHING WINDOW OPTIONS PROTECTION OF ROUGH OPENINGS ROUGH OPENING PREPARATION JAMB PARAPET - CAP FLASHING PARAPET/ WALL TERMINATION PARAPET - SOLID SUBSTRATE SOFFIT/FASCIA INTERSECTION SOFFIT - UNINSULATED INSIDE/OUTSIDE CORNERS OUTSIDE CORNER - HIGH IMPACT FLOORLINE DETAIL - APPLICATION SEQUENCE HORIZONTAL SLIP JOINT - EXTENDED 2D VIEW HORIZONTAL SLIP JOINT TWO-STAGE JOINT - EXTENDED 2D STRUCTURAL EXPANSION JOINTS PENETRATIONS WALL PENETRATIONS SIGN ATTACHMENT AESTHETIC REVEALS HORIZONTAL JOINT AT STONE VENEER SOFFIT VENT DRYVIT MAKES NO REPRESENTATION REGARDING CONFORMITY OF ITS SUGGESTIONS TO APPLICABLE BUILDING CODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS OR PROJECT LOCATIONS. ALL COMPONENTS INDICATED IN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BE REQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BE DESIGNED, DETAILED AND ENGINEERED BY REPRESENTATIVES OF THE ARCHITECT, OWNER OR CONTRACTOR TO BE IN CONFORMANCE WITH MODEL CODES, ARCHITECTURAL AND ENGINEERING REQUIREMENTS PERTAINING TO SPECIFIC BUILDING PROJECTS. DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED, AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, OR WORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMS OR PRODUCTS. THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THE EXSULATION S5000 LIMITED COMMERCIAL WARRANTY. CONTACT DRYVIT FOR A FULL AND COMPLETE COPY OF THE WARRANTY.
Exsulation S5000 Substrate Primus DM Adhesive ribbons Dryvit Secondary Barrier Approved mechanical fastener Mineral wool insulation slab Primus DM Basecoat Primus DM Basecoat EXS.0.0.01 reinforced with Panzer 15 or 20 Mesh prior to Standard Plus Mesh. in contract drawings. 2. Install Mechanical Fixings Backwrap NORMAL IMPACT Substrate Primus DM Adhesive ribbons Dryvit Secondary Barrier Approved mechanical fastener Mineral wool insulation slab Primus DM Basecoat Primus DM Basecoat Primus DM Basecoat Backwrap HIGH IMPACT Normal and High Impact
Exsulation S5000 EXS.0.0.02A Application Sequence 1. Apply Backstop NT over Grid Tape. 2. Apply Dryvit secondary barrier onto approved substrate sheathing. 3. Dryvit AquaFlash applied over at foundation transition. 2 4. For added drainage apply Dryvit adhesive in vertical notched trowel configuration (1/2" x 1/2" x 2" o/c) over the secondary barrier and allow to dry. 1 610 mm (2'-0") max. 3 4 200mm (8") min. Foundation with Drainage Strip - Application Sequence
Exsulation S5000 EXS.0.0.02B Dryvit adhesive in vertical notched trowel configuration applied over the secondary barrier Approved mechanical fixing Dryvit Backstop TM NT over Grid Tape TM Sheathing Mineral wool insulation slab reinforced with Panzer 15 or 20 Mesh prior to Standard Plus Mesh. in contract drawings. 2. Expansion joint is required along top of foundation if 610mm (2'-0") dimension is exceeded. 3. Notched trowel size minimum of 1 2" x 1 2", by maximum 2" on centre. 610 mm (2'-0") max. (see note 2) 200mm (8") min. Dryvit basecoat 4. Install Mechanical Fixings Slope grade away from foundation wall Dryvit Detail TM Mesh wrapped to backside of insulation slab min. 63.5 mm (2 1 2") Dryvit Aquaflash applied over barrier coating at foundation (see note 2) Foundation with Drainage Strip - Extended 2d View
Exsulation S5000 EXS.0.0.03 48" typ. Approved mechanical fastener and plate 24" typ. Fixing in centre Mineral wool insulation slab 1. Fixings are to penetrate concrete by no less than 1 inch or in accordance with fastener's specs. 2. Additional fasteners to be installed at corners and other system terminations (maximum 12" on centre). 3. Step 2 occurs following application of basecoat and reinforcement mesh. 4. It is recommended to puncture mesh and base coat at fastener location prior to installation. This will minimize "pull in" and surface deformation. MECHANICAL FIXINGS - Step 1 5. Fasteners may be installed while initial mesh and basecoat application is still wet. 12" typ. 12" typ. 6. Fasteners on outside of mesh should be spotted prior to the application of an additional basecoat over the entire surface. More coats may be required to achieve flat surface. Fixing in centre Basecoat 24" typ. MECHANICAL FIXINGS - Step 2 Mechanical Fixing Patterns
Exsulation S5000 EXS.0.0.04 Approved mechanical fixing Dryvit Drainage Strip set in dabs of AP Adhesive See Protection of Rough Opening as per EXS.0.0.06 and EXS.0.0.07 Dryvit adhesive in vertical notched trowel configuration applied over secondary barrier Mineral wool insulation slab notched to accommodate Drainage Strip, flashing, and AquaFlash System Wrap Dryvit Detail Mesh wrapped to backside of insulation slab min. 63.5 mm (2 1 2") Dryvit Demandit or Color Prime on surface(s) to receive sealant Dryvit compatible sealant with closed cell backer-rod and weep tubes every 600 mm (24"), by others 19 mm (3/4") min. Provide air seal, by others, around interior of window per window manufacturer's requirements Continuous flashing, by others Fillet caulk with bond breaker, by others Dryvit AquaFlash System Wrap Dryvit Detail Mesh wrapped to backside of insulation slab min. 63.5 mm (2 1 2") Continuous pan flashing with end dams, by others, see detail below Dryvit compatible sealant, by others 38mm (1-1/2") min. Sill Pan Flashing Detail BY OTHERS DRYVIT EXSULATION S5000 SYSTEM traffic, or deliberate impact reinforced with Panzer 15 on contract drawings. 2. Install Mechanical Fixings Head/Sill
Exsulation S5000 EXS.0.0.05 Dryvit Drainage Strip set in dabs of AP Adhesive Approved mechanical fixing Dryvit AquaFlash mesh embedded in Dryvit AquaFlash Liquid lapped over window flange See Protection of Rough Opening as per EXS.0.0.06 and EXS.0.0.07 Dryvit adhesive in vertical notched trowel configuration applied over secondary barrier Mineral wool insulation slab notched to accommodate Drainage Strip, flashing, and AquaFlash. Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab Dryvit Demandit or Color Prime on surface(s) to receive sealant Dryvit compatible sealant with closed cell backer-rod and weep tubes every 600 mm (24"), by others 19 mm (3/4") min. Provide air seal, by others, around interior of window per window manufacturer's requirements Window integral flashing Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab Dryvit compatible sealant, by others Dryvit AquaFlash System Dryvit Demandit or Color Prime on surface(s) to receive sealant 19 mm (3/4") min. BY OTHERS DRYVIT EXSULATION S5000 SYSTEM ground floor applications traffic, or deliberate impact reinforced with Panzer 15 Standard Plus mesh. zones should be indicated 2. Additional head flashing may be necessary for windows that are not self flashing. Sill pan flashing, by others Dryvit AquaFlash Transition flashing 3. Install Mechanical Fixings Drainable Sill Option Head/Sill for Self Flashing Window Options
Exsulation S5000 Substrate and sheathing assembly EXS.0.0.06 Application Sequence and 1. Apply water-resistive barrier (WRB) over sheathing and into rough opening. Dryvit AquaFlash System 1 2 63.5mm (2 1 2") min. 3 2. Embed Detail Mesh into WRB, stopping at sill. Embed diagonal mesh as shown at all corners. 3. Once embedment is complete, apply WRB over remainder of the substrate as illustrated. 4. Apply AquaFlash and AquaFlash mesh as per DSC196 - Sills only if WRB is applied around the balance of the rough opening. AquaFlash is applied using a brush or deep-nap roller. Embed AquaFlash Mesh into wet AquaFlash and allow to set. 4 63.5mm (2 1 2") min. 4th* (See Note) Mesh embedded in water-resistive barrier Apply second coat fully covering the AquaFlash Mesh. Alternatively, Dryvit's Flashing tape or EIFS tape may be used and is applied around the entire rough opening, but not returning to the header. See illustration below. 3rd 2nd Apply 1st Min. 2" EIFS Tape Application Protection of Rough Openings * Water-resistive barrier to be applied over EIFS tape with a positive lap of 2" minimum.
Exsulation S5000 Step #1 Step #2 Step #3 EXS.0.0.07 63.5mm min. Install AquaFlash System at sill (see note 2) Install sill pan flashing Install Dryvit AquaFlash Mesh embedded in AquaFlash at head and over upturned pan flanges Step #4 Step #5 Apply AquaFlash Mesh and AquaFlash over Flashing 1. The AquaFlash System is a combination of AquaFlash Liquid used in conjunction with AquaFlash Mesh to seal substrates around windows, doors and other openings. Install flashings at head 2. Install AquaFlash System (including diagonal "butterflies") onto sill and allow to dry. 3. Alternatively, Dryvit Flashing Tape or EIFS tape may be used. Install Dryvit AquaFlash Mesh embedded in at jambs. Refer to EXS.0.0.08 for jamb detail Rough Opening and Sill Preparation - AquaFlash System
Exsulation S5000 EXS.0.0.08 BY OTHERS DRYVIT EXSULATION S5000 SYSTEM Mineral wool insulation slab Air Seal Approved Substrate 19 mm (3/4") min. Dryvit Grid Tape in Dryvit Demandit or Color Prime on surfaces to receive sealant Continuous Dryvit compatible sealant and closed cell backer-rod, by others Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab Dryvit adhesive in vertical notched trowel configuration reinforced with Panzer 15 2. Install Mechanical Fixings Jamb
Exsulation S5000 EXS.0.0.09 Framing Roof assembly Parapet cap sheet Approved mechanical fixing Metal cap flashing, by others Dryvit AquaFlash system Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab 63.5 mm (2-1/2") min. Dryvit compatible sealant with bond breaker, by others (see note 2) reinforced with Panzer 15 2. Ensure parapet capping is water tight if sealant is to be applied here. Otherwise extend capping overlap as required to avoid moisture migration behind system. 3. Install Mechanical Fixings Dryvit adhesive in vertical notched trowel configuration applied over secondary barrier Mineral wool insulation slab BY OTHERS DRYVIT EXSULATION S5000 SYSTEM Parapet - Cap Flashing
Exsulation S5000 EXS.0.0.10 Mineral wool insulation slab Dryvit AquaFlash Mesh embedded in Dryvit Drainage Strip Flashing sleeve shown in exploded view 4" (102mm) 6" (153mm) Dryvit compatible sealant w/ closed cell backer rod and weep tubes every 600 mm (24") by others. Roof flashing and counter flashing, by others 4" (102mm) 6" (153mm) Metal coping flashing at parapet wall Dryvit Exsulation S5000 System Aluminium reglet Roofing System traffic, or deliberate impact reinforced with Panzer 15 2. Lap all flashing and water-resistant barriers in shingle fashion. 3. Use Dryvit AquaFlash System at wall/sleeve transition. 4. Install Mechanical Fixings Parapet/Wall Termination
Exsulation S5000 EXS.0.0.11 Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab 200 mm (8") min. Parapet cap sheet Metal cap flashing (by others) Dryvit compatible sealant (by others) Roof flashing and counter flashing, by others Roof assembly Dryvit AquaFlash Mesh embedded in AquaFlash Liquid as water-resistive Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab Dryvit compatible sealant, by others (see note 3) Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab 63.5 mm (2-1/2") min. Approved mechanical fixing reinforced with Panzer 15 2. If system on back of parapet exceeds 610mm (2'-0") in height, provisions for drainage are required along wall base. 3. Ensure parapet capping is water tight if sealant is to be applied here. Otherwise extend capping overlap as required to avoid moisture migration behind system. 4. Install Mechanical Fixings BY OTHERS DRYVIT EXSULATION S5000 SYSTEM Parapet - Solid Substrate
Exsulation S5000 EXS.0.0.12 BY OTHERS DRYVIT EXSULATION S5000 SYSTEM Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab reinforced with Panzer 15 2. Bottom edge of Dryvit Drainage Strip shall be masked during installation to prevent clogging of drainage channels. 3. Install Mechanical Fixings embedded in Dryvit water-resistive barrier coating Approve mechanical fixing 19 mm (3/4") min. Dryvit Drainage Strip Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab. Do not block Drainage Strip with base coat. Soffit/Fascia Intersection
Exsulation S5000 EXS.0.0.13 Dryvit Detail Mesh embedded in BY OTHERS DRYVIT EXSULATION S5000 SYSTEM Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab Approved mechanical fixing Wrap Dryvit Detail Mesh 63.5mm (2 1 2") min. at backside of insulation slab Dryvit Drainage Strip 25 mm (1") max. reinforced with Panzer 15 2. Soffits without mineral wool insulation require expansion joints every 6 m (20 ft). 3. Refer to Dryvit publication DSC173 for specific requirements for soffit areas. 4. Bottom edge of Dryvit Drainage Strip shall be masked during installation to prevent clogging of drainage channels. 5. Install Mechanical Fixings Soffit - Uninsulated
Exsulation S5000 BY OTHERS DRYVIT EXSULATION S5000 SYSTEM EXS.0.0.14 Dryvit reinforcing mesh embedded in Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab Reinforcing mesh 200mm (8") min. (see notes 2 and 3) reinforced with Panzer 15 2. Double wrap outside corners with reinforcing mesh or use Corner Mesh. 3. Do not lap reinforcing mesh within 200mm (8") of a corner. 4. Install Mechanical Fixings Approved mechanical fixing 200mm (8") min. (see notes 2 and 3) Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab Must overlap 200 mm (8") min. See above and notes 2 and 3 embedded in Dryvit water-resistive barrier coating Inside/Outside Corners
Exsulation S5000 EXS.0.0.15 Dryvit adhesive in vertical notched trowel configuration embedded in Dryvit water-resistive Mineral wool insulation slab Dryvit base coat Dryvit Panzer reinforcing mesh Dryvit base coat Corner render profile reinforced with Panzer 15 2. Install Mechanical Fixings Dryvit corner mesh Dryvit Standard Plus reinforcing mesh overlap min. 200 mm (8") at corner Dryvit base coat 200 mm (8") min. Outside Corner - High Impact
Exsulation S5000 1 Apply coat of Dryvit water-resistive barrier onto substrate EXS.0.0.16A reinforced with Panzer 15 2. Install Mechanical Fixings 2 Dryvit Aquaflash System applied over at floorline joint Closed-cell backer-rod 3 Apply Detail Mesh at system termination so to extend fully behind insulation 63.5 mm (2 1 2") Apply Dryvit adhesive in vertical notched trowel configuration over backwrapping mesh and allow to dry. 4 Dryvit base coat Dryvit Mesh embedded in base coat Dryvit base coat Approved mechanical fixing (see note 2) Mineral wool insulation slab Floorline Detail - Application Sequence
Exsulation S5000 EXS.0.0.16B Vertically applied adhesive Dryvit base coat Dryvit mesh embedded in base coat Dryvit base coat reinforced with Panzer 15 2. Install Mechanical Fixings Approved mechanical fixing on insulation slab Lamella notched to accomodate Drainage Strip and AquaFlash System Slope bottom surface for positive drainage Dryvit Detail Mesh prewrapped and Dryvit AquaFlash System lapped onto lower section and terminating at sealant bond line Dryvit AquaFlash System Closed cell backer-rod Horizontal Slip Joint - Extended 2d View
Exsulation S5000 EXS.0.0.17 Slip type connection Closed cell backer-rod BY OTHERS Dryvit AquaFlash System Dryvit AquaFlash System applied over top of previous coat and extended towards bottom sloped surface for drainage DRYVIT EXSULATION S5000 SYSTEM Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab Dryvit compatible sealant with closed cell backer-rod, by others 19 mm (3/4") min. Slope bottom surface for positive drainage Dryvit Demandit or Color Prime on surfaces to receive sealant Wrap Dryvit Detail Mesh 63.5 mm (2 1 2 ") min. at backside of insulaion slab Approved mechanical fixing reinforced with Panzer 15 2. Expansion joint in the Exsulation S5000 System is necessary where significant differential movement is expected at floor lines. 3. Locate external sealant joint within 50 mm (2") of break in sheathing. 4. Apply Dryvit AquaFlash System over prepared joint at change in substrate. 5. Install Mechanical Fixings Horizontal Slip Joint
Exsulation S5000 EXS.0.0.18 Approved Substrate Mineral wool insulation slab Backer-rod reinforced with Panzer 15 2. Install Mechanical Fixings Sealant and backer-rod 50.8mm (2") min. 25.4mm (1") min. Drainage space Dryvit water resistive AquaFlash System Exterior face of system Drain opening Two-Stage Joint - Extended 2d
Exsulation S5000 EXS.0.0.19 19 mm (3/4") min. Interior seal, by others BY OTHERS DRYVIT EXSULATION S5000 SYSTEM Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab Dryvit Demandit or Color Prime on surfaces to receive sealant Dryvit compatible sealant withclosed cell backer-rod, by others Mineral wool insulation slab Dryvit adhesive in vertical notched trowel configuration Dryvit compatible sealant with closed cell backer-rod, by others Dryvit Demandit or Color Prime on surfaces to receive sealant Dryvit AquaFlash System (see note 2) Wrap Dryvit Detail Mesh 63.5 mm (2 1 2") min. at backside of insulation slab Dryvit AquaFlash System (see note 2) Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab Interior seal, by others 19 mm (3/4") min. traffic, or deliberate impact reinforced with Panzer 15 2. Sealant should not be in direct contact with the AquaFlash System. 3. Apply water-resistive barrier over remainder of wall surface. 4. Install Mechanical Fixings Structural Expansion Joints
Exsulation S5000 EXS.0.0.20 BY OTHERS DRYVIT EXSULATION S5000 SYSTEM barrier coating AquaFlash System Dryvit Demandit or Color Prime on surfaces to receive sealant Dryvit compatible sealant with closed cell backer-rod, by others reinforced with Panzer 15 2. Install Mechanical Fixings 19 mm (3/4") min. Secondary seal, by others 19 mm (3/4") min. Dryvit Demandit or Color Prime on surfaces to receive sealant Wrap Dryvit Detail Mesh 63.5 mm (2 1 2 ") min. at backside of insulation slab Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab Penetrations
Exsulation S5000 EXS.0.0.21 reinforced with Panzer 15 2. Locate insulation boards such that board edges do not align with corners of penetration. 3. Apply a piece of 240 mm (9 1/2") x 300 mm (12") detail reinforcing mesh diagonally at each corner. Mineral wool insulation slab 4. Install Mechanical Fixings Wrap insulation slab with Dryvit Detail Reinforcing Mesh Dryvit Detail Reinforcing Mesh 240 mm (9 1/2") x 300 mm (12") (typ.) Wall Penetrations
Exsulation S5000 Installation Instructions: EXS.0.0.22 1. Pre-drill through EIFS stopping at water-resistive barrier. 2. Cut sleeve to equal depth of system from WRB to outside face. Framing member Approved substrate 13 mm (1/2") min. Dryvit adhesive in vertical notched trowel configuration Lamella 3. Gun neutral cure silicone sealant into hole and insert sleeve. 4. While sealant is wet, install fastener and tool sealant around edges as shown. Non-corrosive pipe sleeve Blocking (secure to framing) Screw/bolt attachment to building framing/ blocking Neoprene washer Sign fixture BY OTHERS DRYVIT EXSULATION S5000 SYSTEM BY OTHERS Dryvit compatible sealant and bond breaker tape, by others Sealant with bond breaker tape between sleeve and barrier coating, by others Sign Attachment
Exsulation S5000 EXS.0.0.23 19 mm (3/4") min. reinforced with Panzer 15 EPS (See note 4) Framing member Mineral wool insulation slab Approved mechanical fixing 63.5 mm (2 1/2") Dryvit adhesive in vertical notched trowel configuration Dryvit Detail Mesh 2. Slope bottom edge of reveal for positive drainage. 3. Install Mechanical Fixings 4. EPS can be used at reveal location. This must be pre-approved by design authority. BY OTHERS DRYVIT EXSULATION S5000 SYSTEM Aesthetic Reveals
Exsulation S5000 EXS.0.0.24 Approved mechanical fixing Dryvit AquaFlash System Dryvit Drainage Strip BY OTHERS 19 mm (3/4") min. DRYVIT EXSULATION S5000 SYSTEM Dryvit adhesive in vertical notched trowel configuration Mineral wool insulation slab notched to accommodate Dryvit Drainage Strip, flashing, and Dryvit AquaFlash System lapped over flashing embedded in base coat Wrap Dryvit Detail Mesh 63.5 mm (2 1 2 ") min. at backside of insulation slab Dryvit Demandit or Color Prime on surface(s) to receive sealant Dryvit compatible sealant with closed cell backer-rod and weep tubes every 600 mm (24"), by others reinforced with Panzer 15 2. Install Mechanical Fixings Continuous flashing, by others Sealant with bond breaker, by others Secondary barrier extended behind flashing, by others Stone veneer system, by others Horizontal Joint at Stone Veneer
Exsulation S5000 EXS.0.0.25 VARIES Substrate Soffit vent by others VARIES reinforced with Panzer 15 2. Caulk all butt joints, intersections, and end of vents. 3. Install Mechanical Fixings Uninsulated Substrate Dryvit adhesive Soffit vent by others VARIES VARIES Mineral wool insulation slab Insulated Soffit vent