Speaker: Jarvis Penner. VAV Laboratory Airflow Control Solutions Venturi Valve vs. Single Blade Damper

Similar documents
VAV Laboratory Room Airflow The Lowdown on Turndown

Demand Based Static Pressure Reset Control for Laboratories

Venturi Air Valve or Single-Blade Damper What s Right for You?

Dual Maximum VAV Box Controls

ENHANCED LABORATORY HVAC SYSTEM

Basic Selection & Proper Application of Overhead Air Distribution Devices

Healthcare Solutions Room Pressure Monitors and Controls

Appendix B: VAV Controller Flow Calculation Constants

SAM HOUSTON STATE UNIVERSITY

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG March 24, 2010

MULTIZONE APPLICATION OF SOLUTION UNITS

SUMMARY of PRODUCTS. HVAC Systems Control Airflow, Space, & Building Pressurization. Accurate airflow measurement for demanding applications

HVAC Calculations and Duct Sizing

Centrifugal Fans and Pumps are sized to meet the maximum

Comparing Energy Savings of Different VAV Systems

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

ANSI/AHRI Standard 880 (I-P) with Addendum Standard for Performance Rating of Air Terminals

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

LABORATORY DESIGN HANDBOOK

Duct Design. Presented by Dave Janquart

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

AMD-33 Air Measuring Station with VCD-33 Control Damper

HVAC Air Duct Leakage. November 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Guide Specification for Laboratory Fume Hood Commissioning

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

HIGH EFFICIENCY RTU. HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

Acoustical Design Guidelines for HVAC Systems in Schools

Duct Leakage Testing. Ken Helfers, TSI Inc. 2011, TSI Incorporated

Metrics for Energy Efficiency

Fan Applications & System Guide

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Exhaust Calculation Booklet

ANSI/AHRI Standard 1350 (I-P) 2014 Standard for Mechanical Performance Rating of Central Station Air-handling Unit Casings

plenum slot diffusers

PIEZOMETER AIRFLOW MEASURING RING

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling

LEV Integrated with Mechanical Covers to Achieve Energy Savings

Welcome. Green HVAC Ductwork Done Right! John Reints, PE Eugene Smithart, PE

Metrics That Matter: Pam Greenley MIT EHS Associate Director Steve Lanou MIT Deputy Director, Sustainability

Chapter 12 Industrial Ventilation

LOW-PRESSURE-DROP HVAC DESIGN FOR LABORATORIES

SLIM LINE FUME HOOD MONITOR

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

HVAC. Kitchen Exhaust. rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier!

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

SECTION TESTING, ADJUSTING, AND BALANCING

SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.

LABORATORY FUME HOOD CONTROL SYSTEMS

AIR DISTRIBUTION FOR COMFORT AND IAQ

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14 Preparer: Owner: Approver: S/IH Team Leader S/IH Team Leader Manager LA Hub

PNEUMATIC CONTROLS Selection and Description

FIRE DAMPER APPLICATION GUIDE

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Testing Protocol for Differential Pressure Measurement Devices API MPMS Chapter 22.2

PRODUCT PROFILE FEATURES

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

Principles of Ventilation. Patrick N. Breysse, PhD, CIH Peter S.J. Lees, PhD, CIH Johns Hopkins University

NFPA Combustible Dust Compliance and the Industrial Ventilation System

Ventilation Standard For Health Care Facilities

Mechanical Systems Proposal revised

Answers to Your Questions from the Webinar

Pressure drop in pipes...

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE

VariTrane Duct Designer An in depth look...

Energy and Flow Measurement for Hydronic Systems

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Understanding How Cabinet Door Perforation Impacts Airflow by Travis North

AIR DISTRIBUTION ENGINEERING

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Mixing Valves. ARGUS Application Note: Mixing Valves

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

Fume Hood Questions and Answers

security products metric sizes Redefine your comfort zone.

Case Studies: Infrared Heating in Industrial Applications

LOCATING AIR INTAKES AND EXHAUSTS

15850 Laboratory and Industrial Ventilation Systems

Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums

On-Demand Ventilation Energy Saving in Industrial Applications

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

MEASURING RATES OF OUTDOOR AIRFLOW INTO HVAC SYSTEMS

Central Plant Air Systems: Keeping the Heart and. Title Style. Better Buildings Summit May 2016

Chapter 3.5: Fans and Blowers

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories

HVAC Basic Science - System Capacity

CHAPTER 4 VENTILATION

Damper Selection and Sizing

HVAC Design Industrial Ventilation

HVAC Processes. Lecture 7

General Information... 2

Degrees of Freedom In HVAC Controls Design BY JOHN VARLEY, P.E., HBDP, MEMBER ASHRAE

Technical Information

Chemical Fume Hoods. Environmental Health and Safety

FUME HOOD PERFORMANCE TESTING

Transcription:

Speaker: Jarvis Penner VAV Laboratory Airflow Control Solutions Venturi Valve vs. Single Blade Damper

Agenda Introduction Control Valve Fundamentals Control Valve Design Criteria Summary

Standards & Guidelines Primary Standards ANSI Z9.5 2012 ASHRAE 110 1995 NEBB Fume Hood Testing 2009 Related Standards ASHRAE 90.1 2010 NFPA 45

Laboratory Valves

Control Valve Fundamentals Airflow Control Valves Blade Damper Control Valve Direct airflow measurement using instream flow sensors Typical 6:1 turndown ratios Typically require three duct diameters of straight duct leading into and out of the valve

Control Valve Fundamentals Airflow Control Valves Venturi Valves Electronic flow feedback Mechanical pressure independent control valves Typical 16:1 turndown ratio No straight inlet/outlet duct run requirements

Control Valve Fundamentals Mechanical Operation

Control Valve Fundamentals Pressure Dependent Positioning 500 CFM 500 CFM 0.5 WC 1 WC Increased airflow area Reduced airflow area Blade Damper Control Valve Airflow remains constant Damper position not constant

Control Valve Fundamentals Mechanical Pressure Independence Venturi Valve Expanded spring increased airflow area Compressed spring reduced airflow area Airflow remains constant Damper position constant

Control Valve Fundamentals Mechanical Pressure Independence Valve Calibration

Control Valve Fundamentals Airflow Control Concepts Closed Loop Control Blade Damper Control Valve A closed loop or feedback control measures actual changes in the controlled variable and actuates the controlled device to bring about a change. * *2005 ASHRAE Handbook Fundamentals of Control, Chapter 15

Control Valve Fundamentals Airflow Control Concepts Flow Characteristics of the Blade Damper Control Valve 100% Flow Quick opening characteristic 0% Closed Position Full Open In a closed loop flow control application, accuracy depends mainly on the airflow transducer but the resolution of the blade damper will greatly impact the flow measurement accuracy at low flows.

Control Valve Fundamentals Airflow Control Concepts Open Loop Control Venturi Valve Control An open-loop control does not have a direct link between the value of the controlled variable and the controller. An open-loop control anticipates the effect of an external variable on the system and adjusts the set point to avoid excessive offset. * Potentiometer *2005 ASHRAE Handbook Fundamentals of Control, Chapter 15

Control Valve Fundamentals Airflow Control Concepts Flow Characteristics of the Venturi Valve 100% Stable opening characteristic Flow 0% Closed Position Full Open In an open loop application, flow control depends entirely on the flow versus position relationship of the valve but control resolution is improved at low flows.

Control Valve Fundamentals Airflow Control Accuracy Air Flow Transducers Advantages Common in HVAC industry Relatively inexpensive Disadvantages Accuracy typically percent of full scale CFM Actual VP* Transducer Error Measured VP Measured CFM Error 1000 0.4522 0.01 0.4622 1011 1.1 % 500 0.1131 0.01 0.1231 521 4.2 % 200 0.0181 0.01 0.0281 249 24.5 % 100 0.0045 0.01 0.0145 179 79.0 % *Size 10 blade damper control valve; K-Factor = 1487

Control Valve Fundamentals Airflow Control Accuracy Factory Valve Calibration 48 point characterization N.I.S.T.* traceable equipment +/- 5% accuracy Calibrated Flow Range Error 30 scfm to < 100 scfm 4.0% 101 scfm to < 250 scfm 2.5% 251 scfm to < 5000 scfm 1.4% *National Institute of Standards and Technology

Control Valve Fundamentals Airflow Sound Valve Size Flow (CFM)** Terminal Discharge NC Value* Terminal Radiated NC Value * Venturi Discharge NC Value* Venturi Radiated NC Value* Size 8 400 21 21 31 23 Size 10 750 25 21 37 29 Size 12 900 27 21 32 24 Size 14 1500 26 26 41 44 *Test data obtained in accordance with AHRI Standard 880-2011 and ASHRAE Standard 130-2008 *NC values are calculated based on typical attenuation values outlined in Appendix E, AHRI Standard 885-2008 ** Flow measurements taken at 1.5 in.w.c.

System Objectives Safety Speed of Response Reduce Operating Costs Airflow Capacity Minimum Operation Pressure

Speed of Response ANSI Z9.5 2012 Section 6.5.3.2 VAV Response shall be sufficient to increase or decrease flow within 90% of the target flow or face velocity in a manner that does not increase potential for escape A response time of < 3 sec. after completion of the sash movement is considered acceptable for most operations. Faster response times may improve hood containment following the sash movement.

Speed of Response ANSI Z9.5 2012 Section 6.5.3.2 VAV Response shall be sufficient to increase or decrease flow within 90% of the target flow or face velocity in a manner that does not increase potential for escape A response tie of <3 sec. after completion of the sash movement is considered acceptable for most operations. Faster response times may improve hood containment following the sash movement.

Speed of Response ASHRAE 110-1995 - Section 6.4 The sash shall be fully opened in a smooth motion at a velocity between 1.0 ft/s and 1.5 ft/s. The time it takes from the start of the sash movement until the sash reaches the top and the time it takes from the start if the sash movement until the face velocity reaches and maintains, within 10%, the design face velocity shall be recorded

Speed of Response ASHRAE 110-1995 - Section 6.4 The sash shall be fully opened in a smooth motion at a velocity between 1.0 ft/s and 1.5 ft/s. The time it takes from the start of the sash movement until the sash reaches the top and the time it takes from the start if the sash movement until the face velocity reaches and maintains, within 10%, the design face velocity shall be recorded

Speed of Response NEBB Fume Hood Performance Testing - Section 9.3 VAV hoods are also to be tested to determine response time to return to a near steady state condition after a change in sash position. The response time test involves 3 cycles of opening and closing the sash position from full closed to the operating sash position. When changing the sash position, use a smooth continuous motion and move the sash at a rate of approximately 1.5 ft/s. Measure, record and report the VAV Speed of Response Time to first obtain a velocity equal to 90% of the baseline for each iteration.

Speed of Response NEBB Fume Hood Performance Testing - Section 9.3 VAV hoods are also to be tested to determine response time to return to a near steady state condition after a change in sash position. The response time test involves 3 cycles of opening and closing the sash position from full closed to the operating sash position. When changing the sash position, use a smooth continuous motion and move the sash at a rate of approximately 1.5 ft/s. Measure, record and report the VAV Speed of Response Time to first obtain a velocity equal to 90% of the baseline for each iteration.

Speed of Response 119 1200 99 1000 79 800 PERCENT 59 0.8 Seconds 600 CFM Sash position Airflow 39 400 19 200-1 0 2 3 4 5 6 7 8 SECONDS Venturi Valve Time from completion of sash movement *Results from testing completed at Engineered Air Balance Laboratory, Houston - 2014

Speed of Response 119 1200 99 1000 79 800 PERCENT 59 2.5 Seconds 600 CFM Sash position Airflow 39 400 19 200-1 0 2 3 4 5 6 7 8 SECONDS Venturi Valve Time from start of sash movement *Results from testing completed at Engineered Air Balance Laboratory, Houston - 2014

Speed of Response 119 1200 99 1000 79 800 PERCENT 59 39 19 1.25 Seconds 600 400 200 CFM Sash position Airflow -1 2 3 4 5 6 7 8 0 SECONDS Blade Damper Control Valve Time from completion of sash movement *Results from testing completed at Price Research Center North, Winnipeg - 2014

Speed of Response 119 1200 99 1000 79 800 PERCENT 59 39 19 3.1 Seconds 600 400 200 CFM Sash position Airflow -1 2 3 4 5 6 7 8 0 SECONDS Blade Damper Control Valve Time from completion of sash movement *Results from testing completed at Price Research Center North, Winnipeg - 2014

Airflow Capacity Laboratory spaces are subject to high makeup airflow rates, especially if the room has multiple fume hoods. Designing diversity into laboratories can allow for the ability to downsize equipment and reduce operating costs. Diversity = Actual Volume Flowrate Total Installed Exhaust Capacity

Airflow Capacity The biggest driver of lab energy is make up air delivered to the space What are the drivers of outside air in labs? Fume Hood airflow requirements Thermal loads Ventilation rates For many VAV labs the minimum hood exhaust rate is a bigger factor in reducing energy usage than face velocity

Airflow Capacity Lab valve/boxes need proper sizing Hood valve sized to cover min to max flow Supply range based on lab design General exhaust sized for cooling & efficiency

Airflow Capacity ANSI Z9.5-2003 ANSI Z9.5-2012

Airflow Capacity ANSI Z9.5-2003 Approx. 10 cfm/ft^2 ANSI Z9.5-2012

Fume Hood Minimum Exhaust Airflow Example: A typical bench type fume hood has a working depth of approximately 2 feet. Airflow necessary to maintain 25 cfm per square foot of internal work surface for each linear foot of width becomes: 2 ft (Depth) 1 ft (Width) 25 cfm/ft2 = 50 cfm

Fume Hood Minimum Exhaust Airflow Example: A typical bench type fume hood has a working depth of approximately 2 feet. Airflow necessary to maintain 25 cfm per square foot of internal work surface for each linear foot of width becomes: 2 ft (Depth) 1 ft (Width) 25 cfm/ft2 = 50 cfm Airflow necessary to maintain 10 cfm per square foot of internal work surface for each linear foot of width becomes: 2 ft (Depth) 1 ft (Width) 10 cfm/ft2 = 20 cfm

Fume Hood Minimum Exhaust Airflow Example: Constant volume at 300 CFM Flow in CFM 1000 800 600 400 200 0 3" 18" Sash Position Fume Hood Exhaust A 6 foot hood would give a min flow of 300 CFM Affects flow rates at minimum or closed sash positions

Fume Hood Minimum Exhaust Airflow Example: Constant volume at 120 CFM Flow in CFM 1000 800 600 400 200 0 1.2" 18" Sash Position Fume Hood Exhaust A 6 foot hood would give a min flow of 120 CFM Affects flow rates at minimum or closed sash positions

Fume Hood Minimum Exhaust Airflow Example: Constant volume at 120 CFM Flow in CFM 1000 800 600 400 200 0 1.2" 18" Sash Position Fume Hood Exhaust A 6 foot hood would give a min flow of 120 CFM Affects flow rates at minimum or closed sash positions Does not affect face velocity

Fume Hood Maximum Exhaust Airflow Example: ANSI Z9.5 recommends and average face velocity of 80-120 fpm Exhaust airflow needed to maintain an average face velocity of 100 fpm for each foot of sash width is: 1.5 ft (Height) 1 ft (Width) 100 ft/min = 150 cfm Fume hood with a fully open vertical sash will have a maximum exhaust airflow of approximately 150 cfm for every foot of sash width.

Fume Hood Maximum Exhaust Airflow Example: ANSI Z9.5 recommends and average face velocity of 80-120 fpm Exhaust airflow needed to maintain an average face velocity of 100 fpm for each foot of sash width is: 1.5 ft (Height) 1 ft (Width) 100 ft/min = 150 cfm Fume hood with a fully open vertical sash will have a maximum exhaust airflow of approximately 250 cfm for every foot of sash width. A 6 foot hood would give a max flow requirement of 900 CFM.

Airflow Capacity The fundamental selection criteria for a flow control device is the range of flow rates Sizing Parameter Maximum Airflow Minimum Airflow Blade Damper Control Valve Venturi Valve Criteria Typical Valve Criteria Typical Valve System may be considered too loud or have too a high pressure drop The flow sensor may be inaccurate due to low velocity pressures 1,000-3,000 fpm. 0-500 fpm. Calibrated flow when actuator fully open. Calibrated flow when the actuator fully closed. 1,700-1,900 fpm. 100-200 fpm.

Airflow Turndown Airflow turndown is commonly used to express the airflow control range without the need to have specific max and min flow rates A valve with a turndown of 16:1 does not equate to double the airflow of a valve with an 8:1 turndown.

Airflow Capacity A blade damper control valves typically have a larger airflow capacity than a venturi air valve of the same diameter but the turndown ratio is reduced due to the increase in minimum airflow. Valve Size Terminal Unit Terminal Turndown Low Pressure Valve Low Pressure Turndown Medium Pressure Valve Medium Pressure Turndown Size 8 130-800 6:1 35 500 14:1 35 700 20:1 Size 10 220-1350 6:1 50 550 11:1 50 1000 20:1 Size 12 300-2100 7:1 90 1200 13:1 90 1500 16.5:1 Size 14 440-3000 7:1 200 1400 7:1 200 2500 12.5:1

Fume Hood Valve Selection Example: Old Criteria ANSI Z9.5 2003 Using the 6 foot hood example, a turn down of 3:1 is required to achieve the full range of 300 900 CFM for the hood. Valve Selection: or Size 12 Venturi Valve Low Pressure 90-1200 CFM Size 10 Blade Damper Control Valve 220-1350 CFM Both valves can achieve the required minimum turndown and maximum flow for the fume hood

Fume Hood Valve Selection Example: New Criteria ANSI Z9.5 2012 Using the 6 foot hood example, a turn down of 7.5:1 is required to achieve the full range of 120 900 CFM for the hood. Valve Selection: or Size 12 Venturi Valve Low Pressure 90-1200 CFM Size 10 Blade Damper Control Valve 220-1350 CFM At $7.5/CFM/yr*, selection of the venturi valve will give a savings of ~$500/yr if sash is closed 70% of the time *http://fumehoodcalculator.lbl.gov/

Operating Pressure Minimum pressure drop is an important parameter of an airflow control device. It is the pressure drop across a fully open device at a given airflow rate.

Operating Pressure The minimum pressure drop depends on the size of the airflow area. Sizing Parameter Maximum Pressure Drop Blade Damper Control Valve Venturi Valve Criteria Typical Valve Definition Typical Valve Above this pressure, control may become difficult. Dampers have been applied successfully at 6 in. WC of drop. At this pressure drop, the spring can no longer regulate airflow. 3 in. WC for all available Venturi air valves. Minimum Pressure Drop Pressure measured across the fully open damper at a rated flow. Usually less than 0.1 in. WC. At this pressure drop, the spring can no longer regulate airflow. 0.6 in. WC for medium pressure valves or 0.3 in. WC for low pressure valves.

Operating Pressure

Pressure Drop Cost of Static Pressure Loss The fan power is directly proportional to the pressure loss; twice as much pressure consumes twice as much power Fan Power = Airflow x Fan Pressure Fan Efficiency Valve Type Operation Pressure (in. WC) Fan Power (kw) * Blade Damper Control Valve 0.1 0.017 Low Pressure Venturi Valve 0.3 0.052 Medium Pressure Venturi Valve 0.6 0.1 *Per 1000 cfm assuming 70 % fan efficiency

Pressure Drop Example Assume a laboratory has 20 fume hoods on a 18,000 CFM system. Using the same fan efficiency of 70%,the difference in kw between a blade damper control valve and venturi valve would be as follows Fan Power = Airflow x Fan Pressure Fan Efficiency Blade Damper Control Valve = 0.306 kw Low Pressure Venturi Valve = 0.936 kw Savings by selecting the blade damper control valve would be at most $550/year* *Assuming 10 cents/kwh and a total annual usage of 8760 hours

Pressure Drop Example Using the same example of a laboratory has 20 fume hoods on a 18,000 CFM system that are sized the same as the previous Air Capacity example. 20 Fume Hoods x $500 Savings/hood = $10,000 This shows that reducing the airflow provides a significantly higher impact to the potential savings from reducing the system static pressure.

Summary Required speed of response for fume hood control can be achieved using both blade damper and venturi control valves depending on what test standard is to be applied. Cutting flow is the most effective way to reduce energy consumption in a laboratory and with changes to minimum hood flow rates in ANSI Z9.5, venturi valves can provide additional savings over terminal units. Delivering air more efficiently by minimizing system static pressure comes second to reducing airflow rates to lower energy costs.

Summary Questions & Discussion