AIR DISTRIBUTION ENGINEERING
|
|
|
- Jean Alexis Lane
- 10 years ago
- Views:
Transcription
1 AIR DISTRIBUTION ENGINEERING a1 a1-1
2 a1 Table of Contents Terms & Definitions...a1-...a1-3 Primary Jet...a1-3 Entrainment, Jet Interface, Primary Air, & Total Air...a1-4 Natural Convection Currents...a1-5 Return Intake, Room Air, & Performance of Supply Outlets...a1-6 Pressure Measurements...a1-7 Continuous Duct Applications...a1-8 Occupant Comfort...a1-9 Air Diffusion Performance Index ()...a1-9 GRD...a1-1 Air Diffusion Performance Index () Selection Guidelines...a1-11 Air Distribution Performance Index () Charts...a1-13 Overhead Perimeter Heating, Return and Exhaust Openings, & Acoustical Considerations...a1-14 References...a1-16 Engineering Terms & Definitions (Air Diffusion Performance Index): Statistically relates the space conditions of local temperatures and velocities to occupant s thermal comfort. The design goal in an office environment is to maintain high comfort levels by obtaining high values. In order to obtain high values, we must define a few terms for the selection procedure. CFM: Cubic feet per minute - a measurement of volumetric air flow rate. Clo: A unit used to express the thermal insulation provided by garments and clothing ensembles, where 1 clo =.155 m C/W (.88 ft h F/Btu). Coanda Effect: In the 193 s the Romanian aerodynamicist Henri-Marie Coanda ( ) observed that a stream of air (or other fluid) emerging from a nozzle tends to follow a nearby curved or flat surface, if the curvature of the surface or angle the surface makes with the stream is not too sharp. Entrainment: To draw in and transport (as solid particles or gas) by the flow of a fluid. FPM: Feet per minute - measure of air velocity. Insulation, Clothing / Ensemble (Icl): The resistance to sensible heat transfer provided by a clothing ensemble. Expressed in clo-units. L/s: Liters per second: A measurement of volumetric air flow rate. LwDIS: Discharge sound power level. a1- LwRAD: Radiated sound power level. Met: A unit used to describe the energy generated inside the body due to metabolic activity. It is defined as 58. W/m (18.4 Btu/h ft ) which is equal to the energy produced per unit surface area of an average person, seated at rest. The surface area of an average person is 1.8 m (19 ft ). Metabolic Rate (M): Rate of energy production of the body by metabolism, which varies with activity. Expressed in met units in this standard. NC: Noise criterion represented by NC curves that were developed to represent lines of equal hearing perception in all bands and at varying sound levels. Most air terminal products are currently specified and reported as a single number NC rating. Occupied Zone: The region normally occupied by people within a space, generally considered to be between the floor and 1.8m (6ft) above the floor and more than 1. m (3.3ft) from outside walls/windows or fixed heating, ventilating or air conditioning equipment and.3m (1ft) from internal walls. RC: Room Criteria represented by both a numerical value and a letter quality rating. The number represents the spectrum s speech interference level (SIL), and is obtained by taking the arithmetic average of the noise levels in the 5-, - and - Hz octave bands. The letter denotes the sound s quality as it might subjectively be described by an observer. Excellence in Air Distribution RH: The amount of water vapor actually in the air divided by the amount of water vapor the air can hold. Relative humidity is expressed as a percentage and can be computed in a variety of ways. One way is to divide the actual vapor pressure by the saturation vapor pressure and then multiply by to convert to a percent. SCIM: Abbreviation for Standard Cubic Inches per Minute with Standard conditions are defined as 14.7 psia and F. Sound Power Level (Lw or Pwl): The level, in db as a ratio relative to some reference level, at which a source produces sound, usually given in octave bands. The equation is as follows: Sound Power Level (PWL) = 1 log1 (Wsource/Wref) db where: Wref is 1-1 Watts and Wsource is sound power in Watts. Sound Pressure Level (lp or SPL): The level of sound energy, measured in db, at a specific location. The frequency range of the measurement or calculation must be indicated along with the sound level in db. The equation is as follows : Sound Pressure Level (SPL) = 1 log1 (P /Pref ) db, where: Pref = 1-5 Pa and P = sound pressure in Pa. WG: Inches of water gage - measure of pressure.
3 DECREASING a1 AIR DISTRIBUTION BASICS Primary Jet Extensive studies have shown that the air jet from free round openings, grilles, perforated panels, ceiling diffusers, and other outlets is defined by the Throw, Drop, and Spread,. Throw - The horizontal or vertical axial distance an airstream travels after leaving an air outlet before the maximum stream velocity is reduced to a specific terminal value (15,, 5 fpm). Drop - The vertical distance that the lower edge of a horizontally projected airstream drops between the outlet and the end of its throw. Spread - The divergence of the airstream in a horizontal or vertical plane after it leaves the outlet. The primary air jet is defined as the air delivered to a room through the supply duct plus the entrained room air that lies within an envelope of arbitrary velocity, usually taken as some value between 5 and 15 fpm. The jet discharged from the free opening has four zones of expansion. The centerline velocity of this primary jet in any zone is related to the initial velocity (See Figure: Throw & Drop of Free Air Jet ). Regardless of the type of outlet, the airstream will tend to assume a circular shape in free space, provided the jet does not impinge on or flow along a boundary or surface. In many cases, isothermal jet performance can be analyzed to determine the following. Angle of Divergence or Spread Velocity Patterns Along the Jet Axis Velocity Profile at Any Cross-section in the Zone of Engineering Significance Entrainment Ratios in the Same Zone The angle of divergence is usually well defined near the outlet face with the boundary contours becoming billowy and poorly defined as the velocity nears the terminal velocity of -5 fpm (See Figure: Spread of Free Air Jet ). External forces, local eddies, and surges easily influence the boundary. The zones of expansion for an isothermal jet can be described as follows. (See Figures: Expansion Zones & Centerline Velocities of Axial & Radial Jets) Zone 1 - A short zone, extending about four duct diameters from the outlet face (or vena contract for orifice discharge) in which the maximum velocity of the airstream, or the centerline velocity, remains practically unchanged. EXPANSION ZONES PRIMARY AIR I II III IV TOTAL AIR ZONES HIGH VELOCITY INDUCED ROOM AIR GENTLE MOVEMENT GREATEST POSSIBLE SOURCE OF DRAFTS THROW & DROP OF FREE AIR JET CENTERLINE VELOCITIES OF AXIAL & RADIAL JETS 1. SPREAD ISOVEL LINE CONSTANT VELOCITY THROW DROP ZONE I ZONE II 15 fpm fpm SPREAD OF FREE AIR JET V X / V ZONE III THROW SPREAD TERMINAL VELOCITY ENVELOPE 5 fpm ZONE IV ANGLE OF DISCHARGE X A o INCREASING V o - Outlet Velocity A o - Outlet Area X - Throw Distance V x - Terminal Velocity Providing You With Air Distribution Solutions a1-3
4 a1 Zone - A transition zone, extending about eight duct diameters for round outlets or for rectangular outlets of small aspect ratio, over which maximum velocities vary inversely as the square root of the distance from the outlet. For rectangular outlets of large aspect ratio, this zone is elongated and extends from about four widths to a distance approximately equal to the width multiplied by four times the aspect ratio. Zone 3 - A long zone of major engineering importance in which the maximum velocities vary inversely as the distance from the outlet. This zone is often called the zone of fully established turbulent flow and may be 5- duct diameters long, depending on the shape and area of the outlet, the initial velocity and the dimensions of the space into which the outlet discharges. Zone 4 - A terminal zone, in the case of confined spaces, in which the maximum velocity decreases at an increasing rate, or in the case of large spaces free from wall effects, the maximum velocity decreases rapidly in a few duct diameters to a velocity below 5 fpm. Measured angles of divergence usually range from to 4 with an average value of. Entrainment As the primary jet discharges or exits from the outlet, it begins to induce the room air into the jet stream, exchanging the momentum of the jet to increase momentum in the room air. The entrainment increases the volumetric flow at a given section of the jet and increases the width of the jet causing spread. Jet Interference Jets discharging near obstructions, walls, ceilings, or near other jets may be influenced in several ways. Jets flowing parallel to a ceiling or wall will attach to the surface, so the maximum velocity will exist near the surface. Entrainment takes place along the surface of the half cone, or the free surface of the jet, which is known as the Coanda effect. The Coanda effect, or surface effect, creates a low-pressure region between the mass airflow and the ceiling or wall. The resulting higher pressure on the room side holds the airstream to the surface, which increases throw and decreases drop (See Figure: Jet Patterns ). As catalog data includes this effect, throw for most ceiling diffusers should be reduced by 3% if no ceiling is present. The interior layout, local sources of heat gain or loss, and outlet performance factors, all influence the final selection of an air distribution system. These all must be considered in selecting the type and location of the supply outlets. In an attempt to control room air motion, some basic principles of air delivery to a space must be understood. Primary Air Primary air is the starting point when laying out or investigating room air motion. By definition, primary air is the mixture of air supplied to the outlet and induced room air within an envelope of velocities greater than 15 fpm. The primary pattern can be completely defined by high velocity envelopes taken through two perpendicular planes. Data obtained isothermally (no temperature difference between the supply and room air) down a1-4 JET PATTERNS Excellence in Air Distribution THROW FREE ISOTHERMAL JET THROW ISOTHERMAL JET NEAR CEILING DROP THROW COOLING JET NEAR CEILING to a velocity of 15 fpm apply equally well for heating and cooling. Total Air Total air is the mixture of primary and entrained room air, which is under the influence of the outlet conditions. Normally, total air has a relatively high velocity, but it does not have a sharply defined lower limit. Even though the total air follows the general pattern indicated by the primary air, its spread and travel may not be in proportion to that of the primary air. Other factors, such as ceiling height, obstructions, and internal and external loads disturb the orderly course of the airstream. Temperature differences between total air and room air produce a buoyancy effect, which causes cool total air to drop and warm total air to rise. The most complete mixing of total air and room air occurs during isothermal conditions. Consequently, the type of outlet and location reduce buoyancy effects and increase the travel of total air (restricts drop) during cooling, when cool air is induced and mixed rapidly with the primary air. This also reduces stratification during heating, when warm air is induced and mixed rapidly with the primary air. In addition to the outlet type and location, buoyancy effects are dependent on the temperature differential between supply air and room air. Total air has a tendency to scrub surfaces near diffusers or
5 a1 air outlets. A near perfect situation can be envisioned where total air covers all of the walls and ceiling with a thin film. The occupied space would then be completely enclosed within an envelope of conditioned air. From the smudging standpoint, effective air distribution usually requires that the surfaces be used, no matter how desirable it might be to keep the total air off the surfaces. Since the total air within a confined space is affected by factors other than the outlet conditions, it is not subject to complete analytical treatment. However, it is possible to estimate the total air characteristics for cooling and heating within a free AIR MOTION CHARACTERISTICS OF OUTLETS IN OR NEAR FLOOR WITH NON-SPREADING VERTICAL JET INSIDE WALL COOLING PRIMARY AIR TOTAL AIR NATURAL CONVECTION CURRENTS AND ZONE RETURN INTAKE INTAKE 9' CEILING 6' 4' INTAKE HEATING space, which is a condition where the airstream does not come in contact with confining walls or ceiling until the airstream has been reduced to a low velocity. Natural Convection Currents Currents are created by buoyancy effects, which are caused by differences in temperature between room air and the air in contact with a warm or cold surface. Air in contact with a warm surface will rise; the air in contact with a cold surface will fall. These currents are caused not only by the windows and walls, but also by internal loads such as people, lights, machines, etc. In most cases, natural convection currents will not only affect the room air motion, but they can also play a major role in the comfort of a space. For example, convection currents falling down at the outside wall during the heating season can produce a feeling of coolness. EXPOSED WALL INTAKE INTAKE Stratification layers, as shown to the left, actually exist in practice and in many tests. A similar situation often occurs in practice, which is identified by a region where a layer of smoke, for visualization, will hang for some time. Whether a stagnant layer actually exists is not important, but the concept of a stagnant layer and zone leads to a better understanding of air distribution. It may be noted that the natural convection currents form a stagnant zone between the stagnant layer and the ceiling during cooling and between the stagnant layer and the floor during heating. Studies have shown that with well mixed air supply systems (typical ceiling supply and return systems), with less than 1.5 cfm/ft, the primary driver of room air motion is local convection sources, not the diffuser induced air currents. Room air motion is primarily dependent on room load, not diffuser air supply rate. As a result, room air motion levels with VAV (Variable Air Volume) systems at part load are comparable to those of CAV (Constant Air Volume) systems at the same load condition. ROOM AIR 9' CEILING 6' 4' HEIGHT AVERAGE ROOM VERTICAL TEMPERATURE TEMPERATURE SETPOINT TEMPERATURE F TEMPERATURE F The temperature gradient curves, as shown left, emphasize how some of the factors discussed are interrelated and how they affect the space temperature distribution. Where the air motion is uniform (between the total air and stagnant layer), the temperatures are approximately equal and uniform (as indicated by the almost vertical portion of the gradient). As the stagnant Providing You With Air Distribution Solutions a1-5
6 a1 layer is crossed, the temperatures in the stagnant zone vary considerably. The gradients in the stagnant zones show that the air is stratified in layers of increasing temperatures with an increase in space height. causes the total air to drop along the opposite wall and flow slowly for some distance across the floor. For heating, under the same airflow capacity, the total air does not descend along the opposite wall as far. The stagnant zone depends on natural currents, magnitude of the heating or cooling load, space construction and volume, and the area of exposure of the load, as in the case of internal loading. Consequently, the magnitude of the temperature variations between levels will be smaller in mild climates than in severe climates, as well as in spaces having exposed walls with greater resistance to heat flow with minimum internal loads. Hence, with no loading, the temperature gradient curves would be vertical, indicating that all of the air temperatures in the conditioned space are equal to the control temperature. Return Intake Return intakes typically affect only the air motion within its immediate vicinity. Even the natural convection currents may possess enough energy to overcome the draw of the intake. This does not mean that the return location is not important, but only that it has little effect on the room air motion. Room Air The room air motion diagram is completed when the remaining room air is shown to drift back toward the primary air and total air envelopes. The highest air motion in the space is in and near the primary and total air, while the most uniform air motion is between the total air and the stagnant layer. The lowest air motion is in the stagnant zone. Through careful selection, by limiting air temperature differential between supply and room air and by maintaining airflow rates high enough to ensure mixing through induction, adequate room air motion can be obtained while minimizing stratification in the occupied zone. The figure Air Motion Characteristics of Ceiling, Group A Diffusers shows a ceiling outlet application in which the total air movement is counteracted by the rising natural convection currents along a heated perimeter wall, compared to the descent along a cooler interior wall on the opposite side. These outlets discharge horizontally near the ceiling with significant spread, allowing the warmest air in the space to mix with the cool primary air far above the occupied zone. Therefore, these outlets are capable of handling relatively large quantities of air at large temperature differentials while providing acceptable levels of room air motion and temperature uniformity in the occupied zone. AIR MOTION CHARACTERISTICS OF HIGH SIDEWALL, GROUP A GRILLES A PLAN VIEW SIDE VIEW SECTION A-A COOLING SETPOINT - + TEMPERATURE F Performance of Supply Outlets Construction features of supply outlets vary significantly to accommodate several different applications. The following are examples of typical applications and the performance criteria required from the supply outlets as defined by Straub et. al. A HIGH SIDE WALL SECTION A-A HEATING SETPOINT - + TEMPERATURE F Group A: Horizontal Discharge Near Ceiling - This group includes high sidewall grilles, sidewall diffusers, ceiling diffusers and linear ceiling diffusers. The figure Air Motion Characteristics of High Sidewall, Group A Grilles shows a primary air envelope or isovel with a two-jet pattern for a high sidewall ceiling outlet. Outlet vane settings may cause a discharge in one, two, or three jets; however, the overall effect in each is the same. During cooling, the total air drops into the occupied zone at a distance from the outlet, which depends on air quantity, supply velocity, temperature difference between supply and room air, deflection setting, ceiling effect and type, and amount of loading in the space. Also revealed, for cooling, is a potential overthrow condition, which a1-6 AIR MOTION CHARACTERISTICS OF CEILING, GROUP A DIFFUSERS PLAN VIEW OUTLET Excellence in Air Distribution SIDE VIEW SECTION A-A SECTION A-A COOLING SETPOINT SETPOINT - + TEMPERATURE F HEATING - + TEMPERATURE F
7 a1 Group C: Vertical Discharge from or Near Floor - This group includes floor diffusers, low sidewall units, and linear grilles in the floor or windowsill. The figure Air Motion Characteristics of Floor Mounted Outlets with Vertical Discharge, Group C Grilles shows the similar type of vertical discharge from the floor region, however includes a wide spreading jet. This diffusing action of the outlet makes it difficult to project the cool air, but it also provides a greater area for induction of room air. Additionally, it AIR MOTION CHARACTERISTICS OF FLOOR MOUNTED OUTLETS WITH VERTICAL DISCHARGE: GROUP C GRILLES PROFILE COOLING OUTLINE 4 4 BLADE SETTING TOTAL AND ROOM AIR STAGNANT PRIMARY AIR ISOVEL HEATING STAGNANT OUTLET IN OR NEAR FLOOR, SPREADING VERTICAL JET AIR MOTION CHARACTERISTICS OF CEILING OUTLETS WITH VERTICAL DISCHARGE: GROUP E DIFFUSERS SIDE VIEW SIDE VIEW COOLING HEATING SETPOINT - + TEMPERATURE F SETPOINT - + TEMPERATURE F shows that a stagnant zone occurs outside the total air zone and above the occupied zone. Below, the temperature uniformity and room air motion is acceptable. This may not apply to larger zones; however, a distance of approximately 15 - between the drop region and the exposed wall is a conservative design value. In heating applications, the stagnant region is small due to the air being entrained in the immediate vicinity of the outlet, very close to the stagnant area. This is beneficial during heating because the induced air comes from the lower regions of the room. The result is greater temperature uniformity in the space when compared to other types of supply outlets during heating. Group E: Vertical Discharge from or Near Ceiling - This includes ceiling diffusers as well as linear diffusers and grilles designed for vertical downward air projection. The figure Air Motion Characteristics of Ceiling Outlets with Vertical Discharge, Group E Diffusers shows that in cooling, total air is projected vertically to the floor and continues along throughout the floor, leaving the stagnant area near the ceiling. During heating, the total airflow reaches the floor and folds back toward the ceiling. If the projected air does not reach the floor, a stagnant zone results. The Laminar Flow CFD Model on the next page shows vertical discharge from the ceiling of the non-turbulent laminar flow type diffusers. Laminar flow occurs when the discharge velocities leaving the diffuser are uniformly moving in the same direction at relatively low speeds. A large mass volume of low velocity air projects vertically to the floor without much change in overall air speed. The result is not a mixing type diffuser, but a laminar device that experiences very little entrainment from the space. This is especially important for clean air applications in such areas as hospital operating rooms, clean rooms, and critical work areas. See the Krueger Model 5 Series diffuser. The TAD CFD Model on the next page shows air discharge from the ceiling in a uniform, low velocity radial isovel. This is not considered to be a laminar device in that the air velocities are not moving in the same direction. Hence, this is a non-entraining radial displacement diffuser. The concept is to displace particulates away in the space in all directions without mixing, which is important in critical environments such as pharmaceutical laboratories, chemistry laboratories, animal holding rooms, isolation wards, clean rooms, etc. - where particulate control and air change effectiveness are high priority. See the Krueger Model TAD and RadiaFlo radial displacement diffusers. Pressure Measurements Engineers require pressure data for air outlets to properly size the air delivery system within a building. To size and balance air delivery systems, one must have an understanding of three types of pressure measurement. Static Pressure (Sp) - The outward force of air within a duct, measured in inches of water column. Velocity Pressure (Vp) - The forward moving force of air within a duct, measured in inches of water column. Providing You With Air Distribution Solutions a1-7
8 a1 Total Pressure (Tp) - The sum of the velocity and static pressures, measured in inches of water column. Tp = Vp + Sp. LAMINAR FLOW CFD MODEL TAD CFD MODEL Continuous Duct Applications The ASHRAE handbook does not give advice on the application of a series of diffusers/grilles along a section of duct. Experience has shown, however, that a successful design requires a constant diameter duct, rather than a constant velocity/stepped size duct, for the most uniform air delivery. As velocity pressure decreases, or as air is lost through diffusers/ grilles, the static pressure drop will decrease as well, due to duct friction, and actual static will increase slightly. In a good design, minimum static pressure will be reached at a point /3 of the way down the duct. Several rules are recommended for constant delivery along the entire duct run. The larger the supply duct, the better. Minimum diameter should be a function of desired length, not flow rate. Duct velocities should never exceed fpm. A constant duct diameter is required to achieve the required static regain. Stepping the duct to maintain duct velocity is not only counter-productive, but also results in less than optimal supply distribution. Required inlet pressures are very low. In most cases, less than. in. Sp is required (when properly ducted). A major source of noise has been found from pressure reducing/ balancing dampers required at the supply inlet to the large duct. Friction in the supply duct is beneficial. Interior fiberglass lining s rough surface allows smaller duct diameters than a smooth sheet metal duct. The air has to be turned to get the discharge perpendicular to the duct run. If not turned properly, air tends to pile up in the room at the end opposite the supply inlet. As there is some temperature rise on long runs, it may be beneficial to size the duct slightly smaller than optimal, which will result in more airflow at the far end than at the supply, which will allow a continuous btuh/ft, rather than cfm/ft supply flow. Outlet total pressure, referenced in the catalog performance tables, is the amount of total pressure required by the air source to push a given amount of flow (cfm) through a desired supply outlet. Total and static pressures are measured in the supply duct at a minimum of 1.5 duct diameters upstream of the outlet as per ASHRAE Standard. The procedure requires a traverse to assure that static regain is not affecting the data. In many cases, data must be taken as far as 1 upstream from large inlet diffusers that may tend to extract air. Alternatively, the ASHRAE procedure allows for measuring total pressure in a large plenum (with a short aerodynamic duct attached to the diffuser), and calculating pressure drop. This method is preferred for many types of diffusers. Return grille and duct pressures must be conducted with the air inlet located on a large flat surface, if that is the intended application. This can have a significant effect on reported pressure drop. Also, it is not proper to report the difference between a duct with and without the exhaust grille as the return pressure. This results in very low reported pressure drops. a1-8 Excellence in Air Distribution For duct mounted spiral duct grille applications, this has several implications. When properly sized (ie: large enough), a duct mounted grille s scoop damper may not be needed. As a result of static regain, undampered airflow may be essentially constant, but discharge throw will be at a slight angle. The vertical blades in the grille can be adjusted after installation to account for this, but there will be some increase in noise level from this adjustment. We have estimated this increase to be no more than 5 NC, and we estimate a slight (1%) increase in total pressure. (As the duct velocities should be low, velocity pressure will be low, and most of the increase will be in terms of static pressure.) If duct velocities are higher, or duct pressures vary (often the result of stepping down the duct size), some dampering will likely be required, further increasing the sound produced. The Krueger Model DMG Series performance data is therefore based on the Krueger Model 8 Grille Series performance data, with the NC increased by 5 and the total pressure increased by 1%. This will be a conservative estimate for most applications.
9 a1 Occupant Comfort Occupant Comfort Many applications for the spiral duct mounted grille will be near the ceiling. If within one diameter of a horizontal surface, the air pattern will likely attach itself to that surface, and the grille will exhibit a characteristic grille throw pattern (which is shown in the Krueger Model DMG Series of Duct Mounted Grilles performance data). When the duct is further than one duct diameter from an adjacent surface, the grille will have a free jet pattern. Testing shows that this will result in a 3% decrease in throw. When duct mounted linear diffusers are used in a length of continuous duct, similar rules apply. Ducts should not be stepped down, and if sufficiently large, air discharged will be at a relatively continuous rate. There will be some sideways deflection in the direction of airflow, except at the end of the run. In conclusion, maintaining a constant diameter (as large as practical) will result in the optimum application of grilles and diffusers along the run. Slight increases in grille sound levels and static pressure will result from optimizing discharge angles. The data provided for the Krueger Model DMG Series of Duct Mounted Grilles will probably be conservative, if the duct is large enough, and doesn t step down. (In many cases, the cost of the step-down transition is more than the cost of feet of straight duct. Typically, a constant diameter run of spiral is the same cost as one that is stepped.) For duct-mounted linear diffusers, again, a constant diameter duct is an optimal design. There will be some directionality to the jets that cannot be avoided. (Effective turning vanes have been engineered in the past, but never employed because of cost). When properly sized, scoops and balancing dampers may not be required. OCCUPANT COMFORT Room air distribution plays a very important role in providing comfort to the occupants of a building. Before understanding air distribution, one must understand what comfort means to occupants in a space. In typical commercial office environments, occupants are generally considered thermally comfortable when body heat loss equals the body s metabolic heat production without conscious involvement of the body s thermo-regulatory mechanisms, such as sweating or shivering. Body heat loss to the environment can be attributed to radiation, conduction, convection, or evaporation. In an attempt to provide acceptable comfort levels for occupants in a space, the designer or engineer is challenged by the variables that influence the heat transfer of the human body: Dry Bulb and Mean Radiant Temperatures Relative Humidity Air Movement Activity Level of the Occupants (Met Units) Insulating Value of Occupant Clothing A thermal comfort program based on the ASHRAE Thermal Comfort Standard (Standard 55-4) is available on Krueger s website, at The standard identifies STANDARD 55-4 COMFORT ENVELOPE thermal comfort based on clothing levels, a revised upper humidity level, and no minimum humidity level, compared to previous versions of the standard. Proper selection and location of air distribution devices (grilles, registers, diffusers) is key in the control of occupant comfort levels. Although other entities of the HVAC system are important, it is the space air distribution that directly impacts the average temperature and air movement within the occupied zone. The ability to control the air distribution will result in overall acceptable thermal comfort levels for all occupants within the space. Air Diffusion Performance Index () The relationship of room air motion and temperature as it relates to occupant comfort has been studied for years and continues today. Generally, occupant comfort can be achieved when the following conditions are maintained: Air Temperature Maintained Between 73 F - 77 F Relative Humidity Maintained Between 5% - % Maximum Air Motion within Occupied Zone (6 to 6 Vertical, within 1 of Walls) < 5 fpm Maximum Vertical Temperature Variation No Greater than 5 F from 6 to 6 Level Researchers evaluate occupant comfort primarily on the effects of local air motion (velocity), local temperature, and ambient temperature relative to the feeling of warmth or coolness. Criteria for the feeling of comfort at the neck vs. varying room temperatures vs. air velocities are shown in the graph on the next page. This graph represents what is known as effective draft temperature, which is expressed in the following equation: ø= (tx - tc) -.7 (Vx - 3) Where ø = Effective Draft Temperature tx = Local Air Temperatures, F tc = Ambient Temperature, (Average Room Temperature or Control Temperature, F) Vx = Local Air Velocity, fpm Providing You With Air Distribution Solutions a1-9
10 a1 PERCENTAGE OF OCCUPANTS OBJECTING TO DRAFTS IN AIR CONDITIONED ROOM Occupants objecting to the temperature and velocity conditions are represented by the percentage curves in the above graph. The dashed line indicates the difference between the feeling of heating and cooling. Research indicates that % of the occupants in a typical office environment would feel comfortable at -3 < ø < + with a velocity less than fpm. This % comfort criteria is represented by the shaded parallelogram. is for cooling mode conditions only. Heating conditions can be evaluated using ASHRAE Standard 55 guidelines. The technique uses isothermal throw data, determined under ASHRAE Standard, to predict what will happen under cooling conditions. Once space parameters are understood, proper air distribution devices can be selected to assure acceptable ratings. GRD SELECTION & DESIGN CONSIDERATIONS For the best thermal comfort conditions and the highest ventilation effectiveness in an occupied space, the entire system performance of air diffusers should be considered. This is particularly true for open spaces, where airstreams from diffusers may interact with each other and for perimeter spaces, where airstreams from diffusers interact with hot or cold perimeter walls. While throw data for individual diffusers are used in system design, an air diffuser system should maintain a high quality of air diffusion in the occupied space with low temperature variation, good air mixing and no objectionable drafts in the occupied space. Studies show that can be improved by moving diffusers closer together by specifying more diffusers for a given space and air quantity and by limiting the differential temperatures of supply air to room air. For VAV (Variable Air Volume) systems, the diffuser spacing selection should not be based on maximum or design air volumes, but rather on the air volume range in which the system is expected to operate most of the time. Based on the effective draft temperature equation, temperatures and velocities can be uniformly measured in an occupied space to determine the Air Diffusion Performance Index. ASHRAE Standard 113 provides a method for testing to determine these values, typically in a laboratory setting. The expresses the number of points at which the draft temperature satisfies the comfort criteria as a percentage of the total number of points. Thus, an occupied space with an rating of translates to % of the occupants will be comfortable when located anywhere within the occupied space (floor to 6 level). The higher the rating, the better. An greater than % is indicative of a well mixed air distribution system. In order to obtain an acceptable rating, the designer or engineer must study a variety of variables. Temperature Differentials of Supply and Room Air Outlet Type and Design Supply Air Volumetric Flow Rates Space and Diffuser Layout Design Heating and Cooling Loads The throw of a jet is defined as the distance from the outlet device to a point in the air stream where the maximum velocity occurring in the stream cross section has been reduced to a selected terminal velocity (vt). Catalog performance tables list terminal velocities at 15, & 5 fpm under isothermal conditions (except when noted otherwise). The throw distance of a jet is denoted by the symbol Tv, where the subscript number indicates the terminal velocity for which the throw is given. The characteristic room length L is generally defined as the distance from the outlet device to the nearest boundary wall in the principle horizontal direction of the airflow. However, where air injected into the room does not impinge on a wall surface, but mixes with air from a neighboring outlet, the characteristic length L is defined as one-half the distance between outlets plus the distance the mixed jets must travel downward to reach the occupied zone. The table to the left summarizes definitions of characteristic length for various air outlet devices. CHARACTERISTIC ROOM LENGTH FOR DIFFUSER TYPES Diffuser Type High Sidewall Grille Circular Ceiling Diffuser Sill Grille Ceiling Slot Diffuser Perforated, Louvered, Ceiling Diffusers Characteristic Length, L Distance to Wall Perpendicular to Jet Distance to Closest Wall or Intersecting Air Jet Length of Room in the Direction of the Jet Flow Distance to Wall or Midplane between Outlets Distance to Wall or Midplane between Outlets a1-1 Excellence in Air Distribution
11 a1 Selection Guidelines Optimal comfort levels in a space can be estimated using the various outlet types and different room loads. The recommendations in the following nine types of graphs cover cooling loads of up to Btuh/ft of floor surface. The loading is distributed uniformly over the floor up to about 7 Btuh/ft, lighting contributes about 1 Btuh/ft and a concentrated load against one wall that simulates a business machine or a large sun-loaded window supplies the remainder. The maximum condition is lower for the highest loads; however, the optimum design condition changes only slightly with the load. For a given diffuser type, the performance as a function of room load and /L has been studied in ASHRAE research, and is available in the ASHRAE Handbook of Fundamentals. Refer to the example graph to the right of a round pattern diffuser, such as Krueger s Model 14 Louvered Diffuser, which has a Type 3 Circular Ceiling Pattern indicating the performance. EXAMPLE: GRAPHICAL SELECTION GUIDE 1 Btuh/ft² Btuh/ft² 1.5 Btuh/ft².5 TYPE 1: SEMI-CIRCULAR PATTERN CEILING DIFFUSER TYPE : CROSS FLOW PATTERN CEILING DIFFUSER Btuh/ft² 5 Btuh/ft² 1 Btuh/ft² 5 Btuh/ft² 5 Btuh/ft² 51 Btuh/ft² TYPE 3: CIRCULAR CEILING PATTERN TYPE 4: CEILING SLOT DIFFUSER 1 Btuh/ft² T Btuh/ft².5 3 Btuh/ft² Btuh/ft² Btuh/ft² Btuh/ft² Providing You With Air Distribution Solutions a1-11
12 a1 TYPE 5: LIGHT TROFFER TYPE 6: HIGH SIDEWALL Btuh/ft² Btuh/ft² 4 Btuh/ft² TYPE 7: SILL GRILLE STRAIGHT VANES Btuh/ft² Btuh/ft² TYPE 8: SILL GRILLE SPREAD.5 Btuh/ft² Btuh/ft² Btuh/ft² Btuh/ft² Btuh/ft² Btuh/ft² Btuh/ft².5 3 TYPE 9: SQUARE CEILING PATTERN Btuh/ft² Btuh/ft² Btuh/ft² a1-1 Excellence in Air Distribution
13 a1 14, 4x4x14 in inlet, 4 way Spacing for % EXAMPLE: 14 4 x4 PANEL, 14 INLET, 4-WAY (SPACING FOR % ) (NO DAMPER) 36 1/ Unit Separation Distance, L NC= CFM CFM/Sq.Ft. NOTE: Chart based on Btuh/ft loads. Charts This data can be used to prepare an performance envelope graph for any type of ceiling diffuser based on neck size and resultant throw, as a function of room air loading, or cfm/ft. For most interior spaces, heat load is less than Btuh/ ft. An example of such a graph, for a Krueger Model 14 Louvered Diffuser with a 14 inlet, is provided above. The effective operating airflow rate range for a space with the above diffuser can be estimated by following this procedure. 1. Determine the maximum air volumetric flow requirements based on load and room size. For VAV systems, evaluation should include the range of flow rates from minimum occupied to design load.. Enter the above graph at the maximum (design) airflow rate per unit area (cfm/ft, x-axis). 3. Proceed up to the airflow resulting in the maximum allowed sound level. 4. Proceed across to the value of L for that airflow rate (y-axis). This is the maximum half diffuser spacing for acceptable. ( of %) 5. Determine the minimum flow rate for that diffuser by starting at the separation distance, proceeding to the right to the left-most edge of the acceptable envelope, and proceeding down to the minimum CFM/ft. Example: Room Size: 9 x 9 with 9 Ceiling Load: 1.6 Btuh/ft or 5 Btu/h Volumetric Flow: 1 cfm/ft Diffuser: Krueger Model 14 Louvered Diffuser with 14 Neck Maximum Allowable NC: 35 Determine: L (Characteristic Length) and Minimum Volumetric Flow for Acceptable %. Solution: 1. Refer to the performance envelope graph for the 14 series with 14 neck and 4 x4 panel with 4-way throw. This chart is based off Btuh/ft.. Draw a vertical line from the x-axis value of 1 cfm/ft [point 1] to line with NC = 35 (85 cfm line) [point ]. 3. Draw a horizontal line from [point ] to the y-axis [point 3]. Point 3 is the value of L. In this example, L = To find minimum volumetric flow, locate [point 4] created by the line drawn from [point ] to [point 3]. From [point 4] draw a vertical line down to the x-axis to [point 5]. Point 5 is the minimum volumetric flow for acceptable flow. In this example, the value is.33 cfm/ft. NOTE: performance envelope graphs are provided for most ceiling diffusers in their performance sections throughout this catalog. Providing You With Air Distribution Solutions a1-13
14 a1 Overhead Perimeter Heating A critical application of horizontal pattern ceiling diffusers involves heating a perimeter zone in the winter from a ceiling located diffuser. In order to provide the best overall performance in both heating and cooling, providing the diffuser pattern will not be changed as the seasons change, tests have shown that several rules need to be followed. The discharge temperature cannot be more than 15 F above room temperature (heating mode) or excessive stratification will result. The discharge pattern should be both towards and away from the glass for both summer and winter acceptability. The 15 fpm terminal velocity (measured across the ceiling and then down the glass) must come to within 4.5 of the floor, or the jet will go back up to the ceiling and not mix with the cold convective current falling off the glass. OVERHEAD HEATING Return & Exhaust Openings The selection of return and exhaust openings depend on the following. Velocity in the Occupied Zone Near the Openings Permissible Pressure Drop Through the Openings Noise Room air movement is typically not influenced by the location of the return and exhaust outlets beyond a distance of one characteristic length of the exhaust or return grille. Air approaches the opening from all directions, and its velocity decreases rapidly as the distance from the opening increases. Therefore, drafty conditions rarely occur near return openings. The table below shows recommended return opening face velocities. RETURN FAN VELOCITY Recommended Return Inlet Face Velocities Inlet Location Velocity Across Gross Area, FPM Above Occupied Zone > Within Occupied Zone, Not Near Seats - Within Occupied Zone, Near Seats 4 - Door or Wall Louvers - 3 Through Undercut Area of Doors - 3 Failure to meet any of these requirements will usually result in vertical temperature stratification that does not meet ASHRAE comfort limitations and has poor system temperature response and ventilation short-circuiting. (ASHRAE Standard 6.1, 4 Addenda N mandates that these conditions be met, or an increase in ventilation rates is required.) To achieve the required heating throw, most systems will need to supply at least.8 cfm/ft in heating mode. In most northern climates, it will only require 1 F T (above room) to meet design heating load requirements. The location of return and exhaust openings is far less critical than that of supply outlets. However, the return should be located in an area to minimize short circuiting of supply air. If a return is located in a stagnant zone, it will return the warmer air in the space during cooling. In rooms with vertical temperature stratification, such as computer rooms, theaters, bars, kitchens, dining rooms, etc., exhaust openings should be located near the ceiling to collect warm air, odors, and fumes. Acoustical Considerations The most acceptable frequency spectrum for HVAC noise is a balanced spectrum. This means that it sounds neutral and is not too hissy (high-frequency content) or too rumbly (low-frequency content). The room criterion (RC) curves approximate the balanced spectrum deemed acceptable by most people. They are straight lines sloped at -5 db per octave band on a sound level versus frequency graph. Although still widely in use, the noise criterion (NC) curves are beginning to be replaced by the RC curves because an RC rating provides more information about sound quality. When energy codes do not allow for high enough air supply rates with VAV-reheat units for the diffuser to be effective when heating, either fan powered terminals or a separate heating system may be required. If a separate system is used, a vertical pattern diffuser or jet, at the glass, may provide an effective means of heating a perimeter zone without the supply temperature limitations previously noted. a Excellence in Air Distribution The top graph on the following page shows an indoor sound spectrum and the manner in which fan noise and diffuser noise contribute to that spectrum at various frequencies. The fan noise has been attenuated such that it approaches the sound criterion (in this case, an RC-35 contour) only in the lower octave bands. If this were the only noise present in the space, it would be considered rumbly by most listeners. However, the diffusers have been selected to balance the spectrum by filling in the higher frequencies so that the quality of the sound is more pleasant. Unfortunately, achieving a balanced sound spectrum is not usually this easy, as there may be numerous
15 a1 other sound sources to consider. AHRI 885 provides a method of estimating space sound levels from known sound power levels. A spreadsheet (885-calc.xls) is available on the Krueger website at to analyze the effect of diffuser noise along with air terminal radiated and discharge sound. Sound levels reported for diffusers are conducted in accordance with ASHRAE Standard, in a reverberant room. This procedure requires ten equivalent diameters of straight duct leading to the unit being tested. In practice, however, there is seldom even one equivalent diameter of straight run at the diffuser inlet. Our tests indicate that while the effect on sound generation differs from unit type to unit type, an average effect of +3 NC can be used to estimate these inlet effects. Additionally, room NC levels published for diffusers use a 1 db reduction for room effect. Most rooms, if the observer is standing under the diffuser, will have an effective reduction less than 1, more like 8 db, which results in an additional correction of + NC. The sum of these two realities is that catalog NC values should probably be increased by five to estimate sound levels in the space. On the other hand, the typical NC=35 requirement for most open plan offices is probably too low to provide the desired speech privacy levels, and an NC=4 is seldom objectionable in that situation. As a result, selecting at a catalog NC=35, which results in an RC=4N, will usually provide occupant acceptance on open plan offices. BALANCED SOUND SPECTRUM RESULTING FROM PROPER SELECTION OF AIR OUTLETS AND ADEQUATE FAN NOISE ATTENUATION OCTAVE BAND OCTAVE SOUND BAND PRESSURE SOUND PRESSURE LEVEL, db LEVEL, db RC-35 CONTOUR RC-35 CONTOUR FAN SOUND ATTENUATED TO MEET RC-35 FAN SOUND ATTENUATED TO MEET RC-35 SOUND OF DIFFUSER SELECTED FOR RC-35 SOUND OF DIFFUSER SELECTED FOR RC OCTAVE BAND CENTER FREQUENCIES, Hz FREQUENCIES AT WHICH VARIOUS TYPES OF MECHANICAL AND ELECTRICAL EQUIPMENT OCTAVE GENERALLY BAND CENTER CONTROL FREQUENCIES, SOUND DIFFUSER Hz SPECTRA NOISE STRUCTURE-BORNE VIBRATION DAMPER NOISE RECIPROCATING DIFFUSER AND NOISE CENTRIFUGAL CHILLERS TRANSFORMERS AND DAMPER NOISE FLUORESCENT BALLASTS RECIPROCATING AND TERMINAL CENTRIFUGAL BOXES CHILLERS TRANSFORMERS AND FAN FLUORESCENT AND PUMP NOISE BALLASTS TERMINAL BOXES FAN AND PUMP NOISE 8 STRUCTURE-BORNE VIBRATION OCTAVE BAND CENTER FREQUENCY, Hz OCTAVE BAND CENTER FREQUENCY, Hz Providing You With Air Distribution Solutions a1-15
16 a1 References References a1-4: Centerline Velocities of Axial & Radial Jets. 1 ASHRAE Fundamentals Handbook; Chapter 3, Figure. a1-6: Air Motion Characteristics of Outlets In or Near Floor with Non-Spreading Vertical Jet. a1-7: Air Motion Characteristics of High Sidewall; Group A Grilles. a1-7: Air Motion Characteristics of Ceiling; Group A Diffusers. a1-8: Air Motion Characteristics of Outlets Mounted In or Near Floor that Discharge Air Vertically in a Spreading Jet. a1-8: Air Motion Characteristics of Outlets Mounted In or Near the Ceiling that Project Primary Air Vertically. Straub, H.E., S.F Gilman, and S. Konzo Distribution of Air Within a Room for Year-Round Air Conditioning - Part I. University of Illinois Engineering Experiment Station, Bulletin No a1-1: Standard 55-93R Comfort Envelope. ASHRAE Standard ISO 773. a1-11: Percentage of Occupants Objecting to Drafts in Air Conditioned Room. 1 ASHRAE Fundamentals Handbook; Chapter 3, Figure 1. Parallelogram defined in ASHRAE Standard a1-16: Balanced Sound Spectrum Resulting from Proper Selection of Air Outlets and Adequate Fan Noise Attenuation (top). Frequencies at which Various Types of Mechanical and Electrical Equipment Generally Control Sound Spectra (bottom) ASHRAE Fundamentals Handbook; Chapter 7, Figure 1. a1-3: NC Chart. 1 ASHRAE Fundamentals Handbook; Chapter 7, Figure 6. a1-11: Characteristic Room Length for Several Diffuser Types. 1 ASHRAE Fundamentals Handbook; Chapter 3, Table 3. a1-15: Recommended Return Inlet Face Velocities. 1 ASHRAE Fundamentals Handbook; Chapter 3, Table 5. a1-4: NC Radiated Reductions. Data in Accordance with AHRI Standard a1-4: NC Discharge Reductions. Data in Accordance with AHRI Standard 885-8, Appendix E. a1-4: Ratio of Branch Flow to Total Flow. Data in Accordance with AHRI Standard a1-5: Recommended Indoor Design Goals (NC Ranges). 1 ASHRAE Fundamentals Handbook; Chapter 7, Table II. a Excellence in Air Distribution
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
AIR DISTRIBUTION FOR COMFORT AND IAQ
AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant
SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.
SECTION EG Air Distribution Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. Space Air Diffusion AIR DISTRIBUTION ENGINEERING GUIDE Proper selection of air diffusion
Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
plenum slot diffusers
light powered Redefine your comfort zone. www.titus-hvac.com dual-function smart logic light powered energy solutions Table of Contents PLENUM SLOT IFFUSERS products Plenum Slot iffusers Products... 4
CHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
HVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial
Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Duct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer
Fundamentals of Acoustics & Practical HVAC Design Considerations Demir Doken Acoustic Engineer What is sound? Sound is a mechanical wave that is an oscillation of pressure transmitted through some medium
Noise in the Classroom
ASHRAE JOURNAL Copyright 2000, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission of ASHRAE Journal. This article may not be copied nor distributed
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
DUCT SYSTEM DESIGN CONSIDERATIONS Part 1
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic
Displacement ventilation
General The displacement ventilation principle is the oldest form of ventilation and can be achieved without the use of fans. Air movement occurs by means of the density differences between supply air
Comparing Energy Savings of Different VAV Systems
Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd [email protected] EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
DSRQ - DSRSQ - DSRSQ-THERM
DSRQ - DSRSQ - DSRSQ-THERM Specification item: Variable geometry diffuser on 597x597 mm panel developed for rooms with high ceilings where a long throw and a high induction ratio are required. Made up
Acoustical Design Guidelines for HVAC Systems in Schools
Acoustical Design Guidelines for HVAC Systems in Schools Seminar 9, ASHRAE Summer Meeting Albuquerque, New Mexico Sponsor: TC 2.6 Sound and Vibration Robert M. Lilkendey Associate Principal Consultant
CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
HVAC Code Requirements
one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
applications laminar flow Laminar Flow Diffusers CRITICAL ENVIRONMENT LAMINAR FLOW: GENERAL
LMINR FLOW: GENERL Conventional vs. Critical Space pplications With human comfort in mind, conventional air distribution strategies typically employ rapid mixing of supply and room air for thermal equalization
Dual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER
International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)
Below are detailed instructions for using the EMS load calculator.
Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs Fan Performance (Paper I.D. 021) Mark Stevens Air Movement and Control Association International Abstract
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
Fan Applications & System Guide
Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation
Relationship between Sound Pressure and Sound Power Levels
Relationship between Sound Pressure and Sound Power Levels 4 W. T. W. CORY Chairman of the Eurovent WG 1 Fans If we wish to know the sound power transmitted through a fan and ducting system, it is preferable
HVAC Characteristics. Test Space HVAC Characteristics
HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,
Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories
Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2
CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2 Eddy Rusly 1 and Mirek Piechowski 2 1,2 Meinhardt (VIC), Melbourne, Australia ABSTRACT
HVAC - How to Size and Design Ducts
HVAC - How to Size and Design Ducts Course No: M06-032 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
ENGINEERING DATA. Fan Performance Troubleshooting Guide
Information and Recommendations for the Engineer ENGINEERING DATA Aerovent TC Ventco Fiber-Aire Twin City Fan & Blower TC Axial Clarage Fan Performance Troubleshooting Guide ED- Introduction Trying to
Air Conditioning Clinic
Air Conditioning Clinic Air Conditioning Fans One of the Equipment Series February 2012 TRG-TRC013-EN Air Conditioning Fans One of the Equipment Series A publication of Trane Preface Air Conditioning
Welcome. Green HVAC Ductwork Done Right! John Reints, PE Eugene Smithart, PE
Welcome Green HVAC Ductwork Done Right! John Reints, PE Eugene Smithart, PE High Velocity Duct Design Tips: Fundamentals of High Velocity, Static Regain, Duct Design Key Advantages Do s Don ts Biggest
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics
Lecture 6 - Boundary Conditions Applied Computational Fluid Dynamics Instructor: André Bakker http://www.bakker.org André Bakker (2002-2006) Fluent Inc. (2002) 1 Outline Overview. Inlet and outlet boundaries.
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
FIRE DAMPER APPLICATION GUIDE
FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
Essam E. Khalil [email protected]
AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil [email protected] PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
AIR SYSTEM BASICS. form the groundwork for the design, installation, operation, troubleshooting of these systems. Air duct Manometer
... AIR SYSTEM BASICS One of the fundamental concepts that apply to air systems is the fluid mechanics of conveying air. This article presents the basic principles that form the groundwork for the design,
ANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals
ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:
Air distribution effectiveness with stratified air distribution systems
Lee, K.S., Jiang, Z., and Chen, Q. 2009 Air distribution effectiveness with stratified air distribution systems, ASHRAE Transactions, 115(2). Air distribution effectiveness with stratified air distribution
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
IDES-EDU. Educational Package Ventilation. Lecture 8: Sizing mechanical ventilation systems IEE/09/631/SI2.558225 28.10.2011.
Introduction Educational Package Ventilation Lecture 8: Sizing mechanical ventilation systems IEE/09/631/SI2.558225 28.10.2011 Air Flow : Relation between air flow, air speed and duct section Ventilation
Product Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
SECTION 15936 AIR INLETS AND OUTLETS
SECTION 15936 AIR INLETS AND OUTLETS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Diffusers. 2. Registers. 3. Grilles. 4. Louvers. 5. Lowered Penthouses. 6. Gravity Roof Hoods. 7. Gravity Roof
Solving Simultaneous Equations and Matrices
Solving Simultaneous Equations and Matrices The following represents a systematic investigation for the steps used to solve two simultaneous linear equations in two unknowns. The motivation for considering
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.
1 ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS. - EXPERIENCE FROM A PLANT RECONSTRUCTION BASED ON A NEW SUPPLY AIR TERMINAL
security products metric sizes Redefine your comfort zone. www.titus-hvac.com
metric sizes secure lethal objects monitoring areas suicide deterrent Redefine your comfort zone. www.titus-hvac.com humid areas prevents corrosion minimum security medium security maximum security Table
L EED & G r e e n B u i ldi ngs
L EED & G r e e n B u i ldi ngs A P P L I C AT I O N G U I D E contents 3 - General 3 - Introduction 3 - Leadership in Energy & Environment 3 - Purpose 3 - LEED Rating System 4 - Energy & Atmosphere 4
Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.
COOLING FAN REQUIREMENTS CALCULATIONS Determining System Impedance Determining the actual airflow produced by a fan mounted in an enclosure is much more difficult than calculating the airflow required.
Optimum Solar Orientation: Miami, Florida
Optimum Solar Orientation: Miami, Florida The orientation of architecture in relation to the sun is likely the most significant connection that we can make to place in regards to energy efficiency. In
RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS
Paper Presented at ITHERM 2004 Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems June 1-4, Las Vegas, NV RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
UDSA - UDSBD unit heater
APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the
Natural Convection. Buoyancy force
Natural Convection In natural convection, the fluid motion occurs by natural means such as buoyancy. Since the fluid velocity associated with natural convection is relatively low, the heat transfer coefficient
Case Studies Illustrating Acoustic Design Guidelines for HVAC Systems in Schools
Cleveland, Ohio NOISE-CON 2003 2003 June 23-25 Case Studies Illustrating Acoustic Design Guidelines for HVAC Systems in Schools Robert M. Lilkendey, Siebein Associates, Inc. 625 NW 60 th Street, Suite
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN Umesh Atre Innovative Design Inc 850 W Morgan St Raleigh, NC 27603 [email protected]
FUNDAMENTALS OF ACOUSTICS
FUNDAMENTALS OF ACOUSTICS APPLICATION GUIDE Supercedes: Nothing Form 102.20-AG4 (406) ACOUSTICS AND THE HVAC INDUSTRY For an acceptable indoor air quality (IAQ) design, temperature and humidity control
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
CFD ANALYSIS CHALLENGES IN BUILDING SIMULATION FOR SIMBUILD2004 CONFERENCE. Ferdinand Schmid and Galen Burrell Architectural Energy Corporation
CFD ANALYSIS CHALLENGES IN BUILDING SIMULATION FOR SIMBUILD2004 CONFERENCE Ferdinand Schmid and Galen Burrell Architectural Energy Corporation ABSTRACT This paper discusses the capabilities and challenges
THE PSYCHROMETRIC CHART AND ITS USE
Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader
Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP)
Lee, K.S., Xue, G., Jiang, Z., and Chen, Q. 0. Thermal environment in indoor spaces with under-floor air distribution systems:. Impact of design parameters (5-RP), HVAC&R Research, 8(6), 8 9. Thermal environment
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Solar Heating Basics. 2007 Page 1. a lot on the shape, colour, and texture of the surrounding
2007 Page 1 Solar Heating Basics Reflected radiation is solar energy received by collectorsfrom adjacent surfaces of the building or ground. It depends a lot on the shape, colour, and texture of the surrounding
DRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
CHAPTER 3. The sun and the seasons. Locating the position of the sun
zenith 90 summer solstice 75 equinox 52 winter solstice 29 altitude angles observer Figure 3.1: Solar noon altitude angles for Melbourne SOUTH winter midday shadow WEST summer midday shadow summer EAST
How To Test A Fume Cupboard
Jürgen Liebsch WALDNER Labor EN 14175 Requirements for Fume Cupboards DIN 12924 EN 14175 The contents of the DIN 12924 part 1 standard is divided into 5 parts in the EN 14175 standard: 14175-1 Terms and
Chapter 12 Industrial Ventilation
Chapter 1 Industrial Ventilation Introduction Industrial Ventilation is an important method for reducing employee exposures to airborne contaminants. Ventilation is used to reduce or remove contaminates
Under sill units. Type FSL-B-ZAS
.1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
Element D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
Accurate Air Flow Measurement in Electronics Cooling
Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: [email protected] Air is the most commonly used medium to remove heat from electronics
Residential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: [email protected] SUMMARY Heating, ventilating and air-conditioning (HVAC)
ASHRAE STANDARD. Thermal Environmental Conditions for Human Occupancy. BSR/ASHRAE Standard 55P -1992R. Proposed American National Standard
BSR/ASHRAE Standard 55P -1992R This draft standard will be submitted to the American National Standards Institute Board of Standards Review (BSR) for approval. ASHRAE STANDARD Proposed American National
Practice Problems on Boundary Layers. Answer(s): D = 107 N D = 152 N. C. Wassgren, Purdue University Page 1 of 17 Last Updated: 2010 Nov 22
BL_01 A thin flat plate 55 by 110 cm is immersed in a 6 m/s stream of SAE 10 oil at 20 C. Compute the total skin friction drag if the stream is parallel to (a) the long side and (b) the short side. D =
Experiment (13): Flow channel
Introduction: An open channel is a duct in which the liquid flows with a free surface exposed to atmospheric pressure. Along the length of the duct, the pressure at the surface is therefore constant and
MULTIZONE APPLICATION OF SOLUTION UNITS
MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages