Comparing Energy Savings of Different VAV Systems
|
|
|
- Rudolf Porter
- 9 years ago
- Views:
Transcription
1 Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd EnergySoft LLC th Street, Suite A Novato, CA Last Modified: March 2012
2 Comparing Energy Savings of Different VAV Systems Realistic Models Require Turndown Schedules For Occupancy, Plug, and Lighting Loads Abstract The designer must never forget that the primary purpose of HVAC is comfort for the building s. Fortunately, comfort and saving energy go hand in hand with Variable Air Volume (VAV) systems. The ultimate is a VAV zone for each building providing temperature satisfaction and avoiding the energy waste of any overcooling or overheating. In addition to comfort and energy savings, the benefits of a VAV zone for each include higher worker productivity and improved ability to lease the space. Most buildings operate the majority of time in turndown and it is during turndown that VAV systems save energy because they match the reduced loads both the exterior loads, such as temperature and solar, and the interior loads of occupancy, plugs, and lighting. Also the energy penalty of reheat is during turndown. A model applying an average and using a single load schedule across a building accounts only for the portion of energy savings from the diversity of exterior loads (primarily during the spring and fall shoulder seasons) and completely misses the important year around energy savings from the diversity of interior loads. A realistic model also includes the energy savings from interior load diversity by randomly assigning one of several occupancy schedules to each. This modeling guide demonstrates a good way to do realistic comparisons. For future use, the additional load schedules should be included in the energy modeling software library. Recommendations for low energy VAV systems are also provided. Overview The subject here is saving energy but the designer must never forget that the primary purpose of HVAC is comfort for the building s. Fortunately comfort and saving energy go hand in hand with Variable Air Volume (VAV) systems. VAV systems provide small zones within the building where the temperature for each is controlled by varying the amount of conditioned air being supplied. A building with many VAV zones raises the chances of comfort satisfaction. Having many VAV zones also reduces the chances of overcooling or overheating which lowers fan speeds and lowers the central conditioning requirement both of which result in lower energy use. The ultimate is a zone for each building providing temperature satisfaction and avoiding the energy waste of any overcooling or overheating. Small zones can also eliminate an unexpected energy use when s bring in fans and electric heaters to be more comfortable. It should be noted that, in addition to saving energy, the benefits of a VAV zone for each include higher worker productivity and improved ability to lease the space. Expensive office workers are more productive when there is no distraction from being uncomfortable. Increases in office worker productivity when comfortable were 2 to 3% when measured in a study by Carnegie Mellon University under direction of the National Science Foundation. Also, the ability to lease office space is much better when offering a thermostat for each person. These should be included in any payback calculations. A basic VAV system consists of a fan, cooling and heating coils, filters, supply and return ducting and VAV terminals each with a room thermostat. VAV terminals can be either VAV diffusers or VAV boxes 2 of 9
3 with standard diffusers. See the comparison table below. The fan is almost always equipped with a Variable Speed Drive (VSD) to reduce fan speed and fan energy use when the VAV terminals can satisfy the temperature with reduced air flow. Less air flow through the coils also results in lower cooling and heating requirements allowing the chiller or packaged VAV unit and boiler to operate using less energy. Table 1 A Comparison of VAV Diffuser and VAV Box Systems Attribute VAV Box Reheat System VAV Diffuser Reheat System System Description Comfort Energy savings/operating cost First Cost 1 (see note below) Central cooling fans on roof supply 55 to 60 F air in ceiling mounted ducts to VAV reheat boxes in perimeter zones. Cooling only in interior zones - reheat boxes optional. Return air by ceiling plenum. Cooling fans have 100% outside air economizer. VAV box zones with multiple diffusers do not provide individual temperature control. Good cooling performance on exterior zones. Fair heating performance due to stratification - can be improved with high induction diffusers. Can only maintain uniform temperatures in interior office zones with similar loads. Overcooling or overheating may occur except in the space with the box thermostat. Minimum flow set point of 30% of design air flow, except for boxes with special controllers. Pressure drop over box of 0.5"wg to 1.0"wg. Installed cost of a VAV box with controls is usually between $2000 and $ Installed cost for box zones with 4 to 8 diffusers or smaller is more than for VAV diffusers. Justify any higher incremental first costs with paybacks for energy saving features and comfort benefits. Low shell and core costs. Indoor air quality Outside air economizer allows 100% outside air most of the year. Maintenance cost Flexibility VAV boxes require occasional maintenance. Rooftop equipment may require frequent maintenance. Any number of zones may be added but at a higher cost. Central cooling fans on roof supply 55 to 60 F air in ceiling mounted ducts to self-powered VAV diffusers in all zones. Reheat coils in ducts to perimeter zones - optional for interior zones. Return air by ceiling plenum. Cooling fans have 100% outside air economizer. Each VAV diffuser is a zone of temperature control with a built in thermostat allowing an individual set point for each building. Good cooling performance and less stratification when heating in all zones due to the high induction almost constant discharge velocity at both full and turn down flows. Maintains uniform temperatures in all zones with the possible exception during reheat in large reheat zones with wide differences in loads. No overcooling or overheating when loads vary between spaces. Lowest possible minimum flow set point of 10% of design air flow. Low pressure drop over diffuser of 0.05"wg to 0.25"wg. Installed cost of a self-powered VAV diffuser is usually between $200 and $ Installed cost is less than for a VAV box zone of 4 to 8 diffusers. Justify any higher incremental first costs with paybacks for energy saving features and comfort benefits. Low shell and core costs. Perception of improved air quality due to personal temperature set point and uniform temperature. Outside air economizer allows 100% outside air most of the year. VAV diffusers require almost no maintenance. Rooftop equipment may require frequent maintenance. VAV diffusers are easily moved or added to accommodate changes in interior layouts. 1 First Cost: Dollar values for the first cost are from: ENERGY DESIGN RESOURCES. December Advanced Variable Air Volume VAV System Design Guide. Pacific Gas and Electric Company. Depending upon the local market, these costs might vary as much as $2000 to $6000 for a VAV box installed and $200 to $450 for a VAV diffuser installed. 3 of 9
4 Applications VAV systems have been commonly applied in various kinds of commercial office buildings for over 30 years. Many of these, however, have neither provided satisfactory comfort nor met baseline energy efficiency standards due to emphasis on first cost without considering the quick paybacks on any incremental cost of energy saving features or for achieving the other comfort benefits. Energy modeling software can be used to determine the energy savings from the many ways of making VAV systems more efficient which, in turn, can provide a basis for payback calculations. Special Considerations Most buildings operate the majority of time in turndown and it is during turndown that VAV systems save energy because they match the reduced loads both the exterior loads, such as temperature and solar, and the interior loads of occupancy, plugs and lighting. A model applying an average and using a single load schedule across a building* accounts only for the portion of energy savings from the diversity of exterior loads (primarily during the spring and fall shoulder seasons) and completely misses the important year around energy savings from the diversity of interior loads. Realistic modeling also includes the energy savings from interior load diversity by randomly assigning one of several occupancy schedules to each. This modeling guide demonstrates a good way to do realistic modeling. For future use, the additional load schedules should be included in the energy modeling software library. * An example is the load schedule from ASHRAE and addenda which, in the ASHRAE Standard User's Manual, is suggested for guidance where actual schedules are not known. Modeling and Input Approaches The input descriptions that follow assume that, other than the VAV system, all project data, including entering location, envelope data, basic mechanical, etc., has already been created. These data remain unchanged for the different VAV systems to be compared, with the possible exception of increased envelope insulation. Select Supply Fan and Return Fan (if used) Designing the VAV system for the lowest possible pressure drop is critical to selecting a fan with the lowest horsepower and energy usage. 1. Determine Design Air Flow Make load calculations and determine an air flow per square foot (cfm/sqft) for each exposure and for the interior. Multiply these air flows by the respective perimeter areas for each exposure and the interior area. Keep in mind that systems rarely operate at design and avoid overly conservative estimates of lighting and plug loads. 2. Determine Design Total Static Pressure Design each portion of the VAV system for the lowest possible pressure drop (see Design for the lowest possible pressure drop in the VAV system in the recommendations below). Designing a low pressure drop VAV system deserves extra attention because fans use significant energy (tending to account for more energy consumption than the chiller), because significant cost savings are possible and because fans contribute a significant amount to peak energy demand. If using VAV diffusers, lower the pressure drop accordingly. (see Recommendations for Low Energy VAV Systems). 3. Select the smallest and most efficient fan available (see Select the lowest horsepower fan and control it for low turndown horsepower in the recommendations below). 4. Determine the brake horsepower of the fan/motor/drive package from the manufacturer s data at design conditions. 4 of 9
5 5. Enter the air flow and fan break horsepower into the model. Note: Most software follows NEMA premium motor efficiencies and the VFD efficiency curve in ASHRAE 90.1 Appendix G Table G Select VAV Terminal Data for all VAV terminals already exists in most software. If not, enter data for any missing terminal. If using VAV diffusers, lower the turndown ratio accordingly (see Recommendations for Low Energy VAV Systems). Also, most software automatically calculates the minimum amount of air required to meet ventilation standards and automatically increases the turndown ratio where required to meet the standards. Develop a Realistic Model Realistic comparisons of different systems can only be made using the reduced loads during VAV system turndown for several reasons. -Systems operate the majority of the time in turndown. -The energy savings of VAV systems are in turndown. -The energy penalty of reheat is in turndown. Exterior load turndown is automatically modeled based on the weather data. Interior load schedules are more difficult to predict because actual turndown conditions are random due to diversity of occupancy, lighting and plug loads. Applying an average and using a single load schedule across a building 1 will not capture the energy savings of interior load diversity and allow accurate comparisons of VAV systems. Interior load schedules are best simulated by randomly assigning one of several load schedules to each of the s. These schedules should go up and down throughout the day. For simplicity, use nine load schedules three highs, three mediums and three lows. Model the same schedule for all weekdays of the year. The same schedule for s, lights and plug loads can be used as research has shown that plug and lighting loads correlate with occupancy 2. Randomly assign one of these schedules to each. The appendix shows nine typical load schedules for a single which can be applied randomly. These schedules can also be placed into the library and used again for other buildings. A single room zone with a single is modeled with the assigned schedule. A single room zone with multiple s is modeled by adding the proportional shares of each s assigned schedule for each hour of the day. See appendix. A zone with multiple single rooms is modeled as fully occupied for each hour with at least one present because of the control/thermostat arrangement. This can be a temperature sensor in each room and a signal selector which allows the sensor farthest off set point to control. Alternatively, the zone can have one thermostat in a single room which, if the room with the thermostat is unoccupied, is adjusted by the s of the other rooms to remain comfortable. Both control the zone as fully occupied when at least one room is occupied. See appendix. 1 An example is the load schedule from ASHRAE and addenda which, in the ASHRAE Standard User's Manual, is suggested for guidance where actual schedules are not known. 2 MODELING OFFICE BUILDING OCCUPANCY IN HOURLY DATA-DRIVEN AND DETAILED ENERGY SIMULATION PROGRAMS, ASHRAE Transactions, 01-JUL-08, and Jessen Page, SIMULATING OCCUPANT PRESENCE AND BEHAVIOUR IN BUILDINGS, Ecole Polytechnique Fédérale de Lausanne, 19 October, and Newsom, Mahdavi, Beausoleil-Morrison, A STOCHASTIC MODEL FOR PREDICTING OFFICE LIGHTING ENERGY CONSUMPTION. 3rd European Conference on Energy-Efficient Lighting 5 of 9
6 Eliminate or Reduce the Need for Reheat Reheat wastes energy and if at all possible should be eliminated (see Eliminate or reduce the need for reheat below). If elimination of reheat is not possible, consider raising the base supply air temperature and using supply air temperature reset during cool weather. Supply air reset may be either be a simple reset to a higher temperature or demand based using the warmest temperature that will satisfy all of the zones in cooling (warmest zone). Results Most software automatically compares a VAV approach to a baseline. When comparing different VAV approaches, a separate model and report is required for each simulation. The energy simulation results often report the annual predicted usage of the various energy end uses for the building. Of particular interest will be the consumption of the heating and cooling systems, as well as ventilation fan systems. Depending upon the type of system, possibly pumping and cooling tower consumption will be included. As the air system is optimized through the strategies presented here, reductions in all of these uses can be expected. In addition, as other optimizations are made to the building such as reduced internal loads from lighting, or possibly lower external loads from better fenestration, the resulting energy usage will decrease given a VAV system s ability to respond to reduced loads in the building. An efficient all low pressure design with small zones of control can result in energy savings of 15-57% over traditional VAV systems. Summary The lowest energy VAV systems tend to have a VAV zone for each and an air system with a low pressure drop. The true advantage of such a low energy VAV system is best revealed by a model which, in addition to exterior load diversity, includes the energy savings from interior load diversity. This can be achieved by randomly assigning one of several occupancy schedules to each. Recommendations for Low Energy VAV Systems Select the lowest horsepower fan and control it for low turndown horsepower Maximum fan power should not exceed 0.72 W/cfm. Use a more efficient scroll type airfoil centrifugal fan when noise and space limits allow. Use a variable speed drive (VSD) on the fan. Control the VSD from a static pressure sensor located close to the last VAV terminal in the duct run. Use multiple sensors for duct work with multiple branches. Use the lowest pressure drop air system possible. (See Design for the lowest possible pressure drop in the VAV system below. Specify that no balancing damper shall be installed before the last VAV terminal or the last diffuser (alternatively that the balancing damper before the last VAV terminal or last diffuser shall remain open) so that the system will be balanced at the lowest possible fan speed. 6 of 9
7 Eliminate or reduce the need for reheat Eliminate the need for reheat by adding enough inexpensive insulation to the building envelope until the heat loss through the envelope at outside temperature below winter design is less than the heat gain of the s and other internal loads in perimeter spaces. Warm-up heating may still be required. Eliminate the need for reheat by using separate air handling units for each heating zone such as one per exposure and one for the interior. Use high induction diffusers to reduce stratification. (All VAV diffusers are high induction.) Use the lowest possible minimum flow set point. Must be the higher of the minimum ventilation requirement or the lowest allowed by the terminal (10% of design air flow for VAV diffusers, higher for most VAV boxes). Use a slightly higher supply air temperature. An increase in the supply air temperature will require a larger volume of air. Use the model to find the ideal compromise between reheat energy and fan energy. Increasing the use of fan energy to lower use of central plant energy can seldom be justified except when also reducing reheat. One method is to reset supply air temperature during cool weather and size interior zones for 60 F or higher supply air. Supply air reset may not be beneficial in warm climates and in high humidity locations where alternate dehumidification may be required. Provide the smallest possible zones Try to provide a VAV zone and a thermostat for each. Design for the lowest possible pressure drop in the VAV system Fan Minimize the fan outlet effect with a straight run duct or an elbow in the direction of the fan rotation. Use duct liner only where necessary for sound attenuation. Use the minimum needed. Avoid sound traps. Coils Select the largest coil that can fit in the space - maximum face velocity of 450 fpm and minimum water side ΔT of 15 F. Filters Avoid pre-filters. Use the largest filter bank that can fit in the space. Select low pressure drop extended surface area filters. Risers Place the shafts close to the air handler but, for sound attenuation, not directly under it (except connect ducts to rooftop units through insulated roof curb to avoid ducts outside the building envelope). Size for 800 to 1200 fpm at the floor closest to the air handler. Consider multiple air shafts for large floor plans. Supply air ducting Make as straight as possible with a minimum of transitions and joints. Use large radius elbows and low pressure drop fittings and takeoffs. Size for a pressure drop no greater than 0.08 wg per 100 ft and a maximum of 1200 fpm. 7 of 9
8 Limit use of flex ducting to a maximum of 5ft at the diffusers. Use duct liner only where necessary for sound attenuation. Avoid sound traps. VAV terminals Use VAV diffusers instead of VAV boxes a lower pressure drop by 0.25 wg to 0.75 wg usually reduces fan HP by 30 to 50% Size terminals for low static pressure drops between 0.25 wg and 0.05 wg for VAV diffusers and 1 wg to 0.5 wg for VAV boxes Return air Provide at least one return air grill for each VAV zone, more if the zone is large. Use ceiling return air plenums (except in high humidity locations such as DOE climate zone 1.). Seal ceiling plenums for minimum air infiltration. Size ducts for pressure drop no greater than 0.04 wg per 100 ft. Size grills for pressure drop no greater than 0.08 wg. Provide separate auxiliary cooling systems to serve 24/7 process loads such as server rooms and telecom closets and other loads that do not operate on the normal HVAC schedule. 8 of 9
9 Appendix Example Room Zone with a Occupant Light Medium Heavy Light Medium Heavy Light Medium Heavy Hour Time ASHRAE (12-1 am) 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 2 (1-2 am) 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 3 (2-3 am) 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 4 (3-4 am) 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 5 (4-5 am) 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 6 (5-6 am) 0% 0% 0% 0% 0% 0% 0% 0% 0% 0% 7 (6-7 am) 10% 0% 0% 0% 0% 100% 100% 0% 0% 0% 8 (7-8 am) 20% 100% 100% 100% 0% 100% 100% 100% 100% 100% 9 (8-9 am) 95% 100% 0% 100% 0% 0% 100% 100% 100% 100% 10 (9-10 am) 95% 0% 100% 100% 0% 0% 100% 100% 100% 100% 11 (10-11 am) 95% 0% 100% 100% 0% 0% 0% 100% 100% 100% 12 (11-12 pm) 95% 0% 0% 0% 0% 0% 100% 0% 0% 100% 13 (12-1 pm) 50% 0% 100% 100% 100% 100% 100% 0% 0% 0% 14 (1-2 pm) 95% 0% 0% 100% 100% 100% 100% 0% 0% 0% 15 (2-3 pm) 95% 0% 100% 100% 100% 100% 100% 0% 0% 0% 16 (3-4 pm) 95% 0% 100% 100% 100% 100% 100% 0% 100% 100% 17 (4-5 pm) 95% 0% 0% 0% 0% 0% 100% 0% 100% 100% 18 (5-6 pm) 30% 0% 0% 0% 0% 0% 0% 0% 0% 100% 19 (6-7 pm) 10% 0% 0% 0% 0% 0% 0% 0% 0% 100% 20 (7-8 pm) 10% 0% 0% 0% 0% 0% 0% 0% 0% 100% 21 (8-9 pm) 10% 0% 0% 0% 0% 0% 0% 0% 0% 0% 22 (9-10 pm) 10% 0% 0% 0% 0% 0% 0% 0% 0% 0% 23 (10-11 pm) 5% 0% 0% 0% 0% 0% 0% 0% 0% 0% 24 (11-12 am) 5% 0% 0% 0% 0% 0% 0% 0% 0% 0% ASHRAE 90.1 User's Manual ANSI/ASHR AE/IES Standard Hours in Remainder Out of Office (Meetings and Sales Calls) 6 Hours in 1 Hour Lunch and 2 Hours Breaks/Meet ings 8 Hours in 1 Hour Lunch 4 Hours in Morning Out of Office (Meetings and Sales Calls) 6 Hours in Morning Meeting and Lunch 10 Hours in 1 Hour Lunch 4 Hours in Afternoon Out of Office (Meetings and Sales Calls) 6 Hours in Lunch and Afternoon meeting 10 Hours in 3 Hour Lunch Example Room Zone with Multiple Example Zone with Multiple Occupants Occupant Rooms Hour Time (12-1 am) 0% 0% 0% 0% 0% 0% 2 (1-2 am) 0% 0% 0% 0% 0% 0% 3 (2-3 am) 0% 0% 0% 0% 0% 0% 4 (3-4 am) 0% 0% 0% 0% 0% 0% 5 (4-5 am) 0% 0% 0% 0% 0% 0% 6 (5-6 am) 0% 0% 0% 0% 0% 0% 7 (6-7 am) 0% 67% 0% 0% 100% 0% 8 (7-8 am) 100% 67% 100% 100% 100% 100% 9 (8-9 am) 67% 33% 100% 100% 100% 100% 10 (9-10 am) 67% 33% 100% 100% 100% 100% 11 (10-11 am) 67% 0% 100% 100% 0% 100% 12 (11-12 pm) 0% 33% 33% 0% 100% 100% 13 (12-1 pm) 67% 100% 0% 100% 100% 0% 14 (1-2 pm) 33% 100% 0% 100% 100% 0% 15 (2-3 pm) 67% 100% 0% 100% 100% 0% 16 (3-4 pm) 67% 100% 67% 100% 100% 100% 17 (4-5 pm) 0% 33% 67% 0% 100% 100% 18 (5-6 pm) 0% 0% 33% 0% 0% 100% 19 (6-7 pm) 0% 0% 33% 0% 0% 100% 20 (7-8 pm) 0% 0% 33% 0% 0% 100% 21 (8-9 pm) 0% 0% 0% 0% 0% 0% 22 (9-10 pm) 0% 0% 0% 0% 0% 0% 23 (10-11 pm) 0% 0% 0% 0% 0% 0% 24 (11-12 am) 0% 0% 0% 0% 0% 0% schedules 1, schedules 4, schedules 7, schedules 1, schedules 4, schedules 7, 2 and 3. 5, and 6. 8, and 9. 2 and 3. 5, and 6. 8, and 9. Modeled by adding the proportional shares of each s assigned schedule for each hour of the day. Modeled as fully occupied for each hour with at least one present (Tip! In Excel use the MAX function over the 's assigned schedules for each hour of the day.) 9 of 9
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)
CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning) Objectives Survey current HVAC system(s), operating procedures, and maintenance schedule. Analyze results of energy audit for HVAC system(s)
Mechanical Systems Proposal revised
Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option
Preliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Rev. No. 0 January 5, 2009
ENERGY & ENVIRONMENTAL ENERGY ISSUES COMMITTEE 415 Main Building Telephone (574) 631-6666 Notre Dame, Indiana Facsimile (574) 631-5883 46556 USA Energy Conservation Plan For HVAC Systems Rev. No. 0 January
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN Umesh Atre Innovative Design Inc 850 W Morgan St Raleigh, NC 27603 [email protected]
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
Design Options For HVAC Distribution System
PDHonline Course M147 (4 PDH) Design Options For HVAC Distribution System Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088
Case Studies: Infrared Heating in Industrial Applications
Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
AIR DISTRIBUTION FOR COMFORT AND IAQ
AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
Demand Based Static Pressure Reset Control for Laboratories
LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a
Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History
Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems Ryan R. Hoger, LEED AP 708.670.6383 [email protected] History VAV systems came into favor for mid and large size
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
DUCT SYSTEM DESIGN CONSIDERATIONS Part 1
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic
for K-12 School Buildings
Advanced Energy Design Guide for K-12 School Buildings HVAC Section John Murphy Applications Engineer, LEED AP Trane La Crosse, Wisconsin [email protected] www.trane.com AEDG-K12 HVAC Subcommittee John
Key energy-efficient features of your new home
Key energy-efficient features of your new home Your thermal envelope The thermal envelope, or shell, of your home (walls, roof and floor) is designed to keep you dry and comfortable. It protects you from
Xcel Business Customers: Program and Rebate Summary
Xcel Business Customers: Program and Rebate Summary Rebates for New Energy-Efficient Equipment Xcel offers prescriptive rebates to its business customers. What s a prescriptive rebate? It simply means
Design Options for HVAC Distribution Systems
Design Options for HVAC Distribution Systems Course No: M06-017 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)
Product Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
Energy Savings in High-Rise Buildings Using High-Reflective Coatings
Energy Savings in High-Rise Buildings Using High-Reflective Coatings Executive Summary: Nevertheless, the simulation analyses showed that when designing a building for low energy consumption, even in cold
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
HEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
Flexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Acoustical Design Guidelines for HVAC Systems in Schools
Acoustical Design Guidelines for HVAC Systems in Schools Seminar 9, ASHRAE Summer Meeting Albuquerque, New Mexico Sponsor: TC 2.6 Sound and Vibration Robert M. Lilkendey Associate Principal Consultant
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
MULTIZONE APPLICATION OF SOLUTION UNITS
MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages
Applying Schedules and Profiles in HAP
This HAP e-help discusses the importance of properly applying schedules and profiles in HAP. We will also discuss potential misapplications of these user inputs. First, we need to understand the differences
SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.
SECTION EG Air Distribution Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. Space Air Diffusion AIR DISTRIBUTION ENGINEERING GUIDE Proper selection of air diffusion
Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
Dual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
The sample report format is applicable to many different building types and systems and the examples provided cover a variety of applications.
Purpose Power Smart s Minimum Requirements for an Energy Study (see Appendix) provides a comprehensive list of the basic elements which must be included in an Energy Study Report. The intent of this sample
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
Element D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE <[email protected]
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE
Section 2: Estimating Energy Savings and Incentives
Section 2: Estimating Energy Savings and Incentives 2.1 Estimating Energy Savings and Incentives... 2 2.2 Customized Measures - Estimation Software... 2 2.2.1 AC&R I - High Efficiency Chiller... 3 2.2.2
Using Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Red River College MECB 101 School of Construction and Engineering Technologies Manitoba Energy Code for Buildings 101 (MECB 101)
Manitoba Energy Code for Buildings 101 (MECB 101) The National Research Council of Canada (NRC) has issued the National Energy Code for Buildings (NECB) in 2011. The main objective of NECB 2011 was to
ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations
ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations MECHANICAL SYSTEMS DESIGN STANDARDS Appendix A RECOMMENDED HVAC SYSTEMS BY TYPE OF SPACE Matt Higgins Valentin Lucero
for Plans Examiners and Building Inspectors
Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared
Noise in the Classroom
ASHRAE JOURNAL Copyright 2000, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission of ASHRAE Journal. This article may not be copied nor distributed
Fan Applications & System Guide
Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client
Order of Magnitude Mechanical Estimating Justin Apprill, P.E. Topics for Today Estimate Goals A Concept for Accurate Conceptual Estimating HVAC Systems Common System Types and Rules of Thumb Pricing Example
HVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
Printing and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency
Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Because HVAC systems comprise a large amount of a building s operating costs, it makes sense to ensure these systems
HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Mechanical Insulation. Hospitals and Schools
Study on Mechanical Insulation in Hospitals and Schools March 1, 2011 Study Mechanical Insulation in Hospitals and Schools G. Christopher P. Crall, P.E. Ronald L. King Executive Summary Mechanical insulation
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center [email protected] 402-559- 5301 402-630-
newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
HVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
plenum slot diffusers
light powered Redefine your comfort zone. www.titus-hvac.com dual-function smart logic light powered energy solutions Table of Contents PLENUM SLOT IFFUSERS products Plenum Slot iffusers Products... 4
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
EarthCents (DSM) Program Summary
EarthCents (DSM) Program Summary Renewable Energy EarthCents Programs Solar Water Heating This program is available to residential customers for the installation of a qualifying solar thermal water heater.
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
MEETING AGENDA. Project Administrator:
MEETING AGENDA Project Administrator: To: Ann Green M. Baker, SLCS C. Bullinger, SLCS R. Clark, SLCS Board C. Cox, SLCS S. Dotinga, Granger J. Graham, SLCS J. Gusick, SLCS, Board C. Hanshaw, SLCS Board
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
SIMULATION OF RADIANT COOLING PERFORMANCE WITH
SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard
ASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
Catalyst RTU Controller Study Report
Catalyst RTU Controller Study Report Sacramento Municipal Utility District December 15, 2014 Prepared by: Daniel J. Chapmand, ADM and Bruce Baccei, SMUD Project # ET13SMUD1037 The information in this report
Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011
Fans and Air Handling Units Will Rea and Paul Pilutti February 16 th, 2011 HTS Lunch and Learns Available Online Visit www.htseng.com Engineering Tools Resource Center Contents Fans Fan Curves Fan Laws
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
Integrated Solar Radiant Systems
Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant
Heating, Ventilation and Air Conditioning Rebate Catalog Saving energy for a brighter future
Pacific Gas and Electric Company Energy-Efficiency s for Your Business Heating, Ventilation and Air Conditioning Catalog Saving energy for a brighter future Customers may be eligible to participate in
Duct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1
WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 Wallet card photocopy Inspection Authority: Signature: Date: / / Submitted For: ( Owner ) Name Address City Prov Postal code Phone ( ) Fax ( ) Designer/Signature:
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return