Venturi Air Valve or Single-Blade Damper What s Right for You?
|
|
|
- Paulina Robbins
- 9 years ago
- Views:
Transcription
1 Technology Report September, 2008 Venturi Air Valve or Single-Blade Damper What s Right for You? This report examines and compares the attributes of a Venturi air valve and a single-blade damper to assist a ventilation system designer. Single-blade dampers have been on the scene for generations and are probably one of the earliest HVAC control devices. They were initially used to manually adjust the chimney draft of wood and coal burning stoves. This made it possible to regulate the stove's heat output. Blade dampers were later coupled with automatic operating mechanisms for various HVAC control applications and continue to be widely used, especially to control ventilation systems. Single-blade dampers function by simple rotation and perhaps provide the least obstruction to airflow when in the maximum open position. Round blade dampers are sometimes called butterfly dampers. This term may be better reserved for dampers that function by a folding and unfolding action (much like a butterfly's wings). VENTURI AIR VALVE The Venturi air valve is a newer airflow control device with a more elaborate mechanical design. Mechanical Operation Figure 1 shows the basic mechanical operation of each device. The single-blade damper consists of a disk mounted on a shaft. As the shaft rotates, the disk blocks more or less of the air path. This rugged arrangement allows gradual adjustment of the flow area from nearly blocked to almost fully open. A Venturi air valve has a curved body that functions as a valve seat, and a cone that moves in and out of the throat of the Venturi to restrict airflow. When used with a suitable airflow controller, either a Venturi air valve or single-blade damper can effectively modulate airflow. SINGLE BLADE DAMPER ACTUATOR SHAFT LEVER ARM ACTUATOR DAMPER SHAFT CRANK ARM ACTUATOR SHAFT ACTUATOR CONE CONE SHAFT VENTURI BODY AREA DUCT HOUSING THE ACTUATOR SHAFT IS CONNECTED TO THE CONE SHAFT BY A LEVER ARM. AS THE ACTUATOR SHAFT EXTENDS OR RETRACTS IT CAUSES THE LEVER ARM TO MOVE THE HORIZINTAL CONE SHAFT. MOVEMENT OF THE CONE SHAFT VARIES THE AREA BETWEEN THE CONE AND THE VENTURI BODY. THE ACTUATOR SHAFT IS CONNECTED TO THE DAMPER SHAFT CRANK ARM. AS THE DAMPER SHAFT EXTENDS OR RETRACTS IT ROTATES THE BLADE DAMPER WHICH VARIES THE AREA BETWEEN THE DAMPER BLADE AND THE DUCT HOUSING. Figure 1. Basic Operation of a Venturi Air Valve and Single-Blade Damper Air Terminal. Siemens Industry, Inc. Page 1 of 8
2 Mechanical Pressure Independence The brief description of the damper operation skipped over an interesting characteristic of the Venturi air valve. In many valves, the actuator shaft does not directly move the cone. Instead, they are connected by a special spring. This gives the cone some freedom to move along the shaft. The spring exerts a force on the cone, but so does the air that flows through the valve. The cone slides along the shaft to the position where the air pressure balances the spring. Through this mechanical force balancing process, the Venturi air valve can be made pressure independent. That is, as pressures change in the duct system, the cone moves on the shaft, altering the airflow path, counteracting the pressure change, and tending to keep that airflow rate constant. This behavior depends on a careful mechanical design that matches the characteristics of the specially designed, variable-stiffness spring to the shapes of the cone and the Venturi body. REMAINS CONSTANT LOWER STATIC PRESSURE HIGHER STATIC PRESSURE EXPANDED SPRING -- INCREASED AREA COMPRESSED SPRING -- DECREASED AREA Figure 2. Pressure Independence by the Venturi Air Valve Pressure Compensation Spring. Figure 2 illustrates action of the cone and spring. The upper diagram shows, that when a lower static pressure acts on the upstream side of the cone, the spring is only slightly compressed, and the cone sits relatively far out of the throat of the valve. The resulting airflow area between the cone and Venturi body allows the required airflow rate. The lower diagram shows what happens when the duct pressure increases. Pressure on the upstream side of the cone pushes the cone along the shaft (towards the throat) and compresses the spring. This movement of the cone restricts the airflow, countering the effect of the pressure increase. The result is that the airflow rate stays nearly constant. When the system static pressure decreases, the cone spring expands and slides the cone back (away from the throat). This increases the airflow area and maintains the required airflow rate. Clearly, this is a sophisticated mechanical device. Performance depends on carefully selected and maintained mechanical parameters. Pressure independent operation is effective over a range of operating pressures specified for the valve (typically 0.6 in. WC to 3.0 in. WC, 150 Pa to 750 Pa). Stability of this non-linear, spring-mass system depends on the shock absorbing effect of the dash tube (the hollow core of the cone) and the cone bushing (a spacer that supports the small end of the cone on the shaft). As the cone moves along the shaft, it squeezes air through the precise opening between the bushing and the dash tube wall. This shock absorber dissipates energy and keeps the cone from bouncing continually on its spring. Critical mechanical tolerances allow the cone sufficient freedom for motion with sufficient damping. Airflow Control Concepts Closed Loop Control: The most common approach to airflow control in a ventilation system is the closed loop, also called feedback control. By definition, each adjustment by a closed loop controller depends on the measured results of previous movements. 1 As the flow controller adjusts the damper (singleblade, Venturi, or other) it also reads an airflow sensor to measure the flow rate and compare it to the desired value (called the setpoint). If the duct pressure changes, and affects the airflow, the controller measures that change and quickly adjusts the damper opening, continuing to sense airflow until the required rate is restored. This is the usual way to accomplish pressure independent flow control ASHRAE Handbook - Fundamentals of Control, Chapter 15, Page Page 2 of 8 Siemens Industry, Inc.
3 Open Loop Control: Another approach uses a Venturi air valve as a simple metering device without measuring airflow. In this scenario, the Venturi operates as an open loop flow controller. This concept is valid as long as the system keeps the valve within the operating range of the spring and cone mechanism. In some installations, the Venturi assembly includes a sensor, which measures position of the actuator shaft. This can be useful. That position signal is sometimes mislabeled as flow feedback, but it s not actually sensitive to airflow. In the open loop design, events in the duct system that change the airflow do not move the actuator, and are not reflected by the position sensor. Operators and designers have mistaken the speed and stability of the position signal as a true indication of airflow, overlooking the dynamic events that occur inside the valve, as the cone and spring continually seek the changing balance point. Most ventilation system designers recognize the value of an airflow measurement. Nearly all specifications call for a flow feedback signal. Position of the actuator should not be construed to satisfy that need. Linearity of Control Components Control engineers characterize components in terms of input/output responses. They consider dynamic characteristics such as speed and overshoot, as well as the steady-state responses. If the steady-state response of a component (for example, airflow versus damper position) can be described with a straight line, the component is called linear. In the days before digital control, linearity was greatly beneficial to engineers piecing systems together from signal processing components. Product developers went to great lengths to linearize responses because it simplified system design. Today, non-linearity in a component is easier to address in software. The physics of airflow is full of non-linearity. For example, the relationship between the position of the cone in the valve, and the corresponding airflow at a particular pressure depends on the complex geometry of the cone and valve body, and is highly non-linear. Similarly, the relationship between the position of the actuator and the resulting position of the cone depends on the non-linear spring in the cone and the pressure forces in the duct. Some manufacturers still linearize their valves by adding a non-linear electronic circuit to distort the relationship between the command voltage and the position of the actuator. These days, that step is usually unnecessary. Airflow Control Accuracy In a closed loop flow control application, accuracy depends mainly on the airflow sensor; the characteristics of the damper (blade or Venturi) have little effect. In such a case, the expression accuracy of the flow control damper doesn t actually mean anything. Sensors are available for a wide range of accuracy requirements. It s important to select sensors appropriate to the application. That means relating the sensing range and accuracy to the ventilation objectives. There is no single accuracy specification that makes sense for all applications. It also means considering the geometry and vulnerability of the components in the air stream. In exhaust systems it s crucial to prevent fouling; a rugged geometry with minimum obstruction of the air path is preferred. A low-profile orifice ring with large pressure taps is very reliable. VENTURI AIR VALVE MEASUREMENT SENSOR SINGLE BLADE DAMPER Figure 3. Venturi Air Valve and Damper Air Terminals with Integrated Airflow Sensors. In an open loop application, (a Venturi air valve without an airflow sensor) flow control depends entirely on the reliability of the flow versus position relationship of the valve. This depends, in turn, on the precisely coordinated mechanical parameters described earlier. Deviations over time in the mechanical parameters degrade open-loop Siemens Industry, Inc. Page 3 of 8
4 accuracy. The following issues are known to cause mechanical parameters to degrade: 1. With continued use, springs exhibit some departure from their original spring rate curve due to material aging and fatigue. Therefore, mechanical pressure independence is not as precise, nor will it provide the long-term stability that is achieved with closed loop flow control. 2. Reliable pressure independent operation depends on precise mechanical clearance inside the cone, where the dash tube slides back and forth over the cone bushing. Material from the air stream is normally deposited on exposed surfaces in the valve, and over time, can work into this critical area. Figure 4 shows the condition of several air valves removed from service. The center left image shows the cone assembly covered in dust. The bottom left image shows the cone bushing has been damaged by deposited material. Because performance is so sensitive to the condition of these friction surfaces, a clean air stream improves reliability. Figure 4. Venturi Air Valves Fouled During Use. 3. Proper valve orientation (horizontal or vertical) is very important for mechanical pressure independence. In the vertical position, the weight of the cone has an impact on the pressure compensation spring. Thus, the proper spring must be installed in the factory Page 4 of 8 corresponding to the position (horizontal or vertical) in which the valve will be installed. Therefore, it is mandatory that a Venturi air valve is installed in the proper horizontal or vertical position and not in a slanted (angular) position. 4. The air valve is not only susceptible to fouling of the precise friction surfaces. Gross contamination can also upset the open loop relationship of flow versus position. The images in the top and bottom right of Figure 4 illustrate the sort of debris that an air valve can catch in an exhaust system (in this case, large debris). These valves were removed from service after it was observed that the airflow did not seem right. The actuator position signal did not indicate any problem. Flow and Pressure Characteristics The fundamental selection criteria for a flow control device are the range of flow rates, and corresponding pressure drops across the device. These numbers (flow range and pressure range) are a good starting point for a designer selecting a device. It s important to remember that they are not exactly comparable. For the Venturi air valve, these values are the hard limits of the pressure independent operation. Because these values are hard, physical limits, prudent designers leave a cushion, and do not apply the valves right at the limit. For a single-blade damper, the ranges are based on a more flexible set of engineering rating criteria. It s always possible to push more or less air through the damper if the effects on the system are acceptable. Table 1 defines each term and contrasts the meaning between a single-blade damper and a Venturi air valve. Air Capacity Because of the greater airflow area of a single-blade damper type of air terminal, its airflow capacity is significantly more than a Venturi air valve of the same diameter. Since the maximum Venturi air valve size is typically 12 inches in diameter, larger airflows require having multiple units arranged in parallel (ganged together). Figure 5 indicates airflow ranges of Venturi air valves and single-blade air terminals of various sizes. Siemens Industry, Inc.
5 Table 1. Definition of Sizing Parameters. Sizing Parameter Single-blade Damper Venturi Air Valve definition typical value definition typical value Maximum Airflow A selected rating value. Above this point, system may be considered too loud or lose too much pressure. Often selected between 2,000 and 3,000 fpm. The flow rate approximately maintained by the spring when the actuator is at the end of the stroke. Typically occurs at 1,700 to 1,900 fpm. Minimum Airflow A selected rating value. Below this point, the flow sensor may be inaccurate. Depends on the sensor and the required accuracy. Usually between 0 and 500 fpm. The flow rate approximately maintained by the spring when the actuator is at the other end of the stroke. Typically occurs at 100 to 200 fpm. Maximum Pressure Drop Above this pressure, control may become difficult. Dampers have been applied successfully at 6 in. WC of drop. At this pressure drop, the spring is fully compressed and can no longer regulate airflow. 3 in. WC for all available Venturi air valves. Minimum Pressure Drop Pressure measured across the fully open damper at a rated flow. Usually less than 0.1 in. WC. At this pressure drop, the spring is fully extended and can no longer regulate airflow. Usually 0.6 in. WC or 0.3 in. WC for low pressure valves. LGS_18 AV_312 AV_212 LGS_16 AV_210 LGS_14 LGS_12 AV_112 LGS_10 AV_110 LGS_08 AV_108 LGS_06 AV_106 LGS_04 TYPE FLOW RANGES OF TERMINAL UNITS & VENTURI AIR VALVES The system pressure drop is an important factor in fan energy consumption. Designers motivated by the Green Building movement and sustainability strive to select low-pressure components, so they favor single-blade dampers. 2 3 Like the air capacity, the minimum pressure drop depends on the size of the airflow area. Figure 6 compares of the airflow open area for a Venturi air valve and a single-blade damper FLOW (CFM) STARTING FROM to FLOW SIGNAL to 1000 FPM TU SHUT-OFF 0.02" (~350FPM) AV CAL MIN Figure 5. Airflow Ranges for Venturi Air Valves and Single-blade Dampers of Various Sizes. Minimum Pressure Drop Minimum pressure drop is an important parameter of an airflow control device. It is the pressure drop across a fully open device at a given airflow rate. The minimum pressure drop (along with the pressure drop of the other system components) determines the static pressure that the supply and exhaust fans must provide to achieve the desired system airflow. 2. U.S. Department of Energy, Low-Pressure-Drop HVAC Design for Laboratories, DOE/GO (February 2005). 3. Siemens Building Technologies, Inc., Green Lab Facilities: Steps Toward Sustainability Technology Report, , (April 2008). Siemens Industry, Inc. Page 5 of 8
6 VENTURI AIR VALVE (END VIEW) AREA SINGLE BLADE DAMPER (END VIEW) AREA Figure 6. Maximum Airflow Areas for the Wide Open Position. Figure 6 shows that a blade damper's fully open airflow area is much greater in comparison to a fully open Venturi air valve of the same diameter. A fully open single-blade damper s airflow area equals the internal duct area less the area occupied by the damper shaft. For a fully open Venturi air valve, the airflow area is limited by the diameter of the cone. The airflow through a Venturi air valve also changes direction as it flows around the cone. For these reasons, a Venturi air valve has a significantly higher minimum (wide open) pressure drop than a singleblade damper air terminal of the same diameter. Typically, a Venturi air valve has a non-recoverable minimum static pressure drop of 0.6 in. WC (150 Pa). Some manufacturers also offer low pressure Venturis with a drop of about 0.3 in. WC (75 Pa) In contrast, the larger airflow area of a fully open single-blade damper results in a non-recoverable minimum static pressure drop of about 0.01 to 0.05 in. WC (2.5 Pa to 12.5 Pa). 4 Cost of Static Pressure Loss The effect of pressure loss on energy consumption can be complicated, but it doesn t have to be. Some lab control publications have confused the issue, perhaps unintentionally. 5 With the right perspective, it can be simple. There are many mathematical ways to express the power that a fan consumes in a ventilation system. For this purpose (calculating the effect of pressure 4. For single duct supply air terminals the pressure drop of the reheat coil must also be considered when selecting and sizing air terminals for a given application. 5. For more information, contact Systems Applications in Buffalo Grove. losses for a given airflow rate) the following equation applies: Airflow Fan Pressure Fan Power Fan Efficiency This means fan power is directly proportional to pressure loss: twice as much pressure consumes twice as much power. If a fan system runs at 5 in. WC of pressure, and we can save 0.5 in. WC by selecting more efficient terminals, that saves 10% of the fan power. If the system is more efficient (for example, 3.0 in. WC) the percentage savings achievable at the terminals is even greater. Some lab control publications mistake the valve pressure drop for the: 1. Static pressure measured at the terminal. If a system runs with 0.5 in. WC (125 Pa) at the terminal, that includes the drop across other components, not just the valve. 2. Signal pressure generated by the airflow sensing element. The sensing pressure is not a loss in the system, and is often many times greater than the drop across the valve. Airflow Sound When airflow through a device causes a pressure drop, that energy is dissipated as heat and sound. The heat component of this energy transformation causes a slight rise in the air temperature flowing through the device, but this is usually small and is disregarded for practical purposes. However, the sound component can be significant and annoying. Therefore, sound ratings are an important consideration when choosing air terminals. A Venturi air valve terminal will typically create somewhat more discharge and radiated sound power for a given airflow than a single-blade damper type of an air terminal due to its greater pressure drop for a given airflow Determining the resulting room sound level caused by HVAC component sound can be a very complex matter. Aside from the air terminal sound, many other factors affect the room's ambient sound level. For additional insight into ventilation related sound, see the Technology Report No. 5 Attaining Acceptable Ventilation Related Sound in Laboratory Rooms ( ) and to Siemens comprehensive Application Guide Minimizing Excessive Sound in Ventilation System Designs ( ). Page 6 of 8 Siemens Industry, Inc.
7 Airflow Control Loop Performance Performance of an airflow control system can be evaluated without regard to the type of components. Figure 7 displays dynamic airflow data from two chemical fume hoods, one with a Venturi air valve and the other with a single-blade damper. Each plot shows the airflow as a function of time when the fume hood sash is opened. Both hoods exhibit the quick, stable flow control needed for safe laboratory work Air Flow Rate (cfm) time (seconds) time (seconds) Figure 7. Dynamic Airflow Control by a Single-Blade Damper (L) and a Venturi Air Valve (R). Applications for Mechanical Pressure Independence A common application of mechanical pressure independence is in constant air volume (CAV) ventilation systems. Constant airflow can be maintained in critical parts of the CAV system by applying Venturi air valves with pressure independent capability. This eliminates the need for separate airflow controllers and valve actuators and, thus, reduces the overall control system cost. CAV pressure independent applications include CAV fume hood exhaust, biological safety cabinet exhaust, laboratory room specialty equipment exhaust, lab bench exhausts (snorkels), and even the overall room ventilation supply and general exhaust airflow. In pressure independent applications, the Venturi air valve is used without an actuator and with the lever arm in a fixed position. (See Figure 1 for a description of the Venturi air valve components.) To obtain the required airflow, the lever arm must be manually positioned until the required airflow is attained and then the lever arm can be locked into position by a wing nut or a similar means. 7 Conclusion This report explains the issues surrounding use of the Venturi air valve and the single-blade damper as an airflow control device. The Venturi air valve is a more intricate mechanical device compared to the simple damper. Both are successfully applied as components high performance ventilation systems. Table 2 compares the major attributes of a Venturi air valve and a single-blade damper r. The performance achieved in a particular application is primarily a function of the overall airflow control system that includes, and depends on, the controller capability. Performance being equal, owners and engineers should base the decision of Venturi air valve versus single-blade damper on specific application, economical, and safety needs. Regardless of the end device, knowledge of actual airflow is important for informed operation. A thoroughly effective design includes airflow sensors. 7. The airflow through the Venturi air valve must be measured during the setup process in order to establish the proper lever arm position. Siemens Industry, Inc. Page 7 of 8
8 Table 2. Comparison of Major Air Terminal Characteristics. Attribute Venturi Air Valve Single-Blade Damper Physical Configuration Airflow Capacity More complex physical configuration with more operating components. Higher airflows require multiple ganged units, which takes up more space, increases the unit cost, and requires more duct transitions. Lower maximum airflow due to less airflow area for a given size (diameter) of air terminal. Higher airflow capacities require multiple (parallel ganged) units. Cost Higher cost per unit. Lower cost per unit. Mechanical Pressure Independence Control Curve Yes (within a specific static pressure range) Non-Linear (equal percentage) airflow control action. (Linear control is accomplished by applying a controller with closed loop control capability or the unit must be factory calibrated for use with an open loop controller.) Very simple physical configuration with minimal operating components only two damper shaft pivot points. Duct transitions and the installation are easier especially when higher airflows are required. Higher maximum airflow (70% to 100% greater than the Venturi air valve) for the same size (diameter) air terminal due to the large airflow area. No Non-linear (quick opening) airflow control action. (Linear control output is accomplished by applying a controller with closed loop control capability.) Control Accuracy Nominally +/- 5% as an open loop device Depends on the airflow sensor; which should be selected according to the application Control Turndown Minimum Pressure Drop Sound Generation Materials available to resist corrosion Susceptibility to the effects of chemical or airborne particulate Installation Requirements 8-to-1 with closed loop control. From 10-to-1 through 16-to-1 without closed loop control in. WC (75 Pa) for low pressure model in. WC (750 Pa) for medium pressure model. (This pressure drop is required to enable the mechanical pressure independent function to operate.) Somewhat higher than a round blade damper for the same airflow and pressure drop. Spun aluminum outer shell with Hersite and Teflon protective coatings are available for the shell, cone and shaft. Particulate accumulation on the internal surfaces will degrade the self-contained (non-closed loop) pressure independent function. External closed loop control is required to prevent degraded performance. Each unit must be installed in either the horizontal or vertical orientation in which it was factory calibrated. Higher airflow (ganged) units are cumbersome, heavy, and more difficult to install. Limited by leakage around damper seal. Sometimes reaches 20-to-1. Pressure drop is very low (0.01 to 0.05 in. WC or 2.5 to 12.5 Pa) with the damper wide open. (No minimum pressure drop is required for operation.) Somewhat lower than a Venturi air valve for the same airflow and pressure drop. Multiple materials available for the entire unit: Galvanized steel, Type 316L Stainless Steel and Teflon coating. Particulate accumulation will not degrade the closed loop control action. Units can be installed in any orientation vertical, horizontal, or angular. Higher airflow units are less cumbersome. Maintenance No routine maintenance required.* No routine maintenance required.* * All laboratory ventilation safety standards require periodic (typically on an annual basis) inspections of a laboratory ventilation system's performance. Product or company names mentioned herein may be the trademarks of their respective owners Siemens Industry, Inc. Siemens Industry, Inc. Printed in the USA Building Technologies Division 1000 Deerfield Parkway Page 8 of 8 Buffalo Grove, IL USA
Demand Based Static Pressure Reset Control for Laboratories
LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Powers Controls TH 192 S Single Temperature Room Thermostat
Technical Instructions Document No. 155-065P25 TH 192-1 Powers Controls TH 192 S Single Temperature Room Thermostat 50 60 70 80 TH0355R1 70 80 POWERS Description The TH 192 S thermostats are proportional
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
Chemical Fume Hoods. Environmental Health and Safety 974-5084
Chemical Fume Hoods Environmental Health and Safety 974-5084 Regulatory References Prudent Practices in the Laboratory 2011 (National Research Council of The National Academies): Laboratory chemical hoods
AMD-33 Air Measuring Station with VCD-33 Control Damper
Application and esign Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) Frame Type 5 in. x 1 in. hat channel - Blade Material Galvanized
Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.
ASGMT / Averaging Pitot Tube Flow Measurement Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. Averaging Pitot Tube Meters Introduction
Healthcare Solutions Room Pressure Monitors and Controls
Healthcare Solutions s and Controls TOUCHSCREEN ROOM PRESSURE MONITOR The Touchscreen Room Pressure Monitor (PMT) provides precise room pressure monitoring for critical spaces such as isolation rooms,
SAM HOUSTON STATE UNIVERSITY
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
Powers Controls TH 192 HC Heating/Cooling Room Thermostat
Powers Controls TH 192 HC Heating/Cooling Room Thermostat Technical Instructions Document No. 155-066P25 TH 192-2 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 192 HC thermostats are proportional
Signature and ISX CM870 Fuel System
Signature and ISX CM870 Fuel System Cummins Ontario Training Center HPI-TP Fuel System Heavy Duty High Pressure Injection - Time Pressure Fuel System The fuel system developed for the Signature and ISX
AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application and Design. Ratings. Features and Control Options.
Application and esign Thermal ispersion Air Measuring Station with VC-23 Control amper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage
Accurate Air Flow Measurement in Electronics Cooling
Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: [email protected] Air is the most commonly used medium to remove heat from electronics
Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009
Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort
Ceriani Replica GP35R forks. Technical description
Ceriani Replica GP35R forks Technical description This is an advanced racing replica of the GP35 forks. The legs are made from 6061 aluminium, mounted with CNC machined fittings, the stanchions are from
SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE
SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE Cable Processor Module overview WARNING! When tipping the Cable Processor Module back, (after removing the toggle arm pin), use extreme caution not to drop
Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat
Document No. 155-068P25 TH 193-4 Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 193 HC thermostats are proportional dual
POWERS Controls No. 4 Pneumatic Damper Actuator
POWERS Controls No. 4 Pneumatic Damper Actuator Technical Instructions Document No. 155-032P25 AP 331-2 Actuator Assembly 331-2929 Typical Actuator Assembly 331-2904 Typical Actuator Assembly 331-3000
PNEUMATIC CONTROLS Selection and Description
PNEUMATIC CONTROLS Selection and Description Carnes pneumatic controlled throttling units are suitable for a standard 20 psi control system and may be supplied with pressure dependent or pressure independent
The Effect of Forced Air Cooling on Heat Sink Thermal Ratings
zpero 1 The Effect of Forced Air Cooling on Heat Sink Thermal Ratings By Paul Bachman, Fellow Engineer & Ronnie Haiduk, Applications Engineer, Crydom, Inc. ABSTRACT A heat sink s ability to dissipate thermal
Design Information. Designing Your Dust Collection System. Typical dust or fume collection system
Design Information Designing Your Dust Collection System There are five simple steps to designing an effective and efficient dust collection system. 1. Draw a floor plan of your shop Important Terms to
Threaded Inline Air Heaters
Threaded Inline Air Heaters FOR SAFETY & LONG HEATER LIFE, CAREFULLY READ THIS MANUAL BEFORE USE. Safety SHOCK HAZARD! Only qualified individuals should install this heater and related controls. Follow
Cane Creek Double Barrel Instructions
Cane Creek Double Barrel Instructions Congratulations on your purchase of the Cane Creek Double Barrel (CCDB) rear shock. Developed in partnership with Öhlins Racing, the Double Barrel brings revolutionary
Index 11.1. Page. Pumping Systems...11.2-11.4 Intensifiers...11.5 Gas Boosters...11.6-11.7 High Pressure Generators...11.8-11.9
Pumping Systems, Intensifiers, Gas Boosters and High Pressure Generators High Pressure Equipment Company produces a number of components and systems for general industrial, elevated pressure applications.
ENGINEERING DATA. Fan Performance Troubleshooting Guide
Information and Recommendations for the Engineer ENGINEERING DATA Aerovent TC Ventco Fiber-Aire Twin City Fan & Blower TC Axial Clarage Fan Performance Troubleshooting Guide ED- Introduction Trying to
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
Fundamentals of Mass Flow Control
Fundamentals of Mass Flow Control Critical Terminology and Operation Principles for Gas and Liquid MFCs A mass flow controller (MFC) is a closed-loop device that sets, measures, and controls the flow of
Force measurement. Forces VECTORIAL ISSUES ACTION ET RÉACTION ISOSTATISM
Force measurement Forces VECTORIAL ISSUES In classical mechanics, a force is defined as "an action capable of modifying the quantity of movement of a material point". Therefore, a force has the attributes
Introduction to Accuracy and Repeatability in Linear Motion Systems
Introduction to accuracy and repeatability in linear motion systems By Gary Rosengren, Director of Engineering Tolomatic, Inc. About the Author Gary Rosengren is Director of Engineering at Tolomatic and
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
Chapter 11 SERVO VALVES. Fluid Power Circuits and Controls, John S.Cundiff, 2001
Chapter 11 SERVO VALVES Fluid Power Circuits and Controls, John S.Cundiff, 2001 Servo valves were developed to facilitate the adjustment of fluid flow based on the changes in the load motion. 1 Typical
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace Our thanks to OK International for allowing us to reprint the following. Why do we need fume extraction? Today s Electronics workplace
COUNTERBALANCE VALVES
COUNTERBALANCE VALVES Introduction They are modulating valves which allow free flow into the actuator and then block the reverse flow until they feel a pilot pressure inversely proportional to the load
Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.
DAN-LIQ-TG-44-rev0208 February 2008 Daniel Liquid Control Valves Technical Guide www.daniel.com Daniel Measurement and Control Theory, Principle of Operation and Applications This brochure has been prepared
Prelab Exercises: Hooke's Law and the Behavior of Springs
59 Prelab Exercises: Hooke's Law and the Behavior of Springs Study the description of the experiment that follows and answer the following questions.. (3 marks) Explain why a mass suspended vertically
MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard
MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard Advances in testing procedures, coupled with greater pressure for better IAQ, leads to a new standard By Ron Wilkinson, P.E.
Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard
LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled
A descriptive definition of valve actuators
A descriptive definition of valve actuators Abstract A valve actuator is any device that utilizes a source of power to operate a valve. This source of power can be a human being working a manual gearbox
FIRE DAMPER APPLICATION GUIDE
FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire
General Information... 2
Pneumatic VAV Reset Volume Controllers CSC 2000 Series Applications Guide General Information... 2 CSC 2000 Series Overview...2 odels and Specifications...3 ounting...4 Connections...4 All Units...4 Beige
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
How To Use A Ds340 (Dsp)
Ideal for monitoring dust levels in the exhaust gas of industrial combustion or air filtration processes. Innovative Dynamic Detection Principle (DDP) measurement technique Immune to gradual reductions
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
Model 43AP Pneumatic Controller, Style B
Instruction MI 011-476 January 1980 Model 43AP Pneumatic Controller, Style B Installation and Operation Model 43AP Controller continuously detects the difference between a process measurement and its set
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners
M/MR Modulating Valves design certified For Atmospheric, Infrared, and Direct Fired urners TALE OF CONTENTS Description/Specifications... 1 Introduction... 2 Direct Fired Applications (Negative Pressure)...
SELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS D-Series Engine Automatic Overspeed Shut Down Valves (Spindle Types with Air Pressure and Manual Shut Down Options) SELECTION, APPLICATION AND MAINTENANCE Valve Numbers D92-AP
Coal Handling Plant Alignment Standards For Shaft To Shaft Alignment. By Makarand Joshi M.Tech
Coal Handling Plant Alignment Standards For Shaft To Shaft Alignment By Makarand Joshi M.Tech 1.0 Abstract: - Shaft alignment is a technical skill that is not common in the construction and maintenance
T U R B I N E G A S M E T E R
TURBINE GAS METER TURBINE GAS METER CGT 1 2 3 4 5 6 7 Design and function page 2 General technical data page 3 Measurement outputs page 4 Dimensions and weights page 5 Performance page 7 Pressure loss
Flow Measurement Options for Pipeline and Open Channel Flow
Flow Measurement Options for Pipeline and Open Channel Flow October 2013 Presented by Molly Skorpik - 2013 Montana Association of Dam and Canal Systems Conference Irrigation Training and Research Center
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
Why Lead Screws are the Best Fit for Many Linear Motion Applications - and How to Rightly Apply Them
Why Lead Screws are the Best Fit for Many Linear Motion Applications - and How to Rightly Apply Them Robert Lipsett, Engineering Manager, Thomson BSA Thomson Industries, Inc. San Jose, CA 800.882.8857
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Baumann 24003 3 Way Bronze or Stainless Steel Control Valve
Product Bulletin D1039X012 24003 Valve Baumann 24003 3 Way Bronze or Stainless Steel Control Valve 3 Way Rugged Industrial Control Valve For Mixing and Diverting Applications The Baumann 24003 3 way control
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid
MULTIZONE APPLICATION OF SOLUTION UNITS
MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages
POWERS CONTROL RC 195 Single Input Receiver-Controller
Document No. 155-119P25 RC 195-4 POWERS CONTROL RC 195 Single Input Receiver-Controller Description The RC 195 Single lnput Receiver-Controller is a pneumatic instrument which receives one pneumatic input,
PRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
SUMMARY of PRODUCTS. HVAC Systems Control Airflow, Space, & Building Pressurization. Accurate airflow measurement for demanding applications
SUMMARY of PRODUCTS HVAC Systems Control Airflow, Space, & Building Pressurization Accurate airflow measurement for demanding applications Airflow Measuring Stations FAN-E AIRFLOW MEASURING STATION. The
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc.
Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc. Abstract The technology for connecting lead and magnet wires for electric motors and electro mechanical devices
Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
PORTER MASS FLOW MEASUREMENT AND CONTROL SYSTEMS
PORTER MASS MEASUREMENT AND CONTROL SYSTEMS PORTER: THE STANDARD OF EXCELLENCE IN MASS Porter Mass Flow products reflect nearly three decades of experience in the design and manufacture of precision instruments
MAXIMIZING THE OUTPUT OF YOUR BRAKES Getting Your Pedal Geometry Right
MATCO mfg 2361 S 1560 West Woods Cross, UT 84087 801-335-0582 801-335-0581 (F) www.matcomfg.com MAXIMIZING THE OUTPUT OF YOUR BRAKES Getting Your Pedal Geometry Right Brake Specifications Energy Rating
Chapter 12 Industrial Ventilation
Chapter 1 Industrial Ventilation Introduction Industrial Ventilation is an important method for reducing employee exposures to airborne contaminants. Ventilation is used to reduce or remove contaminates
Submersion/Insertion Toroidal Sensor
Instruction Sheet PN 51A-228/rev.P December 2010 Model 228 Submersion/Insertion Toroidal Sensor For additional information, please visit our website at www.emersonprocess.com/raihome/liquid/. CAUTION SENSOR/PROCESS
Application Note 142 August 2013. New Linear Regulators Solve Old Problems AN142-1
August 2013 New Linear Regulators Solve Old Problems Bob Dobkin, Vice President, Engineering and CTO, Linear Technology Corp. Regulators regulate but are capable of doing much more. The architecture of
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD
Basic Hydraulics and Pneumatics
Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:
Unit 24: Applications of Pneumatics and Hydraulics
Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 4 DIRECTIONAL CONTROL VALVES The material needed for outcome 2 is very extensive
Baumann 87000 Flexsleev Sanitary Control Valve
Product Bulletin D103345X012 Baumann 87000 Flexsleev Sanitary Control Valve The Baumann 87000 control valve (figures 1 and 2) is excellent for throttling high purity liquid or gaseous media commonly found
Chemistry 112 Laboratory Experiment 6: The Reaction of Aluminum and Zinc with Hydrochloric Acid
Chemistry 112 Laboratory Experiment 6: The Reaction of Aluminum and Zinc with Hydrochloric Acid Introduction Many metals react with acids to form hydrogen gas. In this experiment, you will use the reactions
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
Class II, Type A2 Biological Safety Cabinet HEPA Filter Loading Capacity
Class II, Type A2 Biological Safety Cabinet HEPA Filter Loading Capacity Best Products. Best Performance. Best Protection. NuAire, Inc. 2100 Fernbrook Lane Plymouth, MN 55447 U.S.A ph: 763.553.1270 fx:
Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
SELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine
VOLU-probe/SS. Stainless Steel Pitot Airflow Traverse Probes. Accurate airflow measurement for demanding applications
VOLU-probe/SS Stainless Steel Pitot Airflow Traverse Probes Accurate airflow measurement for demanding applications VOLU-probe/SS The VOLU-probe/SS Stainless Steel Pitot Airflow Traverse Probe is ideally
SECTION 15950 - TESTING, ADJUSTING, AND BALANCING
SECTION 15950 - TESTING, ADJUSTING, AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Industrial Steam System Process Control Schemes
Industrial Steam System Process Control Schemes This paper was developed to provide a basic understanding of the different process control schemes used in a typical steam system. This is however a fundamental
LAB 6: GRAVITATIONAL AND PASSIVE FORCES
55 Name Date Partners LAB 6: GRAVITATIONAL AND PASSIVE FORCES And thus Nature will be very conformable to herself and very simple, performing all the great Motions of the heavenly Bodies by the attraction
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
PIEZOMETER AIRFLOW MEASURING RING
PIEZOMETER AIRFLOW MEASURING RING M.K. Plastics is pleased to introduce The Piezometer Airflow Measuring Ring, now available as an accessory for our steel Axijet fans. The system consists of a Piezometer
CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB
Compact automatic flow rate regulator with polymer cartridge 127 series REGISTERED BS EN ISO 9001:2000 Cert. n FM 21654 UNI EN ISO 9001:2000 Cert. n 0003 CALEFFI 01166/09 GB Function The AUTOFLOW devices
Unit 24: Applications of Pneumatics and Hydraulics
Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 3 HYDRAULIC AND PNEUMATIC MOTORS The material needed for outcome 2 is very extensive
Welcome to this presentation on LED System Design, part of OSRAM Opto Semiconductors LED 101 series.
Welcome to this presentation on LED System Design, part of OSRAM Opto Semiconductors LED 101 series. 1 To discuss the design challenges of LED systems we look at the individual system components. A basic
DRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
NEW SIX-SEALS CUTTING RING. INTERNATIONAL INDUSTRIAL PATENT Nr. 864061 of the 10/03/99 FLANKS AND DOES NOT REPLACE THE STANDARD RING CURRENTLY IN USE
B4 NEW SIX-SEALS CUTTING RING. INTERNATIONAL INDUSTRIAL PATENT Nr. 864061 of the 10/03/99 FLANKS AND DOES NOT REPLACE THE STANDARD RING CURRENTLY IN USE AVAILABLE IN CARBON AND STAINLESS STEEL 23 THEORY
A99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
1 DESCRIPTION OF THE APPLIANCE
1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers
DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE
- 90 - DESIGN CRITERIA AND OPERATIONAL LIMITS FOR AXIAL FLOW FANS OPERATED IN PARALLEL MODE Dr.-Ing. Schiller, F. Howden Ventilatoren GmbH, Heidenheim ABSTRACT Axial Flow Fans are the preferred fan types
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 [email protected] www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS
Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation
Instruction Manual 1052 Size 20 Actuator (F & G) Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation Contents Introduction... 1 Scope of manual... 1 Description... 1 Specifications...
Ford F-Series Column Shift Repairs
Ford F-Series Column Shift Repairs I ve had it on my list to tighten up the linkage on my 52 s column shift setup for a long time. I tried to get it apart when I had all the front end sheet metal off,
Technical Guide No. 100. High Performance Drives -- speed and torque regulation
Technical Guide No. 100 High Performance Drives -- speed and torque regulation Process Regulator Speed Regulator Torque Regulator Process Technical Guide: The illustrations, charts and examples given in
FAN PROTECTION AGAINST STALLING PHENOMENON
FAN PROTECTION AGAINST STALLING PHENOMENON Roberto Arias Álvarez 1 Javier Fernández López 2 2 1 ZITRON Technical Director [email protected] ZITRON Technical Pre Sales Management [email protected]