SECTION SWITCHBOARDS

Similar documents
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SECTION SWITCHBOARDS

SECTION MEDIUM VOLTAGE SWITCHGEAR

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Secondary Unit Substations

Hyperlinks are Inactive

Sample - No Commercial Use

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

B. Related Sections: 1. Section Raceway and Boxes for Electrical Systems.

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

MCC Ratings. Voltage Rating

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

This section applies to the design and installation of transformers.

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Primary and Secondary Electrical Distribution Systems

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

Unified requirements for systems with voltages above 1 kv up to 15 kv

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Power Management Module 2. Installation

Circuit Breakers. NRC Series. NRC Series

SECTION LOW VOLTAGE LIGHTING CONTROLS

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

PREFACE. The products covered by this Guide are:

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Sentron Series Circuit Breakers

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

SECTION MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR

Circuit Breakers. Next Generation of Protection Capabilities

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

Switchgear and Metal-Enclosed Bus

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

ASCO SERIES 185 Power Transfer Switches

Engineers Edge, LLC PDH & Professional Training

SECTION VARIABLE FREQUENCY DRIVES

A. Shop Drawing submittals shall include, but not be limited to, the following:

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

SECTION SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

IRRIGATION PUMPING Table of Contents - Section 900

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

SECTION ZONED (DC LOOP) FIREALARM SYSTEM

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Atlanta Chapter IEEE Industry Applications Society

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

City of Riverside Building & Safety Division Phone: (951)

ELECTRICAL SAFETY RISK ASSESSMENT

Short Circuit Current Calculations

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Mini Power-Zone Unit Substation

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

INSTALLATION INSTRUCTIONS

8146/5 Series Breaker Panelboards

FAQs-Main switchboard design criteria

Electrical Grounding. Appendix C

D Youville College July 31, 2008 New Academic Building Cannon Design Project No

SECTION HEAT PUMPS

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

Requirements for Electrical Installations

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE

Cable/Conduit Conversion

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

DESIGN CLARIFICATION (DC)

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

Ducoterra Radiant Heating Panel Installation Manual

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

ADDENDUM #1(BID PACKAGE # 3)

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

Fusible Disconnect Switch

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

CONDUCTOR SHORT-CIRCUIT PROTECTION

NEC 2014 Code Changes

Transcription:

SECTION 16441 - SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes service and distribution switchboards rated 600 V and less. 1.3 DEFINITIONS A. EMI: Electromagnetic interference. B. GFCI: Ground-fault circuit interrupter. C. RFI: Radio-frequency interference. D. RMS: Root mean square. E. SPDT: Single pole, double throw. 1.4 SUBMITTALS A. Product Data: For each type of switchboard, overcurrent protective device, transient voltage suppression device, ground-fault protector, accessory, and component indicated. Include dimensions and manufacturers' technical data on features, performance, electrical characteristics, ratings, and finishes. B. Shop Drawings: For each switchboard and related equipment. 1. Dimensioned plans, elevations, sections, and details, including required clearances and service space around equipment. Show tabulations of installed devices, equipment features, and ratings. Include the following: a. Enclosure types and details for types other than NEMA 250, Type 1. b. Bus configuration, current, and voltage ratings. c. Short-circuit current rating of switchboards and overcurrent protective devices. d. Features, characteristics, ratings, and factory settings of individual overcurrent protective devices and auxiliary components. 2. Wiring Diagrams: Power, signal, and control wiring. 3. Coordination study of the Main or submains and the largest branch circuit devices downcircuit of the switchboard. Submittals shall be made on log log paper and included with Halff Associates, Inc., McAllen, TX Office 16441-1

the original submittals for the switchboard. Ground fault settings shall be indicated on the study. Minimum setting of 20% of the main or submain device shall be provided for the ground fault device to insure coordination. Time delays shall allow for g of a 20 Ampere 277 volt device to clear before the ground fault device trips the main or submain breaker. C. Field quality-control test reports including the following: 1. Test procedures used. 2. Test results that comply with requirements. 3. Results of failed tests and corrective action taken to achieve test results that comply with requirements. 1.5 QUALITY ASSURANCE A. Product Selection for Restricted Space: Drawings indicate dimensions for specific switchboards including clearances between switchboards and adjacent surfaces and other items. If equipment included exceeds dimensions on plans advise engineer of any addition space required. Furnish dimension drawing for approval. Otherwise provide equipment as shown. B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. C. Comply with NEMA PB 2, "Deadfront Distribution Switchboards." D. Comply with NFPA 70. 1.6 DELIVERY, STORAGE, AND HANDLING A. Deliver in sections or lengths that can be moved past obstructions in delivery path. B. Store indoors in clean dry space with uniform temperature to prevent condensation. Protect from exposure to dirt, fumes, water, corrosive substances, and physical damage. C. If stored in areas subjected to weather, cover switchboards to provide protection from weather, dirt, dust, corrosive substances, and physical damage. Remove loose packing and flammable materials from inside switchboards; install electric heating (250 W per section) to prevent condensation. D. Handle switchboards according to NEMA PB 2.1 and NECA 400. 1.7 PROJECT CONDITIONS A. Installation Pathway: Remove and replace access fencing, doors, lift-out panels, and structures to provide pathway for moving switchboards into place. B. Environmental Limitations: Rate equipment for continuous operation under the following conditions, unless otherwise indicated: 1. Ambient Temperature: Not exceeding 104 deg F. 2. Altitude: Not exceeding 6600 feet. Halff Associates, Inc., McAllen, TX Office 16441-2

C. Service Conditions: NEMA PB 2, usual service conditions, as follows: 1. Ambient temperatures within limits specified. 2. Altitude not exceeding 6600 feet. D. Interruption of Existing Electric Service: Do not interrupt electric service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary electric service according to requirements indicated: 1. Notify Architect, Construction Manager and Owner no fewer than 14 days in advance of proposed interruption of electric service. 2. Indicate method of providing temporary electric service. 3. Do not proceed with interruption of electric service without Owner's written permission. 1.8 COORDINATION A. Coordinate layout and installation of switchboards and components with other construction including conduit, piping, equipment, and adjacent surfaces. Maintain required workspace clearances and required clearances for equipment access doors and panels. B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Division 3. 1.9 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Potential Transformer Fuses: Equal to 10 percent of amount installed for each size and type, but no fewer than 2 of each size and type. 2. Control-Power Fuses: Equal to 10 percent of amount installed for each size and type, but no fewer than 2 of each size and type. 3. Fuses and Fusible Devices for Fused Circuit Breakers: Equal to 10 percent of amount installed for each size and type, but no fewer than 3 of each size and type. 4. Fuses for Fused Switches: Equal to 10 percent of amount installed for each size and type, but no fewer than 3 of each size and type. 5. Fuses for Fused Power-Circuit Devices: Equal to 10 percent of amount installed for each size and type, but no fewer than 3 of each size and type. 6. Indicating Lights: Equal to 10 percent of amount installed for each size and type, but no fewer than 1 of each size and type. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: 1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified. Halff Associates, Inc., McAllen, TX Office 16441-3

2. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. 2.2 MANUFACTURED UNITS A. Manufacturers: 1. Eaton Corporation; Cutler-Hammer Products. 2. General Electric Co.; Electrical Distribution & Protection Div. 3. Siemens Energy & Automation, Inc. 4. Square D. B. Front- and Side-Accessible Switchboard: Fixed, individually mounted main device; panelmounted branches; and sections rear aligned. C. Nominal System Voltage: 480Y/277 V. D. Main-Bus Continuous: 1000 A. E. Enclosure: Steel, NEMA 250, Type 3R. F. Enclosure Finish for Outdoor Units: Factory-applied finish in manufacturer's standard color, undersurfaces treated with corrosion-resistant undercoating. G. Enclosure Finish for Indoor Units: Factory-applied finish in manufacturer's standard gray finish over a rust-inhibiting primer on treated metal surface. H. Space Heaters: Factory-installed electric space heaters of sufficient wattage in each vertical section to maintain enclosure temperature above expected dew point. I. Hinged Front Panels: Allow access to circuit breaker, metering, accessory, and blank compartments. J. Buses and Connections: Three phase, four wire, unless otherwise indicated. 1. Phase- and Neutral-Bus Material: Hard-drawn copper of 98 percent conductivity with feeder circuit-breaker line connections. 2. Tin-plated, high-strength, electrical-grade aluminum, aluminum circuit-breaker line connections. 3. Hard-drawn copper of 98 percent conductivity. a. If bus is copper, use copper for feeder circuit-breaker line connections. 4. Load Terminals: Insulated, rigidly braced, silver-plated, copper runback bus extensions equipped with pressure connectors for outgoing circuit conductors. Provide load terminals for future circuit-breaker positions at full ampere rating of circuit-breaker position. 5. Ground Bus: 1/4-by-2-inch- minimum-size, hard-drawn copper of 98 percent conductivity, equipped with pressure connectors for feeder and branch-circuit ground conductors. For busway feeders, extend insulated equipment grounding cable to busway ground connection and support cable at intervals in vertical run. 6. Contact Surfaces of Buses: Silver plated. 7. Main Phase Buses, Neutral Buses, and Equipment Ground Buses: Uniform capacity for entire length of switchboard's main and distribution sections. Provide for future extensions from both ends. Halff Associates, Inc., McAllen, TX Office 16441-4

8. Isolation Barrier Access Provisions: Permit checking of bus-bolt tightness. 9. Neutral Buses: 100 percent of the ampacity of phase buses, unless otherwise indicated, equipped with pressure connectors for outgoing circuit neutral cables. Bus extensions for busway feeder neutral bus are braced. K. Future Devices: Equip compartments with mounting brackets, supports, bus connections, and appurtenances at full rating of circuit-breaker size specified. 2.3 OVERCURRENT PROTECTIVE DEVICES A. Molded-Case Circuit Breaker: NEMA AB 3, with interrupting capacity to meet available fault currents. 1. Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads, and instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for circuit-breaker frame sizes 250 A and larger. 2. Adjustable Instantaneous-Trip Circuit Breakers: Magnetic trip element with frontmounted, field-adjustable trip setting. 3. Electronic trip-unit circuit breakers shall have RMS sensing, field-replaceable rating plug, and the following field-adjustable settings: a. Instantaneous trip. b. Long- and short-time pickup levels. c. Long- and short-time time adjustments. d. Ground-fault pickup level, time delay, and I 2 t response. e. Intregal Ammeter. 4. Frame sizes 400 A and smaller; let-through ratings. 5. Thermal-magnetic trip element with integral trip activation on fuse opening or on opening. 6. GFCI Circuit Breakers: Integral with 30-mA trip sensitivity. B. Molded-Case Circuit-Breaker Features and Accessories: Standard frame sizes, trip ratings, and number of poles. 1. Lugs: Mechanical style, suitable for number, size, trip ratings, and conductor material. 2. Ground-Fault Protection: Integrally mounted relay and trip unit with adjustable pickup and time-delay settings, push-to-test feature, and ground-fault indicator on main or submain. 3. Shunt Trip: 120-V trip coil energized from separate circuit, set to trip at 75 percent of rated voltage. C. Enclosed, Insulated-Case Circuit Breaker: Fully rated, encased-power circuit breaker with interrupting capacity rating to meet available fault current. 1. Fixed circuit-breaker mounting. 2. Two-step, stored-energy closing. 3. Microprocessor-based trip units with interchangeable rating plug, LED trip indicators, and the following field-adjustable settings: a. Instantaneous trip. b. Long- and short-time pickup levels. c. Long- and short-time time adjustments with I 2 t response. d. Ground-fault pickup level, time delay, and I 2 t response. 4. Control Voltage: 125-V, ac. Halff Associates, Inc., McAllen, TX Office 16441-5

2.4 INSTRUMENTATION A. Instrument Transformers: NEMA EI 21.1, IEEE C57.13, and the following: 1. Potential Transformers: Secondary voltage rating of 120 V and NEMA accuracy class of 0.3 with burdens of W, X, and Y. 2. Current Transformers: Ratios shall be as indicated with accuracy class and burden suitable for connected relays, meters, and instruments. 3. Control-Power Transformers: Dry type, mounted in separate compartments for units larger than 3 kv. B. Multifunction Digital-Metering Monitor: Microprocessor-based unit suitable for three- or fourwire systems and with the following features: 1. Switch-selectable digital display of the following values with maximum accuracy tolerances as indicated: a. Phase Currents, Each Phase: Plus or minus 1 percent. b. Phase-to-Phase Voltages, Three Phase: Plus or minus 1 percent. c. Phase-to-Neutral Voltages, Three Phase: Plus or minus 1 percent. d. Megawatts: Plus or minus 2 percent. e. Megavars: Plus or minus 2 percent. f. Power Factor: Plus or minus 2 percent. g. Frequency: Plus or minus 0.5 percent. h. Megawatt Demand: Plus or minus 2 percent; demand interval programmable from 5 to 60 minutes. i. Accumulated Energy, Megawatt Hours: Plus or minus 2 percent. Accumulated values unaffected by power outages up to 72 hours. 2. Mounting: Display and control unit flush or semiflush mounted in instrument compartment door. 2.5 CONTROL POWER A. Control Circuits: 120 V, supplied through secondary disconnecting devices from control-power transformer. B. Control-Power Fuses: Primary and secondary fuses for current-limiting and overload protection of transformer and fuses for protection of control circuits. C. Control Wiring: Factory installed, with bundling, lacing, and protection included. Provide flexible conductors for No. 8 AWG and smaller, for conductors across hinges, and for conductors for interconnections between shipping units. PART 3 - EXECUTION 3.1 PROTECTION A. Temporary Heating: Apply temporary heat to maintain temperature according to manufacturer's written instructions. Halff Associates, Inc., McAllen, TX Office 16441-6

3.2 EXAMINATION A. Examine elements and surfaces to receive switchboards for compliance with installation tolerances and other conditions affecting performance. B. Proceed with installation only after unsatisfactory conditions have been corrected. 3.3 INSTALLATION A. Install switchboards and accessories according to NEMA PB 2.1 and NECA 40. B. Install and anchor switchboards level on concrete bases, 4-inch nominal thickness. Concrete base is specified in Division 16 Section "Electrical Supports and Seismic Restraints," and concrete materials and installation requirements are specified in Division 3. 1. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. 2. Install anchor bolts to elevations required for proper attachment to switchboards. C. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from switchboard units and components. D. Operating Instructions: Frame and mount the printed basic operating instructions for switchboards, including control and key interlocking sequences and emergency procedures. Fabricate frame of finished wood or metal and cover instructions with clear acrylic plastic. Mount on front of switchboards. E. Install overcurrent protective devices, and instrumentation. 1. Set field-adjustable switches and circuit-breaker trip ranges. 3.4 IDENTIFICATION A. Switchboard Nameplates: Label each switchboard compartment with engraved metal or laminated-plastic nameplate mounted with corrosion-resistant screws. 3.5 FIELD QUALITY CONTROL A. Prepare for acceptance tests as follows: 1. Test insulation resistance for each switchboard bus, component, connecting supply, feeder, and control circuit. 2. Test continuity of each circuit. B. Perform the following field tests and inspections and prepare test reports: 1. Perform each electrical test and visual and mechanical inspection stated in NETA ATS, Sections 7.1, 7.5, 7.6, 7.9, 7.10, 7.11, and 7.14 as appropriate. Certify compliance with test parameters. 2. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest. Halff Associates, Inc., McAllen, TX Office 16441-7

3. Perform the following infrared scan tests and inspections and prepare reports: 3.6 CLEANING A. On completion of installation, inspect interior and exterior of switchboards. Remove paint splatters and other spots. Vacuum dirt and debris; do not use compressed air to assist in cleaning. Repair exposed surfaces to match original finish. 3.7 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain switchboards, overcurrent protective devices, instrumentation, and accessories. Refer to Division 1 Section "Demonstration and Training." END OF SECTION 16441 Halff Associates, Inc., McAllen, TX Office 16441-8