A. Section includes switchboards, distribution panelboards, and lighting and appliance branch circuit panelboards.

Similar documents
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Mini Power-Zone Unit Substation

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Electrical Service Guidelines

IRRIGATION PUMPING Table of Contents - Section 900

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

Approved Meter Sockets and Cabinets

SECTION SWITCHBOARDS

Customer Substation Manual 08/05/02

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Secondary Unit Substations

MCC Ratings. Voltage Rating

Engineers Edge, LLC PDH & Professional Training

Sample - No Commercial Use

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

8146/5 Series Breaker Panelboards

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

Addendum #2 Contract UK-11-13

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

A. Shop Drawing submittals shall include, but not be limited to, the following:

Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features

NEC 2014 Code Changes

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

B. Related Sections: 1. Section Raceway and Boxes for Electrical Systems.

Hyperlinks are Inactive

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL INSPECTION BULLETIN (Effective )

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Switchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR

LCP Coordination Panel Operations & Maintenance Manual Table of Contents

Distribution Dry Type Transformers

Section 10 Electric Switchboards: 0 Through 600 Volts

Bolted contact switches. Pringle switches

Questions and Answers for Heating and A/C Contractors

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General

Applications. Remote Display Mounting Kits

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Fusible Disconnect Switch

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

Electrical Practices for Construction Work

City of Riverside Building & Safety Division Phone: (951)

Electrical. This section applies to the design and installation of building power distribution systems.

Guide for Electric Service and Meter Installations

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

ASCO SERIES 185 Power Transfer Switches

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

Medium Voltage Electrical Distribution

Cluster Box Units. (CBU s) 3300 Series CBU Door Sizes. Fully Integrated Parcel Lockers CLUSTER BOX UNITS FRONT LOADING. continued on pages 7-11

Top Commercial / Residential Electrical Requirements *

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

SECTION LOW VOLTAGE LIGHTING CONTROLS

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

Type 1, 3, & 3R Enclosures

Electrical Code Regulation

INSTALLATION INSTRUCTIONS

Element D Services Electrical

Continuous Power... Continuous Protection

LVA Take Offs in Bid Manager

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

Requirements for Electrical Installations

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

Multiple Meter Installation Amperes Per Position -Single Phase, Self-contained

Switchgear and Metal-Enclosed Bus

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

Customer Metering and Services Guide

The following components are common to most cubicles; this example is an ABB HK cubicle.

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

Bypass transfer switch mechanisms

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Section 5 Meters and Service Entrance Equipment

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

APC 3Phase Power Distribution

San Diego Area Chapter International Code Council

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Roped Hydraulic Residential Elevator Specifications

SECTION MEDIUM VOLTAGE SWITCHGEAR

METERING INSTALLATION REQUIREMENTS

Transcription:

26 24 00 PART 1 - GENERAL 1.01 SUMMARY A. Section includes switchboards, distribution panelboards, and lighting and appliance branch circuit panelboards. 1.02 PERFORMANCE REQUIREMENTS A. Seismic performance: Switchboards and panelboards shall withstand the effects of earthquake motions determined according to the most current USGS adopted seismic zone. 1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified, and the unit will be fully operational after the seismic event". PART 2 - PRODUCTS 2.01 GENERAL REQUIREMENTS FOR A. Enclosures: Flush and surface mounted cabinets. 1. Rated for environmental conditions at installed location. i. Indoor dry and clean locations: NEMA 250, Type 1. ii. Outdoor locations: NEMA 250, Type 3R. iii. Kitchen and wash down areas: NEMA 250, Type 4X, stainless steel. iv. Other wet or damp indoor locations: NEMA 250, Type 4. 2. Front: Secured to box with concealed trim clamps. For surface-mounted fronts, match box dimensions; for flush-mounted fronts, overlap box. 3. Hinged front cover: Entire front trim hinged to box and with standard door within hinged trim cover. 4. Directory card: Typewritten only; inside panelboard door; mounted in transparent card holder. Hand-written cards will not be accepted. B. Incoming mains location: Top or Bottom, as required for the installation. C. Phase, neutral, and ground buses: Hard-drawn copper, 98 percent conductivity.

26 24 00 D. Conductor connectors: Suitable for use with conductor material and sizes. 1. Material: Hard drawn copper, 98 percent conductivity. 2. Main and neutral lugs: Mechanical type. 3. Ground lugs and bus configured terminators: Mechanical type. 4. Feed-through lugs: i. Mechanical type, suitable for use with conductor material. ii. Locate at opposite end of bus from incoming lugs or main device. iii. Shall not be acceptable between floors. iv. Shall be used only for side-by-side panel installations. 5. Sub-feed (double) lugs: i. Mechanical type suitable for use with conductor material. ii. Locate at same end of bus as incoming lugs or main device. E. Future devices: Install bussing for full length of panelboard. Provide mounting brackets, bus connections, filler plates, and necessary appurtenances required for future installation of devices. F. Panelboard short circuit current rating: Fully rated for the available fault current. Series-rated panelboards shall be pre-approved by the WSU Construction Manager or Engineering Services. These shall typically be used only where fully rated panelboards are not economical or do not exist for the available fault. G. All switchboards and panelboards shall be of one manufacturer for entire project. 2.02 DISTRIBUTION SWITCHBOARDS A. Manufacturers: 1. Eaton Electrical Inc.; Cutler-Hammer Business Unit 2. General Electric Company; GE Consumer & Industrial - Electrical Distribution 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric

26 24 00 B. Switchboards: Conform to NEMA PB 2. C. Doors: Exterior switchboards shall be secured with vault-type latch; lock and keys per section 08 70 00 Hardware and Keying. D. Where main overcurrent protection is required, circuit breakers are preferred. E. Overcurrent protective devices: 1. Bolt-on circuit breakers only; stab-in circuit breakers shall not be accepted. 2. Provide fused switches only if recommended by the equipment manufacturer or where magnitude of available fault prevents the use of circuit breakers. 2.03 DISTRIBUTION AND BRANCH CIRCUIT PANELBOARDS A. Panelboards shall be dead front, 20-inches wide, surface or recessed mounted, have copper busing and 100% rated isolated neutral, a ground bus, and accept bolt-on circuit breakers only. 1. Recessed panelboards shall have a single 1 empty conduit for every three spaces and spares, stubbed to accessible space for future use. B. Manufacturers: 1. Eaton Electrical Inc.; Cutler Hammer Business Unit 2. General Electric Company; GE Consumer & Industrial - Electrical Distribution 3. Siemens Energy & Automation, Inc. 4. Square D; a brand of Schneider Electric C. Panelboards: Conform to NEMA PB 1. D. Mains: Circuit breaker or Main Lugs only. E. Branch overcurrent protective devices: Bolt-on circuit breakers, replaceable without disturbing adjacent units. 1. Panelboard circuit breakers shall be thermal-magnetic, quick break, quick make, trip indicating. Multi-pole circuit breakers shall have a common trip. 2. Breakers shall be rated for the following:

26 24 00 i. 208Y/120 volt panelboards: 10,000 AIC symmetrical, minimum. ii. 480Y/277 volt panelboards: 14,000 AIC symmetrical, minimum. F. Doors: Concealed hinges; secured with flush latch; lock and keys per section 08 70 00 Hardware and Keying. G. Wire connections shall be rated for 75 degrees Celsius. H. A minimum of 25% spares/spaces shall be provided in each panelboard. I. Panelboards shall be mounted with top at six foot-six inches (6'-6") above the floor. J. Selective TVSS protection only where protection of electronic equipment is required. 2.04 SERVICE ENTRANCE SWITCHBOARDS A. Provide copper bussing rated at 1,000 amperes per square inch. Space for future disconnects shall have complete provisions made so that only the adding and connecting of the device will complete the installation. B. TVSS protection required at all Service Entrance Switchboards. C. All breakers within service entrance switchboards shall be 100% rated. D. All shunt breakers used for load shedding shall be motorized on and off, and shall be connected and controlled by the WSU BAS. 2.05 ELECTRICAL METERING A. Meters shall be installed as follows: 1. Main Metering: Each main building service and/or feeder entrance at the first overcurrent protective device, or as otherwise designated by the WSU Facilities Services Energy Group. 2. Sub-Metering: As required by local jurisdiction or as designated by the WSU Facilities Services Energy Group. B. Provide meter as described below: 1. Standard Model: SEL 735 power revenue meter, vertical configuration number 0735VX00944CXXXXXX16102XX. 2. Centerline of the meter is to be 54 66 above finished floor.

26 24 00 3. The meter shall have direct Ethernet connection to the Facilities Services Private Network Ethernet Switch. C. Each meter cubicle shall have a phenolic label, white face/black letters (3/8 min.), with the following engraved information (example only): MS-1 Main 480V Service Switchgear Meter Meter Location Number: PB0050_ENMAAA480 CT Ratio: 200/5, PT Ratio: 1/1 D. Switchboard Meter Installation: 1. Electrical switchboards shall be provided with meter enclosure cubicle with hinged front door allowing safe access to the rear face of the meter, Current Transformer (CT) shorting blocks, etc., for inspection, testing, and calibration while switchboard is in service. i. CT terminal blocks shall be shorting style and all CT terminations shall utilize ring tongue connections. ii. Switchboard manufacturer shall install a complete functional metering system, in accordance with meter manufacturer s specifications and recommendations, to include CTs and potential taps. Switchboard meters shall not be field-installed. iii. Switchboard manufacturer shall confirm that meter potential and current input phasing and polarity are correct. E. Panelboard Meter Installation: 1. Electrical panelboards shall be provided with a separate meter mounted in a NEMA 4X enclosure with hinged front door allowing safe access to the rear face of the meter, Current Transformer (CT) shorting blocks, etc., for inspection, testing, and calibration while panelboard is in service. i. CT terminal blocks shall be shorting style and all CT terminations shall utilize ring tongue connections. 2. Contractor shall install a complete functional metering system, in accordance with meter manufacturer s specifications and recommendations, to include CTs and potential taps. 3. Contractor shall confirm that meter potential and current input phasing and polarity are correct. F. Contractor shall contact WSU Engineering Services, through the Construction Manager, for assistance with meter setup files.

26 24 00 G. Prior to transformer secondary terminations, Contractor shall coordinate with WSU Construction Manager to schedule a meeting to confirm correct phasing from utility substation bus to switchgear bus and meter. H. Meter commissioning shall include comparison to values gathered simultaneously using a Contractor-provided portable 3-phase energy meter and shall include confirmation that voltage/current phasor relationships are correct and positive ABC rotation exists. WSU Facilities Services Energy Group representative must be present during meter commissioning. 2.06 ENCLOSED SWITCHES: FUSED AND NON-FUSED A. Switches shall have copper bussing, be quick break, quick make and rated heavy duty. Switches shall have a defeatable cover interlock and have provisions for padlocking. A neutral bus shall be provided for circuits requiring a neutral. 2.07 ACCESSORY COMPONENTS AND FEATURES A. Portable test set: 1. For testing functions of solid-state trip devices without removing from panelboard. Include relay and meter test plugs suitable for testing panelboard meters and switchboard class relays. PART 3 - EXECUTION 3.01 INSTALLATION A. Install all switchboards and panelboards that extend to the floor on 4-inch concrete housekeeping pads. B. Mount panelboard cabinet plumb and rigid without distortion of box. While recessed panelboards are less desirable, they are to be mounted with fronts uniformly flush with wall finish and mating with back box. Surface mounted panelboards are preferable for ease of maintenance and for adding new circuits. C. Panels shall not be installed in underground vaults, tunnels, etc. D. Where programmable solid-state breakers are used, copies of the manufacturer s user guide and maintenance instructions shall be made available on the breaker enclosure and the facility Operations and Maintenance (O&M) manuals. END OF SECTION