SECTION INCLUDES REFERENCES SUBMITTALS QUALIFICATIONS DELIVER, STORAGE, AND HANDLING MAHLUM KING'S SCHOOL KING S JUNIOR HIGH SCHOOL MODERNIZATION

Similar documents
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Mini Power-Zone Unit Substation

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Contractors Guide Central Inverter System Installation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

SECTION SWITCHBOARDS

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1

Engineers Edge, LLC PDH & Professional Training

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

IRRIGATION PUMPING Table of Contents - Section 900

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Secondary Unit Substations

Power Management Module 2. Installation

SECTION MEDIUM VOLTAGE SWITCHGEAR

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Extend the Life of Existing Switchgear

SECTION LOW VOLTAGE LIGHTING CONTROLS

MCC Ratings. Voltage Rating

SECTION VARIABLE FREQUENCY DRIVES

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

RAY-MAX Integrated Solar Power Strip

DUPLEX 120 VOLT FLOAT CONTROL PANEL STANDARD SPECIFICATION

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, (210) 16 (407) 5.5 (140) (283) 16 (407) 5.5 (140)

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

This section applies to the design and installation of transformers.

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

Diesel Engine Driven Generators Page 1 of 6

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Roped Hydraulic Residential Elevator Specifications

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Sample - No Commercial Use

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Andersen Electric Window Opener for Andersen Awning and Roof Windows

Primary and Secondary Electrical Distribution Systems

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Requirements for Electrical Installations

Low Voltage Transformers Sealed, General Purpose, Dry Type

Sentron Series Circuit Breakers

Electrical. This section applies to the design and installation of building power distribution systems.

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

INTRUSION DETECTION SYSTEM Section

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

CalMod Design-Build Electrification Services

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Utility Distribution Systems

Doc Ref: baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

B. Related Sections: 1. Section Raceway and Boxes for Electrical Systems.

DESIGN CLARIFICATION (DC)

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

Electrical Grounding. Appendix C

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

Installation Manual Version 7.3 IMPORTANT:

Rack Installation. Unpacking the System. Choosing a Setup Location. General Server Precautions. Barracuda Appliances

SECTION HEAT PUMPS

A. "Provide" means furnish, install and connect unless otherwise described in specific instances.

WE-350 Series ¼ Turn Electric Actuator

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Parallel Redundant Uninterruptible Power Supply

SECTION COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

Data Bulletin. Circuit Breaker Characteristic Trip Curves and Coordination Class 0600 TRIP CURVES AND COORDINATION CIRCUIT BREAKER TRIP CURVES

A. Shop Drawing submittals shall include, but not be limited to, the following:

AU-110 racking guide NBXPN: 023

CLEAR-DIVISIONS CENTERFOLD

Medium Voltage Motor Control Assemblies

Transcription:

PART 1 1.1 1.2 1.3 1.4 1.5 GENERAL SECTION INCLUDES A. Main Switchboard Furnish and install the Service Entrance switchboard(s) as herein specified and shown on the associated electrical drawings. B. Distribution Switchboard Furnish and install the Distribution Switchboard(s) as herein specified and shown on the associated electrical drawings. C. See section 260573 for protective device coordination study requirements. All equipment specified herein shall comply with the requirements of 260573. All equipment shall be increased in size, electronic trip added, wire and conduit size increased as require to provide a complete selectively coordinated system. Nothing in the following specification relieves the contractor from providing a complete selectively coordinated system. Fuses shall not be used to provide selective coordination REFERENCES A. The switchboard(s) and overcurrent protection devices referenced herein are designed and manufactured according to the following appropriate specifications. 1. ANSI/NFPA 70 - National Electrical Code (NEC). 2. ANSI/IEEE C12.16 - Solid State Electricity Metering. 3. ANSI C57.13 - Instrument Transformers. 4. NEMA AB 1 - Molded Case Circuit Breakers and Molded Case Switches. 5. NEMA PB 2 - Deadfront Distribution Switchboards, File E8681. 6. NEMA PB 2.1 - Proper Handling, Installation, Operation and Maintenance of Deadfront Switchboards Rated 600 Volts or Less. 7. NEMA PB 2.2 - Application Guide for Ground Fault Protective Devices for Equipment. 8. UL 50 - Cabinets and Boxes. 9. UL 98 - Enclosed and Dead Front Switches. 10. UL 489 - Molded Case Circuit Breakers. 11. UL 891 - Dead-Front Switchboards. 12. UL 943 - Ground Fault Circuit Interrupters. 13. Federal Specification W-C-375B/Gen - Circuit Breakers, Molded Case, Branch Circuit And Service. SUBMITTALS A. Shop Drawings shall indicate front and side enclosure elevations with overall dimensions shown; conduit entrance locations and requirements; nameplate legends; one-line diagrams; equipment schedule; and switchboard instrument details. QUALIFICATIONS A. To be considered for approval, a manufacturer shall have specialized in the manufacturing and assembly of switchboards for at least fifty (50) years. B. Furnish products listed by Underwriters Laboratories Incorporated and in accordance with standards listed in Article 1.03 - References. C. The manufacturing facility shall be registered by Underwriters Laboratories Inc. to the International Organization for Standardization ISO 9002 Series Standards for quality. DELIVER, STORAGE, AND HANDLING A. Deliver, store, protect, and handle products in conformance with manufacturer's recommended practices as outlined in applicable Installation and Maintenance Manuals. B. Each switchboard section shall be delivered in individual shipping splits for ease of handling. They shall be individually wrapped for protection and mounted on shipping skids. 2015 MAHLUM PERMIT SET Issue Date: 11 SEPTEMBER 2015 PAGE 1 OF 5

C. Inspect and report concealed damage to carrier within their required time period. 1.6 1.7 1.8 PART 2 2.1 2.2 D. Store in a clean, dry space. Maintain factory protection and/or provide an additional heavy canvas or heavy plastic cover to protect structure from dirt, water, construction debris, and traffic. Where applicable, provide adequate heating within enclosures to prevent condensation. E. Handle in accordance with NEMA PB 2.1 and manufacturer's written instructions. Lift only by lifting means provided for this express purpose. Handle carefully to avoid damage to switchboard internal components, enclosure, and finish. ENVIRONMENTAL REQUIREMENTS A. Conform to NEMA PB 2 service conditions during and after installation of switchboards. MAINTENANCE MATERIALS A. Provide installation and maintenance instructions with each switchboard. Instructions are to be easily identified and affixed within the incoming or main section of the line-up. WARRANTY A. Manufacturer shall warrant equipment to be free from defects in materials and workmanship for the lesser of one (1) year from date of installation. PRODUCTS MANUFACTURERS A. Shall be Square D Company or General Electric (No Substitute). B. All switchboards, distribution switchboards, and panels shall have copper bus SWITCHBOARD GENERAL A. Utility Metering Compartment: Not applicable, primary metered campus. B. Short Circuit Current Rating: Switchboards shall be rated with a minimum short circuit current rating as shown on drawings. C. Future Provisions: All unused spaces provided, unless otherwise specified, shall be fully equipped for future devices, including all appropriate connectors and mounting hardware. D. Enclosure: Type 1 - General Purpose. 1. Sections shall be aligned front and rear. 2. Removable steel base channels (1.5 inch floor sills) shall be bolted to the frame to rigidly support the entire shipping section for moving on rollers and floor mounting. 3. The switchboard enclosure shall be painted on all exterior surfaces. The paint finish shall be a medium gray, ANSI #49, applied by the electro-deposition process over an iron phosphate pre-treatment. 4. All front covers shall be screw removable with a single tool and all doors shall be hinged with removable hinge pins. 5. Top and bottom conduit areas shall be clearly indicated on shop drawings. E. Nameplates: Provide 1 inch high x 3 inches engraved laminated (Gravoply) nameplates for each device. Furnish black letters on a white background for all voltages. F. Bus Composition: Shall be plated copper only. Plating shall be applied continuously to all bus work. The switchboard bussing shall be of sufficient cross-sectional area to meet UL Standard 891 temperature rise requirements. The phase and neutral through-bus shall have an ampacity as shown in the plans. For 4-wire systems, the neutral shall be of equivalent ampacity as the phase bus bar. Tapered bus is not acceptable. Full provisions for the 2015 MAHLUM PERMIT SET Issue Date: 11 SEPTEMBER 2015 PAGE 2 OF 5

addition of future sections shall be provided. Bussing shall include all necessary hardware to accommodate splicing for future additions. G. Ground Bus: Sized per NFPA70 and UL 891 Tables 25.1 and 25.2 and shall extend the entire length of the switchboard. Provisions for the addition of future sections shall be provided. 2.3 2.4 SWITCHBOARD INCOMING MAIN SECTION DEVICES A. Main Circuit Breaker(s) 1. Electronic trip molded case full function 100% rated circuit breaker(s) with ground fault protection. a. All electronic circuit breakers shall have the following time/current response adjustments: Long Time Pickup, Long Time Delay, Short Time Pickup, Short Time Delay, Ground Fault Pickup Ground Fault Delay and Instantaneous settings. Each adjustment shall have discrete settings (fully adjustable) and shall be independent of all other adjustments. b. Circuit breaker trip system shall be a microprocessor-based true rms sensing designed with sensing accuracy through the thirteenth (13th) harmonic. Sensor ampere ratings shall be as indicated on the associated schedule. c. Local visual trip indication for overload, short circuit and ground fault trip occurrences. d. Long Time Pickup indication to signal when loading approaches or exceeds the adjustable ampere rating of the circuit breaker shall be provided. e. Communications capabilities for remote monitoring of circuit breaker trip system, to include phase and ground fault currents, pre-trip alarm indication, switch settings, and trip history information shall be provided. f. Circuit breaker shall be provided with Zone selective Interlocking (ZSI) communications capabilities on the short-time and ground fault functions compatible with all other electronic trip circuit breakers and external ground fault sensing systems as noted on schedules. SWITCHBOARD DISTRIBUTION SECTION DEVICES A. Group mounted circuit breakers through 1200A 1. Circuit breaker(s) shall be group mounted plug-on with mechanical restraint on a common pan or rail assembly. 2. The interior shall have three flat bus bars stacked and aligned vertically with glass reinforced polyester insulators laminated between phases. The molded polyester insulators shall support and provide phase isolation to the entire length of bus. 3. Circuit breaker(s) equipped with line terminal jaws shall not require additional external mounting hardware. Circuit breaker(s) shall be held in mounted position by a selfcontained bracket secured to the mounting pan by fasteners. Circuit breaker(s) of different frame sizes shall be capable of being mounted across from each other. 4. Line-side circuit breaker connections are to be jaw type. 5. All unused spaces provided, unless otherwise specified, shall be fully equipped for future devices, including all appropriate connectors and mounting hardware. 6. Thermal magnetic molded case circuit breakers through 2500A. a. Molded case circuit breakers shall have integral thermal and instantaneous magnetic trip in each pole. 1) Circuit protective devices shall be molded case circuit breaker(s). B. Individually Mounted circuit breakers greater than 1200A 1. Electronic trip molded/insulated case full function 100% rated circuit breaker(s) through 2000A. 2015 MAHLUM PERMIT SET Issue Date: 11 SEPTEMBER 2015 PAGE 3 OF 5

2.5 2.6 2.7 a. All electronic circuit breakers shall have the following time/current response adjustments: Long Time Pickup, Long Time Delay, Short Time Pickup, Short Time Delay, Ground Fault Pickup Ground Fault Delay and Instantaneous settings. Each adjustment shall have discrete settings (fully adjustable) and shall be independent of all other adjustments. b. Circuit breaker trip system shall be a microprocessor-based true rms sensing designed with sensing accuracy through the thirteenth (13th) harmonic. Sensor ampere ratings shall be as indicated on the associated schedule. c. Local visual trip indication for overload, short circuit and ground fault trip occurrences. d. Long Time Pickup indication to signal when loading approaches or exceeds the adjustable ampere rating of the circuit breaker shall be provided. e. Communications capabilities for remote monitoring of circuit breaker trip system, to include phase and ground fault currents, pre-trip alarm indication, switch settings, and trip history information shall be provided. f. Circuit breaker shall be provided with Zone selective Interlocking (ZSI) communications capabilities on the short-time and ground fault functions compatible with all other electronic trip circuit breakers and external ground fault sensing systems as noted on schedules. g. 1000 amps and over shall have GFI protection METERING (CUSTOMER) A. Manufacturers: 1. Square D 2. Power Logic B. The switchboard shall be metered using: 1. Square D Type PM 850 with digital readout a. Digital Power Meter with 0.25% accuracy with the following features: b. A, V, kw, kvar, kva, PF, F, kwh, kvarh, kvah, KYZ, RS-485 communications C. Provide modbus output and pulse initiator for connection to the DDC system METERING TRANSFORMERS A. Manufacturer: Shall be Square D Company or equal B. Current Transformers: ANSI C57.13; 5 ampere secondary. C. Voltage Transformers: ANSI C57.13; 120 V single secondary, (Not required for type PM meters). SURGE PROTECTOR: PROVIDE 30AMP 3POLE CIRCUIT BREAKER CONNECTED TO INNOVATIVE TECHNOLOGY #PTX-160 SURGE PROTECTOR OR TPS ST SERIES. MAXIMUM LEAD LENGTH IS 12 INCHES. PART 3 EXECUTION 3.1 3.2 INSPECTION A. Examine area to receive switchboard to provide adequate clearance for switchboard installation. B. Check that concrete pads are level and free of irregularities. C. Start work only after unsatisfactory conditions are corrected. INSTALLATION A. Install switchboard in accordance with manufacturer's written guidelines, the NEC, and local codes. 2015 MAHLUM PERMIT SET Issue Date: 11 SEPTEMBER 2015 PAGE 4 OF 5

3.3 3.4 3.5 3.6 FIELD QUALITY CONTROL A. Inspect completed installation for physical damage, proper alignment, anchorage, and grounding. B. Measure, using a Megger, the insulation resistance of each bus section phase-to-phase and phase-to-ground for one minute each, at minimum test voltage of 1000 VDC; minimum acceptable value for insulation resistance is 1 megohms. NOTE: Refer to manufacturer's literature for specific testing procedures. C. Check tightness of accessible bolted bus joints using calibrated torque wrench per manufacturer's recommended torque values. D. Physically test key interlock systems to check for proper functionality. E. Test ground fault systems by operating push-to-test button. HOUSEKEEPING PAD A. Provide minimum 3-inch housekeeping pad under all switchboards. Extend 3-inches beyond footprint. ADJUSTING A. Adjust all operating mechanisms for free mechanical movement per manufacturers specifications. B. Tighten bolted bus connections in accordance with manufacturer's instructions. C. Adjust circuit breaker trip and time delay settings to values as instructed by the Architect/Engineer. CLEANING A. Touch up scratched or marred surfaces to match original finish. END OF SECTION 2015 MAHLUM PERMIT SET Issue Date: 11 SEPTEMBER 2015 PAGE 5 OF 5