Switchboard assembly and installation guide

Similar documents
P System Cubicles. Certified for more safety

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Securing your electrical installations Prisma,

IEC & 2 standard. The reference for safe and reliable LV switchboards

Installation. Smart-UPS VT MGE Galaxy Maintenance Bypass Panel kva 400 V

FAQs-Main switchboard design criteria

know-how Giant in distributing electricity for industry Prisma GK

Unified requirements for systems with voltages above 1 kv up to 15 kv

IEC >>> IEC GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

The Intelligent AX1 Switchgear for Medium Voltage

Functional system Prisma P

Comparative study for cables and busbars

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

R.C.C.B. s two-pole LEXIC

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Explosion proof enclosures

The power distribution board that sets new standards

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

Industrial Process Plants. Residential & Commercial Buildings. Roads & Tunnels. Airports & Seaports

Distribution Boards & Consumer Units

SURGE PROTECTIVE DEVICES

IEC specifications for LV assembly switchboards

Linkeo 19" freestanding cabinets

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

Low Voltage Products. Switches Automatic Transfer Switches

NEW RANGE OF CABINETS DRIVIATM. Innovation at your service. THE GLOBAL SPECIALIST in electrical and digital building infrastructures

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

GE Power Controls. MiniFORM Switchboards

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

39HQ Airovision Air Handling Units

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

KAM A Lighting Busbar System KAP A Plug-in Busbar Distribution System

SIVACON The Versatile Low-Voltage Switchboard

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV

The complete guide to Low Voltage switchgear

SECTION DRY-TYPE TRANSFORMERS

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Low Voltage Switchboards The Best Technical Solution for Your Ship

LIEBERT VNSA Installation Sheet

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation

Installation. Smart-UPS VT and MGE Galaxy Maintenance Bypass Panel with Power Distribution (wall-mount) kva 208 V

SAFETY ALERT SWITCHBOARD INTERNAL SEGREGATION AND IP RATING. May 2014 BACKGROUND

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

MCR1900 Media Converter 19-Slot Chassis

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

Installation Manual. BYD Wall-mounted AC Charging Box

Lightning Arresters P KVA P KVA. Description & Installation

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

Terminal Boxes Series 8146

Sample - No Commercial Use

4 Technical Application Papers

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Guide to enclosures for potentially explosive atmospheres

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Current distribution Comb busbars for Declic and SFT residential devices

Operating instructions

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

EC DECLARATION OF CONFORMITY FOR MACHINES

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

Co-location Interconnect Power Panel (CIPP) Installation Guide

Mounting Instructions for SP4 Power Modules

Switchboard system. NorLine 800

08. SEK IDC CONNECTORS

AC-DC Converter Application Guidelines

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

Givare NC-SRS 280 och 880

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Washer, Electrical Equipment Bond. WEEB Patent Pending INSTALLATION INSTRUCTIONS. For Kinetic Solar K-Rack only

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

The easy way to build switchgear and controlgear assemblies in compliance with the regulations

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

EMC Engineering Guidelines For Automation Systems PS 4 PS /97 AWB GB

CAS 36 Ring Main Unit

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c Erlangen Germany.

Expanding a 40-Type Cabinet

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

SELECTION, APPLICATION AND MAINTENANCE

Installation, operation and maintenance manual TX 35A

Safe and secure distribution of medium voltage with AX1

Packaged Terminal Air Conditioner Wall Sleeve Installation

TriLine ASSEMBLY System PowerModules

Technical Application Papers No.11 Guidelines to the construction of a low-voltage assembly complying with the Standards IEC Part 1 and Part 2

Transcription:

Switchboard assembly and installation guide

Preface Dear Customers, Here is the new edition of the Switchboard Assembly and Installation Guide, designed to help you build type-tested switchboards in compliance with standard IEC 60439-1. By following the instructions presented, you will achieve the level of quality necessary for electrical switchboards, in compliance with standard IEC 60439-1. It provides for Prisma Plus information to complement that already found in the catalogues and technical manuals. This version has been updated to take into account the most recent editions of standards and the latest technology applicable to switchboard manufacturing. In this way, you can be sure to provide end-users with switchboards satisfying industrial standards and presenting the level of quality they expect. This guide draws on experience acquired by and its customers, both switchboard builders and end-users, over many years. It is intended for use by switchboard builders in the factory and on site and also by design engineers. The information is presented in a logical order, from switchboard assembly in the factory through to transport.

Contents 1 Delivery and Storage 3 pages Assembling the enclosures 2 b Mechanical assembly b Electrical continuity b Degrees of protection: IP, IK Main busbars 3 b Designing the busbars b Protective conductor b Partitioning b Installation of current transformers Installing the devices 4 b Device layout b Mounting the devices b Safety Power connections 5 b Connecting the power devices b Connecting to the main busbar b Preparing the bars b Assembling the bars b Connecting with flexible bars b Connecting with cables b Distribution blocks Auxiliary and low power circuits 6 b Wiring running b General remarks b Communication circuits Labelling and marking 7 b Switchboard and device marking b Conductor marking Final factory inspection 8 b Facilities b Tests b Check list b marking b Final inspection record report Packing 9 b Switchboard preparation b Packing definition b Dispatch file Handling and transport 10 b Handling b Transport 6 7 9 12 17 19 24 28 34 36 38 41 43 45 49 54 58 60 64 66 70 72 76 77 80 81 83 86 87 88 90 93 11 Standards and technical documentation 95 Index 97 1 Assembly and installation guide

2 Assembly and installation guide

Delivery and Storage 1 3 Assembly and installation guide

Delivery and Storage Delivery and storage of components Delivery of components Check the number of packages received against the delivery slip. Check that the packing has not been damaged in a way which may have harmed the equipment inside. If necessary, the receiver should make a damage claim to the transporter. Should material damage be detected on any of the products, it must be witnessed by a representative of the transport firm. Most packages use plastic film allowing visual inspection of the equipment and the assembly manual. The Prisma Plus kit system offers additional storage space. Storage and preparation prior to assembly The components must be stored on indoor, ventilated and dust-free premises. They should, in so far as possible, be left in their packing until final installation as this will protect them against risks commonly encountered in the factory or on site (spraying, impacts, etc.). If they do need to be unpacked, the protective cover should be replaced until the switchboard is finally installed. For optimised organisation of the factory, 3 separate areas are identified: b 1 storage area b 1 working area: v with dedicated receptacles for recovery of metal, plastic, cardboard waste, etc... v with working tables. b 1 test area. Storage temperature: -25 C to +70 C Relative humidity: 95 % at 55 C Do not unpack all the packages. Follow the assembly order recommended in the assembly guide or manuals. Provide a table with non-aggressive panels for paintwork (plastic coating, mat), 90 cm high, for assembly of wall-mount and floor-standing enclosures. The packaging can be made up of different materials, provided that these materials are easy to separate (plastic film, cardboard) to allow recycling. The packaging can be re-used in some cases (e.g. floor-standing enclosures) for transport following on-site assembly. 4 Assembly and installation guide

Assembling the enclosures 2 5 Assembly and installation guide

Assembling the enclosures Mechanical assembly General Whether supplied as a kit or in one piece, the structure of an electrical switchboard must be sufficiently rigid to withstand forces generated by: b the weight of the devices b the electro-mechanical forces due to a short-circuit b transport. Delivering enclosures in kit form simplifies, among other things, storage and transport. Assembly is quick and reliable and can be carried out in the factory or on site. Assembling the structure If the enclosure has been delivered in kit form, the structure must be assembled on a flat, clean surface or floor. Use the mounting hardware provided with the enclosure, following the assembly sequence and applying the tightening torques specified in the product technical manual. Installation of a pair of rafters under each framework or on framework + plinth ensures, among other things: b secure packing b better vertical stability during mounting and cabling b easy handling with a pallet truck b prevention of damage to the protective paintwork. The wall-mount and floor-standing enclosures are designed to be mounted and cabled horizontally on a work table to enhance cabling ergonomics. The cubicle cross-members are drilled to secure the rafters under the framework. As an option a stabiliser can be supplied. Vacuum enclosure standard: EN 50-298 The class 8-8 nuts and bolts supplied with the various components ensure tight and durable mechanical connections. The appropriate tightening torques for the various nut and bolt diameters were determined by testing, with an accuracy of ± 10 %. nut and bolt diameter M5 7 M6 13 M8 28 tightening torque (in N.m) The table above is provided by way of an example for nuts and bolts of the class 8-8 type with contact washer. Other assembly types are possible: b tapped burst holes 5 (8 N.m) b self-tapping screws 5 (4.4 N.m) b bell-shaped joining 6 (13 N.m). 6 Assembly and installation guide

Assembling the enclosures Electrical continuity General The exposed conductive parts on a switchboard must be electrically connected to one another and to the main protective conductor. The electrical connection is achieved by screws and bolts or by assembly design. For this purpose: b use only the components, screws, bolts and accessories delivered b comply with the assembly instructions given in the manuals b tighten to the required torque. 2 Solutions are tested and require no additional earthing braids. Electrical continuity for fixed parts Paint reduces the electrical continuity of the assembled parts. Special devices must therefore be used: screws with built-in serrated lock washer with external teeth, serrated lock washers with external teeth or earthing wires. To ensure electrical continuity, the mechanical assemblies (front plates, mounting plates, etc.) are made using devices that cut through the paint up to the metal b clips b 1/4 turn screws b self-tapping screws b screws with built-in serrated lock washer with external teeth. tooth tooth 1/4 turn screw 1/4 tooth Screws + washers with teeth 7 Assembly and installation guide

Assembling the enclosures Electrical continuity Electrical continuity for moving parts Standards: IEC 60364 IEC 60439 A protective conductor (e.g. earthing wire) must be fitted to all metal moving parts (door, panels, hinged front plates) to which electrical components, other than class 2 components, are secured. Standard IEC 60364-5-54 defines the minimum cross-sectional area of the connection as a function of the live conductors of the installed electrical equipment. By design the Prisma Plus system ensures electrical continuity of moving parts by means of hinges. An earthing wire is supplied as standard for doors accommodating HSI (Human Switchboard Interface) electrical components. An earthing wire is supplied optionally for doormounted electrical components and for insertion of communication and low power circuit cables: analog, digital and telecom cables. claw Connections between earthing wire and painted sheetmetal: Electrical continuity is ensured using special washers with teeth which cut through the paint to reach the metal. Assemblies use nuts and bolts in conjunction with contact washers with teeth, on the painted sheetmetal, and nuts and contact washers on the earthing wire lug. Connections between earthing wires and welded studs: The stud is not painted and can consequently be used to provide electrical continuity. The connection is implemented using a nut with a contact washer on either side. For the weatherproof wall-mount or floorstanding enclosure offer, the connection is implemented on a self-cleaning stud by a fan type lockwasher and a nut + washer with teeth. 8 Assembly and installation guide

Assembling the enclosures Degrees of protection: IP, IK Degree of protection Standard IEC 60439-1 distinguishes between assemblies intended for indoor or outdoor installation. These enclosures are designed for indoor use, corresponding to the majority of installation requirements. 2 The degree of protection is subject to agreement between the manufacturer and the user for all the enclosure surfaces. IEC 60439 The floor and the walls cannot act as an enclosure component for compliance with the IP. IEC 60529 IEC 60439 EN 50-102 Degree of protection IP: The appropriate degree of protection is allocated after a series of standard tests. Standard IEC 60529 defines an IP code (degree of protection) which characterises the ability of an enclosure to withstand the following external factors: penetrating solid objects (1st figure) and liquids (2nd figure), protection of persons. According to standard IEC 60439-1, no IP code can be given unless type tests are carried out or tested prefabricated enclosures used. Degree of protection IK: A code, IK (EN 50-102), characterises the withstand of the enclosures to external mechanical impacts (shocks). The enclosures are subjected to type tests corresponding to their IP level. For Prisma Plus, the minimum degree of protection is IP30: b IP31: with canopy or tightness kit for wall mounted and floor standing enclosures and cubicles b IP43: with canopy and door and tightness kit for wall mounted and floor standing enclosures b IP55: for the "weatherproof" cubicle and wall-mount enclosure offer. For Prisma Plus, the minimum IK degree of protection is: b IK07 without door b IK08 with door b IK10 for the IP55 offer. The cable gland guarantees the same degree of protection as the enclosure on which it is mounted. Gland plate on cubicle Gland plate on floor-standing enclosure 9 Assembly and installation guide

Assembling the enclosures Degrees of protection: IP, IK Protection of persons The degree of protection of an electrical switchboard accessible to unqualified persons must always be equal to at least P2X. For Prisma Plus, the minimum degree of protection is IP30. The device control toggles can be operated without any danger. The front plates only allow access to equipment controls and not to their adjustment devices. GK IP55 wall-mount enclosure IP30 cubicle 10 Assembly and installation guide

Main busbars 3 11 Assembly and installation guide

Main busbars Designing the busbars Principle IEC 60439 The type and cross-section of the busbars should be sufficient to carry the required current for a given temperature rise, thus ensuring that the electrical switchboard functions correctly. The design tables for Prisma Plus busbars were established using calculations checked by type tests, in compliance with standard IEC 60439-1. Type of materials Aluminium: Choose a quality of aluminium which is easy to use and which provides excellent conductivity and a surface coating guaranteeing electrical contact and good resistance to corrosion. Copper: Choose a quality of copper which is easy to use and which provides excellent conductivity and good resistance to corrosion. The Linergy busbars have undergone surface treatment (anodisation) and the contact surface has been prepared. The copper busbars are of the type Cu ETP (H12) conform to standards and are qualified. Merlin Gerin 5 or 10 Busbar number and crosssection IEC 60439 Follow the manufacturer s recommendations when determining the number and crosssection of the bars for each phase. The acceptable cross-sections and currents of the busbars are given in the assembly manuals and the catalogue. Calculations allow for: b the continuous current to be carried by the switchboard b the short-circuit current b the ambient temperature (35 C as per IEC 60439-1) b the degree of protection provided by the enclosure. Busbar position Edgewise bars: Preference should be given to this arrangement encouraging heat loss. In most of our busbar installation solutions, busbars are arranged edgewise. This bar position is frequently used as it encourages cooling by convection. 12 Assembly and installation guide

Main busbars Bar position (continued) Flat bars: For flat bars, use the calculation aids defined for edgewise bars and apply a derating coefficient. When using flat bars (transfers of an incoming device on busbar), a 0.8 derating coefficient is recommended. For example: Two 80 x 5 bars, operating in a comparable environment and with the same ambient temperature, carry: b 1600 A if the bars are edgewise b 1280 A (1600 x 0.8) if the bars are flat. 3 Clearance Clearance is the shortest distance in the air between: b two live conductors b a live conductor and an exposed conductive part. xx mm Standard, tested components can be used to produce electrical switchboards with a rated insulation voltage (Ui) and a rated impulse withstand voltage (Uimp) appropriate for the devices connected to them: b distribution busbar (Multi 9) v Ui = 500 V v Uimp = 6 kv b distribution busbar (Compact): v Ui = 750 V v Uimp = 8 kv b main busbar: v Ui = 1000 V v Uimp = 12 kv. IEC 60439 Standard IEC 60439-1 specifies a rated impulse withstand voltage according to: b the rated insulation voltage b the location of the switchboard. The same standards indicate the minimum clearances required to withstand, in all cases, impulse voltages for altitudes ranging from 0 to 2000 m. 75 mm The minimum clearance to be complied with is 14 mm (Ui = 1000 V) between live parts. In Prisma Plus, the clearance between phases is 75 mm and the busbars are installed on insulating supports. Standard IEC 60439-1 8.2.5 stipulates the presence of a 14 mm clearance between a bare live part and the enclosure components, allowing for possible deformation of parts of the enclosure. Tests were carried out as per the degree of protection against impacts IK of the Prisma Plus enclosures; they made it possible to ensure that clearance was maintained. 13 Assembly and installation guide

Main busbars Designing the busbars Creepage distance Creepage distance is the shortest distance along the surface of an insulator between: b 2 live conductors b 1 live conductor and an exposed conductive part. As the comparative tracking index (CTI) for the supports is 175 V, standard IEC 60439-1 specifies a minimum creepage distance of 16 mm for an operating voltage of up to 1000 V. IEC 60439 Standard IEC 60439-1 specifies a value in mm for creepage distance. It depends on: b the rated insulation voltage of the switchboard b the type of insulating support (group of materials) b the degree of pollution in the surroundings. 16 mm Arrangement of the bars If the installation requires several bars per phase, leave sufficient space between them to ensure normal ventilation of the busbar. The same support ensures that a 5 mm or 10 mm gap is left between the busbars according to bar thickness. 10 mm Leave at least the equivalent of a single bar thickness between two live conductors of the same phase. 180 180 5 mm 14 Assembly and installation guide

Main busbars Securing the bars The number of supports and the distance between their centres depend on the following forces: b electrical (prospective short-circuit current) b mechanical (bar weight and position). Each configuration has been determined according to the electro-dynamic forces produced in the event of a short-circuit and has been validated by tests carried out in compliance with standard IEC 60439-1. 50 mm 3 IEC 60439-1 The distance between the centre of the last support and the end of the bar must be 50 mm maximum. The supports (or part of them) must be made of a non-magnetic material to avoid any temperature rise due to loop effects around conductors. The busbar supports do not use metal countersupports. The counter-supports of the bottom Linergy busbars are made of metal, but the fixing screws are made of non-magnetic material. The supports of side Linergy busbars are made of completely insulated material. 15 Assembly and installation guide

Main busbars Designing the busbars Busbar arrangement in the enclosure The connections must be accessible from the front when the switchboard is mounted against a wall. The Linergy channelled busbar is installed sideways in the bar zone, to the left or right of the switchgear zone. Their staggered arrangement, due to their suppports, means that all the connection points are accessible from the front of the switchboard. N Staggered busbars. The Linergy busbar offers a number of advantages over flat busbars: b enhanced emissivity increasing heat radiation and reducing busbar temperature rise b better moment of inertia, thus reducing the number of supports b substantial weight savings. Support for channelled Linergy busbars. 16 Assembly and installation guide

Main busbars Protective conductor Protective conductor PE It should be sufficiently sized and properly secured to the switchboard to withstand the thermal and electrodynamic forces produced by the fault current. Standard IEC 60439-1 defines a method for calculating the crosssection of the protective conductor: S PE = I 2 t k b S PE : cross-section of PE in mm 2 b I 2 : value of the phase-to-earth fault current = 60 % of the phase-to-phase fault curent (standard IEC 60439-1 8.2.4.2) b t: duration of the fault current in seconds b k: a factor depending on the conductor material. k = 143 for a PVC-insulated copper conductor. It should be earthed to the switchboard earthing terminal. It must be easily accessible: b to permit factory and on-site connections b to check tightening. The PE protective conductor is normally installed in the cable compartment. It can be produced using: b a Linergy busbar b a vertical flat bar b a horizontal flat bar, secured to the top or bottom of the switchboard (opposite the main busbar). Choix du PE : Icw Linergy busbar cross- (ka rms/1s) busbar (A) section (mm) y 40 630 25 x 5 > 40 800 50 x 5 Icw = permissible short-time rated curent PE by Linergy busbar 3 IEC 60439 NB: Each protective conductor terminal can only accommodate a single cable. PE by flat bar Equipotential bonding Accessible conductive parts of a device must be connected to the assembly protective circuit (for protective bonding) either by its own fastening means or by a conductor with a cross-section chosen from the table below: minimum cross- section of a copper bonding conductor (mm 2 ) S rated operational current (Ie) Ie y 20 20 < Ie y 25 2.5 25 < Ie y 32 4 32 < Ie y 63 6 Ie > 63 10 S = cross-section of the phase conductor In Prisma Plus, equipotential bonding of device exposed conductive parts is achieved by their means of fastening to their supports. Moreover, the supports (mounting plates, vertical and horizontal, frameworks) are bonded equipotentially by their assembly devices. G F E D C B A Example: Unpainted Masterpact mounting plate. 17 Assembly and installation guide

Main busbars Protective conductor PEN conductor Cross-section: The cross-section of a PEN conductor is determined in the same way as for a neutral conductor, in other words: b for single-phase or three-phase circuits with a copper cross-section of y 16 mm 2 it must be equal to the phase conductor cross-section b for three-phase circuits with a copper cross-section > 16 mm 2 it may be: v equal to the phase conductor cross-section, v or less on condition that: - the current likely to flow through the neutral under normal operating conditions is lower than the permissible current in the conductor, - the power of the single-phase loads does not exceed 10% of total power. Installation: It must be readily accessible to: b allow factory and on-site connections b check tightening. The PEN conductor can take the place of the neutral. It must be connected to the protective conductor by a removable joint (using a special tool) to allow insulation measurements to be taken. It is normally installed in the cable compartment and produced using a Linergy busbar. Implementing a PEN conductor in LV switchboards IEC 60439 According to standard IEC 60439-1 and French decree dated 14 November 1988, the rules for implementing a PEN conductor are as follows: b at the entry to the assembly, the PEN connection point must be near that of the phases b within the assembly, the PEN conductor need not be insulated from exposed conductive parts (except on premises where there is a fire or explosion hazard) b the cross-section of the PEN conductor must be at least equal to that of the neutral b a constant cross-section must be used on the main busbars b the transition from a TN-C to a TN-S earthing system must be made at a single point in the switchboard, via a marked neutral disconnection bar, accessible and removable to facilitate fault loop impedance measurements b from the point of transition to a TN- S system, it is prohibited to recreate a TN-C system. The PE and neutral conductors must satisfy their specific requirements. 18 Assembly and installation guide

Main busbars Partitioning Internal separation by barriers or partitions IEC 60439 The separations within an assembly are defined in section 7.7 of standard IEC 60439-1. They are subject to agreement between the manufacturer and the end-user. Four typical levels (forms) of internal separation are defined for protection against direct contact. The minimum separation IP is IP2X. Prisma Plus handles the functional unit from the busbar to the external cable connection terminals. In most installations, Prisma Plus enclosures require no specific partitioning to guarantee protection of persons and the installation. However, Prisma Plus offers a variety of partitioning types to create separations within electrical switchboards (forms 2, 3 and 4) and facilitate and guarantee the safety of people authorised to perform operation and maintenance. Protection is provided by: b the presence of front plates that can only be opened by a special tool b key-locking of doors accessing live parts b covering of the upstream connection of the incoming unit. For protection of persons, recommends, in addition to the standard s recommendations, systematic installation of the following: b a form 2 barrier on the top or bottom horizontal busbar partitioning of the upstream connection of the incoming unit, so that operator safety is guaranteed at all points of the switchboard when the incoming unit is in the open position b prefabricated connections with built-in plastic insulating cover or installation of upstream and downstream terminal shields on all devices. 3 Form 1: No separation inside the enclosure. B C D A E F A Incoming unit B Main busbars C Distribution busbars D Outgoing unit E Terminals for external conductors F Enclosures (at least IP2X). 19 Assembly and installation guide

Main busbars Partitioning Internal separation by barriers or partitions (continued) Form 2a: The functional units are separated from the busbars, but not from the terminals. G G G Partitioning at least IP2X. Form 2b: The functional units and the terminals are separated from the busbars. The terminals are not separated from one another. Prisma Plus proposes form 2b cubicles offering enhanced safety. This takes the form of physical separation betwen the horizontal and vertical busbars and the functional units, as per standard 60439-1. IEC 60439 Form 2b barrier in cubicle Prisma Plus proposes metal barriers for wallmount and floor-standing enclosures in order to: b separate the functional units from one another b separate the devices from a busbar or a distribution block in a duct. Form 2b horizontal barrier in a floor-standing enclosure. 20 Assembly and installation guide

Main busbars Internal separation by barriers or partitions (continued) 3 Form 2b vertical barrier in a floor-standing enclosure. Form 3a: The functional units are separated from one another and from the busbars, but not from the terminals. 21 Assembly and installation guide

Main busbars Internal separation by barriers or partitions (continued) Partitioning Form 3b: The functional units are separated from one another and from the busbars. The terminals are separated from the busbars but not from one another. 22 Prisma Plus proposes form 3b cubicles, produced by separating from one another the functional units in a form 2 switchboard. The devices must be equipped with terminal shields downstream. Furthermore, the connection transfer assemblies create a separation between the connection terminals and the functional unit. Assembly and installation guide

Main busbars Internal separation by barriers or partitions (continued) Form 4a: The functional units are separated from one another and from the busbars. The terminals, which form an integral part of the functional units, are separated from one another. Form 4b: The functional units are separated from one another and from the busbars. The terminals are separated from one another and from the functional units. 23 3 The left cubicle represents form 4a. The right cubicle represents form 4b. Assembly and installation guide