GROUND MEASURING TECHNIQUES: ELECTRODE RESISTANCE TO REMOTE EARTH & SOIL RESISTIVITY

Similar documents
SOIL RESISTIVITY MEASUREMENTS

Earth Ground Resistance

Understanding Soil Resistivity Testing

Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria

12 Appendix 12 Earth Electrodes And Earth Electrode

A practical guide to earth resistance testing

Multi-Function Ground

Designing For A Low Resistance Earth Interface (Grounding) Roy B. Carpenter, Jr. Joseph A. Lanzoni

GroundRod AC Substation Earthing Tutorial

Coupling Effect in Substation Ground Measurements

UNDERSTANDING GROUND RESISTANCE TESTING. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-on Measurements E I

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

Grounding & Bonding Why it is done And How to Install Properly

Earthing Techniques 1. SOIL RESISTIVITY TESTING THEORY OF SOIL RESISTIVITY INTERPRETATION AND MODELLING OF RESULT...

How Much Voltage Drop Is Acceptable?

EARTHING SYSTEM CALCULATION

Operating Instructions

GROUNDING AND BONDING ELECTRICAL SYSTEMS

Substation Grounding Study Specification

STREETLIGHT SYSTEM GROUNDING AND BONDING

Module 1 : Site Exploration and Geotechnical Investigation. Lecture 5 : Geophysical Exploration [ Section 5.1 : Methods of Geophysical Exploration ]

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

Chapter 9. Bonding and Grounding

V=5 L 3 GROUNDING ELECTRODES EXPLAINED

Hyperlinks are Inactive

Electrical Grounding. Appendix C

DET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers

The Basics of Loop Vehicle Detection

Physics 41, Winter 1998 Lab 1 - The Current Balance. Theory

Determination of Thermal Conductivity of Coarse and Fine Sand Soils

FORCE ON A CURRENT IN A MAGNETIC FIELD

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

TABLE OF CONTENT

Strength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines

Specifications for Lightning Protection. ASAE Engineering Practice

Fault location on power cables. Fault location on power cables

BASIC NEC CODE RULES AND DESIGN PRACTICE

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

Operating Instructions

DET3 and 4 Contractor Series Earth/Ground Resistance Testers

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Lightning Protection Introduction

ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES

DET3 Contractor Series

Model RI ICE Pack Impressed Current Electronic Package the remedy for Mag headaches Typical Applications:

Cable Installation Notes

Combined Close Interval Potential Surveys and Direct Current Voltage Surveys for Increased Pipeline Integrity

Lab E1: Introduction to Circuits

Modeling of Transmission Lines

I = V/r P = VI. I = P/V = 100 W / 6 V = amps. What would happen if you use a 12-volt battery and a 12-volt light bulb to get 100 watts of power?

FIREFIGHTER SAFETY. Stay safe during substation fires

Heat Transfer. Energy from the Sun. Introduction

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

Voltage Drop (Single-Phase)

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

CONSTANT HEAD AND FALLING HEAD PERMEABILITY TEST

Earth electrode. and. earth loop impedance testing. Theory and applications

Electrical Fundamentals Module 3: Parallel Circuits

NEGRP TEST SUMMARY. Joseph A. Lanzoni, November 2005

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

[4] SA1.2 The student demonstrates an understanding of the processes of science by observing,

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

WEATHERING, EROSION, AND DEPOSITION PRACTICE TEST. Which graph best shows the relative stream velocities across the stream from A to B?

Measuring Soil Moisture for Irrigation Water Management

The electrical field produces a force that acts

New Residential Service Requiring Construction

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

Beware of Simplistic Voltage Drop Calculations. By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION

rpsa FIRE PROTECTION ENGINEERS

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

Principles of Rice Drying How does rice dry?

DC MOTOR ANALYSIS & TROUBLESHOOTING

Douglas J. Reinemann, Ph.D. University of Wisconsin-Madison, Department of Agricultural Engineering Madison, Wisconsin. and

(1) Discuss the determination of the need for public visitation. Visitor center density within 100 miles.

Experiment NO.3 Series and parallel connection

Voltage Loss Formula s

Earthing Guidance Notes

Electricity. Confirming Coulomb s law. LD Physics Leaflets P Wie. Electrostatics Coulomb s law

Digital Ground Resistance Tester. Models 4620 & Digital Ground Resistance Tester

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.

A Method to Detect and Locate Roof Leaks Using Conductive Tapes

How To Keep An Eye On Electric Safety

Video Camera Installation Guide

CHAPTER 2 HYDRAULICS OF SEWERS

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

Introduction to Data Centre Design

Introduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory

Installation Instructions Hustler 6-BTV Trap Vertical

Elementary circuits. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Wire types and sizes

User Guide. 4 wire Earth Resistance Tester Model GRT300

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

Section B: Electricity

PRODUCT / APPLICATION INFORMATION

LAB 24 Transpiration

Transcription:

GROUND MEASURING TECHNIQUES: ELECTRODE RESISTANCE TO REMOTE EARTH & SOIL RESISTIVITY Elvis R. Sverko ERICO, Inc. Facility Electrical Protection, U.S.A. Revision Date: February 11, 1999 Abstract: This paper presents different concepts and procedures for ground measuring techniques. A few of the techniques that are discussed are the measuring of resistance to remote earth for a single earth electrode or for an entire earth electrode system, and also the resistivity of the local soil using an earth system tester. 1. Introduction A good grounding system (also known as an earth electrode system) is important for the protection of an overall system facility. There are many factors that determine how well a grounding system performs. Two major parameters are its resistance to remote earth and the resistivity of the local soil. Each of these values can be measured to help determine and design the best solution for the grounding system. The resistance to remote earth of the grounding system needs to be at a minimum in order to sustain its effectiveness. A few of the components that make up this resistance are the physical properties of the material used to make the electrode and conductor, all connections made, contact resistance between the electrode and the soil, and the soil resistivity. A complete grounding system might include only one earth electrode, an entire group of electrodes with a grounding grid, or anything in between and beyond. The earth electrodes from any of these types of systems can have their resistance to remote earth determined. 2. Theory vs. Practice Theoretically, the resistance to remote earth of an earth electrode can be calculated. This calculation is based on the general resistance formula: where: R = (ρ x L) / A R = resistance to remote earth (Ω) ρ = soil resistivity (Ω-cm) L = length of conducting path (cm) A = cross-ectional area of path (cm) This general formula is a simplified version of some complex formulas (derived by Professor H. B. Dwight of Massachusetts Institute of Technology) used to calculate the resistance to remote earth for a grounding system. The assumption in the general formula is that the resistivity of the soil is constant throughout the considered area, or averaged for the local soil. In the practical (real) world, soil resistivity is not constant, properties of electrodes and their connections vary (except with CADWELD TM ), and complex equations just don t cut it. Therefore, an actual measuring technique is necessary. This technique is done with an earth resistance tester, often called a megger. One example of the earth tester is the ERICO EST301Universal Earth System Tester, seen in figure 1, (please refer to the ERICO EST301 Operating Instructions manual for detailed instructions on its use.) This type of instrument can be used at various stages in the life of a grounding system, once during installation to see if it meets all specifications, and anytime thereafter to observe any possible changes. Figure 1: ERICO EST301 Universal Earth System Tester 3. Earth Electrode Measurement (Single Electrode) There exists different measuring techniques for resistance to remote earth of a grounding system. One such technique is the 3-pole earth electrode measurement for a single electrode. This technique uses the electrode under test (EUT), a reference probe, and an auxiliary probe, set in a straight line. Figure 2 shows the single electrode measuring method, and figure 3 shows the single electrode measuring setup for the ERICO EST301 earth tester.

4. Earth Electrode Measurement (Multiple Probe System) Figure 2: Single Electrode Measuring Method A second earthing resistance measuring technique is the process of measuring the resistance to remote earth of a single earth electrode in a multiple electrode grounding system. This technique is used when the earth electrode cannot be disconnected from the rest of the grounding system such as a communication tower installation. When the earth electrode can be disconnected, the previous 3-pole single electrode technique may be used. Caution should always be taken when disconnecting any earth electrode. The same principles apply to this technique as they did for the single probe technique, the only difference is that for the multiple electrode grounding system, the current is measured with a current transformer around the EUT, (see figures 5 and 6.) After the proper voltage and current values are measured, a simple Ohm s Law equation determines the electrode s resistance to remote earth. Figure 3: Single Electrode Measurement Setup After applying a voltage at the designated location in the circuit, the current between the EUT and auxiliary probe is measured, and the voltage between the EUT and the reference probe is measured. Using Ohm s Law, the resistance can now be calculated. This routine is completed by the earth tester. It has been determined that the distance D be approximately 100 feet, and the distance between the EUT and reference probe be 0.62 times the value of D. These values have been tested using the fall of potential method to give optimal results (see figure 4.) But due to the large amounts of uncertainty in all properties of probes and soil, the value of D should be varied for each individual test until reasonably consistent values appear; however, it is recommended that the value of D stay greater than 80 feet. It is also necessary to take a second set of readings at 90 o to the original in case of interference from overhead power lines or any underground electrical equipment or metal objects. Figure 5: Multiple Electrode Measuring Method 60 Fall of Potential Figure 6: Multiple Electrode Measurement Setup Resistance (Ohms) 50 40 30 20 10 0 0 20 40 60 80 100 Distance between earth electrode and ref. probe (ft.) Figure 4: Fall of Potential Once the resistance to remote earth for each electrode in the entire grounding system is determined, one can calculate the resistance to remote earth for the entire grounding system in one of two ways. The first approach is in understanding that the electrodes are in parallel with each other (through the grounding grid and ground itself.) Because they are in parallel, the rule for parallel resistances can be used.

where R s = 1 / [ (1/R 1 ) + (1/R 2 ) + (1/R 3 ) + (1/R n ) ] R s = resistance to remote earth for entire grounding system (Ω) R 1,2,3 n = resistance to remote earth for each individual electrode (Ω) However, this rule is not completely accurate in this application because of the extra resistance to remote earth through the grounding grid. The second approach used to calculate the resistance to remote earth for the entire grounding system assumes that the resistances to remote earth for each electrode are equal. Then, for the entire grounding system, the resistance to remote earth is 40% lower for a system with only two electrodes, 60% lower for a system with three electrodes, and 66% lower for a system with four electrodes (compared to the resistance to remote earth for one of the equal electrodes.) These values are slightly larger than the values given by the parallel resistance rule. 5. Soil Resistivity The second major factor in determining how well a grounding system performs, is the resistivity of the local soil. Soil resistivity is the resistance measured between two opposing surfaces of a 1m 3 cube of homogeneous soil material (see figure 7,) usually measured in Ω m, or Ω cm. Soil resistivity has a direct effect on the resistance of the grounding system. The evaluation of the resistivity of the local soil can determine the best location, depth, and size of the electrodes in a grounding system, and can also be used for many other applications. A geological survey uses the soil resistivity to locate ore, clay, gravel, etc. beneath the earth s surface. Depth and thickness of bedrock can also be determined. The degree of corrosion of the local soil also can be obtained from its resistivity value. Due to these many reasons, it is necessary to measure the resistivity of the local soil. Many different factors have a direct effect on the resistivity of the local soil. A large factor is the type of soil. The resistivity range can go from 1 Ω cm to the upwards of over 1,000,000 Ω cm (see figure 8.) Moisture content can be a large factor in determining the resistivity of the local soil. The drier the soil, the higher the resistivity. The soil resistivity remains relatively low (and constant) if the moisture content of the soil is greater than 15% (by weight,) and skyrockets for lower values of moisture content. Another large factor in the determination of soil resistivity is the content of minerals, such as salts or other chemicals. For values of 1% (by weight) salt content, the soil resistivity remains low (and constant,) and skyrockets for lower values of salt content. Finally, compactness and temperature can set the resistivity of the local soil. With temperature, the colder the soil is, the higher the resistivity. Due to seasonal changes where the temperature can change drastically for a particular area, the resistivity of the local soil can also change drastically (see figure 9.) Many of these factors (moisture content, mineral content, compactness, and temperature,) of the local soil can change during the life of the grounding system, and therefore change the resistance to remote earth of that grounding system. Soil Resistivity (Ω-cm) lower upper Surface Soils 100 5,000 Clay 200 10,000 Sandy Clay 10,000 15,000 Moist Gravel 5,000 70,000 Dry Gravel 70,000 120,000 Limestone 500 1,000,000 Sandstone 2,000 200,000 Granites 90,000 110,000 Concrete 30,000 50,000 Figure 8: Resistivity range for different types of soil Earth Resistance (Ohm) 35 30 25 20 15 10 5 0 Typical year 0 2 4 6 8 10 12 Month Figure 9: Typical electrode resistance to remote earth in a year Figure 7: Soil Resistivity Definition Cube Like the resistance to remote earth of an electrode, measuring the resistivity of the local soil can be done with a specific metering device. The process is

sometimes referred to as the four pole (or four-terminal) method (see figures 10 and 11.) of readings be taken at different values of a, as well as in a 90 o turned axis, so that the measuring results are not distorted by any underground pieces of metal (pipes, ground cables, etc.) These final values should be plotted, so that a consistant value be determined. 6. Improving the Grounding System Figure 10: Soil Resistivity Four Pole Method Figure 11: Soil Resistivity Four Pole Setup If it is determined that a grounding systems resistance to remote earth is not low enough, there are several ways that it can be lowered. The first approach would be to lengthen the electrodes, which puts them deeper into the ground. If it is difficult to drive ground rods keep into the ground, a horizontal crows foot approach using copper tape, may be used. Another approach would be to use multiple ground rods. The National Electrical Code (NEC 1996) states that if one electrode is being used and it s resistance to remote earth is greater than 25Ω, then only one additional electrode needs to be installed. A final way to help lower the resistance to remote earth for a grounding system, is to treat the soil with some type of ground enhancing material (i.e. GEM TM, salt, chemical rod, etc.) The thickness of the electrode used plays only a small part (and it is not very economical) in helping to reduce the total resistance to remote earth of the grounding system. Four small electrodes (auxiliary probes) are placed in a straight line at intervals of a, to a depth of b. A current is passed through the outer two probes, and the potential voltage is then measured between the two inner probes. A simple Ohm s Law equation determines the resistance. From this information, it is now possible to calculate the resistivity of the local soil by using the Equally Spaced (or Wenner Arrangement) method. ρ = [ 4 x π x a x R ] / [ 1 + ( ( 2 x a ) / SQRT ( a 2 + 4 x b 2 )) ( a / SQRT ( a 2 + b 2 ) ) ] where ρ = resistivity of the local soil (Ω-cm) a = distance between probes (cm) b = depth of probes into the ground (cm) R = resistance determined by the testing device (Ω) For most practical circumstances, a is twenty times larger than b, where we can then make the assumption that b=0, and the formula becomes simply: 7. Conclusion It is important for a facility to have a good grounding system. The safety of all personnel and equipment is at stake. In order to be sure that a good grounding system is in place, it is necessary to maintain a low resistance to remote earth of all the electrodes, and a low resistivity of the local soil. There are different methods for obtaining these measurements. Due to variations in electrodes and soil, a number of measurements should be taken and evaluated for a consistancy. It is the intent that this paper be used as a guide for descriptions and definitions of different ground measuring techniques for electrode resistance to remote earth and soil resistivity. Detailed instructions on the use of any earth testing device should be fully read and understood before they are used. There always exists the possibility of ground faults in a system, and step and touch potentials. It is important to note that before attempting to test any grounding system, all safety precautions be taken. ρ = 2 x π x a x R These values give an average resistivity of the soil to a depth of the value of a. It is recommended that a series

References Earley, Mark W., Editor in Chief, National Electrical Code Handbook, Seventh Edition, 1996 Elmes, UNILAP GEO X Earth Tester Operating Instructions, LEM Getting Down to Earth, Manual on Earth-Resistance Testing for the Practical Man, Fourth Edition, Biddle Instruments, 1982 Author Elvis R. Sverko Applications Engineer ERICO, Inc. Facility Electrical Protection 34600 Solon Road Solon, Ohio 44139 U.S.A. Phone: (440) 248-0100 Fax: (440) 519-1675 email: esverko@erico.com IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System, ANSI/IEEE Std 81-1983 Simmons, J. Philip, Soares Book on Grounding, International Association of Electrical Inspectors, Fifth Edition, Editor1996 Superior Grounding, http://www.superiorgrounding.com/soils.html Switzer, W. Keith, Practical Guide to Electrical Grounding, ERICO Understanding Ground Resistance Testing, AEMC Instruments, Workbook Edition 6.0