Earth electrode. and. earth loop impedance testing. Theory and applications
|
|
|
- Chad Austin
- 9 years ago
- Views:
Transcription
1 Earth electrode and earth loop impedance testing Theory and applications 1
2 Contents Introduction 3 Earth electrode testing 4 Resistivity v resistance 4 Earth system resistance 5 Earth system resistance test methods 8 Earth loop testing 17 What is the loop and why do we test it? 18 Loop impedance test methods 19 Test instrument accuracy 24 External factors influence measured values 26 Testing at source simple work-around 31 PFC and PSCC testing 32 Loop testing summary 34 2
3 Introduction As two of the most common testing subjects debated amongst electricians - as well as generating the highest percentage of calls to the Megger Technical Support desk - this series of presentations and supporting booklet hope to clarify some of the obstacles faced by an electrical contractor, or test and inspection engineer, out testing today. The intention is not to delve in to the physics of the tests, but rather look at the practical issues relating to the measurements. We will also clarify the different test techniques, detail some of the reasons why fluctuating values will be seen and hopefully instil a greater confidence in the day to day results obtained when testing in the field. This booklet, although designed to be read in isolation, is in no way a definitive guide. There have been written a plethora of articles and application notes and it is recommended that should further information be required, a quick search of the internet will return a wealth of additional material, from basic How To guides, to complete scientific papers on the subjects. 3
4 Earth electrode testing Resistivity v resistance When talking about earth electrode testing, there are two basic test types: earth resistivity and earth system resistance. In a nutshell, resistivity testing is used when looking to site a new earthing system and system resistance testing is used to check an existing resistance is low enough for a desired application. Resistivity Resistivity testing is primarily used when surveying an area, prior to sinking rods, mesh, mats etc. Soil resistivity can vary across a site by significant amounts and the cost implications involved make surveys invaluable in identifying the optimal location to locate the new installation. There are numerous factors that will influence the resistance readings obtained the soil composition, the moisture level and temperature as well as geographic features within the ground. In addition, when surveying, the variables of moisture content, water table level and temperature have to be accounted for as these will change dependent upon the season. Fairly obviously, as the moisture content of the soil increases, the resistance value decreases, so an allowance would have to be made for readings taken in mid-winter as opposed to a reading taken through the summer months. The most popular method for earth resistivity surveys is the 4-pole (Wenner method), utilised with the standard formula for average earth resistivity: p = 2 AR 4
5 Where: is average earth resistivity to depth A in ohm-cm A is the distance between the spikes R is the resistance read from the earth tester I meas E meas C1 (E) P1 (ES) P2 (S) C2 (H) A A A <A/20 This cm value is of interest to a design engineer, because by rearranging the formula and utilising published tables, the resistance of the earth electrode required can be calculated: p = 2 AR ( Ωcm) therefore electrode resistance R = p / 2 A Earth system resistance It is important to remember why earth resistance testing is being undertaken and why a low resistance value is normally required. In essence, the earth is provided to either enable protective devices to operate, reduce ground potential rises or to provide a safe passage to earth for lightning strikes and static charges etc. Different applications will call for different maximum permissible earth resistance values and there are numerous variables that will contribute to this. Published standards or specific design 5
6 criteria will dictate what values are necessary and these should be referred to in all cases. Earthing systems fall within 2 categories: Simple or Complex. Simple systems consist of either a single or small number of electrodes driven in to the ground, whereas a complex system will have multiple earthing points. So what makes up an earth electrode resistance value? There are 3 main components involved: 1. Resistance of the electrode itself (dependent on material) and the connections to it 2. Contact resistance between the electrode and the soil it is driven into 3. Resistance of the surrounding body of soil 1 - Electrode resistance will vary slightly due to the type of material used. Copper is the preferred material for earth rods and mats, but it is not uncommon to find steel or iron used. The resistance value between the materials is measurable but not normally significant. Contact resistance between connections is where issues may arise primarily down to incorrect termination techniques or corrosion. 2 - Contact resistance is often thought of as one of the main contributors to high earth resistance readings, but provided the electrode is free from paint and grease and the earth is packed firmly, the value is negligible 3 - Finally, an electrode driven in to the earth of uniform resistivity will radiate current in all directions. By envisaging the electrode surrounded by shells of earth of equal thickness, it is easy to realise that the nearest shell will have the smallest surface area, but as you move further away the surface area of each shell is somewhat larger and offers less resistance. Finally, a distance from the electrode will be reached where additional 6
7 shells will not add significantly to the resistance of the earth surrounding the electrode. It is this critical volume of soil that determines the effectiveness of the electrode. In most cases, the greatest influence on the earth resistance value will be the depth of the electrode. Doubling the depth can see a reduction of up to 40% in the measured value. If multiple rods are required, as a rule of thumb, the spacing of the rods needs to be at least equal to the driven depth. Effect of temperature C Resistivity (Ohm-cm) 20 7, ,900 0 (water) 13,800 0 (ice) 30, , ,000 Resistivity of different soil types Resistivity (Ohm-cm) Surface soils, loam, etc ,000 Clay ,000 Sand and gravel 5, ,000 Surface limestone 10,000-1,000,000 Shale ,000 Sandstone 2, ,000 Granites, basalts, etc. 100,000 Slates, etc. 1,000-10,000 7
8 Earth system resistance test methods 2-pole or direct measurement (Dead Earth) Although the simplest form of resistance testing, this method is generally used as a last resort as it requires using unknown factors and involves making certain assumptions. In essence, a measurement of two electrodes in series is made with one of the electrodes being an existing earth i.e. a water pipe. For the reading of the electrode under test to be accurate, an extremely low resistance value would be needed from the existing earth but this cannot be proven. Although an extensive metallic water pipe system may indeed have a low resistance value, there would be no guarantee that non-metallic couplings have been used and without comprehensive schematics, the electrode under test could be placed firmly within the sphere of influence created by the existing earth. C1 (E) P1 (ES) I meas P2 (S) C2 (H) E meas Earth electrode under test 8
9 Fall of potential method This is the classic method for measuring resistance of a single electrode, or a system of electrodes, to Earth. Two auxiliary spikes are driven into the ground in line with the electrode/s under test. Current is generated by the instrument between the electrode/s under test and the auxiliary C spike. The resultant potential across the soil resistance is then measured between the electrode under test and the auxiliary P spike. However to measure the true resistance of the electrode/s under test, the auxiliary C spike must be far enough away from the electrode/s under test for the spheres of influence not to interfere with each other. This is determined by moving the P spike in steps between the electrode/s under test and the C spike and plotting the resistance curve caused by the fall of potential. The plotted curve must have a flat, see diagram, and the true resistance of the electrode/s is measured here. If there is no flat the distance between the electrodes under test and the C spike must be increased until there is. Ground Electrode Under Test (X) Current Probe (C) Ground Electrode Under Test (X) Potential Probe (P) Position Current Probe (C) True system resistance measured here Resistance in Ohms X Ground Electrode Position Distance of Potential Probe from X (d p ) C Current Probe Position X Ground Electrode Position Distance of Potential Probe from X (d p ) When testing a single earth electrode the C spike can usually be placed 15 m away from the electrode under test, with the P spike placed 9m away. With a small grid of two electrodes, C can be placed about 100 m from the electrodes under test; P spike about 62 m away. Larger earth systems consisting of several rods or plates in parallel required the distance for C to be increased to possibly 200 m and P to some 125 m. Resistance in Ohms C Current Probe Position 9
10 Lazy spike method Megger earth testers can operate with high temporary spike resistances and still give accurate, reliable results. This means auxiliary spikes do not have to be inserted too far into the ground. However another advantage is that in urban concrete locations where driving in spikes is impossible the spikes may be laid flat on a wet patch of concrete and a measurement made. However, structural steelwork and buried metal piping could affect readings and should be taken into account. 61.8% rule Assuming the C spike is far enough away from the electrode under test, the soil mass is homogenous, and there are no buried objects the correct P spike position will always be at 61.8% of the distance from the electrode/s under test and the C spike. This is definitely a rule to be treated with great care. 10
11 ART Attached rod technique Based on the Fall of Potential method, instruments with ART capability use the ICLAMP to measure only the instruments test current flowing down the electrode under test, negating the requirement to disconnect the electrode under test. X Building earth Connection connection/s I System I Total Ie 3 Ie 1 Ie 2 Ie test Test Potential Probe (P) Current Probe (C) Ground Electrodes Ie Test > I Total 20 Earth system leakage and current range Instruments equipped with ART and ICLAMP also have a current measurement range. This is an important feature; it enables the operator to check if there is current flowing, should an electrode have to be disconnected from a system, ensuring his safety 11
12 The slope method When testing very large earth systems, such as that encountered on large substations, it may be impractical to get the required auxiliary P and C spike distances. The result is that the plotted resistance curve would not have a flat area, remain a slope. In this method three measurements are taken, inserted into a formula and a value calculated. This value can then be looked up in a table to find the correct P spike distance required to measure the true resistance of the system under test. I meas µ=(r 3 -R 2 )/(R 2 -R 1 ) E meas P1 (ES) R = E meas /I meas C1 (E) C2 (H) 0.2B R 1 R 1 = 9.3 ohm B I meas µ=(r 3 -R 2 )/(R 2 -R 1 ) E meas P1 (ES) R = E meas /I meas C1 (E) C2 (H) Earth electrode under test 0.4B R 2 R 1 = 9.3 ohm R 2 = 16 ohm B I meas µ=(r 3 -R 2 )/(R 2 -R 1 ) P1 (ES) E meas R = E meas /I meas µ = ( ) / (16 9.3) C1 (E) C2 (H) B 0.6B R 3 R 1 = 9.3 ohm R 2 = 16 ohm R 3 = 19.2 ohm 12
13 I meas µ=(r 3 -R 2 )/(R 2 -R 1 ) P1 (ES) E meas R = E meas /I meas µ = ( ) / (16 9.3) C1 (E) P2 (S) C2 (H) 0.2B 0.4B R 1 R 2 0.6B Auxiliary test R 3 electrodes µ =0.478 B The resulting value of u (which in this example = 0.478) is then looked up in the table shown below. In this example the correct earth system resistance would be measured with the P spike at 0.632, or 63.2% of the C spike distance from the electrode under test. Chart for use with the Slope Method Values of P t / d c for Values of µ Values of P t / d c for Values of µ µ P t / d c µ P t / d c µ P t / d c µ P t / d c µ P t / d c µ P t / d c
14 SAFETY NOTES There is always the possibility that a fault in a power system will cause high current to flow into the ground system while the test is in progress. This may cause unexpected high voltages to appear at the current and voltage probes and also at the terminals of the instrument. The person responsible for the tests, taking into account potential fault current and expected step and touch potentials, must evaluate this risk, take suitable precautions, and observe safe systems of work. The clamp on or stakeless method ICLAMP Building earth connection/s VCLAMP Ground Electrode Under Test ICLAMP VCLAMP R Meas. = 50.6 Ohms R4 R3 R2 R1 R test 25 Ohms 22 Ohms 19 Ohms 25 Ohms 45 Ohms R Meas. = R test + 1 / (1/R1 + 1/R2 + 1/R3 + 1/R4) 14
15 This method measures the resistance of the loop including all connections and cables and is ideal for many applications, including lightning protection. The readings taken are ideal for comparative condition monitoring testing. Intersecting curves, star delta and four potential methods These 3 methods are either very complex, time consuming or both! Details of their specific applications, advantages and disadvantages along with their operational procedures - can be found in the Megger publication Getting Down To Earth, available as a free PDF download from Intersecting Curves I meas P1 (ES) E meas R = E meas /I meas C1 (E) R1 R2 R3 R4 R5 R6 Earth electrode under test P2 (S) C2 (H) 0.2B 0.4B Auxiliary test electrodes 0.5B 0.6B 0.7B 0.8B B 15
16 Selecting Earth System / Electrode Test Method Chart Method Best Application 1. Fall of Small electrode Potential systems; Complex system if full resistance curve is plotted. 2. Simplified Small and Fall of medium Potential electrode systems % Rule Small and medium electrode systems 4. Slope Large systems like substations 5. Dead Earth (2 pole) 6. Intersecting Curves Not recommended Large systems like substations 7. Star Delta Ground systems located in urban areas and/or rocky terrain 8. Four Potential 9. Clamp-on / Stakeless Medium to large ground systems Simple ground system with existing return path through multiple grounds Advantages Extremely reliable; conforms to IEEE 81; ART (with clamp) no requirement to disconnect electrode. Easier than Fall of Potential; much faster. Simplest to carry out; minimal calculation; fewest number of test probe moves Knowledge of electrical centre not required. Long distance to probes not required Quick and simple to perform Knowledge of electrical centre not required. Long distance to probes not required Long distances for test probe positioning not necessary Knowledge of electrical centre not required Quick, easy; includes bonding and overall connection resistance 16 Limitations Requires long distances (and long test leads) on medium and large systems; time consuming. Ineffective if the electrical centre unknown. Less accurate than Fall of Potential. Assumes perfect conditions; ineffective if electrical centre is unknown; soil must be homogeneous; less accurate Susceptible to nonhomogeneous soil; less accurate; requires maths Problems with resistance overlap. Numerous calculations and drawing of curves Resistance areas should not overlap; a number of calculations required Long distances to test probes is s required; a number of calculations Effective only in situations with multiple grounds in parallel
17 Earth loop impedance testing When looking at making measurements of Earth loop Impedance, or Prospective Fault Current (PFC) for that matter, it is always worth remembering why the reading is being taken. All too often time is lost on site because the principle of what the test is expected to prove is lost. Loop testing could be described as a Dark Art it is the most difficult measurement taken by the electrical contractor on his day to day business. By difficult, it should be clarified that the difficulty remains in the method of obtaining the elusive, stable, repeatable reading we all look for, not the application of the test itself. When you look at and compare the principles of continuity, insulation, loop or RCD testing, loop tests should not cause the level of consternation that they do. It is a simple test. What is the resistance that a fault between live and earth will be subjected to? Earth loop testing has been carried out for decades, so why do we still get fluctuating readings on certain circuits or worse still, readings that on the face of it would condemn an installation? Test equipment manufacturers continue to search for the Holy Grail of earth loop test techniques one test that can be used on any circuit, at any location, on any voltage, that will give us the stable accurate reading we desire. With each technological advance in testing, circuits and their components change, throwing obstacles in to the path of the poor loop impedance tester! What we hope this booklet will do is give you an insight into the different techniques that are available on the market today and arm you with the knowledge to go about your daily routine, confident in the readings being taken and recorded. 17
18 What is the loop and why do we test it? If a fault occurs in an electrical system, we must prove that the over-current device will operate within the prescribed time by ensuring that the circuit impedance is low enough to allow sufficient current to flow. The required values of impedance and time will change dependent upon the type of installation (TN/TT etc.) and the type of protection, whether it be a miniature circuit breaker (MCB), cartridge fuse or re-wireable fuse for example. The fault current can either be in the Line-Neutral or Line-Earth circuit, so there is a need to confirm the loop impedance of each. 18
19 Earth fault loop return path TNC-S installation The testing of the Line-Neutral loop impedance does not throw up many issues as the circuit has no earth leakage protection and a straight forward high current test returns repeatable, stable readings. Loop impedance tests methods As it stands today, most contractors will use one of 5 different test techniques when loop impedance testing: 2-wire high current test 2-wire No-Trip d.c. saturation test (Obsolete) 3-wire No-Trip test 2-wire No-Trip test 4-wire grid impedance test Determining which test to use will depend upon a number of factors, not least being which one is available on the test meter being used! The following information will hopefully go some 19
20 way to explain some of the applications and limitations of these different options when in the field. 2-wire high current test This is the traditional loop impedance test. Using a test current of up to 20 A and a simple 2 wire connection, it is by and large the fastest, most accurate test available on a day to day basis. Most standard loop impedance testers will incorporate this type of test. Because of the relatively high test current, the readings are not generally influenced by external factors and will return repeatable, stable readings in most scenarios. Unfortunately, it does have its limitations. When first conceived, earth leakage monitoring RCDs and RCBOs were not part of the electrical installation and because it relies on a short between Line-Earth for the earth loop test, albeit only for 2 cycles (or 40 ms) of the AC waveform, the test will cause the RCD/RCBO to operate. In addition, some early instruments whose test time was not so tightly restricted had cause to operate some of the low current MCB s as well. Where earth leakage protection was in place, the contractor was left with no option but to bypass it to allow for the test to be undertaken a time consuming and rather un-safe practice as it left the system unprotected for the duration of the test. That said, this test still has its place in a contactors toolkit and should be the go to solution wherever possible. When carrying out a Ze measurement of an installation or taking a Zs reading on an unprotected circuit, this is still the most accurate, easiest test to use. 20
21 2-wire No-Trip d.c. saturation test To overcome the problems caused by the introduction of earth leakage protection, a test technique was developed whereby a DC test current was injected in to the circuit prior to carrying out a standard 2 wire high current test. The aim of this DC test was to saturate the monitoring coil within the RCD, allowing enough time for the high current AC test to be carried out. This anesthetising effect proved very effective. At the time, there were claims that the saturation left the coil in a potentially unresponsive state, but this was never substantiated. However, due to the increase in electronic RCDs, this method now has limited applications with some newer RCDs and RCBOs specifically monitoring for DC voltage being present on the system. This technique is no longer incorporated within the current range of instruments on the market. 3-wire No-Trip test The 3 wire method of no-trip loop testing has become the norm over the past 20 years. This test method overcame the need to by-pass even the new electronic protection devices by utilising a low current Line-Earth test current, whilst still returning a degree of accuracy. Not having to by-pass the RCD/RCBO obviously introduced a time saving factor. In addition, by having the requirement of connecting to Line, Neutral and Earth, the testers were now able to confirm the presence of all three as well as indicate if there was a reverse polarity at the test point and, due to the limited test current, there was no issue with tripping the MCB. There remain limitations with the 3-wire test however. Due to the lower test current, readings became more susceptible to 21
22 external factors (much more on these later) introducing instability on certain circuits and a reduction in consistency. In some circumstances the internal impedance of the RCD can be seen or existing system earth leakage can combine with the test signal to cause the protective device to operate. 2-wire No Trip test The 2 wire no-trip option has come and gone in various guises over the years. Some testers opted for a low current test, but this affected accuracy on the low end, where as other techniques never proved accurate and were dropped as soon as they were launched. The latest 2-wire no-trip units have a much improved technique offering far better repeatability, but still suffer from limitations. Obviously, they will allow for testing most RCDs and RCBOs without having to bypass them. With no neutral connection required, they maintain a true 2-handed operation, but will no longer indicate reverse polarity or warn of a missing neutral. The test current does not combine with existing leakage, so there is no accumulation effect, as suffered by the 3 wire test. Although the physical test time is similar to that of the 3-wire method, the time saving of not having to bypass the RCD still makes for a more efficient test. External factors can again affect the reading taken, but the simplicity of 2 handed testing can outweigh this limitation in a lot of cases. The Megger range of loop and multifunction testers also incorporate an Auto-Start feature, whereby once the probes are connected and the voltage verified, the test will automatically start alleviating the need to clip one of the leads to free up a hand to press the test button 22
23 4-wire grid impedance test This new method of testing will only be undertaken in certain circumstances. The test uses a 4 wire Kelvin connection, negating internal lead and contact resistance; such is the accuracy of the test. With test currents up to 1000 A, measurements down as low as 10 mohm can be accurately made. Consequently, there is no No-Trip option with this test method. With specific applications being measurement in sub-station/switch room environments, this tester gives the test engineer the ability to take accurate readings when sited next to the main transformer something that has caused problems for many years when trying to sign off jobs with readings based on design engineers calculations down as low as Ohm! As stated, this test set will have a limited market, notwithstanding the size and cost of the unit, but also the safety aspect of working in HV environments. 23
24 Test instrument accuracy Having an understanding of the published accuracy and uncertainties for the test equipment you use is paramount. Test equipment manufacturers have an obligation to stamp on the instrument the accuracy the operator can expect on any given range and interpreting this can alleviate a number of queries raised when deducing results. BS EN requires that loop testers measure no worse than 30% accuracy across a stated range, in the presence of operational uncertainties. Achieving this is no great feat, but manufacturers realise that this would fall far short of the repeatability in readings required to instil confidence when using their instruments. As such, the accuracy statements you see will far exceed this requirement. It should be noted, however, that accuracy will normally be shown across a measuring range so, for example, on the Megger MFT1700 series multifunction tester, for a high current loop test the accuracy is claimed for the range 0.1Ω to 1000 Ω, compared to 1 Ω to 1000 Ω for non-trip testing. Guidance Note 3 Inspection & Testing talks about basic measurement accuracy of 5%. Here, the discrepancy between basic and operational accuracy is introduced. To clarify, basic accuracy can be deemed to be achieved within controlled laboratory type conditions, whereas operational accuracy looks at real world, field readings. It goes on to state that operational accuracy is always worse than basic accuracy. The Electrical Safety Council publication back up this measurement discrepancy in their published Best Practice Guide No.7 Test Instruments for Electrical Installations: Accuracy and Consistency where they state that readings on a high current test will be susceptible to errors once readings below 0.2 Ω are 24
25 being made, whereas on the no-trip test ranges, anything below 1.0 Ω will be subject to significant errors. They recommend taking multiple readings if there is any concern about the result of a test. Real world example Accuracy needs to be looked at and understood. Here are 2 examples: Example A: Range: 0.1 Ω to 1000 Ω Accuracy: 5% +/ digits Example B: Range: 0.1 Ω to 1000 Ω Accuracy: 3% +/- 0.1 digits In this example, we have a known clean loop impedance value of 0.5 Ω Example A: 5% +/ digits 5% accuracy = 0.03Ω add the 5 Digits = +/- 0.08Ω Therefore, before any external influence, any reading between 0.42 & 0.58Ω is acceptable! (Variation 0.16 Ω) Example B: 3% +/- 0.1 digits 3% accuracy = 0.015Ω add the 0.1 Digits = +/ Ω Therefore, before any external influence, any reading between & 0.62Ω is acceptable! (Variation 0.23 Ω) What this goes to prove is the acceptable range that an instrument can be deemed to be accurate and just as importantly, a claimed 3% accuracy against 5%, pales in to insignificance when you take account of the +/- digits. 25
26 External factors influence measured values When making a loop impedance measurement, there are numerous challenges that the test signal has to overcome. Some are physical and some are man-made. Having an understanding of the limitations of the various tests that are available goes some way in overcoming some of these obstacles. Just as importantly, knowing the significance of the desired value (usually stipulated by regulation) and an appreciation of the measured value in the real world will help to maintain confidence in the recorded value. Below are a number of factors that will directly influence the readings being taken on a day to day basis, and the challenge is appreciating these and the fact that some are unavoidable and outside of your or the test equipment s control. Line waveform distortion In the UK we rely on the 50Hz supply being a smooth sinusoidal waveform. Unfortunately, due to the explosion of switch mode power supplies, power factor correction equipment and inverter drives, this is no longer the case. Clipped or distorted waveforms can have a significant influence on the test signal. Repeat testing can usually average out any issues arising from waveform issues. 26
27 Harmonic disturbance This has now earned the right of a section within the 17 th Edition and the problems severe harmonics can cause are being formally documented to a far greater extent. The detrimental effect on a loop test signal can be significant, but repeat testing, again, can often overcome this. Line noise Somewhat different to harmonic disturbance, line noise can be a general background signal, superimposed over the normal 50Hz supply. Again this can play havoc with a test signal especially the no-trip techniques. Testing at different times is probably the best solution, as noise will often fluctuate throughout a 24hr period. 27
28 Proximity of transformer As stated earlier in this booklet, we are not looking to venture into the physics of the testing, but suffice to say, when in close proximity of a transformer, the hand-held units available on the market today will struggle to return repeatable readings, when the calculated value is in the realms of milliohms and well below the stated range of the instrument. A work around is shown a bit later in this booklet. Ambient temperature Probably the most overlooked factor that can influence a reading. The changes due to ambient temperature may not be huge, but when making comparative readings, it is always worth bearing in mind when the original values were obtained. Line transients and spikes These do not have to be massive over voltages. More often than not they may well be recorded as sags and swells by line monitoring equipment. Most are manmade and are due to switching either at the substation or from larger industrial complexes running from the same grid. Again, repeat testing will help to alleviate any issues with readings. 28
29 Test lead resistance The one part of any manufacturers test equipment that will be slated more than anything else is ordinarily the test leads. They are the one mechanical component that will be subject to wear and tear, over and above any other component of the test kit. Regular checks should be carried out, especially against known values, as deterioration of lead contact resistance is rarely picked up as it is a gradual phenomenon. Some operators will replace their leads 2 or 3 times a year, whereas some look to change them only when a major issue arises. Regular inspection and checks should overcome any problems the leads may end up giving. Contact resistance This may be a subjective issue, but can be proven on most installations. Whether the resistance is generated by accessibility to the test point, or due to wear on a socket, it is easily rectified. Firm, constant pressure is required across the contact points and even applying a test probe to the centre of a screw as opposed to the outer edge can have a significant affect. With regards to a double socket, always look to test on both as it may be that one is favoured by the usual operator (the cleaner using 1 socket daily, for example). Other examples may be RCD internal resistance due to oxidisation. Testing and resetting can often overcome this factor. Inductance and capacitance These can often be unknown quantities when testing. Capacitance can be seen to be charged by the test signal, therefore directly affecting the reading taken. Inductance would not ordinarily affect a standard test (it is primarily associated with coils of cable) but when testing a third party installation it is a factor that could influence the result if found to be present. Repeat testing at various points on a circuit can usually alleviate the discrepancy seen. 29
30 When some of the issues faced when taking a simple loop impedance test are listed out, you start to get a better understanding of how these can easily influence the reading being taken. Added to this, the variation that the instrument can show whilst still be working within design /accuracy standards, it is easy to see why the loop test causes more head scratching than any of the other readings being taken. The digital age has been our undoing in all this. If we return to the 1970s when we had our traditional analogue balanced moving iron coils, if the reading swung anywhere below 1 or 2 ohms we were happy. 30
31 Testing at source simple work-around One technique that goes someway to obtaining a more stable, repeatable reading when taking measurements close to the source of supply is to add additional resistance to the circuit being measured. Notwithstanding the stated accuracy of the instrument range, if a known resistive value is placed in series with the test circuit, by deducting this away from the measured value a reading for the circuit can be obtained. In some instances, the additional resistance need not be great, for instance, a long test lead set with a known value of 0.15Ω may be sufficient. The 2 wire high current test must be used and numerous readings taken to give an average. 31
32 PFC and PSCC testing Prospective fault current and prospective short circuit testing are measurements that are made to calculate the current that will flow in the event of a fault. Too little current and protective devices may fail to operate in time (if at all) and too much current will cause damage to equipment, may cause fire or prevent the breaker from operating. Interestingly, the calculation should be made using the nominal supply voltage value and not the measured voltage. Loop impedance, either earth loop or line-neutral, will have a greater influence on the PFC/PSCC value the smaller they get, causing issues when taking measurements below the stated range of an instrument. Any PFC measurement should be taken using the high current option no-trip test ranges should only be 32
33 used for verification. If a critical measurement is being made, it should always be confirmed by calculation against design specifications. PFC v Earth Resistance (230 V 50 ohms to earth PFC = 230/50 = 4.6 A ( ohms to earth PFC = 230/0.5 = 460 A ( ohms to earth PFC = 230/0.1 = 2300 A ( ohms to earth PFC = 230/0.05 = 4600 A (4.6 ka) 33
34 Loop testing summary This booklet started out by saying that when loop impedance testing, you should not lose sight of why the test is being carried out. All too often a fluctuating reading or a reading higher or lower than you would have expected causes additional time to be spent on site, when in essence; the difference can be seen as negligible. Again, this harks back to the digital age our brains process 0.39 Ω to be VASTLY different to 0.51 Ω as a reading, yet in essence, with a difference of 0.12 Ω this could be explained as an accuracy fluctuation. It is worth remembering the requirements laid out in BS7671:2008 Typical 32A Circuit with BS EN Breaker Type B Zs < 1.16 Ω (Domestic) Type C Zs < 0.58 Ω (Inductive/Resistive Loads) Typical 6A Circuit with BS EN Breaker Type B Zs < 6.16 Ω (Domestic) Type C Zs < 3.09 Ω (Inductive/Resistive Loads) Values from GN3 Table B4 (80% Rule Applied) 34
35 And remember Maximum Zs to Ensure (Non-Delayed) RCD operation to BS EN & BS EN for final circuits not exceeding 32 Amp 30mA on 230V circuit < 1667 Ω* 100mA on 230V circuit < 500 Ω* 300mA on 230V circuit < 167 Ω (based on a touch voltage limit of 50 V) *A value exceeding 200Ω may not be stable. I hope this booklet has proved interesting and perhaps useful in clarifying some of the issues faced day to day when undertaking earth and loop measurements. If you need more information on any of the subjects, a quick visit to the internet using your favourite search engine will return plenty of additional technical papers, delving in to the physics of what we have brushed upon today. 35
36 If I can ask you to take one thing away from reading this booklet, that I believe will make your life easier when out testing, it would be the following: When testing use the best available test in the following order of preference 2 Wire High Current Test 3 Wire No-Trip Test 2 Wire No-Trip Test One final statement. Where the possibility of accidentally tripping an RCD is NOT ACCEPTABLE, loop impedance testing should not be performed, as it is impossible to absolutely guarantee an RCD will not trip during a loop impedance test. 36
37 37
38 38
39 39
40 M Archcliffe Road Dover CT17 9EN E: 40
12 Appendix 12 Earth Electrodes And Earth Electrode
12 Appendix 12 Earth Electrodes And Earth Electrode Testing 12.1 Introduction This appendix provides guidance and background information an earth electrode testing and some limited information on earth
Earth Ground Resistance
Principles, testing methods and applications Diagnose intermittent electrical problems Avoid unnecessary downtime Learn earth ground safety principles Earth Ground Resistance Why Ground, Why Test? Why
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria
Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria Abstract Gabriel A. Adegboyega and Kehinde O. Odeyemi Department of Electrical and Electronic
DET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com DET3 Contractor Series 3-Terminal DET3 Contractor Series 2 and 3 point testing
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
Lightning Protection Introduction
Lightning Protection Introduction Structural lightning protection design considerations BS 6651 (Protection of structures against lightning) clearly advises strict adherence to the provision of a conventional
A Guide to 17th Edition Testing
Seaward, Bracken Hill, South West Industrial Estate, Peterlee, County Durham, SR8 2SW United Kingdom Tel: +44 (0) 191 586 3511 Fax: +44 (0) 191 586 0227 Email: [email protected] Web: www.seaward.co.uk
SELECTION OF FINAL CIRCUIT PROTECTION
SELECTION OF FINAL CIRCUIT PROTECTION By Phil Williams, Product Marketing Manager, Power Distribution Components, Eaton Executive summary The selection of devices for final circuit protection in electrical
DET3 and 4 Contractor Series Earth/Ground Resistance Testers
DET3 and 4 Contractor Series 2, 3 and 4 point testing ART (Attached Rod Technique) testing capability and stakeless testing technique Choice of digital or analog display Warning indicators prevent test
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
A practical guide to earth resistance testing WWW.MEGGER.COM
A practical guide to earth resistance testing WWW.MEGGER.COM The word Megger is a registered trademark Introduction Nothing is quite so common or abundantly available throughout the world as the earth
Understanding Soil Resistivity Testing
Technical Hotline: (00) -9 Technical Hotline: (00) -9 www.aemc.com www.aemc.com Understanding Testing Effects of on Ground Electrode Resistance Factors Affecting APPLICATION NOTES JULY rev.0 Understanding
DET3 Contractor Series
DET3 Contractor Series 3-Terminal 2 and 3 point testing ART (Attached Rod Technique) testing capability User selectable test voltage (25/50 V) Choice of digital or analog display Warning indicators prevent
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
SOIL RESISTIVITY MEASUREMENTS
SOIL RESISTIVITY MEASUREMENTS APPENDIX B B Soil resistivity directly affects the design of a grounding (earthing) electrode system and is the prime factor that determines the resistance to earth of a grounding
Multi-Function Ground
Multi-Function Ground Resistance SOIL RESISTIVITY TEster Model 6470-B Now measure ground resistance, soil resistivity and bonding resistance with one instrument! 2- and 4-Wire Bond Resistance/Continuity
Electrical Safety Tester Verification
Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that
6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20
USE OF ELECTRICAL TEST EQUIPMENT Test equipment is necessary for determining proper set-up, adjustment, operation, and maintenance of electrical systems and control panels. The following is a general procedure
Substation Grounding Study Specification
Substation Grounding Study Specification Introduction A grounding study is required for name of station, a / / kv substation located in name of location and connected to the following circuits: number
Interference in the ECG and its elimination
Interference in the ECG and its elimination General points The signal voltages in ECG recording are known to be very small and are in the millivolt range, i.e. they have amplitudes of only a few thousands
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
Measuring Insulation Resistance of Capacitors
Application Note Measuring Insulation Resistance of Capacitors A common use of high resistance measuring instruments (often called megohmmeters or insulation resistance testers) is measuring the insulation
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface
MEGGER 210170 Insulation & Low Resistance Tester
MEGGER 210170 Insulation & Low Resistance Tester User Guide SAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.
Electrical Fundamentals Module 3: Parallel Circuits
Electrical Fundamentals Module 3: Parallel Circuits PREPARED BY IAT Curriculum Unit August 2008 Institute of Applied Technology, 2008 ATE310- Electrical Fundamentals 2 Module 3 Parallel Circuits Module
The Different Types of UPS Systems
Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Telecommunication Line Protectors
TN CR 0025 Telecommunication Line s 1.1 The nature of telecom surges The telecom services considered in this report are transported on twisted pair. Each service has two wires, or lines, sometimes called
PROTECTION AGAINST ELECTRIC SHOCK by John Ware
16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created
Coupling Effect in Substation Ground Measurements
SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 9, No. 3, October 2012, 315-324 UDK: 621.316.13.011.2 DOI: 10.2298/SJEE1203315F Coupling Effect in Substation Ground Measurements Alex Farber 1, Boris Katz
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
Measuring Electric Phenomena: the Ammeter and Voltmeter
Measuring Electric Phenomena: the Ammeter and Voltmeter 1 Objectives 1. To understand the use and operation of the Ammeter and Voltmeter in a simple direct current circuit, and 2. To verify Ohm s Law for
PAT120, PAT150 and PAT150R Handheld portable appliance testers
PAT120, PAT150 and PAT150R Handheld portable appliance testers PAT120, PAT150 and PAT150R Handheld portable appliance testers Simple tick or cross, pas or fail indication plus measurement Battery powered
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12
Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of
Electrical Contractors Association
Electrical Contractors Association Presents BS 7671 2008: Amendment No 1 BS 7671: 2008 Amendment No 1, 2011 IEE Wiring Regulations Now called IET Wiring Regulations History 1882 first edition of the Wiring
GUIDE TO THE AM2 EXAM
AM2 GUIDE TO THE AM2 EXAM What is AM2? AM2 or the Achievement Measurement 2 is a practical performance skill test administered by the National Electrotechnical Training (NET). You must take the AM2 test
Handheld portable appliance testers
PAT100 SERIES Handheld portable appliance testers PAT100 SERIES Handheld portable appliance testers Simple Tick/Cross, pass/fail indication plus measurement Battery powered with rechargeable options Includes
Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13
Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified
Episode 126: Capacitance and the equation C =Q/V
Episode 126: Capacitance and the equation C =Q/V Having established that there is charge on each capacitor plate, the next stage is to establish the relationship between charge and potential difference
Best Methods for Safe Hipot Testing
Best Methods for Safe Hipot Testing When working with electrical safety test equipment, instruments that output potentially dangerous voltages and currents, it is always important to regular review and
Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist.
Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist. Abstract. I have been asked to put together a detailed article on a SWR meter. In this article I will deal
Fluke 1650B Series Multifunction Installation Testers
Fluke 1650B Series Multifunction Installation Testers Extended Specifications The installation testing solution for demanding environments The Fluke 1650B Series testers, with new advanced features, are
ECEN 1400, Introduction to Analog and Digital Electronics
ECEN 1400, Introduction to Analog and Digital Electronics Lab 4: Power supply 1 INTRODUCTION This lab will span two lab periods. In this lab, you will create the power supply that transforms the AC wall
Earthing Guidance Notes
Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head
Regulation IO-6.0: Electrical Safety Regulations
Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5
Lab 3 - DC Circuits and Ohm s Law
Lab 3 DC Circuits and Ohm s Law L3-1 Name Date Partners Lab 3 - DC Circuits and Ohm s Law OBJECTIES To learn to apply the concept of potential difference (voltage) to explain the action of a battery in
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements
ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:
The Different Types of UPS Systems
White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by
UNDERSTANDING GROUND RESISTANCE TESTING. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-on Measurements E I
UNDERSTANDING GROUND RESISTANCE TESTING Current supply E I Ammeter (I) Voltimeter (E) X Auxiliary potential electrode Y Auxiliary current electrode Z Rx R1 R2 Rn-1 Rn Ground rod and clamp Contact resistance
CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE
CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2
Odyssey of the Mind Technology Fair. Simple Electronics
Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
6.0 Electrical Installations
6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is
User Guide. www.burntec.com. 4 wire Earth Resistance Tester Model GRT300
User Guide 4 wire Earth Resistance Tester Model GRT300 Introduction Congratulations on your purchase of Extech s 4 Wire Earth Resistance Tester. The Model GRT300 has been designed and tested according
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
Troubleshooting accelerometer installations
Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
Earthing Techniques 1. SOIL RESISTIVITY TESTING... 1.2 THEORY OF SOIL RESISTIVITY... 2. INTERPRETATION AND MODELLING OF RESULT...
Earthing Techniques 1. SOIL RESISTIVITY TESTING... 1.1 INTRODUCTION... 1.2 THEORY OF SOIL RESISTIVITY... 1.3 MAKING A MEASUREMENT... 1.3.1 PRINCIPLES...4 1.3.2 SOIL RESISTIVITY TESTING PROCEDURE GUIDELINES...
GroundRod AC Substation Earthing Tutorial
1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities
Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au
ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks
Understanding Power Impedance Supply for Optimum Decoupling
Introduction Noise in power supplies is not only caused by the power supply itself, but also the load s interaction with the power supply (i.e. dynamic loads, switching, etc.). To lower load induced noise,
7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
Residual Current Circuit Breaker
Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect
The electrical energy produced at the gen
300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
Tutorial on Safety Standard Compliance For Hipot Testing
Chroma Systems Solutions, Inc. Tutorial on Safety Standard Compliance For Hipot Testing 19071, 19073 Hipot Testers Keywords: Safety Issues, Electrical Shock, Fire, Hipot (Dielectric Withstand), Leakage
ACL 395 Resistivity Meter
ACL 395 Resistivity Meter OPERATION MANUAL Meter is warranted for one year from the date of purchase on parts and labor. Calibration is recommended every 12 months. 840 W. 49 th Place Page 1 of 13 [email protected]
REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
Lab E1: Introduction to Circuits
E1.1 Lab E1: Introduction to Circuits The purpose of the this lab is to introduce you to some basic instrumentation used in electrical circuits. You will learn to use a DC power supply, a digital multimeter
ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE
White Paper: Electrical Ground Rules
Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment
CAPACITOR BANK TESTING SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.
Transistor Amplifiers
Physics 3330 Experiment #7 Fall 1999 Transistor Amplifiers Purpose The aim of this experiment is to develop a bipolar transistor amplifier with a voltage gain of minus 25. The amplifier must accept input
By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.
16 Operation of portable generators Operation of portable generators By Mark Coles This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.
T 3000. Substation Maintenance and Commissioning Test Equipment
T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy
Ground Resistance Clamp On Tester
USER MANUAL Ground Resistance Clamp On Tester MODEL 382357 Introduction Congratulations on your purchase of Extech s 382357 Ground Resistance Tester. This Clamp on device allows the user to measure ground
Neutral Wire Facts and Mythology. White Paper #21
Neutral Wire Facts and Mythology White Paper #21 Executive Summary This Technical Note discusses many common misunderstandings about the function of the neutral wire and its relation to power problems.
ACL 800 MEGOHMMETER OPERATION MANUAL
ACL 800 MEGOHMMETER OPERATION MANUAL Meter is warranted for one year from the date of purchase on parts and labor. Calibration is recommended every twelve months. NOTE: THIS MANUAL IS NOT TO BE SEPARATED
Electrical test equipment for use on low voltage electrical systems
Electrical test equipment for use on low voltage electrical systems Guidance Note GS38 (Fourth edition) This general series guidance note is aimed at people (including electricians, electrical contractors,
Polarity. Electrical Quals 2007 1
Polarity Electrical Quals 2007 1 Polarity testing Introduction The polarity test is the 8th test in the sequence. Some people will think of it as the 4th test, (which to a certain extent they are correct).
METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS
METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS Contents Foreword --------------------------------------------------------------------------------------------------------------------
AC-Synchronous Generator
Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008
CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand
DC MOTOR ANALYSIS & TROUBLESHOOTING
DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,
How Much Voltage Drop Is Acceptable?
How Much Voltage Drop Is Acceptable? Article supplied by Ideal The National Electrical Code (NEC) recommends that the combined voltage drop of the electrical system (branch circuit and feeders) not exceed
LUCCI AIRFUSION QUEST II CEILING FAN
LUCCI AIRFUSION QUEST II CEILING FAN WITH IR REMOTE INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. V1.0 QUEST II IR
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
Force measurement. Forces VECTORIAL ISSUES ACTION ET RÉACTION ISOSTATISM
Force measurement Forces VECTORIAL ISSUES In classical mechanics, a force is defined as "an action capable of modifying the quantity of movement of a material point". Therefore, a force has the attributes
The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.
260 17-1 I. THEORY EXPERIMENT 17 QUALITATIVE STUDY OF INDUCED EMF Along the extended central axis of a bar magnet, the magnetic field vector B r, on the side nearer the North pole, points away from this