SECTION SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS

Similar documents
SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION HEAT PUMPS

HI-VELOCITY SYSTEMS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

MAC-120HE-01 Air-Cooled Chiller

Cooling Capacity CFM in. w.c. (125 Pa)

Element D Services Heating, Ventilating, and Air Conditioning

Glossary of Heating, Ventilation and Air Conditioning Terms

Cooling Capacity CFM in. w.c. (125 Pa)

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

Commercial Gas Furnace Upflow

SECTION MORTUARY REFRIGERATORS

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE

A. Air-Conditioning and Refrigeration Institute: 1. ARI Commercial and Industrial Air Filter Equipment.

Innovent LASER Packaged Fresh Air Conditioning Units

Evaluate, Clean, and Tune Guidance

F9MXE. Product Specifications

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin / March 2013

catalog Single Package Vertical Air Conditioners and Heat Pumps

Installation Instructions WARNING: WARNING: WARNING: WARNING: WARNING:

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Basics of HVAC Cleaning

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

HVAC Checklist - Long Form

Bring the fresh in. Dedicated Outside Air Systems

ARMSTRONG AIR HEAT PUMPS

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).

AABC Specifications for Testing and Balancing HVAC Systems

GCS16 GCS20 WARNING CAUTION

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

G9MXE. Product Specifications

Greensource iseries HY Model Unitary Air Handler/Fan Coil

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Cooling Capacity CFM in. w.c. (125 Pa)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

SECTION AIR CONDITIONING UNIT

CE6500 Energy Recovery Ventilator

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

GCS

HVAC Processes. Lecture 7

AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency

Below are detailed instructions for using the EMS load calculator.

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

SAM HOUSTON STATE UNIVERSITY

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA

FTXS. Wall Mount Heat Pump or Cooling Only

Airline. small air handlers and extract fan units. VES Airline part of a complete range of innovative, flexible products from the HVAC experts

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.

1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None

Cooktop Low-Profile Ventilation Hoods

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)

DUCT DESIGN FOR THE TIME CONSTRAINED WORLD

Glossary of HVAC Terms

HVAC Simplified Approach Option

Single Package Vertical Air Conditioners. Vert-I-Pak

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

SINGLE PACKAGE VERTICAL AIR CONDITIONERS

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION BLOWER COIL UNITS

Low Profile Unit Cooler

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

Cooling/Heat Pump Convertible Air Handlers

COMMISSIONING OF HVAC SYSTEMS

A. Section includes air conditioning units, controls and control panels.

1.2 Refrigerant Equipment. General

Split System Heat Pump Product Data

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

Split System Cooling Product Data

Diesel Engine Driven Generators Page 1 of 6

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

ENHANCED LABORATORY HVAC SYSTEM

SECTION GENERAL PROVISIONS FOR HVAC WORK

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Building Performance Solutions HVAC Design Guide, 2007

How To Install An Evaporator Coil

How To Design A Building In New Delhi

Duct Design. Presented by Dave Janquart

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Get the FACTS about SEER and Deliver Better Customer Value

TWE+TTA TWE+TWA T.R.

squrboxbox heat recovery squrboxbox I technical information

Basic Nameplate Information

Engineering Specifications

Johnson Air-Rotation Systems

SPACE COOLERS. P.O. Box 956 Paoli, PA (800) FAX (610) The leader in packaged Space Cooling.

Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health

Test Code: 8297 / Version 1

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

Dehumidification Frequently Asked Questions

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

ASME Packaged Indirect Fired Water Heater

Transcription:

1.0 GENERAL SECTION 15740 SPECIFICATION FOR HI-VELOCITY FAN COIL SYSTEMS 1.01 DESCRIPTION Item A. Scope This section specifies four sizes of fan coil units designed for hydronic heating and air conditioning. Fan coils can be installed in horizontal and vertical flow positions. B. Equipment List Table 1 - Heating BTUH 190 o F EWT 160 o F EWT Kw Electrical Strip TX Cooling BTUH H 2 0 Cooling 42ºF EWT HE-Z-50 / RPM-50 56,200 44,400 5 15 Kw 24,000 26,000 HE-Z-70 / RPM-70 79,700 62,900 5 18 Kw 36,000 37,800 HE-Z-100 / RPM-100-4 112,300 84,300 5 23 Kw 48,000 55,000 HE-Z-100 / RPM-100-5 134,000 100,700 5 23 Kw 60,000 62,900 1.02 PERFORMANCE REQUIREMENTS A. General Fan coil units specified in this section shall be designed as a closed loop hydronic fan coil system, with published BTUH ratings with entering water temperatures set between 130º and 190º F. System shall allow for heating, TX or chilled water-cooling, and heat pump applications with electric coil back-ups. Entering water temperature and BTUH outputs shall match performance listed in Table 1. B. Operating Requirements The fan coil units shall be designed, rated, and approved by CSA/UL and shall conform to applicable ASHRAE, ARI and DOE standards. C. Flow Requirements: Airflow should be minimum of 250 CFM per ton of cooling. Maximum airflow shall be 300 CFM per ton. Any proposed alternate system below 250 CFM per ton shall be up-sized to match the specified airflow and mechanical code make-up air requirements. Any alternate airflows shall be set through the Trim Pot (potentiometer) on the PSB (Pressure Sensing Board) Controller and confirmed by comprehensive airflow analysis. Minimum outlets per ton in heating mode are 3 or 4 on HE (2 3/4 Ø) outlets, and 6 8 on 2 Ø outlets. Minimum per ton in cooling mode is 4 to 5 HE (2 3/4 Ø) outlets, and 8-10 2 Ø outlets. Supply duct design pressures are sized to run between.80 and 1.5 inches static pressure. Typical HE outlet cfm is 50-65 cooling, 45-55 heating, and 25-30 on recirculation. Typical 2 outlet cfm is 25-32 cooling, 22-27 heating, and 12-15 on recirculation. Each outlet will cover between 80 to 100 square feet, depending on heat gains and losses, ventilation and fresh air requirements. See Table 2 for minimum and maximum per fan coil size. D. Electrical The fan coil control electronic circuitry shall be either 110 or 220 voltage, and 50 or 60 hertz cycles. Pre-wired printed circuit board shall allow for heating, cooling, heat pumps, and electrical strip heat, with automatic reset surge protection and fused integral system. Low voltage control circuitry to include provisions for two-stage heating and cooling, economizer operation, dehumidification and constant fan. E. Controls Fan coil operation to be controlled through the PSB (Pressure Sensing Board) Controller, the PSB with internally mounted sensors is to vary the VDC output to the VFD drive to maintain constant unit pressure output adjustable from.35 to 1.65 External Static

Pressure. Onsite adjustment of pressure for each operational selection is made by individual trim pots. The controller will also offer a manual adjustment mode to manually set the VDC for fix rate of performance. Also standard on the PSB controller is fan delay timer, potable water pump timer and Emergency Disconnect to interrupt all control power to the fan coil in event of fire. D. Motor Variable Frequency Drive to be WEG Electric CFW-10 either 110v or 220v input operating from VDC input from the PSB controller shall vary power input to the three phase induction motor. VFD Drive to have diagnostic and read out capabilities. Motor shall be capable of accepting 240/3/60 volt power without extra wiring requirements. Motor to provide operating efficiencies of not less than 75%, and airflow ranges from 300 to 1,300 CFM. Watt draws shall be available for all size fan coils and ranges. Constant fan should not exceed 55 to 75 watts for any size fan coil, should not exceed 320 watts on low heating, 510 watts on high heating, or 720 watts on high speed cooling for any size. F. Piping Sweat water connections are 1/2 Cu for the HV-50, 3/4 for the HV-70 and HV-100. All lines should be piped so as not to restrict use of the access panels, filter section, or electrical enclosure. When the potential for gravity flow of the hot water exists, check valves may be needed on both the supply and return lines. 1.03 QUALITY ASSURANCE A. Fan coil units shall be a total indoor air quality system complete with heating, cooling, air filtration, humidity control and fresh air make up. The fan coil must be factory manufactured, assembled and tested. B. References All equipment furnished under this specification shall comply with the following standards: Reference ASHRAE ARI CSA DOE UL Title American Society of Heating, Refrigerating and Air-Conditioning Engineers Air-Conditioning and Refrigeration Institute Canadian Standards Association Department of Energy Underwriters Laboratories C. Pre-qualification Fan coil manufacturer shall have a minimum five-year history in North America with successful installation and operation of fan coil units. Alternate manufacturers shall submit to the engineer the full requirements of 1.04 A-N, and demonstrate full compliance at least 72 hours prior to bid date to be considered a qualified bidder. 1.04 SUBMITTALS Submittals shall include the following: A. Airflow per ton of cooling (CFM/ton) B. Number of outlets/ton and type of adjustable dampers C. Seer ratings if not exempt, of outdoor condensing unit for A/C applications D Fan coil voltage to be either 110v or 220v and either 50/60 hertz E. Watt draws on Cooling, Heating and Recirculation shall be for each size fan coil F. Wiring diagram G. Heat calc program (or appropriate heat loss/ heat gain calculations) H. Sound test data for minimum and maximum number of outlets I. Coil approvals J. Control panel, or any controller submitted as an alternate, shall meet requirements of 2.03 B K. Unit construction, including finish coating, insulation, metal gauge L. Calculations on air passes through filter/hour to show a minimum of 1.5/hour Preferred range is 2 2.5/hour

M. Show sizing and CFM of make-up air @.35 to.50 changes/hour to meet code. N. A copy of this specification with addenda updates, and all referenced sections, with each paragraph check marked to show specification compliance (COM) or marked to show deviations (DEV) 1.05 ENVIRONMENTAL CONDITIONS Fan coils to be located indoors; however, attic, crawl space and garage conditions are fully acceptable. 2.0 PRODUCTS 2.01 ACCEPTABLE PRODUCTS Fan coils shall be manufactured by Energy Saving Products Ltd, or pre-approved equal. 2.02 MATERIALS A. Components Component Material Casing 22 Gauge Sheet Metal with white polyester powder coating Blower G-90 forward curved centrifugal PSB Controller Capable of all functions in 2.03B Variable Frequency Drive WEG Electric Corporation CFW-10 Motor (FASCO) 3/4 HP 240/3/60 hertz WM (Water Coil Module) Cu tubing, Al Fins, 20 Ga Galv Endsheets RPM (TX Cooling Module) Cu tubing, Al Fins, 16 Ga Galv Endsheets To include site-glass, TX valve, access ports and freeze stat. Factory pre-piped as standard. B. Accessories 1. Unless ordered as a blower unit only, all fan coils shall be shipped complete with heating coil, pre-wired and ready to install. 2. Chilled water or TX cooling coils to be selected by engineer. 3. Electric coil for heat pump back up shall be installed in the fan coil housing 4. HE and 2 flex kits shall include saddle taps and gaskets for supply main. 5. Rough-in boots with adjustable dampers shall be provided for each outlet. 6. Supply and return spiral metal ducts to be provided, installed, insulated (supply), and sealed by contractor. 7. Hi-velocity fan coil units require a hot water source for provision of heat distribution. A high efficiency stainless steel condensing boiler is the preferred choice due to response time and fuel efficiency. Cast iron boilers and dual-purpose hot water tanks may also be used if the engineer approves a de-rated response time and lower BTUH with a hot water tank. 8. Return air base is acoustically lined with 1/2 insulation as is the fan coil unit. 9. A filter or complete air purification package must be included with the fan coil unit. A. Energy Saving Products HE PS or approved equal shall be fully upgradeable by adding two (2) 20 watt UV germicidal lamps and photo catalytic technology for the removal of germs, viruses, bacteria, VOC s, chemicals, odors, carbon monoxide and other hydrocarbons. The photo catalytic grid shall contain a minimum of 70 square feet of titanium oxide catalyst exposure and sized to handle 1.5 to 5 tons. Unit shall be single side access and capable of upgrade without any change to the ductwork. Contractor will be responsible for any required mating transitions in the return air duct. Frame size is W: 21 x H: 25 x D: 10.25. Alternate units with by-pass systems or filters without gaskets to prevent leakage, will not be allowed due to unanticipated contaminants passing untreated and potentially fouling the coils or blower. 2.03 CONSTRUCTION

A. The fan coil shall be fabricated of white powder coated 22 Ga sheet metal with a 1 sound attenuating insulation. The blower is a forward curve fan powered by 115 or 220V energy efficient variable frequency direct drive motor. All coils will be CSA / UL approved. Units must be single side access for coil, motor, and controls access. B. Control panel shall be pre-wired with the following auxiliary control operations: o Terminal contacts for freeze-stat controller o 24V terminals for condensing unit o 24V terminals for 2 or 3 wire zone valves o Terminals for Electric strip coils o Auxiliary SPDT dry contact relay for low or line voltage o Fuseable link and surge protection with automatic reset o Potable water circuit board for circulator with timer override microchip o Fan start-up delay for heating and cooling o Selectable fan operation mode o Automatic Mode to vary VDC output to VFD drive to maintain constant unit pressure o Manual Mode to maintain constant VDC output to VFD drive to maintain fixed flow rate o Trim Pots to set Cooling Heating and Recirculation o Emergency Disconnect to interrupt control power in event of fire. 3.0 EXECUTION 3.01 INSTALLATION A. Location The fan coil unit can be located in a horizontal or vertical position, and can be suspended from the ceiling or placed directly on the floor. Location of the fan coil will vary depending on the following: length of duct runs, usable floor space, serviceability and accessibility to unit, minimizing structural changes, location of heating/cooling source, and available space in mechanical room. B. Ducting The main supply duct attached to the top of the fan coil shall be installed so there is a minimum of 18 of straight duct before a tee or elbow in used. The supply duct shall be sealed for leaks and covered with R8 insulating sleeve if duct is located in an unconditioned area, or any time when cooling is used. Selection of main plenum location shall ensure that the HE or 2 flex duct length is minimized with a maximum run length of 25 ft. Ducting layout to be matched as per the design and install manual of Energy Saving Products Ltd., or pre-approved equal. C. Ducting Return & Fresh Air Return air duct shall be sized per unit as in Table 2. At the contractor s option the duct can be square or rectangular utilizing the round equivalent. If flexible duct is used in lieu of spiral or snap-lock, up size the flex duct to be 2 larger than the specified size. For additional sound attenuation, the return air duct shall be sound lined with a 1 sound acoustic insulation, continuing at least 5 back from the unit. An outside make-up air duct should be inserted into the return air duct, preferably at least five feet from the fan coil unit. The size of the make-up air duct is typically 4 to 6 in diameter, but should be sized with the code requirements and confirmed with the engineer. Return air duct transitions to the filter or cooling coil shall be a 20 angle per side where possible, and not exceed 30 per side for proper airflow. D. Flex Duct Flex duct shall be HE 2 ¾ Ø, or 2 diameter, and insulated either R-4 or R-8 in unconditioned space. For correct airflow and sound attenuation, the standard flex lengths should be either 10 minimum or 15 runs. The effective throw of air mixing out off a flex run and factor supplied diffuser box is 18 feet. If a desired run length is less than 10, the flex duct can be coiled in the allowable space to maintain the 10 minimum. Run lengths may be extended up to a maximum length of 25, however this might cause reduced flow for those areas and an additional run should be added, or consult the factory. The flex duct

kits shall include a saddle tap complete with gasket to attach to the supply duct. Rough-in boots shall also be provided in each flex duct kit. Boots shall have an integral damper capable of fully open and close adjustments at each outlet. Standard faceplates are white plastic and able to accept paint. Directional grilles are a standard option for all faceplates. Optional faceplates can be oak, maple, bronze, brass, or brushed nickel. E. Drilled outlets and linear grills. Drilled outlets in the supply duct may be used in lieu of flex duct in high ceiling, large open area rooms with high occupancy, high vaulted ceiling or atrium type rooms, and rooms with widths over 20 feet. The potential for noise if greater with drilled outlets, and should not be used in residential applications. When calculating the number of outlets, a 1 1/4 drilled outlet is equal to one (1) 2 flex run, and a 2 drilled outlet is equal to two (2) flex runs. For cooling applications, the duct would require a minimum or (8) 1 1/4 holes or (4) 2 holes per ton. Linear grills may be used when grouping 2 or more outlets together, and should be kept a minimum of 6 on center, and within 2 of the open area grill. Contact the factory for design assistance on any applications using drilled outlets or linear grills. F. Table 2 - Units specified and duct sizing and outlet quantity Model # Supply Air & Max. Length* Return Air Min # Outlets (2 ) Max # Outlets (2 ) CFM HE-Z-50 8 Ø 70 12 14 24 550 HE-Z-70 8 Ø 80 12 20 32 750 HE-Z-100-4 10 Ø 100 14 32 42 1,100 HE-Z-100-5 10 Ø 120 16 40 52 1,250 3.03 WARRANTY A. The Heating Coil (heat exchanger), Air Conditioning Coil, Chilled Water Coil and Blower are free from defects in workmanship for one year plus a six month shelf life (18 months in total) from date of purchase. B. The VFD Motor, WEG Controller and PSB Circuit Board are free from defects in workmanship for three years plus a six month shelf life (42 months in total) from date of purchase. C. The Electric Strip Heater is free from defects in workmanship for two years plus a six month shelf life (30 months in total) from date of purchase. D. This warranty applies strictly to the first purchaser and only to the fan coil unit. It does not include connections, attachments and other products or materials furnished by the installer. This warranty excludes any damages caused by changes, relocation to, or installation in a new site. This warranty does not cover any defects caused by failure to follow the installation and operating instructions furnished with the fan coil. This warranty does not cover defects caused by failing to adhere to local building codes and following good industry standards. Failure to correctly install the fan coil, or material related to the unit, may result in improper system performance and/or damages and will void this warranty. Using the fan coil as a source of temporary heating/cooling during construction, will void this warranty. 3.04 TRAINING A factory-authorized representative will supply the fan coil owner with appropriate instructions for the recommended operation and maintenance procedures. Additional training shall be provided if necessary.