Fiber Optics TII FDH1. Indoor Fiber Distribution Cabinet



Similar documents
4RU High Density Shelf Installation Instructions

FTTX Solutions FDH 3000 Cross-Connect

Multiple Solutions for Connecting Multiple Dwelling Units (MDUs) WHITE PAPER

2178-S Fiber Optic Splice Case

4 Small Cables Sealing Kit: Wrap Style

Reliable, Consistent, Quality

HP UPS R1500 Generation 3

SYSTIMAX G2 4U Fixed Rear Access Combination Shelf Instructions

Fiber-to-the-Home/FTTH

This sale agreement is between (buyer) and William Graham (seller) of Mississauga Training Consultants. Authored by: William Graham, Owner

Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

Expanding a 40-Type Cabinet

KEYLESS ENTRY UPGRADE SECURITY SYSTEM for 2004 TOYOTA HIGHLANDER

ELECTRONICS G H I J K L M

Opticom Fiber Optic Splice Module

2003/2004/2005 TOYOTA COROLLA

AT&T. PARTNER Plus Door Phone. Installation and Operation Manual

CamSplice Assembly Manual

Cable Cubby 1200 and 1400 Installation Guide

About the BitStorm 6051 POTS Splitter

Cable Assembly Solutions at the Speed of Light

7.4 3M No Polish Connector

SC, FC and ST * Hot Melt Fiber Optic Connectors

UPDATEUPDATEUPDATE. Converting the tower chassis to a rack-mount chassis. A - M To mount outer member to rack

Pretium Connector Housings

LIEBERT VNSA Installation Sheet

StorTrends 3400 Hardware Guide for Onsite Support

CoolWave r 2 Phase Control Board and Cable Replacement Kits

Packaged Terminal Air Conditioner Wall Sleeve Installation

Intel RAID Maintenance Free Backup Unit 4 Quick Installation User's Guide

Reasons for reissue are in Section 6, REVISION SUMMARY.

UniCam High-Performance Connectors, Multimode and Single-Mode

Digital Link Cross Connect (DLx ) System User Manual

InstaPATCH ZERO Solution Guide

Installation. Smart-UPS VT MGE Galaxy Maintenance Bypass Panel kva 400 V

3M Fiber Optic Splice Closure 2178-LS Series with Gasket

Wall Mounted Products

Express5800/120Ed. Rack Mount Kit Installation Procedures PN:

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

WIRELESS STATUS MONITOR

FACT OPTICAL DISTRIBUTION FRAME SYSTEM

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications

Module Connectors and Cable Specifications

AEROMOTIVE Part # INSTALLATION INSTRUCTIONS

Belden. Optical Fiber Catalog. One Enterprise. One Infrastructure. One Partner. Belden IBDN FiberExpress Systems

FCS-FCT-FCP Housings and Connector Panels. InfiniCor SX+ OM3, InfiniCor 600 OM2, InfiniCor 300 OM1, SMF 28e OS1/OS2

EXPLORE 4-Leg Teaming Table with Screen Share Assembly Instructions

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

UNIVERSAL LUMBAR INSTALLATION INSTRUCTIONS

LANC Fibre Patch Panel Solution

GPS AutoSteer System Installation Manual

Installation Instructions

Installation Instructions

DDP-3 Engineering Guide

ASKING FOR ASSISTANCE

Secure/Keyed LC System Solutions Overview

HP 16/18-Port Cable Management Kit Installation Guide

Patch Cords for Data Center Applications

Canopy Surge. User Manual

Rack installation instructions

Cable Preparation and Pulling Procedure Best Practices for Fiber Optic Indoor Tight-Buffered Cable

RayClic Connection System Installation Instructions

Cabinets 101: Configuring A Network Or Server Cabinet

UniStream CPU-for-Panel

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Andersen Electric Window Opener for Andersen Awning and Roof Windows

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE

with installation dynafact boost GAUGE this manual is for use with systems

Mini-HDMI Series MINIATURE MULTIMODE FIBER OPTIC HDMI TRANSMISSION SYSTEM

Installation Instructions

How To Use The Visifault Visual Fault Locator

5800 Temperature Sensor Cable Assembly

ROUTER TABLE INSERT ASSEMBLY AND OPERATING INSTRUCTIONS

EZ-Steer Assisted Steering System

Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U

Instructions Fiber Optic Splice Case

FTTH ARCHITECTURE WHITE PAPER SERIES

Fiber Optic Cable Installation

15GAL STEEL OIL DRAIN WITH 110V PUMP

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

Installation Guide for Artic Air 24 Volt R134A Air Conditioner

REMOTE AUXILIARY AIR CONDITIONING SYSTEM AND AIR DISTRIBUTION

ilan Ethernet Box for 9100 Installation Manual

Cisco Aironet 2.4-GHz MIMO Wall-Mounted Omnidirectional Antenna (AIR-ANT2440NV-R)

TOYOTA TACOMA HANDS FREE BLU LOGIC Preparation

Guide To Returning Your Satellite Modem and Radio Assembly Model: HN7000S

HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install

Advantium 2 Plus Alarm

Owner s Manual & Safety Instructions

VL3000Q Spot Luminaire VL3000Q Wash Luminaire CAUTION:

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

CHARTER TOWNSHIP OF SHELBY REQUEST FOR PROPOSAL. Fiber Optic and Data Cabling Project Shelby Township Police Building

Self Purging Liquid Trap (SPLT ) User s Manual

Installation Instructions

Copper Pre-terminated Assemblies

MDU SC Connector Termination Procedure

Transcription:

TII FDH1 Fiber Optics Indoor Fiber Distribution Cabinet Fiber Optics. A Division of Tii Network Technologies Inc. 5103 Pegasus Ct., Suite H Frederick, MD 21704 Contact 888-844-4720 301-874-4688 fibersales@tiinetworktechnolgies.com 1 Tii Network Technologies Inc. 2012

Copyright 2012 Tii Network Technologies Inc. All rights reserved. Revision History ISSUE DATE REASON FOR CHANGE 1 3/2012 Original release TRADEMARK INFORMATION TII Network Technologies, Tii, Tii (Logo) and Tii Fiber Optics are trademarks. DISCLAIMER OF LIABILITY Contents herein are as of the date of publication. Tii Network Technologies Inc. (Tii) reserves the right to change the contents without prior notice. In no event shall Tii be liable resulting from the loss of data, loss of use or loss of profits and Tii further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer applies to all products, publications, and services during and after the warranty period. General Safety Precautions Warning Wet conditions increase the potential for an electric shock when installing or using electrically power equipment. To prevent shock, never install or use electrical equipment in a wet location or during a lightning storm. Danger Do not look into the ends of any optical fiber. Exposure to laser radiation may result. Do not assume the laser power is turned off or that the fiber is disconnected at the other end. Caution Always follow corporate safety practices when handing, striping and preparing fiber optic cable, fiber shards can be dangerous if they are not disposed of properly. Always wear proper safety equipment including safety glasses, gloves etc. Refer to corporate standards when in doubt. 2 Tii Network Technologies Inc. 2012

1. General 1.1. The Tii FDH1 Series is a wall mount fiber distribution hub designed to support patching, splicing and optical splitting in one unit. The enclosure has 9 adapter panel positions allowing for a wide variety of patching and splitting combinations. Two compartments separate the network terminations from the distribution terminations and a single outer door. 1.2. Accommodates 12-48 fiber ports for use in indoor demarcation points and MDU distribution applications. 1.3. Available with adapters, splice trays and pigtails. 1.4. Door is removable for easy handling and maintenance. 1.5. Multiple bottom cable entry points for ease of cable entry both top and bottom. 1.6. Two splitter module capacity. 2. Dimensions 3 Tii Network Technologies Inc. 2012

3. Warranty 3.1. See TII Warranty. If this unit fails during the warranty period, the factory should be requested to authorize return. Return the unit prepaid. Units that fail due to normal wear or abuse should be discarded. 4. All cabinet versions. 4.1. Modular LGX bulkhead adapters - for interconnection between feeder and distribution fibers. 4.2. Slack Storage - The FDH1 is designed to allow for storage of pre-terminated 12F SST drop cable inside the unit with tie-downs to secure the cable. 4.3. Output Fiber Management Provides a method of routing fibers to the LGX adapter plates. 4.4. Splitter Compartment Provides a location to mount one or two 1x32 splitters modules. Secured via Velcro straps. 4.5. Interior Grounding Lug Provides a bonding and grounding point for all dielectric fiber cables. 4.6. Entry Ports Equipped with Top and Bottom entry ports to allow for use of input/output cable configurations. 4.7. Removable Outer Door To allow for easy installation in confined spaces. Mounting Ears Slam-latch Padlock Hasp Modular LGX Adapter plates (6,8 or 12) Fiber Routing Guides FIGURE 1. Basic Layout. 4 Tii Network Technologies Inc. 2012

Top Entry Ports Fiber Slack Storage FIGURE 1a. Basic Layout 5. FDH1 Cabinet 5.1. The Tii FDH1 Series Cabinet can be configured in three (3) versions including an all patch version, a patch and splice version and a PON Version. 5.2. Figures 1 and 1a shows the general features of the FDH1. 5.3. The all patch version, shown in figures 1 & 1a, is equipped with LGX plates modular adapter plates (in 6, 8 or 12 adapters) for either24, 32 or 48 patch only configurations. This version assumes the use of pre-stubbed drops with fan-out or field installable connectors on both input and output. 5.4. The unit also is equipped with 1 single LGX modular adapter plate for pass through fiber (where applicable). 6. Patch and Splice 6.1. Shown in figure 2, is equipped with LGX plates modular adapter plates (in 6, 8 or 12 adapters) for either24, 32 or 48 patch configurations and is equipped with up to four (4) splice trays. 6.2. One (1) to accommodate the feeder fiber and three (3) to accommodate splicing of the distribution fibers. 6.3. Optionally the LGX adapters may be ordered with 6, 8 or 12 fiber pigtail assemblies, per-installed into the spice trays. The pigtails may also be purchased separately. 5 Tii Network Technologies Inc. 2012

12 Fiber Feeder- LGX Adaptor Plate 4 12 LGX adapter plates for distribution fibers Fiber Routing Guides 4 Blank LGX plates for 1x32 splitter parking lot FIGURE 2. Patch and Splice. Splice Trays FIGURE 3. Splice tray layout Multiple Entry Ports 6 Tii Network Technologies Inc. 2012

7. PON Version. 7.1. Figure 4 shows the PON version which is a 1x 32 configuration with 1 X 12 fiber pass through and 4 x 8 LGX (32) modules distribution with an additional 4 X 8 LGX (32) modules for a parking lot. Included is a 1 x 32 PON splitter. 7.2. Pigtails from the splitter are routed across the front of the inside door while the distribution fiber are either splice in the splice trays and connected via factory installed pigtails to the modules or via field installed mechanical connectors. Splitter Module Retainer FIGURE 4. PON Version 1 x 12 Feeder fiber module 4 1x 8 LGX Distribution Modules 4 1 x 8 LGX Splitter Parking Lot FIGURE 5. PON Version- Layout with labeling. 7 Tii Network Technologies Inc. 2012

8. Labeling 8.1. Depending upon configuration, the FDH 1 adapter plates will be labeled according to layout. Figure 5, shows F Designating 1-12 Feeder fibers, D designating 1-32 Distribution fibers and PL- Designating 1-32 Splitter Parking Lot. 8.2. Figure 6 shows the standard door label for the recording of Feeder and distribution fiber (Subscriber Termination Field). 8.3. The surface allows for field recording of the designated fiber and subscriber terminations. FDH Label FIGURE 6. 8 Tii Network Technologies Inc. 2012

9. Installation Guide General 9.1. Recommended Tools 9.1.1. Portable work table 9.1.2. Cleaning supplies Squeeky Kleen, alcohol, wipes 9.1.3. Jacket ring tool (or flat drop stripper) 9.1.4. Kevlar sheers 9.1.5. Buffer scribe tool 9.1.6. Strip tool 3mm, 900um, 250um 9.1.7. splice sleeves 9.1.8. Fusion splicer & cleaver set 9.1.9. OTDR, OLTS, or VFL 9.1.10. Screw gun & appropriate screws for install location (wood, metal, concrete etc.) 9.2. Summary of Steps 9.2.1. Wall mount 9.2.2. Install cables 9.2.3. Work area setup 9.2.4. Terminate 9.2.5. Patch 9.2.6. Patch & splice 9.2.7. PON splitter 9.2.8. Store slack 9.2.9. Test 9.3. Mounting 9.3.1. Install 4 x4 x¾ plywood backboard to most secure points practical using appropriate hardware 9.3.2. Concrete block 9.3.3. Brick 9.3.4. Structural studs 9.3.5. Secure FDH to backboard using provided 4 point attaching brackets using ½ wood screws typically centered or as appropriate to install site. 9 Tii Network Technologies Inc. 2012

9.4. Install Cables 9.4.1. Overall lengths will be dependent on work station location to the FDH 9.4.2. The FDH can store approximately 20 ft of feeder cable and home run MDU drops. 9.4.3. Secure cables to provided top and bottom cable entry tie down points using zip ties or hose clamps as appropriate. 9.4.4. Ground and bond any armored cable to provided ground lugs 9.4.5. Pre-measure and cut to length cables to termination points (dependent to configuration patch, patch & splice or PON). 9.5. Work Area Setup 9.5.1. Set a portable table as close to final installation site as feasible and stage items. 9.5.2. Hand tools. 9.5.3. Splicer & Cleaver (if required). 9.5.4. Cleaning supplies. 9.5.5. If configured remove pigtail from slack storage up to breakout, ensure pigtails reach workspace or remove adapter plates if necessary. 10 Tii Network Technologies Inc. 2012

9.6. Prepare Cables 9.6.1. Allow minimum 10 ft of slack cable to route into FDH (site dependent) excess to be cut off. 9.6.2. Remove jacket and armor 2 within entry point. 9.6.3. Secure drop and feeder cables to provided T clamps using zip-ties or hose clamps as appropriate. 9.6.4. Excess cable should be pre-measures and allow enough slack to reach work area and be stored neatly in FHD, cut to length needed for configuration. 9.7. Patch 9.7.1. Install each MDU home run drop cable to rear patch panel, label as required. 9.7.2. Install pre-terminated trunks or field install feeder cables front of patch panel, inactive fibers stored in parking lot. 9.7.3. Dress, route and secure feeder & MDU drops to provided cable management clips 11 Tii Network Technologies Inc. 2012

9.8. Patch & Splice 9.8.1. Prepare workspace for splicing. 9.8.2. Stage splice tray near splicer. 9.8.3. Splice each feeder fiber. 9.8.4. Place splice fiber in trays splice chip holders. 9.8.5. Dress and secure buffer and pigtails to splice tray using zip-ties. 9.8.6. Install up to 4 splice trays and store slack in provided cable management brackets. 9.8.7. Route pigtails to front side of panel, stage fibers in parking lot and secure slack using fiber management clips. 9.8.8. Activate MDU connections by moving from parking lot to MDU dwelling ports as required. 12 Tii Network Technologies Inc. 2012

9.9. Typical PON 9.9.1. Install each MDU home run drop cable to rear patch panel, label as required. 9.9.2. Top most adapter plate for feeder cable high power pass-through and splitter connections. 9.9.3. Splice feeder fiber(s), field terminate or install stub as required rear side of top adapter plate. 9.9.4. Install splitter housing to rear panel using alignment stud and Velcro. 9.9.5. Route splitter legs to front side patch panel. 9.9.6. Install splitter input (blue strand) to top adapter plate feeder cable. 9.9.7. Install splitter outputs (yellow strands) to parking lot. 9.9.8. Activate MDU connections by moving from parking lot to dwelling ports as required. 13 Tii Network Technologies Inc. 2012

9.10. Slack Storage 9.10.1. Coil buffer tube strands around splice tray and store slack in cable management brackets. 9.10.2. Secure buffer tubes and pigtails to cable management clamps using supplied Velcro and or zip-ties. 9.10.3. Secure fan-out kits. 9.10.4. Install splice tray securing grommet and wing nut. 9.10.5. Dress and secure slack cable. 9.11. Test 9.11.1. Clean and inspect any ferrule prior to mating, contamination can damage ferrule end face. 9.11.2. Typical insertion loss of factory terminated pigtails and fusion splice should be expected to be 0.25 0.5 Db. 9.11.3. Typical reflectance -55 db UPC. 9.11.4. Typical reflectance -65 db APC. 9.12. Close unit and secure. 14 Tii Network Technologies Inc. 2012