CONTROLLED SWITCHING FOR CIRCUIT BREAKERS WITH PRE-INSERTION RESISTORS ENERGIZING SHUNT CAPACITOR BANKS

Similar documents
Typical Data Requirements Data Required for Power System Evaluation

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

PROTECTION TECHNIQUE FOR TRANSIENT OVERVOLTAGE DUE TO CAPACITOR BANK SWITCHING IN DISTRIBUTION SYSTEMS USING HIGH PASS FILTER

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

DS1 Diode-based transient-free capacitor switch

Joslyn Clark Controls, Inc.

S&C Circuit-Switchers Mark VI

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

= (0.400 A) (4.80 V) = 1.92 W = (0.400 A) (7.20 V) = 2.88 W

Engineering innovation

CAPACITOR SWITCHING TRANSIENT MODELING AND ANALYSIS ON AN ELECTRICAL UTILITY DISTRIBUTION SYSTEM USING SIMULINK SOFTWARE

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

CONSIDERATION OF THE EFFECT OF PRE-INSERTION IMPEDANCES ON THE OVERVOLTAGES PRODUCED BY THE ENERGIZATION OF A SHUNT CAPACITOR BANK

Circuits. The light bulbs in the circuits below are identical. Which configuration produces more light? (a) circuit I (b) circuit II (c) both the same

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

SPECIFICATION COG-2007

Line Reactors and AC Drives

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

A Trigger Circuit for the 555 Timer IC Scope

Current Limiting Protector For Systems rated kV and continuous currents through 5000A.

Step Voltage Regulators

Hyperlinks are Inactive

STF & STF201-30

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

STATCOM Application at VELCO Essex Substation

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

Protection from Short-circuit

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

Fault Analysis I PowerWorld Corporation

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring

Lightning current simulation in the laboratory - parameters, procedures and test equipment -

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

Transistor Amplifiers

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Shunt Capacitor Bank Fundamentals and Protection


IEC ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed

High Efficiency Motor Protection. Industry White Paper

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

PowerWorld Simulator

SIMULATIONS OF PARALLEL RESONANT CIRCUIT POWER ELECTRONICS COLORADO STATE UNIVERSITY

Bourns Resistive Products

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

A Practical Guide to Dielectric Testing

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

Report to the Minister Responsible for the Qulliq Energy Corporation. Respecting:

Current Transformers

104 Practice Exam 2-3/21/02

Rule Fast Track Analysis for National Life Insurance Co.

Inrush Current. Although the concepts stated are universal, this application note was written specifically for Interpoint products.

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

How To Use Multiisim On A Computer Or A Circuit Design Suite 10.0 (Aero)

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

AP Physics Electricity and Magnetism #4 Electrical Circuits, Kirchoff s Rules

3-Channel Supervisor IC for Power Supply

Transient Recovery Voltages (TRVs) for High-Voltage Circuit Breakers Part 2

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

CAPACITOR BANK TESTING SWP

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Pennsylvania Summer Reliability

ELECTRONIC POWER SYSTEMS

City Of Ottawa High Voltage Substation Inspection, Maintenance Rev July 17 and Testing, ROPEC Page 1

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Solution Derivations for Capa #11

DC LOAD TESTING Gian Trento June 18 th, 2004

Chapter 5. Parallel Circuits ISU EE. C.Y. Lee

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System

Voltage Stability Improvement using Static Var Compensator in Power Systems

Transformers. Special transformers Reactors products

ECEN 1400, Introduction to Analog and Digital Electronics

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE Test Method for AC to DC Power Supplies

Operational Amplifier - IC 741

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.

Wiki Lab Book. This week is practice for wiki usage during the project.

Addendum #2 Contract UK-11-13

NTTG Study Plan for the Public Policy Consideration Scenario

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

The Japan Society of Mechanical Engineers C 2010

EE 242 EXPERIMENT 5: COMPUTER SIMULATION OF THREE-PHASE CIRCUITS USING PSPICE SCHEMATICS 1

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

This is a preview - click here to buy the full publication TECHNICAL REPORT

Introduction to PowerWorld Simulator: Interface and Common Tools

The design and performance of Static Var Compensators for particle accelerators

Primary-Side Transformer Protection

On/Off Controller with Debounce and

LM2704 Micropower Step-up DC/DC Converter with 550mA Peak Current Limit

EMERGENCY EGRESS LIGHTING POWER SUPPLY PART NO COMPONENT MAINTENANCE MANUAL WITH ILLUSTRATED PARTS LIST

Live Tank Circuit Breakers Application Guide

Design of a TL431-Based Controller for a Flyback Converter

New and Improved Protective Grounding-Set Tester

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Introduction. Harmonics and IEEE 519 Page 1 of 19

RLC Resonant Circuits

Radial Distribution Test Feeders

Transcription:

CONTROLLED SWITCHING FOR CIRCUIT BREAKERS WITH PRE-INSERTION RESISTORS ENERGIZING SHUNT CAPACITOR BANKS ZACH SMITH, LUKE COLLETTE, TAKASHI YONEZAWA MITSUBISHI ELECTRIC POWER PRODUCTS, INC. UNITED STATES TOMOHITO MORI, HARUHIKO KOYAMA MITSUBISHI ELECTRIC CORPORATION JAPAN

Introduction 2 Shunt capacitor switching often requires controlled closing, especially at higher voltages Closing resistors sometimes used for shunt capacitor switching at 550kV and higher This case study analyses different switching strategies using EMTP-RV and verifies that result with an in-service circuit breaker

Case study substation layout 3

Original strategy 4 Switching target originally was to initiate current near a voltage zero Improvement over no mitigation strategy Might be adequate, depending on capacitor bank, breaker design, CLR, maintenance cycle

5 Simulation of a close operation without controlled switching and closing resistors Peak inrush current through breaker = 5.1 ka.

6 Simulation of a close operation with only controlled switching Peak inrush current through breaker = 1.7 ka.

7 Simulation of a close operation with the original controlled switching target Electrical make of main contacts. Peak inrush current through breaker = 2.0 ka. Electrical make of resistor contacts.

8 Illustration of original controlled switching strategy RDDS for resistor contacts considering +/-1.0 ms mechanical scatter and +/-10% deviation RDDS for main contacts considering +/-1.0 ms mechanical scatter and +/-10% deviation Voltage across main contacts (absolute value) Pre-insertion resistor is inserted Target 14 o after voltage zero (resistor contacts). Pre-insertion resistor is bypassed Line-to-ground bus voltage Fixed time between resistor and main contact mechanical making Existing Controlled Switching Strategy: Target 14 o after voltage zero (resistor contacts).

Original switching strategy was flawed 9 Voltage on open arcing contacts is actually the voltage across the resistor, not system voltage Peak voltage is roughly 200kV due to 400Ω closing resistor Arcing contacts are electrically making at the peak voltage! What if we target arcing contact voltage zero rather than resistor contact voltage zero?

10 Illustration of proposed controlled switching strategy RDDS for resistor contacts considering +/-1.0 ms mechanical scatter and +/-10% deviation RDDS for main contacts considering +/-1.0 ms mechanical scatter and +/-10% deviation RDDS for resistor contacts RDDS for main contacts Voltage across main contacts (absolute value) Pre-insertion resistor is inserted Target 56 o after voltage zero (resistor contacts). Pre-insertion resistor is bypassed Line-to-ground bus voltage Fixed time between resistor and main contact mechanical making Proposed Controlled Switching Strategy: Target 56 o after voltage zero (resistor contacts).

11 Simulation of the proposed controlled switching strategy optimizing arcing contact inrush Electrical make of main contacts. Electrical make of resistor contacts. Peak inrush current through breaker = 0.8 ka.

Real world measurements 12 Simulations show significant improvement with the new switching target Does real data match simulations? Simulation: 2.0 ka original inrush peak 0.8 ka new inrush peak In-service measurement (average over 15 closes): 1.9 ka original inrush peak 0.7 ka new inrush peak

13 Measured closing operation with original controlled switching target Electrical make of main contacts. Peak inrush current through breaker = 1.9 ka. Electrical make of resistor contacts.

14 Measured close operation with new controlled switching target Electrical make of main contacts. Electrical make of resistor contacts. Peak inrush current through breaker = 0.7 ka.

15 Measured inrush current magnitude and prestrike duration Date PEAK INRUSH CURRENT (A) PRE-STRIKE DURATION (ms) Phase A Phase B Phase C Phase A Phase B Phase C Original Target Points 2-Feb-15 1809 1925 2042 2.1 2.1 2.1 5-Feb-15 2161 1858 1987 2.2 2.1 2.1 9-Feb-15 1907 1889 1894 2.2 2.2 2.1 10-Feb-15 1853 1842 1842 2.2 2.1 2.1 12-Feb-15 1962 2026 1819 2.1 2.2 2.2 Average = 1921 2.1 New Target Points 11-Jan-16 792 647 652 0.5 0.4 0.4 11-Jan-16 846 644 745 0.6 0.3 0.6 13-Jan-16 727 631 603 0.6 0.3 0.4 14-Jan-16 914 678 683 0.7 0.5 0.5 14-Jan-16 918 818 826 0.7 0.4 0.7 Average = 742 0.5

Conclusions 16 Simulations match measurements Inrush current peak: 1921 A 742 A Pre-strike duration: 2.1 ms 0.5 ms 96% reduction in pre-strike arc energy (using i 2 t approximation) When multiple mitigation strategies are combined, their interactions need to be considered to achieve optimal results