Detail Ref. HH-TJ-FF-01 HH-TJ-FF-02 HH-TJ-FF-03 HH-TJ-FF-04 HH-TJ-FF-05 HH-TJ-FF-22 HH-TJ-FF-06 HH-TJ-FF-07 HH-TJ-FF-08 HH-TJ-FF-09 HH-TJ-FF-10 HH-TJ-FF-11 HH-TJ-FF-12 HH-TJ-FF-13 HH-TJ-FF-23 HH-TJ-FF-14 HH-TJ-FF-15 HH-TJ-FF-16 HH-TJ-PW-17 HH-TJ-PW-18 HH-TJ-PW-19 HH-TJ-PW-20 HH-TJ-PW-21 Detail Title Full-Fill - Suspended eam nd lock Flo, Insulation bove Slab Full-Fill - Suspended In-Situ oncrete Flo, Insulation elow Slab Full-Fill - oncrete Ground earing Flo, Insulation elow Slab Full-Fill - Independent Lintel Full-Fill - Steel Lintel, Perfated ase Plate, (Insulated Soffit) Full-Fill - Steel Lintel, Open ack (no continuous base plate) Full-Fill - Sill Full-Fill - Jamb Full-Fill - Intermediate Timber Flo Within Dwelling Full-Fill - Precast oncrete Separating Flo etween Dwellings Full-Fill - Pitched Roof, Gable, Insulation t eiling Level, Ventilated Loft Full-Fill - Pitched Roof, Gable, Insulation t Rafter Level, Unventilated Rafter Void Full-Fill - Pitched Roof, Eaves, Insulation t eiling Level, Ventilated Loft Full-Fill - Pitched Roof, Eaves, Insulation t Rafter Level, Unventilated Rafter Void Full-Fill - Pitched Roof, Eaves - Insulation t Rafter Level, Unventilated Rafter Void Full-Fill - Nmal ner Full-Fill - Inverted ner Full-Fill - Party Wall etween Dwellings Party Wall Masonry, Full Fill - Suspended eam nd lock Flo, Insulation bove Slab Party Wall Masonry, Full Fill - Suspended oncrete Flo, Insulation elow Slab Party Wall Masonry, Full Fill - In-Situ oncrete Ground earing Flo, Insulation elow Slab Party Wall Masonry, Full Fill - Roof, Insulation t eiling Level, Ventilated Loft Party Wall Masonry, Full Fill - Roof, Insulation t Rafter Level, Unventilated Rafter Void 11/2014 HH-TJ-FF-22 & HH-TJ-FF-23 DDED satisfy the relevant parts of the uilding Regulations applicable Thin Joint Junction Details (full Fill) INDEX Y. DRWN Y HEKED Y N.T.S.
full fill cavity elcon thin joint blocks* to inner leaf, above dpc perimeter insulation to provide minimum resistance of 0.8m²K/W traditional mtar base course incpating dpm and dpc cavity to continue at least 215mm from top of beam dpc dpm max. 75mm screed thickness flo insulation to tightly abut wall blockwk precast beam and block flo with elcon Standard infill blocks ventilated void elcon infill blocks built into walls to have the same compressive strength as wall blocks elcon blocks and traditional mtar below ground elcon foundation blocks 11.2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED 11/2013 MX. SREED THIKNESS NOTE DDED Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0022 L Registered onstruction Details E5MFF16-21. Full Fill - Suspended eam nd lock Flo, Insulation bove Slab DRWN Y HH-TJ-FF-01 HEKED Y
full fill cavity elcon thin joint blocks* to inner leaf, above dpc traditional mtar base course incpating lapped dpm and dpc cavity to continue at least 215mm below underside of slab dpc dpm flo insulation to tightly abut wall blockwk elcon blocks and traditional mtar below ground MX. FLOOR THIKNESS NOTE 11/2014 REMOVED. L REFERENE DDED. elcon foundation blocks 09.2014 LOK FORMTS NOTE REVISED 11/2013 MX. FLOOR THIKNESS NOTE DDED Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0023 L Registered onstruction Details E5MFF28-33. Full Fill - Suspended In-Situ oncrete Flo, Insulation elow Slab DRWN Y HH-TJ-FF-02 HEKED Y
full fill cavity elcon thin joint blocks* to inner leaf, above dpc traditional mtar base course incpating lapped dpm and dpc to continue at least 215mm below underside of slab dpc perimeter insulation to provide minimum resistance of 0.8m²K/W dpm flo insulation to tightly abut wall blockwk elcon blocks and traditional mtar below ground MX. FLOOR THIKNESS NOTE 11/2014 REMOVED. L REFERENE DDED. 09.2014 LOK FORMTS NOTE REVISED 11/2013 MX. FLOOR THIKNESS NOTE DDED Y. elcon foundation blocks Jumbo lok = 630mm x 250mm see onstructive Details D0024 L Registered onstruction Details E5MFF22-27. satisfy the relevant parts of the uilding Regulations applicable DRWN Y Full Fill - oncrete Ground earing Flo, Insulation elow Slab HH-TJ-FF-03 HEKED Y
elcon thin joint blocks* to inner leaf full fill cavity minimum frame overlap 30mm external lintel internal lintel PV-U cavity closer fully insulated 11/2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0025 L Registered onstruction Details E2MFF4-6. DRWN Y Full Fill - Independent Lintel HH-TJ-FF-04 HEKED Y
elcon thin joint blocks* to inner leaf full fill cavity minimum frame overlap 30mm insulated steel lintel with perfated base plate (equivalent conductivity 30W/mK less) soffit insulation with min. resistance of 0.6m²K/W MX. LINTEL HEIGHT NOTE 11/2014 REMOVED. LINTEL SEPLTE DDED. L REFERENE DDED 09.2014 LOK FORMTS NOTE REVISED Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0026 L Registered onstruction Details E1MFF4-6. DRWN Y Full Fill - Steel Lintel, Perfated ase Plate, (Insulated Soffit) HH-TJ-FF-05 HEKED Y
ircrete blocks to inner leaf full fill cavity minimum frame overlap 30mm insulated steel lintel no continuous base plate, max steel thickness 3.0mm Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see L Registered onstruction Details E2MFF7-9. DRWN Y HH-TJ-FF-22 Nov 2014 HEKED Y Full Fill - Steel Lintel, Open ack, (no continuous base plate) 0
Jumbo lok = 630mm x 250mm minimum frame overlap 30mm full fill cavity PV-U cavity closer, fully insulated elcon thin joint blocks* to inner leaf see onstructive Details D0027 L Registered onstruction Details E3MFF4-6. DRWN Y 11/2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED satisfy the relevant parts of the uilding Regulations applicable Full Fill - Sill HH-TJ-FF-06 HEKED Y Y.
full fill cavity 300mm max. elcon thin joint blocks* to inner leaf PV-U cavity closer, fully insulated 11.2014 L NOTE DDED. minimum frame overlap 30mm 09.2014 LOK FORMTS NOTE REVISED satisfy the relevant parts of the uilding Regulations applicable Y. Jumbo lok = 630mm x 250mm see onstructive Details D0028 L Registered onstruction Details E4MFF4-6. DRWN Y Full Fill - Jamb HH-TJ-FF-07 HEKED Y
elcon thin joint blocks* to inner leaf full fill cavity Jumbo lok = 630mm x 250mm timber flo joists may be built into inner block leaf suppted on joist hangers see onstructive Details D0029 L Registered onstruction Details E6MFF4-6. DRWN Y 11.2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED satisfy the relevant parts of the uilding Regulations applicable Full Fill - Intermediate Timber Flo Within Dwelling HH-TJ-FF-08 HEKED Y Y.
full fill cavity traditional mtar base course proprietary fire stop dpm elcon thin joint blocks* to inner leaf concrete screed precast concrete plank flo ceiling void 11/2014 PROPRIETRY FIRE STOP NOTE REVISED. L NOTE DDED. 09.2014 LOK FORMTS NOTE REVISED Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0030 L Registered onstruction Details E7MFF4-6. Full Fill - Precast oncrete Separating Flo etween Dwellings DRWN Y HH-TJ-FF-09 HEKED Y
full fill cavity minimum 200mm above ceiling insulation elcon thin joint blocks* to inner leaf pack compressible insulation between last truss and wall ceiling insulation 11.2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED Jumbo lok = 630mm x 250mm see onstructive Details D0031 L Registered onstruction Details E12MFF4-6. Full Fill - Pitched Roof, Gable - Insulation t eiling Level, Ventilated Loft DRWN Y satisfy the relevant parts of the uilding Regulations applicable HH-TJ-FF-10 HEKED Y Y.
fill this void with insulation breathable roof membrane 100mm minimum proprietary fire stop if required min. 150mm rafters void fully filled with insulation insulation under rafters (optional) PROPRIETRY FIRE STOP NOTE 11.2014 REVISED. L NOTE DDED. 09.2014 LOK FORMTS NOTE REVISED full fill cavity Jumbo lok = 630mm x 250mm pack compressible insulation between last rafter and wall elcon thin joint blocks* to inner leaf see onstructive Details D0032 L Registered onstruction Details E13MFF4-6. Full Fill - Pitched Roof, Gable - Insulation t Rafter Level, Unventilated Rafter Void DRWN Y 11/2013 satisfy the relevant parts of the uilding Regulations applicable HH-TJ-FF-11 RFTERS INSULTION THIKNESS NOTE DDED HEKED Y Y.
min. 50mm insulation between wall plate and vent proprietary ventilat between rafters insulation to entirely fill eaves gap between wall insulation and ceiling insulation ventilated loft ceiling insulation between and over roof trusses full fill cavity Jumbo lok = 630mm x 250mm proprietary fire stop if required elcon thin joint blocks* inner leaf see onstructive Details D0033 L Registered onstruction Details E10MFF4-6. WLL PLTE INSULTION OVER 11/2013 NOTE MOVED Full Fill - Pitched Roof, Eaves - Insulation t eiling Level, Ventilated Loft DRWN Y PROPRIETRY FIRE STOP NOTE 11.2014 REVISED. L NOTE DDED. 09.2014 LOK FORMTS NOTE REVISED satisfy the relevant parts of the uilding Regulations applicable HH-TJ-FF-12 HEKED Y Y.
breathable roof membrane insulation to entirely fill eaves gap between and ceiling insulation 150mm min. rafters with insulation between, to sloping ceiling section insulation under rafters (optional) full fill cavity Jumbo lok = 630mm x 250mm proprietary fire stop if required elcon thin joint blocks* to inner leaf see onstructive Details D0034. RFTERS INSULTION NOW 11/2013 SHOWN S 150mm. Full Fill - Pitched Roof, Eaves - Insulation t Rafter Level, Unventilated Rafter Void DRWN Y PROPRIETRY FIRE STOP NOTE 11.2014 REVISED. 09.2014 LOK FORMTS NOTE REVISED satisfy the relevant parts of the uilding Regulations applicable HH-TJ-FF-13 HEKED Y Y.
breathable roof membrane insulation to entirely fill eaves gap between and ceiling insulation 150mm rafters with insulation of λ = 0.044W/mK between, to sloping ceiling section 50mm insulation under rafters, max λ = 0.022W/mK ircrete blocks to inner leaf full fill cavity satisfy the relevant parts of the uilding Regulations applicable Y. Jumbo lok = 630mm x 250mm see L Registered onstruction Details E11MFF4-6. Full Fill - Pitched Roof, Eaves - Insulation t Rafter Level, Unventilated Rafter Void DRWN Y HH-TJ-FF-23 Nov 2014 0 HEKED Y
full fill cavity elcon thin joint blocks* to inner leaf 11.2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0035 L Registered onstruction Details E16MFF4-6. DRWN Y Full Fill - Nmal ner HH-TJ-FF-14 HEKED Y
elcon thin joint blocks* to inner leaf 11.2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED Y. full fill cavity satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0036 L Registered onstruction Details E17MFF4-6. DRWN Y Full Fill - Inverted ner HH-TJ-FF-15 HEKED Y
cavity width min. 75mm up to 100mm max. (subject to Robust Detail requirements) 2 x 100mm thin joint leaves* to separating wall above dpc: elcon Standard (3.6N/mm²) elcon High Strength (7.3N/mm²) elcon Super Strength (8.7N/mm²) 8mm parge coat may be omitted (subject to Robust Detail requirements) full fill mineral wool cavity wall insulation, density up to 40kg/m³ elcon thin joint blocks* to inner leaf separating wall ties to be ncon Staifix HRT4 OR lan PWT4 PROPRIETRY FIRE STOP NOTE 11.2014 REVISED. L NOTE DDED. 09.2014 LOK FORMTS NOTE REVISED Y. proprietary insulated fire stop if required full fill cavity satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0037 L Registered onstruction Details E18MFF7-10. Full Fill - Party Wall etween Dwellings DRWN Y HH-TJ-FF-16 HEKED Y
cavity width min. 75mm up to 100mm max. (subject to Robust Detail requirements) separating wall ties to be ncon Staifix HRT4 OR lan PWT4 traditional mtar base course incpating dpm and dpc insulation to continue at least 215mm below top of beams dpm elcon blocks and traditional mtar below dpc ventilated void dpm 2 x 100mm thin joint leaves* to separating wall above dpc: elcon Standard (3.6N/mm²) elcon High Strength (7.3N/mm²) elcon Super Strength (8.7N/mm²) 8mm parge coat may be omitted (subject to Robust Detail requirements) full fill mineral wool cavity, density up to 40kg/m³ perimeter insulation to provide minimum resistance of 0.8m²K/W max. 75mm screed thickness flo insulation to tightly abut wall blockwk precast beam and block flo with elcon Standard infill blocks elcon infill block built into walls to have the same compressive strength as wall blocks minimum 225mm 11.2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED MX. SREED THIKNESS NOTE 11/2013 DDED elcon foundation blocks Jumbo lok = 630mm x 250mm see onstructive Details D0017 L Registered onstruction Details P1PFF1-2. DRWN Y satisfy the relevant parts of the uilding Regulations applicable Party Wall Masonry, Full Fill - Suspended eam nd lock Flo, Insulation bove Slab HH-TJ-PW-17 Nov 2012 HEKED Y Y.
, cavity width min. 75mm up to 100mm max. (subject to Robust Detail requirements) 8mm parge coat may be omitted (subject to Robust Detail Requirement) elcon blocks and traditional mtar below ground 2 x 100mm thin joint leaves* to separating wall above dpc: elcon Standard (3.6N/mm²) elcon High Strength (7.3N/mm²) elcon Super Strength (8.7N/mm²) full fill mineral wool cavity wall insulation, density up to 40kg/m³ separating wall ties to be ncon Staifix HRT4 lan PWT4 traditional mtar base course incpating lapped dpm and dpc dpm dpm flo insulation to tightly abut wall blockwk insulation to continue at least 215mm below underside of slab MX. FLOOR THIKNESS NOTE 11/2014 REMOVED. L REFERENE DDED. 09.2014 LOK FORMTS NOTE REVISED MX. FLOOR THIKNESS NOTE 11/2013 DDED elcon foundation blocks Jumbo lok = 630mm x 250mm see onstructive Details D0018 L Registered onstruction Details P1PFF3-4. DRWN Y Party Wall Masonry, Full Fill - Suspended oncrete Flo, Insulation elow Slab HH-TJ-PW-18 Nov 2012 satisfy the relevant parts of the uilding Regulations applicable HEKED Y Y.
cavity width min. 75mm up to 100mm max. (subject to Robust Detail requirements) 8mm parge coat may be omitted (subject to Robust Detail Requirement) 2 x 100mm thin joint leaves* to separating wall above dpc: elcon Standard (3.6N/mm²) elcon High Strength (7.3N/mm²) elcon Super Strength (8.7N/mm²) separating wall ties to be ncon Staifix HRT4 lan PWT4 traditional mtar base course incpating lapped dpm and dpc elcon blocks and traditional mtar below ground full fill mineral wool cavity wall insulation, density up to 40kg/m³ perimeter insulation to provide minimum resistance of 0.8m²K/W dpm dpm flo insulation to tightly abut wall blockwk insulation to continue at least 215mm below underside of slab MX. FLOOR THIKNESS NOTE 11/2014 REMOVED. L REFERENE DDED. 09.2014 LOK FORMTS NOTE REVISED 11/2013 MX. FLOOR THIKNESS NOTE DDED Y. satisfy the relevant parts of the uilding Regulations applicable elcon foundation blocks Jumbo lok = 630mm x 250mm see onstructive Details D0019 L Registered onstruction Details P1PFF5-6. Party Wall Masonry, Full Fill - In-situ oncrete Ground earing Flo, Insulation elow Slab DRWN Y HH-TJ-PW-19 Nov 2012 HEKED Y
cavity width min. 75mm up to 100mm max. (subject to Robust Detail requirements) 2 x 100mm thin joint leaves* to separating wall above dpc: elcon Standard (3.6N/mm²) elcon High Strength (7.3N/mm²) elcon Super Strength (8.7N/mm²) separating wall ties to be ncon Staifix HRT4 lan PWT4 minimum 200mm wall insulation above ceiling insulation pack compressible insulation between last rafter and wall ceiling insulation 8mm parge coat may be omitted (subject to Robust Detail requirements) full fill mineral wool cavity, density up to 40kg/m³ 11.2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0020 L Registered onstruction Details P4PFF1-2. DRWN Y Party Wall Masonry, Full Fill - Roof, Insulated t eiling Level, Ventilated Loft HH-TJ-PW-20 Nov 2012 HEKED Y
minimum 100mm insulation breathable roof membrane insulation under rafters (optional) separating wall ties to be ncon Staifix HRT4 lan PWT4 2 x 100mm thin joint leaves* to separating wall: elcon Standard (3.6N/mm²) elcon High Strength (7.3N/mm²) elcon Super Strength (8.7N/mm²) cavity width min. 75mm, up to 100mm max. (subject to Robust Detail requirements) min. 150mm rafters void fully filled with insulation with max. λ = 0.040W/mK pack compressible insulation between last rafter and wall 8mm parge coat may be omitted (subject to Robust Detail requirements) full fill mineral wool cavity, density up to 40kg/m³ RFTERS INSULTION THIKNESS 11/2013 NOTE DDED 11.2014 L NOTE DDED 09.2014 LOK FORMTS NOTE REVISED Y. satisfy the relevant parts of the uilding Regulations applicable Jumbo lok = 630mm x 250mm see onstructive Details D0021 L Registered onstruction Details P5PFF1-2. DRWN Y Party Wall Masonry, Full Fill - Roof, Insulated t Rafter Level, Unventilated Rafter Void HH-TJ-PW-21 Nov 2012 HEKED Y