Generator Differential Relay Electrical Apparatus

Similar documents
Eaton s E-Series protective relay family

Sentron Series Circuit Breakers

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

E-Series protective relay family

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Disturbance Recoder SPCR 8C27. Product Guide

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

ABB PSPS Erich Steinmann; Generator control-2013

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

*.ppt 11/2/ :48 PM 1

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

Voltage Regulator SPAU 341 C. Product Guide

Back-UPS Pro 1300/1500 Installation and Operation

Type SA-1 Generator Differential Relay

EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

GE Protection and Control Business Department. Page 1 Date 5/11/99

Current and voltage measuring relays

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Multi-Range Programmable DC Power Supplies 9115 Series

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Multi-Range Programmable DC Power Supplies 9115 Series

EnerVista TM Viewpoint Monitoring v7.10

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

CSDPR. Multi Powered Over-Current Relay

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

BLOCK OCCUPANCY DETECTOR WITH SEMAPHORE OPERATION BOD1/DAP4-BR

GPD 506/P5 Start-up Procedure and Checklist

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

ELR: ABB range of front panel residual current relays Protection device according to IEC/EN Annex M

Everything you need for protection scheme testing

POINTS POSITION INDICATOR PPI4

Mini Effect Gizmo. User s Manual. RJM Music Technology, Inc.

Numerical transformer protection in medium voltage networks Transformer Protection and Control RET620

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Installation and Operation Back-UPS 1250, 1300, 1500

Nu-Lec Training Modules

NC-12 Modbus Application

Programming Logic controllers

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

Capacitor Protection Relay SPAJ 160 C. Product Guide

Section TELEPHONE AUTOMATIC DIALER SYSTEM

Digital multimeters DMG

Phase Modular Finally the benefits of Modular ups are for all

Test & Data Management Software

Stop Alert Flasher with G-Force sensor

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification

Pilot-wire differential relay for lines with two or more terminals

Belimo Gateway MP to Modbus RTU - UK24MOD

Solid State Timers Type F

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TDMS Test & Data Management Software

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

Operation and Installation Manual

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

32VFD Variable Frequency Drives for Centrifugal Chillers

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date Rev.

Impact of Leading Power Factor on Data Center Generator Systems

THERMAL MANAGEMENT SOLUTIONS

... Electronic Softstarter...

Pump_PT580. Optional. Optional. Modbus. Remote Reset Local Display PLC/DCS PT580-CFG PCM370 DTM96. Buffered Output. Dual Relay Output.

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Keep it Simple Timing

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

White Paper Mervin Savostianik P. Eng. Littelfuse, Inc.

Meritor WABCO Pneumatic Antilock Braking System (ABS) 42.22

Product Guide. Low voltage grounding system. Answers for industry.

PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

FP-4000 Feeder Protection

INSTALLATION & SERVICE MANUAL. Display Panel

Features, Benefits, and Operation

Mini Amp Gizmo. User s Manual. RJM Music Technology, Inc.

NEWTECH PRO KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

Quick Connect. quick - simple - efficient.

Device Support in PowerLogic ION Enterprise 5.6 Service Pack 2

ABB Power T&D Company Inc. Power Automation and Protection Division Coral Springs, FL 33065

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, (210) 16 (407) 5.5 (140) (283) 16 (407) 5.5 (140)

T Substation Maintenance and Commissioning Test Equipment

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February FA-300 SERIES Fire Alarm Control Panel

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Tamura Closed Loop Hall Effect Current Sensors

Transcription:

Generator Differential Relay Electrical Apparatus MD3G Rotating Machine Differential Relay 150-3 The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following functions: Differential elements (87G) for each phase with multi-slope bias characteristics and selectable slope breakpoint. Trip response time of less than cycles. The MD3G is suitable for protecting generators or other rotating machines. Phase overcurrent for stator protection (51P). Restricted ground fault element. stantaneous and low set ground fault protection. Depending upon the input circuit configuration, either stator ground fault (51GN) or sensitive ground fault (87N) protective functions may be implemented. Breaker fail (50BF). 16 cycle oscillographic records of trip events. An oscillographic record may also be triggered externally. The MD3G also shares the following features common to all Edison relays: Simple five button man machine interface (MMI) allows access to all functions, settings, and stored data without the need for a computer. Bright electroluminescent display easily visible even in brightly lit environments. Figure 1. Front View of the MD3G Generator Differential Relay Draw-out design permits relay testing without disturbing connections to case. Modbus communication protocol and RS485 terminal on rear. Modular design allows the draw-out module to be fitted to a variety of space saving cabinet styles. Three programmable Form C (SPDT) output contacts and one Form A/B contact. Pick-up (start-time) elements. Programmable reset characteristics. Dedicated power supply/relay fail output contacts. Applications The MD3G is ideally suited for the protection of generators and large motors against two or three phase internal faults, inter-turn faults, and ground faults in equipment with low-impedance or solidly grounded neutrals. Its multi-slope percentage bias characteristic allows for compensation of CT ratio error mismatch and differences in CT response. For autotransformer-started motors, some differential protection schemes include the autotransformer in the zone of protection. this case rotating machine differential relays such as the MD3G are not suitable as the nd and 5th harmonic restraint functions common to transformer differential relays are required. For this application, the MD3T relay should be used. August 1997 New Issue Printed in USA 1

MD3G Rotating Maching Differential Relay R% Id = 100 = 100 I R (I 1 -I ) (I 1 -I )/ Is/ 4 1 Is = I7 8 0. 0.1 1 I R 3 Id I R Id 3 4 Is = Is = Is I d I d 8 + ( + I R 0.5) (P-0.5)1R% 100 1R% 100 + ( I R -P) 1 Id/ 0 0.5 1 P 3 Is= Effective relay s operation differential current Id= Relay s setting differential current IR Figure. Dual Slope Bias Characteristic of the MD3G Differential Relay Multi-slope Biased Differential Element Each phase is provided with its own differential element having a characteristic as shown in Figure. The relay internally calculates the RMS value of the differential current compensated for any CT ratio and phase angle mismatch. The minimum differential current required for operation is adjustable between 0.0 and 0. pu of the machine s rated current. This setting is fixed up to 0.5 pu of the machine s rated current. Above 0.5 pu compensation of the set point is required for CT saturation which may occur at higher current levels. The slope of each of the two sloping portions of the characteristic are adjustable, as is the breakpoint between the two slopes. The first slope may be adjusted from % to 0%, and applies from 0.5 pu of the machine s rated current, up to the breakpoint, which may be set from 1 to 3 pu. Above the setpoint the slope of the differential element is adjustable between 5% and 50%. Overcurrent Protection A single definite time delay phase overcurrent element is provided to act as overload backup protection. Ground Fault Protection To provide greater coverage for ground faults, the MD3G monitors the fundamental frequency component of current fed into the ground element inputs. Depending upon the connection, this element can perform: Sensitive ground fault protection (87GN). Neutral current protection (stator ground fault) (51N). The 87GN connection is suitable for large generators, or for situations where a number of smaller generators are connected in parallel through a common step up transformer. This connection (shown in Figure 3) allows for very sensitive settings to be made and restricts the element to operate within the zone of the differential element. This ground fault element consists of a definite time high set element. Breaker Fail A programmable time delay is set equal to the breaker clearing time. If the fault is not cleared (i.e., the trip element has not dropped out), before this timer expires, a breaker fail is indicated. The breaker fail element may also be programmed to monitor any combination (or none) of the following elements; differential, phase overcurrent, or ground fault. The breaker fail function may be assigned to operate one or more of the output relays.

150-3 Targets Eight bright LED targets are provided as follows: One red LED for each of the three phase differential elements. One red LED for the restricted ground fault element. One red LED for the breaker fail element. One red LED for the phase overcurrent element. For all of the above, the LEDs flash when the element is picked up, and constantly illuminate upon trip. addition, one yellow LED is provided which illuminates when the blocking input is active. A second yellow LED flashes when the relay is in programming mode, and illuminates constantly upon relay or power supply failure. Blocking put An opto-isolated programmable blocking input is provided. This input may be programmed so that when activated, any combination of the differential, phase overcurrent, or ground fault elements may be blocked. While the blocking input is active, the pickup of any element associated with the blocking input is prevented. Sensing of the input quantities and the countdown of any timers begins only when the blocking is removed. Reset Characteristic The programmable output relays may be programmed to reset in one of two manners. stantaneously upon the input or calculated quantities dropping below the pickup value. Manual reset (by front panel or computer command) only. Measurements and rush Values The following quantities are continuously monitored and are available for display at the relay and are accessible by software: RMS values of each phase s differential current. Fundamental frequency component of the neutral current in per unit of the rated phase current. RMS values of the three high side currents. RMS values of the three low side currents. addition, the maximum values of each of these quantities during the first 100 msec after transformer energization is also recorded. This makes it convenient to quickly review the inrush currents associated with the most recent energization. Last Trip Record The following parameters are stored in non-volatile memory, providing details of the last five trip events: Which element was the cause of the last trip. The values of all measured currents at the time of trip. addition, the relays keep a cumulative total of the cause of all breaker trips. Oscillography The MD3G stores two oscillographic records which are made available for downloading to a PC for graphing. All six input phase currents are recorded. Each oscillographic record consists of 8 pre-trigger and 8 post-trigger cycles, for a total of 16 cycles. The waveform is sampled at 1 samples per cycle. Storage of an oscillographic record may be programmed to occur automatically every time a protective element trips, or to occur only upon an external trigger. Output Elements The following functions may be programmed to one or more of the output relays. The only limitation is that pick-up and time delay functions may not be assigned to operate the same output relay(s). Differential element. Phase overcurrent pickup element. Phase overcurrent time delayed element. Ground fault pickup element. Ground fault time delayed element. Breaker fail element. Diagnostics Complete memory and circuit diagnostics are run upon powering the relay. The revision level of the firmware is displayed at this time. The relay runs a comprehensive set of diagnostics every 15 minutes that includes memory checksum, test of the A/D converters by injection of an internally generated reference voltage, and a check of the ALU. The relay provides two manual test routines which may be run at any time. The first routine performs the same 15 minute test and in addition checks the target LEDs and the control circuitry to the output relays without operating the output relays. The second test is identical but also operates the output relays. Dimensions and Electrical Specifications See Catalog Section 150-05 for electrical specifications and dimensional information on all Edison relays. 3

Figure 3. Wiring Diagram for the MD3G Rotating Machine Differential Relay used for 87G and 87GN Protection 4

150-3 Figure 4. Wiring Diagram for the MD3G Rotating Machine Differential Relay used for 87G and 51N Protection 5

MD3G Rotating Maching Differential Relay TABLE 1 Functional Specifications Nominal system frequency setting range...50 or 60 Hz Programmable rated primary input current of phase CTs...1-9999A in 1A steps Breaker fail (50BF) time delay...0.05 to 1.00 seconds in 0.01 second steps Differential Element (87G) Minimum pick-up level of low set differential element...0.0 to 0.0 pu of rated CT current in 0.01 pu steps Bias percentage slope from 0.5 pu to P pu of rated CT current... - 0% in 1% steps Bias percentage slope at greater than P pu of rated CT current...5-50% in 1% steps Bias slope break point P...1.00 to 3.00 pu of rated CT current in 0.01 pu steps Overcurrent Element (51P) Minimum pick-up level...0.50 to 10.00 pu of rated CT current in 0.01 pu steps Time delay...0.05 to 99.00 seconds in 0.01 second steps Ground Fault Element Minimum pick-up level...0.01 to 1.00 pu of rated CT current in 0.01 pu steps Time delay...0.0 to 9.99 seconds in 0.01 second steps Ordering formation Construct catalog number from Table. Example: MD3GL5JS is an MD3G with low range power supply, 5A CT inputs, in a single relay case. If ordering two or more relays to be fit in a common case, the first relay ordered should indicate the case style desired. This relay will be located in the leftmost bay of the case. Subsequent relays should use the C, C3, or C4 suffixes to denote their position in the case using the leftmost bay as a C1 reference. TABLE Catalog Numbers Description Catalog Number Base Relay MD3G To the above add one each of the following applicable suffixes Power Supply 1 4-110V AC/DC L 90-0V AC/DC H Rated CT put 1A 1 5A 5 Modbus Protocol J Case Style Draw out relay only, no cabinet supplied D Single relay case S Double relay case T 19" Rack mount cabinet N Mounting Position Denotes mounting position in either a double C case or 19" Rack along with other relays C3 ordered at the same time. C4 1 The power supplies are user replaceable and interchangeable. See Catalog section 150-99. The relay itself may be drawn out of any of the listed cases and plugged into any of the other case styles. The catalog number specified during ordering denotes the type of cabinet in which the relay will be shipped. 1997 Cooper Power Systems, c. Edison is a registered trademark of Cooper dustries, c. P.O. Box 1640, Waukesha, WI 53187 http://www.cooperpower.com/ Printed on Recycled Paper