Protects against unwanted thermostat controller tampering. Increases occupancy comfort by providing dehumidification.

Similar documents
English plain text messages with constant backlight that brightens during user interaction. On/Off, Floating, or Proportional 0 to 10 VDC Control

T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers

TEC22x1-3 LONWORKS Networked Single Stage Thermostats

CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter

TEC Series BACnet MS/TP Network Temperature and Humidity Controllers

T600MEP-4 and T600MEP-4+PIR Multi-Stage Economizer Thermostat Controllers

TEC and TEC PIR Single-Stage Wireless Thermostat Controllers

TEC and TEC PIR BACnet MS/TP Networked Heat Pump Thermostat Controllers

T5000 T000 LCD Digital Fan Coil Thermostat

Installation Instructions. Applications. North American Emissions Compliance. Installation

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

FX07 Field Controller

TEC2664Z-3 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Part No , Rev.

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators

FX07 Field Controller

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack

Electronic Control Devices The European Product Catalogue 2007

Communicating Thermostats. Add More Flexibility to Building Automation with New. Communicating Thermostats

Electronic Control Devices The European Product Catalogue 2007

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

Variable Air Volume - VAV

HE-6800 Series Humidity Transmitters with Temperature Sensor

TC-9102 Series Surface Mount Temperature Controllers

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

Network Control Engine Product Bulletin

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued April 17, 2015

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

System 350 A350E Electronic Cooling Control

HVAC and Lighting Control Products for Open Building Automation Systems

Duct Humidity Transmitter

T7560A,B,C Digital Wall Module

HEAT HEAT COOL HEAT PUMP COOL

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

Controls for fan coil units and cassettes

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Thermostat with display

TB7600 Series Communicating RTU Thermostats with Humidity Control

FX16 Master Controller

HP-1000E v2. User s Manual. Powerline Ethernet Adapter. HP1000E v2 User s Manual

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

TR21, TR22, TR23, and TR24 Wall Modules

Smart Thermostat page 1

Communicating Wall Control Installation Manual TSTAT0101SC

3466 Building Energy Management Training Systems

STERILIZERS, LABORATORY DRYING OVENS

AXIS T81B22 DC 30W Midspan

Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities.

Workshop 7 PC Software - Tracker

INSTALLER S & OWNER S MANUAL

Product Catalog BAS-PRC010-E4. Tracker Version 12 Building Automation System. August 2010

T-4000 Series Pneumatic Room Thermostats

AquaTrend Interface. Model AquaTrend Model AquaTrend/SOM Model51400 PortableAquaTrend. Instrument Manual. Catalog Number

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

Installation Instructions

Multi-Range Programmable DC Power Supplies 9115 Series

Product Catalog. Small Building Systems.

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March Emerson Electric Co. All rights reserved.

A99B Series Temperature Sensors

TAC I/NETTM MR-AHU-HP. Application Specific Controller

ABB i-bus KNX Fan Coil Controller FC/S 1.1

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control

Model: DC-A2IO Advanced HVAC Controller

T-100-R Installation Guide

RDY2000 Commercial Room Thermostat

SINGLE MODE FIBER OPTIC A/B SWITCH (LATCHING)

DT92 WIRELESS DIGITAL ROOM THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

Inwall Room Temperature Unit

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

P66 Series Electronic Fan Speed Controls

FX-PCA Advanced Application Programmable Controller Catalog Page

T6570, T8570 Series Digital Fan-Coil Thermostats

T7079A,B Solid State Remote Temperature Controllers

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:

HMI display Installation Guide

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Dielectric Withstand and Ground Bond Testers For Production Line Safety Agency Compliance Testing

What s the Difference? 2 Pipe vs 4 Pipe Fan Coil

FIBER OPTIC A/B/C SWITCH (Latching)

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION SECURITY AND ACCESS CONTROL SYSTEM

RRV934. Multi-controller. Synco living

Commercial Refrigeration Temperature and Defrost Controls

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

Wireless Thermostats 230v and Battery Operated Instruction Manual

DC Electronic Loads 8500 series

MCR1900 Media Converter 19-Slot Chassis

Triple Expansion Chassis

OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada

CM702 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

Multi-Range Programmable DC Power Supplies 9115 Series

Flush-mounted room thermostats

Modular Room Control (MRC) Series Digital Thermostat

EBDSPIR-PRM, EBDSPIR-PRM-IP

Table of Contents. 1 - Specifications Installation Wiring User controls...7

Model VHD-2 VGA to TV / HDTV Scan Converter With Composite, S-Video, and Component (YPbPr) Outputs Linear Pan and Zoom

Transcription:

TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin Code No. LIT-12011607 Issued February 8, 2010 Thermostat Controllers are LONWORKS network devices that provide control of two- or four-pipe fan coils, cabinet unit heaters, or other equipment using on/off, floating, or proportional 0 to 10 VDC control input, three speeds of fan control, and dehumidification capability. The TEC22x6H-4+PIR Series Thermostat Controllers have occupancy sensing capability built into the device. These devices maximize up to 30% energy savings in high-energy usage light commercial buildings, such as schools and hotels, during occupied times by using additional standby setpoints. The technologically advanced TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers feature a Building Automation System (BAS) LONWORKS Network communication capability that enables remote monitoring and programming for efficient space temperature control. Specific models are available to accommodate commercial and hospitality applications. Table 1: Features and Benefits Feature LONWORKS Network Communication Onboard Occupancy Sensor (Passive Infrared [PIR] Models) Password Protection Option Integral Humidity Sensing Capability (Dehumidification Models) Backlit Liquid Crystal Display (LCD) On/Off, Floating, or Proportional 0to10 VDC Control Three Speeds of Fan Control Single/Dual Setpoint Adjustment Benefit Figure 1: TEC22x6-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers Thermostat Controllers feature an intuitive User Interface (UI) with backlit display that makes setup and operation quick and easy. The thermostat controllers also employ a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostat controllers. Provides compatibility with a proven communication network; LONWORKS network is widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers. Provides energy savings without additional installation time and cost. Protects against unwanted thermostat controller tampering. Increases occupancy comfort by providing dehumidification. Offers real-time control status of the environment in easy-to-read, English plain text messages with constant backlight that brightens during user interaction. Offers additional application flexibility by providing more advanced control signals. Provides easy FAN speed selection via interface key, to meet the application requirements. Enables user setpoint options to accommodate application. TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin 1

Table 1: Features and Benefits Feature Override Interface Key (Commercial Models) Temperature Scale Selector (Hospitality Models) Two Configurable Binary Inputs Over 20 Configurable Parameters Optional Discharge Air Sensor Benefit Allows easy access for temporarily overriding the unoccupied mode. Offers guests the ability to select a Fahrenheit ( F) or Celsius ( C) temperature scale display. Provide additional inputs for advanced functions such as remote night setback, service or filter alarms, motion detector, and window status. Enable the thermostat controller to adapt to any application, allowing installer parameter access without opening the thermostat controller cover. Monitors unit efficiency. Product Overview Thermostat Controllers are specifically designed for networked control of common two- or four-pipe heating and cooling equipment using on/off, floating, or proportional 0 to 10 VDC control. The TEC22x6H-4+PIR Series Thermostat Controllers have additional occupancy sensing capability built into the device, which uses additional standby setpoints to maximize energy savings in high-energy usage light commercial buildings during occupied times. In addition to superior temperature control, occupancy sensing, and application flexibility, the TEC22x6(H)-4 and TEC22x6H-4+PIR Series feature LONWORKS Network communication capability, allowing the user to view operation or make adjustments from a remote workstation. Plain text menus, backlit display, and five interface keys make setup and operation quick and easy. IMPORTANT: The TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat controller. Additional Features Thermostat Controllers offer many other features, including: Adjustable Heating/Cooling Deadband Adjusts the minimum heating/cooling deadband from 2.0F /1.0C to 5.0F /2.5C. Adjustable Time Delay for Activating Unoccupied Setpoints Allows the user to adjust time delay before unoccupied setpoints are enabled to maintain comfort temperatures while conserving energy. Occupancy Sensing in Conjunction with Door Switch Toggle Adds more efficiency by associating the door switch into the sequence of operation. Remote Indoor Sensing Accommodates remote indoor sensors. Up to three indoor sensors can be averaged. Five Easy-to-Use Interface Keys Allow for easy commissioning of the thermostat controller, and eliminates the need for DIP switches. Six Levels of Keypad Lockout Provide six levels of keypad lockout that can be set up through the Installer Configuration Menu. Accessible Configuration Parameters Allow local access to all configurable parameters while limiting unwanted parameter tampering once the thermostat controller is set up. Three Light-Emitting Diodes (LEDs) Provide fan, heating, and cooling status at a glance. Adjustable Temporary Occupancy Time Adjusts the temporary occupancy time from 0to24hours. 2

Auxiliary Contact Provides 24 VAC control for reheat, lighting, and other auxiliary functions. Adjustable Heating/Cooling Cycles per Hour (On/Off Control) Configurable for the maximum number of heating and cooling cycles (3 to 8 cycles maximum) in a 1-hour period, balancing temperature control and equipment cycling. Table 2: Thermostat Controller Models Code Number Control Outputs Onboard Occupancy Sensor Nonvolatile Electrically Erasable Programmable Read-Only Memory (EEPROM) Prevents loss of adjusted parameters during a power failure. Remote Access Allowstheusertoread/writeandaccessthe parameters of the thermostat controller via a supervisory controller or LONWORKS configuration tool. Dehumidification Capability Application TEC2216-4 Two On/Off No No Commercial Market TEC2216H-4 Two On/Off No No Hospitality Market TEC2216H-4+PIR Two On/Off Yes No Hospitality Market TEC2226-4 Two On/Off or Floating No No Commercial Market TEC2226H-4 Two On/Off or Floating No No Hospitality Market TEC2226H-4+PIR Two On/Off or Floating Yes No Hospitality Market TEC2236-4 Two On/Off or Floating No Yes Commercial Market TEC2236H-4 Two On/Off or Floating No Yes Hospitality Market TEC2236H-4+PIR Two On/Off or Floating Yes Yes Hospitality Market TEC2246-4 Two Proportional 0 to 10 VDC No No Commercial Market TEC2246H-4 Two Proportional 0 to 10 VDC No No Hospitality Market TEC2246H-4+PIR Two Proportional 0 to 10 VDC Yes No Hospitality Market TEC2256-4 Two Proportional 0 to 10 VDC No Yes Commercial Market TEC2256H-4 Two Proportional 0 to 10 VDC No Yes Hospitality Market TEC2256H-4+PIR Two Proportional 0 to 10 VDC Yes Yes Hospitality Market Table 3: Accessories (Order Separately) Code Number Description SEN-600-1 Remote Indoor Air Temperature Sensor TE-6361M-1 1 Duct Mount Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TE-636S-1 Strap-Mount Temperature Sensor TEC-6-PIR 2 Commercial Fan Coil Cover with Occupancy Sensor TEC-6H-PIR 2 Hospitality Fan Coil Controller Cover with Occupancy Sensor 1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details. 2. The TEC-6-PIR and TEC-6H-PIR Accessory Covers can be used to replace the existing cover on a non-pir TEC22x6(H)-4 Series Thermostat Controller to provide occupancy sensing capability. 3

PIR motion detector saves energy using standby setpoints. Status LED beneath cover indicates network status. Backlit, plain text Liquid Crystal Display (LCD) is easy to read in any condition. Room Temp 70.0ºF C F Light-Emitting Diodes (LEDs) indicate system activity. Five keys on the thermostat controller make operation easy and intuitive. Figure 2: Front Cover of Thermostat Controller (TEC22x6H-4+PIR Model Shown) FIG:TEC22x6H+PIR_frntvw Thermostat Controller User Interface Keys Thermostat Controllers UI consists of five keys on the front cover (Figure 2). The function of each key is as follows: MODE key toggles among the system modes available, as defined by selecting the appropriate operation sequence in the Installer Configuration Menu (Off, Heat, Cool, Auto). FAN key toggles among the fan modes available, as defined by selecting the appropriate fan menu options defined in the Installer Configuration Menu (Low, Med, High, Auto). OVERRIDE key (commercial models) overrides the unoccupied mode to occupied at the local user interface for the specified TOccTime. (TOccTime is defined by selecting the appropriate time period in the Installer Configuration Menu.) If one of the binary inputs is configured to operate as a remote override contact, this OVERRIDE function is disabled. The OVERRIDE key also allows access to the Installer Configuration Menu. (See the Installer Configuration Menu section.) C/ F key (hospitality models) changes the temperature scale to either Celsius or Fahrenheit and allows access to the Installer Configuration Menu. (See the Installer Configuration Menu section.) Note: For hospitality models, binary inputs can override from the unoccupied mode to occupied mode. UP/DOWN arrow keys change the configuration parameters and activate a setpoint adjustment. Backlit LCD Thermostat Controllers include a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens when any user interface key is pressed. The backlight returns to low level when the thermostat controller is left unattended for 45 seconds. LEDs Three LEDs are included to indicate the fan status, call for heat, or call for cooling: The fan LED is on when the fan is on. The heat LED is on when heating is on. The cool LED is on when cooling is on. Integrated PIR Sensor TEC22x6H-4+PIR Series Thermostat Controllers The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Stand-By temperature setpoints without user interaction. This feature generates incremental energy savings during scheduled occupied periods while the space is unoccupied. 4

4-15/16 (125) 4-15/16 (125) Room Temp 70.0ºF Room Temp 70.0ºF C F C F 3-3/8 (86) 3-3/8 (86) 1-1/8 (29) 1-3/8 (36) FIG:dmnsns_tec22x6 Figure 3: Thermostat Controller Dimensions, in. (mm) (TEC22x6H-4 and TEC22x6H-4+PIR Models Shown) Menu Overview Two menus are available to view and configure the TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers: Status Display Menu Installer Configuration Menu The following sections outline the functions and contents of each menu. Status Display Menu The Status Display Menu is displayed during normal thermostat controller operation. This menu continuously scrolls through the following parameters: Room Temperature (All Models) and Humidity (TEC2236 and TEC2256 Models) System Mode Occupancy Status (Occupied/Unoccupied/ Override) Applicable Alarms (The backlight lights up as an alarm condition is displayed.) Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter. Status LED The status LED shows the operational status of the thermostat controller. See Table 4. The Status LED is a small green light under the thermostat controller cover (under the LONWORKS daughter board on the left edge when facing the thermostat controller). Table 4: Status LED Explanation Status LED Explanation Condition Continuously On Flashing at a 0.5 Hz Rate Continuously Off The thermostat controller does not have an application loaded in its memory. The thermostat controller has an application loaded in its memory but is not configured. Use a LONWORKS network management tool to bind the thermostat controller to a LONWORKS network. The thermostat controller has an application loaded in its memory and is bound to a LONWORKS network. Installer Configuration Menu The Installer Configuration Menu is used to set up the thermostat controller for an application-specific operation. To access the menu, press and hold the center key for approximately 8 seconds. Note: If the Password parameter is configured, the configured password is required to proceed. 5

The Installer Configuration Menu includes the following parameters that are accessed by pressing the same center key: Password Protection BI1 and BI2 Input Configuration UI3 Input Configuration to Locally Monitor Supply Air Temperature or Hot/Cold Water Changeover Switching Menu Scroll Auto Mode F and C Temperature Scales % RH Display (Dehumidification Models) Six Keypad Lockout Levels Pipe No. Control Type for TEC2226 and TEC2236 Models (On/Off or Floating) Sequence of Operation Fan Menu Dehumidification Network Lockout (Dehumidification Models) Dehumidification Setpoint (Dehumidification Models) Dehumidification Hysteresis (Dehumidification Models) Maximum Dehumidification Cooling Output (Dehumidification Models) Standby Setpoint Timer Value Unoccupied Timer Value Technical Specifications Standby Heating Setpoint/Standby Cooling Setpoint Unoccupied Heating Setpoint/Unoccupied Cooling Setpoint Maximum Heating Setpoint/Minimum Cooling Setpoint Proportional Band Adjustment Setpoint Type Single/Dual Setpoint Adjustment Temporary Occupancy Time Heating/Cooling Deadband Room Air Temperature Calibration Room Humidity Calibration (Dehumidification Models) Auxiliary Configuration Auto Fan Mode Floating Time (Floating Models) Cycles per Hour (On/Off Models) Direct/Reverse Acting Cycles per Hour (On/Off Models) Reheat Time Display UI3 Value Repair Information If a TEC22x6(H)-4 or TEC22x6H-4+PIR Series Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls representative. TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability (Part 1 of 2) Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or Safety Extra-Low Voltage (SELV) Relay/Triac Contact Rating Analog Output Rating On/Off and Floating Control Fan Relay Output Rating Auxiliary Output Rating Proportional Control Triac Output 19 to 30 VAC, 1.0 A Maximum, 15 ma Minimum, 3.0 A In-Rush 0 to 10 VDC into 2k ohm Resistance (Minimum) 19 to 30 VAC, 1.0 A Maximum, 15 ma Minimum, 3.0 A In-Rush 19 to 30 VAC, 1.0 A Maximum, 15 ma Minimum, 3.0 A In-Rush 6

TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability (Part 2 of 2) Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC) Thermistor Sensors Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Temperature Sensor Type Local 10k ohm NTC Thermistor Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm Diameter) Recommended LONWORKS Network Standard 64 Devices Maximum without a Repeater, 127 Devices Maximum with a Repeater; 6,250 ft (1,905 m) Maximum (Bus Topology) Temperature Backlit Display -40.0 F/-40.0 C to 122.0 F/50.0 C in 0.5 Increments Range Heating Control 40.0 F/4.5 C to 90.0 F/32.0 C Cooling Control 54.0 F/12.0 C to 100.0 F/38.0 C Accuracy Temperature ±0.9F /±0.5C at 70.0 F/21.0 C Typical Calibrated Humidity ±5% RH from 20 to 80% RH at 50 to 90 F (10 to 32 C) Default Minimum Deadband 2F /1C between Heating and Cooling Ambient Operating 32 to 122 F (0 to 50 C); 95% RH Maximum, Noncondensing Conditions Storage -22 to 122 F (-30 to 50 C); 95% RH Maximum, Noncondensing Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A LONMARK Certification 3.4 Canada UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003 Europe CE Mark, EMC Directive 2004/108/EC, standards EN 61000-6-3 and EN 61000-6-1 Australia and C-Tick Mark, Australia/NZ Emissions Compliant New Zealand Shipping Weight TEC22x6(H)-4 Models: 0.75 lb (0.34 kg) TEC22x6H-4+PIR Models: 0.77 lb (0.35 kg) The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. United States Emissions Compliance: This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense. Canadian Emissions Compliance: This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouiller du Canada. Published in U.S.A. Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. 2010 Johnson Controls, Inc. 7 www.johnsoncontrols.com