TEC and TEC PIR Single-Stage Wireless Thermostat Controllers
|
|
|
- Grant Cooper
- 9 years ago
- Views:
Transcription
1 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions TEC and TEC PIR Part No , Rev. B Issued July 13, 2010 Supersedes May 17, 2010 Applications The TEC Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming. This TEC Series System integrates into a supervisory controller that uses BACnet Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP) communications. TEC20 Coordinators allow the supervisory controller to communicate with multiple TEC Wireless Thermostat Controllers. The TEC200x-4 Series Wireless Thermostat Controllers provide networked control of a variety of staged equipment. The TEC Single-Stage Wireless Thermostat Controllers control fan coil units, unit heaters, and single-stage packaged heating/cooling equipment. The TEC PIR Thermostat Controller provides advanced active occupancy logic that automatically switches occupancy from Occupied to Unoccupied as required by the presence of local activity. See the Occupancy Sensor Operation TEC PIR Thermostat Controller section for more information. The wireless mesh network uses ZigBee technology to enable remote monitoring and programming and to enhance reliability by providing redundant transmission paths through other TEC Wireless Thermostat Controllers, creating a resilient, self-healing mesh network. IMPORTANT: The TEC and TEC PIR Wireless Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat controller. North American Emissions Compliance United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense. RF Transmitters: Compliance Statement (Part 15.19) This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation. Warning (Part 15.21) Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment. TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 1
2 Canada This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. RF Transmitters: Industry Canada Statement The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met. Le terme «IC» précédant le numéro d'accréditation/ inscription signifie simplement que le produit est conforme aux spécifications techniques d'industrie Canada. Installation Location Considerations Locate a thermostat controller: on a partitioning wall, approximately 1.5 m (5 ft) above the floor in a location of average temperature away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells, or from behind doors away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference For integrated Passive Infrared (PIR) models, make sure the thermostat controller is located centrally, where occupant movement is frequent. Note: Allow for vertical air circulation to the TEC and TEC PIR Thermostat Controllers. Wireless Signal Transmission Range Line-of-sight transmission ranges between a TEC20 Coordinator and a TEC Wireless Thermostat Controller (or between TEC Wireless Thermostat Controllers) can be less than the recommended distances shown in Table 1. The effective transmission range for indoor applications varies because of Radio Frequency (RF) signal absorption and reflection due to metal obstructions, walls (or floors), and furniture found in typical building interiors. Table 1: Recommended Transmission Ranges Type Distance Through Walls 10 m (30 ft) Open Space 30 m (100 ft) For detailed information on locating devices for optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT ). Installing the Thermostat Controller Follow these steps to install the thermostat controller: 1. Use a Phillips-head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controller cover. Note: Normally, the security screw is packaged separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed on the bottom of the cover. 2. Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1. Note: PIR models have a wiring connection between the cover and the Printed Circuit Board (PCB). This connection allows for proper wiring of the occupancy sensor. Carefully remove the wiring connection from the PCB by pulling up on the connector block. Do not attempt to remove the connector block by pulling on the wires. Figure 1: Removing the Thermostat Controller Cover (TEC PIR Model Shown) FIG:cvr_rmvl 2 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
3 3. Carefully pull the locking tabs on the right side of the mounting base and unlock the PCB. Open the PCB to the left as illustrated in Figure 2. Note: Be careful not to overtighten the mounting screws. PCB Locking Tabs Figure 2: Opening the PCB FIG:prnt_circ_brd Figure 3: Securing the Mounting Base to the Wall FIG:mntng_bs 4. Pull approximately 152 mm (6 in.) of wire from the wall and insert the wire through the hole in the mounting base. 5. Align the mounting base on the wall and use the base as a template to mark the two mounting hole locations. 6. Position the thermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller. Note: If you need to install the thermostat on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures you have enough space for cabling and end-of-line devices, if needed. Note: For surface-mount applications, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface. 7. Secure the mounting base to the wall surface using two mounting screws as illustrated in Figure Swing the PCB back to the right and carefully snap it into the locking tabs on the mounting base. 9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the thermostat controller. Figure 4: Removing the Screw Terminal Blocks FIG:trmnl_blcks TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 3
4 Wiring!! CAUTION: Risk of Electric Shock. Disconnect the power supply before making electrical connections to avoid electric shock. CAUTION: Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment. IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the thermostat controller. When replacing an existing thermostat controller, remove and label the wires to identify the terminal functions. When replacing a thermostat controller of the same model, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat controller. To wire the thermostat controller: 1. Strip the ends of each wire 6 mm (1/4 in.) and connect them to the appropriate screw terminals as indicated in Figure 5. Note: If multiple wires are inserted into the screw terminals, be sure to properly twist the wires together prior to inserting them into the screw terminals. 2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings. 3. Reinsert the screw terminal blocks onto the PCB. 4. Reattach the cover to the mounting base (top side first). 5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat controller cover. See Figure 5 for information on wiring the thermostat controller. Terminal W1 Y1 G RC C RH Aux DI1 DI2 RS Scom OS MS Function Energizes on Call for Heating Energizes on Call for Cooling Energizes Fan in Accordance with the Selected Fan Mode 24 VAC from Equipment Transformer 24 VAC (Common) from Equipment Transformer 24 VAC for Heating Stage Auxiliary Output Configurable Digital Input 1 Configurable Digital Input 2 Remote Room Sensor Sensor Common Auxiliary/Outdoor Air Sensor Remote Monitoring Supply Temperature Sensor Four-Pole Left Top Connector Y1 G RC C RH Seven-Pole Bottom Connector Aux DI1 DI2 RS Scom Two-Pole Right Top Connector W1 OS MS Aux Contact (High Side Common) Lighting On/Off Actuation Exhaust Fan Y1 G RC C RH W1 Aux DI1 DI2 RS Scom OS MS Heat 1 Cool 1 Fan Aux 24 VAC Thermostat Power If using the same power source for the thermostat and heating loads, install a jumper across RC and RH. Remote Room Sensor Auxiliary/ Outdoor Air Sensor Remote Monitoring Supply Temperature Sensor FIG:wrng_2001 Figure 5: Wiring the TEC or TEC PIR Thermostat Controller 4 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
5 Setup and Adjustments Thermostat Controller User Interface Keys The user interface consists of keys on the front cover (Figure 6). The function of each key is as follows: Use the YES key to: - confirm menu selections and to advance to the next menu item - stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu Note: When the thermostat controller is left unattended for 45 seconds, the display resumes scrolling. Use the NO key to decline a parameter change and to advance to the next menu item. Use the MENU key to: - access the Main User Menu or to exit the menu (See the Main User Menu section.) - access the Installer Configuration Menu or to exit the menu (See the Configuring the Thermostat Controller section.) Use the UP/DOWN arrow keys to change the configuration parameters and activate a setpoint adjustment. PIR motion detector saves energy using standby setpoints. Status LED beneath cover indicates network status. Backlit, plain text Liquid Crystal Display (LCD) is easy to read in any condition. Room Temp 70.0ºF Light-Emitting Diodes (LEDs) indicate system activity. Five keys on the thermostat controller make operation easy and intuitive. Figure 6: Front Cover of Thermostat Controller (TEC PIR Model Shown) FIG:2001-4frnt_vw Light-Emitting Diodes (LEDs) Three LEDs are included to indicate the fan status, call for heat, or call for cooling: The fan LED is on when the fan is on. The heat LED is on when heating is on. The cool LED is on when cooling is on. The Status LED, located beneath the cover, flashes at 5-second intervals to provide indication of the network Table 2: Status LED Flashes per Condition Indicated 5-Second Interval 1 Power On 2 Power On, Communicating 3 Power On, Communicating, Found Wireless Network 4 Power On, Communicating, Found Wireless Network, Communicating with TEC20 Coordinator TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 5
6 Backlit Liquid Crystal Display (LCD) The thermostat controller includes a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens when any user interface key is pressed. The backlight returns to low level when the thermostat controller is left unattended for 45 seconds. Integrated PIR Sensor TEC PIR Thermostat Controller The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Unoccupied temperature setpoints without user interaction. This feature generates incremental energy savings during scheduled occupied periods while the space is unoccupied. Programming Overview Three menus are used to view, program, and configure the TEC and TEC PIR Thermostat Controllers: the Status Display Menu, the Main User Menu, and the Installer Configuration Menu. Status Display Menu The Status Display Menu displays during normal operation. This menu scrolls through several parameters: Room Temperature System Mode Schedule Status (Occupied/Unoccupied/Override) Outdoor Temperature An outdoor air temperature sensor must be connected. Applicable Alarms The backlight lights up as an alarm condition is displayed. Note: Press the YES key to temporarily stop this menu from scrolling. Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter. Main User Menu Use the Main User Menu to access and change the basic operating parameters of the thermostat controller. During normal operation, press the MENU key once to access the Main User Menu. This menu is most commonly used by the zone occupant. The Main User Menu includes the following parameters: Temperature Setpoints System Mode Fan Mode The Main User Menu uses Auto Help. Auto Help displays automatically in the Main User Menu when there is a pause in programming activity. For further information, see the Operation section. Installer Configuration Menu Use the Installer Configuration Menu to set up the thermostat controller for application-specific operation. To access the menu, press and hold the MENU key for approximately 8 seconds. Occupancy Sensor Operation TEC PIR Thermostat Controller A TEC PIR Thermostat Controller (or a TEC Thermostat Controller equipped with a PIR accessory cover) provides advanced occupancy logic. Note: The PIR strategy is an occupied strategy. If the thermostat controller is programmed to be Unoccupied, the PIR function does not have an affect on the occupancy strategy. The thermostat controller automatically switches the occupancy level between Occupied and Unoccupied as required, when local movement is sensed. In the Occupied mode, if no movement is detected beyond the Unocc TM parameter setting, the mode changes to Unoccupied. Once movement is detected, the mode changes back to Occupied. Occupancy sensing is enabled only if a PIR cover is installed. The PIR cover, when installed, is auto detected. PIR Diagnostic LEDs The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup. The LEDs do not light up or brighten after the initial 30-minute period. Setpoints The installer must be certain that the difference between the Occupied and Unoccupied setpoints can be recovered within a timely fashion to ensure occupancy comfort. In addition, the difference between the two setpoints must be large enough to warrant maximum energy savings. 6 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
7 These setpoints and Unoccupied time are adjustable to allow for customization, as dictated by the individual space requirements. See Figure 7 for an example of increasing room temperature setpoints. Unocc Heat = 65 F Occ Heat = 72 F Occ Cool = 75 F Room Temperature FIG:rm_tmp Figure 7: Increasing Room Temperature Setpoints Configuring the Thermostat Controller The thermostat controller ships from the factory with default settings for all configurable parameters. The default settings are shown in Table 3. To reconfigure the parameters via the thermostat controller, follow the steps in this section. 1. To access the Installer Configuration Menu, press and hold the MENU key for approximately 8 seconds. Note: If the Password parameter is configured, Password 0 appears on the thermostat controller display indicating that the configured password is required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then press the MENU key to proceed through the Installer Configuration Menu parameters. 2. Once the Installer Configuration Menu begins, release and press the NO key to scroll through the parameters listed in Table When the desired parameter is displayed, use the YES key to choose the desired selection option. 4. Press the YES key and then the NO key to continue scrolling through the parameters. When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the thermostat controller reverts to the Status Display Menu. Configuring Inputs DI1 and DI2 When DI1 and DI2 are configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up. Both inputs can be configured to the Selection Options included in Table 3. Configuring the Wireless Mesh Network Settings Use the following process to configure the wireless mesh network settings. 1. Select a PAN ID and Channel. Use these same values for every TEC Wireless Thermostat Controller (and the associated coordinator) on the same wireless mesh network. 2. Select a Com Address for each thermostat controller (1 to 254). This address must be unique to each TEC Wireless Thermostat Controller on the same wireless network (that is, unique to the PAN ID and Channel combination). After configuring the wireless mesh network settings, refer to the TEC20xx-4 and TEC20xx-4+PIR Series Wireless Thermostat Controller System Technical Bulletin (LIT ) for directions on integrating the TEC Wireless Thermostat Controllers and TEC20 Coordinator with a supervisory controller. TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 7
8 Table 3: Installer Configuration Menu (Part 1 of 5) Parameter Appearing on Display Description and Default Selection Options Pswrd Com addr PAN ID Channel Sets the protective access password to prevent unauthorized access to the Installer Configuration Menu. Default: 0 Note: The default setting does not lock out access to the Installer Configuration Menu. Wireless address at the thermostat controller. Default: 254 Sets the Personal Area Network Identification (PAN ID) of the wireless network. All devices on a network must have the same PAN ID setting to communicate with each other. Default: 0 Sets the mesh network channel the device uses for communication. Only devices using the same mesh network channel can communicate with each other. Default: 10 GET FROM Parameter not available at this time. N/A DI1 Configuration of Digital Input 1. Default: None Range: 0 to 1,000 Range: 000 to 254 Addresses of each item on the wireless bus must be uniquely numbered, increasing from 1. Note: Setting this parameter to 0 disables the function. Range: 0 to 500 Note: Setting this parameter to 0 disables the function. Range: 11 to 26 Note: Setting this parameter to 10 disables the function. (None): No function is associated with an input. (RemNSB): Remote Night Setback (NSB) via a time clock input, an occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied. (RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller. (Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter. (Service): A Service alarm is displayed on the thermostat controller when the input is energized. Tie this input into the air conditioning unit control card, which provides an alarm if a malfunction occurs. (Fan lock): A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized. This alarm is used in conjunction with a local airflow sensor connected to the input. The thermostat controller heating or cooling action is locked out if no airflow is detected 10 seconds after the fan (Terminal G) is energized. Contact open = no airflow; contact closed = airflow present. 8 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
9 Table 3: Installer Configuration Menu (Part 2 of 5) Parameter Appearing on Display Description and Default Selection Options DI2 Configuration of Digital Input 2. Default: None MenuScro Lockout Pwr del 1 Frost pr Heat max 2 Gives the option of having the display continuously scroll the parameters. Default: on Selectable Lockout Levels for limiting end user keypad interaction. Default: 0 Sets the delay time period at thermostat controller powerup, or at each time power is removed and reapplied, before any operation (fan, heating, or cooling) is authorized. Also can be used to sequence the startup of multiple units in one location. Default: 10.0 sec Provides a minimum heating setpoint of 5.5 C/42.0 F to prevent freezing in the zone controlled by the thermostat controller. Default: off Sets the Occupied and Unoccupied maximum Heating setpoint values. Default: 32.0 C/90.0 F (None): No function is associated with an input. (RemNSB): Remote Night Setback (NSB) via a time clock input, an occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied. (RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller. (Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter. (Service): A Service alarm is displayed on the thermostat controller when the input is energized. Tie this input into the air conditioning unit control card, which provides an alarm if a malfunction occurs. (Fan lock): A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized. This alarm is used in conjunction with a local airflow sensor connected to the input. The thermostat controller heating or cooling action is locked out if no airflow is detected 10 seconds after the fan (Terminal G) is energized. Contact open = no airflow; contact closed = airflow present. (off): The scroll is inactive. (on): The scroll is active. Function Resume/Override Scheduling Permanent Temperature Setpoints Temporary Temperature Setpoints Level (0) (1) (2) Access Access No Access Access No Access No Access Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Range: 10.0 to sec (on): Enabled (off): Disabled Range: 4.5 C/40.0 F to 32.0 C/90.0 F TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 9
10 Table 3: Installer Configuration Menu (Part 3 of 5) Parameter Appearing on Display Description and Default Selection Options Cool min 2 Pband Anticycl Heat cph Cool cph Deadband Fan cont Fan del Sets the Occupied and Unoccupied minimum Cooling setpoint values. Default: 12.0 C/54.0 F Proportional Band used by the PI temperature control loop of the thermostat controller. Pband is not converted with C or F scale and is always shown with a range of 2 to 8. Default: 2 (2.0F /1.1C ) Anti-Short Cycle timer sets the minimum on/off times for heating and cooling stages. Default: 2.0 min Note: Set the anti-short cycle timer to 0.0 min for equipment that already has its own anti-short cycle timer. Sets the maximum number of Heating cycles per hour. Default: 4.0 Sets the maximum number of Cooling cycles per hour. Default: 4.0 Sets the minimum deadband between the heating and cooling setpoints. Default: 1.0C /2.0F Determines how the fan is activated in response to a call for heating or cooling. Default: on Note: The Fan cont parameter applies to W1 when the fan is in the Auto mode only. The Fan cont parameter does not affect fan operation on a call for cooling (Y1). Fan delay extends fan operation after a heating or cooling cycle has ended. Default off Note: The fan delay is only active when the fan is in the Auto mode. Range: 12.0 C/54.0 F to 37.5 C/100.0 F Value F Scale Pband/C Scale Pband 2 2.0F /1.1C 3 3.0F /1.7C 4 4.0F /2.2C 5 5.0F /2.8C 6 6.0F /3.3C 7 7.0F /3.9C 8 8.0F /4.4C Note: The use of a larger proportional band is not to use the thermostat controller as a discharge air controller device. The use of a larger proportional band can be used to solve issues for flawed HVAC design with basic sizing and thermostat controller location errors that cannot be worked around. Range: 0.0 to 5.0 min adjustable in 1-minute increments Set the anti-short cycle timer to 0.0 min for equipment that already has its own anti-short cycle timer. Range: 3.0 to 8.0 cycles per hour Range: 3.0 or 4.0 cycles per hour Range: 1.0C /2.0F to 2.0C /4.0F adjustable in 0.5C /1.0F increments (off): Enables the thermostat controller to activate the fan in response to a call for cooling only. (on): Enables the thermostat controller to activate the fan in response to a call for heating or cooling. When there is a call for auxiliary heating, the fan is activated by the equipment fan and limit control. (on): Extends fan operation by 60 seconds after a heating or cooling cycle has ended. (off): No extension of fan operation after a heating or cooling cycle has ended. The fan delay is only active when the fan is in the Auto mode. 10 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
11 Table 3: Installer Configuration Menu (Part 4 of 5) Parameter Appearing on Display Description and Default Selection Options TOccTime Cal RS Cal OS H lock C lock Unocc TM Sets the duration of the Temporary Occupancy Time (when the thermostat controller is in the Unoccupied mode) when a Schedule Override Function is enabled using either the Main User Menu or DI1 or DI2 configured as a temporary override remote contact (RemOVR). Sets the effective duration of the Temporary heating or cooling setpoints set using the UP/DOWN arrow keys. Default: 3.0 hrs Sets the desired room air temperature sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature. Default: 0.0C /0.0F Sets the desired outdoor air temperature sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature. Default: 0.0C /0.0F Disables heating stage(s) operation when the outside air temperature is greater than the configured value. If the fan mode is set to Auto or Smart, the fan output is also disabled. Requires that an outside air temperature sensor be installed and connected. Default: 120 F/49 C Disables cooling stage(s) operation when the outside air temperature is less than the configured value. If the fan mode is set to Auto or Smart, the fan output is also disabled. Requires that an outside air temperature sensor be installed and connected. Default: -40 F/-40 C Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occupancy sensor. Default: 0.5 hours Range: 0.0 to 12.0 hrs adjustable in 1-hour increments Range: -2.5C /-5.0F to 2.5C /5.0F adjustable in 0.5C /1.0F increments Range: -2.5C /-5.0F to 2.5C /5.0F adjustable in 0.5C /1.0F increments Range: -15 F/-26 C to 120 F/49 C adjustable in 5F /5C increments Range: -40 F/-40 C to 95 F/35 C adjustable in 5F /5C increments Range: 0.5 hours to 24.0 hours adjustable in 0.5 hour increments TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 11
12 Table 3: Installer Configuration Menu (Part 5 of 5) Parameter Description and Default Selection Options Appearing on Display Aux cont Energizes peripheral devices (n.c.): Contact open = Occupied; contact closed = Unoccupied. (lighting equipment, exhaust fans, (n.o.): Contact closed = Occupied; contact open = Unoccupied. and economizers). The contact toggles with the internal Occupied/Unoccupied Default: n.o. schedule (or the NSB contact on one of the digital inputs, if used). Note: The contact toggles with the internal Occupied/Unoccupied schedule (or the NSB contact on one of the digital inputs, if used). 1. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and hold the UP or DOWN arrow key to change the numeric value in increments of ten. 2. When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5C /0.5F increments; press and hold the UP or DOWN arrow key to change the value in 5.0C /5.0F increments. Operation Programming the Thermostat Controller After configuring the thermostat controller by means of the Installer Configuration Menu, program its operating parameters by means of the Main User Menu. Access this menu by pressing the MENU key during normal operation. The Main User Menu contains the basic operating features of the thermostat controller. The Main User Menu also uses Auto Help, which is displayed automatically in the menu when there is a pause in programming activity. To exit Auto Help, continue with the programming selection. When the thermostat controller is in the Main User Menu and is left unattended for 45 seconds, the menu reverts to the Status Display Menu. Enabling Override Schedule Note: The Override Schedule prompt only appears when the thermostat controller is in Unoccupied Mode. This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the amount of time specified under the TOccTime parameter. See Table 3. Note: If one of the digital inputs is configured to operate as a remote override contact, this menu is disabled. To override the unoccupied state while in the Main User Menu: 1. Press the NO key to all prompts until the Override Schedule prompt appears. If the thermostat controller is in the unoccupied state, this is the first prompt. 2. Press the YES key to enable the temporary override. The thermostat controller returns to the Status Display Menu. When scrolling through the Status Display Menu, Override now appears for the schedule status parameter. Resuming the Programmed Schedule This menu only appears when the thermostat controller is in the override mode. To resume the schedule while in the Main User Menu: 1. Press the NO key to all prompts until the Resume Schedule prompt appears. If the thermostat controller is in the override state, this is the first prompt. 2. Press the YES key to resume the programmed schedule. The thermostat controller returns to the Status Display Menu. Entering Permanent Temperature Setpoints The first prompt appearing in the Main User Menu of the thermostat controller when in the occupied state is to set the permanent temperature setpoint. Permanent setpoints are stored in the programmed schedule. 12 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
13 To enter the permanent heating and cooling setpoints for the Occupied and Unoccupied Modes, follow the steps in Table 4. When changing the temperatures, press the keys once to change the temperature in 0.5C /0.5F increments; press and hold down the keys to change the temperature in 5.0C /5.0F increments. Table 4: Entering Permanent Temperature Setpoints (Part 1 of 2) Thermostat Description Controller Display RoomTemp 75.0 F Press the MENU key while in the Status Display Menu to enter the Main User Menu. Table 4: Entering Permanent Temperature Setpoints (Part 2 of 2) Thermostat Description Controller Display Unocc HT set? Y/N Unocc HT 62.0 F Press the YES key to change the unoccupied heating setpoint. Press the NO key to advance to the temperature display units. Press the UP/DOWN arrow keys to set the temperature. Press the YES key to store the value and advance to the next menu. Temperat set? Y/N Cooling set? Y/N Press the NO key to all prompts until the temperature setpoint prompt appears on the display (it may be the first prompt). Press the YES key to enter the temperature setting menu. Press the YES key to change the occupied cooling setpoint. Press the NO key to advance to the occupied heating setpoint menu. F/ C set? Y/N Exit? Y/N Press the YES key to set the display units to F or C. Press the NO key to advance to the temperature setpoint type menu. Press the YES key to return to the Status Display Menu or press the NO key to reenter the temperature setting menu. Cooling 75.0 F Heating set? Y/N Heating 68.0 F Unocc CL set? Y/N Unocc CL 80.0 F Press the UP/DOWN arrow keys to set the temperature. Press the YES key to store the value and advance to the next menu. Press the YES key to change the occupied heating setpoint. Press the NO key to advance to the unoccupied cooling setpoint menu. Press the UP/DOWN arrow keys to set the temperature. Press the YES key to store the value and advance to the next menu. Press the YES key to change the unoccupied cooling setpoint. Press the NO key to advance to the unoccupied heating setpoint. Press the UP/DOWN arrow keys to set the temperature. Press the YES key to store the value and advance to the next menu. Entering Temporary Temperature Setpoints To temporarily change the setpoint, press the UP/DOWN arrow keys to change the temporary setpoint for the current mode of operation. Note: Whether the thermostat controller is heating or cooling, the respective setpoint is temporarily adjusted. To toggle between the temporary heating and cooling setpoints, press the NO key while changing the temporary setpoints. Ending Temporary Temperature Setpoints The temporary setpoints remain in effect for the duration set in the TOccTime parameter or until manually released. To release the temporary setpoint sooner, while in the Main User Menu: 1. Press the YES key to the first prompt that appears. 2. If the thermostat controller does not immediately return to the Status Display Menu, press the MENU key again and press the YES key to exit the Main User Menu. The setpoint reverts to the Permanent Temperature Setpoint. TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 13
14 Selecting the System Mode The thermostat controller has four system modes: Automatic Mode (auto): Automatic changeover between heating and cooling. This is the default setting. Cooling Mode (cool): Cooling operation only Heating Mode (heat): Heating operation only Off Mode (off): The thermostat controller is off; however, when frost protection (Frost pr parameter) is enabled, the thermostat controller still calls for heat (if required). To set the system mode while in the Main User Menu: 1. Press the NO key to all prompts until the system mode prompt appears on the display. Press the YES key to select the desired system mode. 2. Press the UP/DOWN arrow keys to locate the desired system mode. Press the YES key to select the desired system mode. 3. Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu. Selecting the Fan Mode The thermostat controller has three fan mode settings: On Fan Mode (on): Energizes the fan all the time for both occupied and unoccupied states, even if the system mode is set to off. Automatic Fan Mode (auto): Energizes the fan only on a call for heating or cooling, for both occupied and unoccupied states. Smart Fan Mode (smart): Energizes the fan all the time for occupied states, and only on a call for heating or cooling in unoccupied states. This is the default setting. To select the fan mode while in the Main User Menu: 1. Press the NO key to all prompts until the fan mode prompt appears on the display. Press the YES key to set the fan mode. 2. Press the UP/DOWN arrow keys to locate the desired fan mode. Press the YES key to select the desired fan mode. 3. Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu. Troubleshooting See Table 5 for display messaging. Refer to the TEC20xx-4 and TEC20xx-4+PIR Series Wireless Thermostat Controller System Technical Bulletin (LIT ) for troubleshooting details. Accessories All the accessories in Table 6 include mounting hardware; contact the nearest Johnson Controls representative to order any of these parts. Note: Review the technical specifications of the accessories prior to their use in an application. Repair Information If a TEC or TEC PIR Single-Stage Wireless Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls representative. Table 5: Display Messages Display Function Frost Indicates that the heating is energized by the low limit frost protection room temperature setpoint 5.6 C (42 F). Fan Lock Indicates that the heating and cooling action are locked out due to a defective fan operation. Service Indicates that there is a service alarm in accordance with a programmable Digital Input. Filter Indicates that the filter(s) is dirty in accordance with a programmable Digital Input. Table 6: Accessories (Order Separately) (Part 1 of 2) Code Number Description SEN Remote Indoor Air Temperature Sensor SEN Remote Indoor Air Temperature Sensor with Occupancy Override and LED TEC-3-PIR 1 Cover with Occupancy Sensor TE-6361M-1 2 Duct Mount Air Temperature Sensor TE-636S-1 Strap-Mount Temperature Sensor 14 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
15 Table 6: Accessories (Order Separately) (Part 2 of 2) Code Number Description TE-6363P-1 2 TEC20-A-1 TEC20-RA-1 3 NPB-PWR 4 TEC20-8X-1 TEC20-9B-1 Outside Air Temperature Sensor Replacement Antenna for TEC20 Coordinator Remote Antenna for TEC20 Coordinator DIN Rail Mount 24 VAC/DC Power Module for TEC20 Coordinator 120 VAC to 15 VDC Power Supply for TEC20 Coordinator Replacement Battery Pack for TEC20 Coordinator 1. The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-pir TEC Thermostat Controller to provide occupancy sensing capability. 2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT ) for more details. 3. This antenna is used when the TEC Coordinator is installed inside a metal cabinet, or when a remote antenna is required by physical installation. 4. DIN Rail: Type NS35/7.5 (35 x 7.5 mm) and DIN rail end clips. Length of DIN rail depends on the number of DIN rail mounted options. Technical Specifications TEC and TEC PIR Single-Stage Wireless Thermostat Controllers (Part 1 of 2) Power Requirements Relay/Triac Contact Rating Relay/Triac Contact Rating Digital Inputs Analog Inputs Wire Size Transmission Range RF Band Transmission Power Temperature Range Temperature Sensor Type Resolution Control Accuracy Auxiliary/Outdoor Air Temperature Indication Range Minimum Deadband Ambient Conditions 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or Safety Extra-Low Voltage (SELV) 19 to 30 VAC, 1.0 A Maximum, 15 ma Minimum, 3.0 A In-Rush, Class 2 or SELV On/Off and Floating Control: 19 to 30 VAC, 1.0 A Maximum, 15 ma Minimum, 3.0 A In-Rush, Class 2 or SELV Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2 Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC) Thermistor Sensors 18 AWG Maximum, 22 AWG Recommended Through Walls: 10 m (30 ft) Line-of-Sight (Open Space): 30 m (100 ft) Direct-Sequence Spread-Spectrum Transmission; 2.4 Ghz unlicensed band 10 mw Maximum Backlit Display: C/ F to 50.0 C/122.0 F Heating Control: 4.5 C/40.0 F to 32.0 C/90.0 F in 0.5 Increments Cooling Control: 12.0 C/54.0 F to F/38.0 C in 0.5 Increments Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor ±0.1C /±0.2F ±0.5C /±0.9F at 21.0 C/70.0 F Typical Calibrated C/-40.0 F to 50.0 C/122.0 F 1C /2F between Heating and Cooling Operating: 0 to 50 C (32 to 122 F); 95% RH Maximum, Noncondensing Storage:-30 to 50 C (-22 to 122 F); 95% RH Maximum, Noncondensing TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 15
16 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers (Part 2 of 2) Compliance Shipping Weight United States: UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to Part Regulations for Low Power Unlicensed Transmitters Canada: UL Listed, File E27734, CCN XAPX7, Under CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003 TEC Model: 0.75 lb (0.34 kg) TEC PIR Model: 0.77 lb (0.35 kg) The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Building Efficiency 507 E. Michigan Street, Milwaukee, WI Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners Johnson Controls, Inc. 16 TEC and TEC PIR Single-Stage Wireless Thermostat Controllers Installation Instructions Published in U.S.A.
English plain text messages with constant backlight that brightens during user interaction. On/Off, Floating, or Proportional 0 to 10 VDC Control
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin Code No. LIT-12011587
T600MEP-4 and T600MEP-4+PIR Multi-Stage Economizer Thermostat Controllers
T600MEP-4 and T600MEP-4+PIR Multi-Stage Economizer Thermostat Controllers Installation Instructions T600MEP-4, T600MEP-4+PIR Part No. 24-9890-943, Rev. Issued September 17, 2009 Applications The T600MEP-4
TEC22x1-3 LONWORKS Networked Single Stage Thermostats
TEC22x1-3 LONWORKS Networked Single Stage Thermostats Installation Instructions Part No. 24-9890-463, Rev. Issued September 8, 2006 Applications The TEC2261-3 programmable and TEC2201-3 non-programmable
Protects against unwanted thermostat controller tampering. Increases occupancy comfort by providing dehumidification.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin Code No. LIT-12011607 Issued
TEC2602-4 and TEC2602-4+PIR BACnet MS/TP Networked Heat Pump Thermostat Controllers
TEC2602-4 and TEC2602-4+PIR BACnet MS/TP Networked Heat Pump Thermostat Controllers TEC2602-4 and TEC2602-4+PIR Applications The TEC2602-4 and TEC2602-4+PIR Thermostat Controllers are BACnet Master-Slave/
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin T600HCx-4, T600HPx-4, T600MSx-4, T600MEP-4, T600HCx-4+PIR, T600HPx-4+PIR, T600MSx-4+PIR, T600MEP-4+PIR The T600xxN-4 and T600xxN-4+PIR
TEC2664Z-3 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Part No. 24-9890-1362, Rev.
TEC2664Z-3 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Part No. 24-9890-1362, Rev. Issued May 13, 2011 Applications The TEC2664Z-3 Rooftop Controller is a BACnet Master-Slave/Token-Passing
Installation Instructions. Applications. North American Emissions Compliance. Installation
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions Part No. 24-9890-1001,
TEC Series BACnet MS/TP Network Temperature and Humidity Controllers
TEC Series BACnet MS/TP Network Temperature and Humidity Controllers Technical Bulletin Code No. LIT-12011592 Issued March 4, 2013 Supersedes May 13, 2011 Refer to the QuickLIT Web site for the most up-to-date
CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter
CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter Product Bulletin CD-Pxx-00-1 Code No. LIT-216525 Issued December 6, 2010 Supersedes September 12, 2008 Johnson Controls offers a complete line of Carbon Dioxide
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Applications The T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers provide control
Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7
THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3
TB7600 Series Communicating RTU Thermostats with Humidity Control
TB7600 Series Communicating RTU Thermostats with Humidity Control TB7600 Series Thermostat INSTALLATION INSTRUCTIONS APPLICATION The TB7600 Series PI thermostat family is specifically designed for single
FX07 Field Controller
Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,
T5000 T000 LCD Digital Fan Coil Thermostat
T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C
Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the
Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions
Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy
Communicating Thermostats. Add More Flexibility to Building Automation with New. Communicating Thermostats
Communicating Thermostats Add More Flexibility to Building Automation with New Communicating Thermostats More Choices. More Possibilities. From zone control to rooftop units and nearly everything in between,
QUICK INSTALLATION GUIDE
QUICK INSTALLATION GUIDE Read Installer Notes before removing cover from Thermostat. 1F85RF-275 Wireless Remote Kit INSTALLER NOTES IMPORTANT Do not apply power to the thermostat or wireless sensor until
FX07 Field Controller
Product Bulletin FX07 Field Controller Issue Date May 5, 2011 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,
User Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
Installation Instructions
TP-PRH-A, TP-NRH-A Performance Series Edge Thermidistat Control Installation Instructions Programmable Control A07049 A07048 Non Programmable Control Designed and Assembled in the USA. NOTE: Read the entire
Wireless Alarm System. Wireless Keypad. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location
Wireless Alarm System Wireless Keypad User s Manual 1 2 3 4 Choice ALERT Control all sensors, accessories and remote transmitters from one location Table of Contents Important Safeguards 4 Introduction
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators Product Bulletin Code No. LIT-1201742 Issued February 12, 2015 The M9102 and M9104 Series Actuators are directmount,
Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types
Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
System 350 A350E Electronic Cooling Control
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0899 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.
MAKING MODERN LIVING POSSIBLE. living connect. Installation and User Guide. Danfoss Heating Solutions
MAKING MODERN LIVING POSSIBLE living connect Installation and User Guide Danfoss Heating Solutions 2 living connect Thank you for buying a Danfoss product Danfoss Heating Solutions 3 Contents 1. System
INSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE
Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack
Compatible with SmartStruxure solution SmartStruxure Lite solution Room Controllers Line Voltage Fan Coil Room Controller with SC3000 Relay Pack Application specific controller with customizable covers
Install Guide CT101. Caution. Caution
Install Guide CT101 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the
Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types
Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,
HEAT PUMP PROGRAMMABLE THERMOSTAT
HEAT PUMP PROGRAMMABLE THERMOSTAT SA PM 3 COOL TEMP Form 44014-01 r010408 Model 43168 Owners Manual 1 Congratulations! Heat Pump Programmable Thermostat Model 43168 THERMOSTAT CONTROLS Switches & Buttons...15
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
HEAT HEAT COOL HEAT PUMP COOL
OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control
1. Overview. WPT Wireless Range Tester Kit User Manual Doc No. 910-00009-01 Rev 05. 1.1. Components. 1.2. Prerequisites for Site Survey
1. Overview The Cypress Envirosystems Wireless Pneumatic Thermostat (WPT) retrofits an existing pneumatic thermostat to provide Direct Digital Control (DDC) like zone control functionality at a fraction
WPR400 Wireless Portable Reader
P516-098 WPR400 Wireless Portable Reader User guide Para el idioma español, navegue hacia www.schlage.com/support. Pour la portion française, veuillez consulter le site www.schlage.com/support. Contents
Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March 2016 2016 Emerson Electric Co. All rights reserved.
Sensi TM Wi-Fi Programmable Thermostat MANUAL OPERATION Version: March 2016 2016 Emerson Electric Co. All rights reserved. Contents MANUAL OPERATION GUIDE Buttons and Icons 3 Basic Functionality 4 Manual
Electronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
LED Security Spotlight User Manual
MOT ION-TR ACKING LED Security Spotlight User Manual www.jascoproducts.com 1-800-654-8483 2 TABLE OF CONTENTS Parts List 3 Questions? Missing Parts? 4 Installation (Wall mount) 6-9 Installation (Eave mount)
Electronic Control Devices The European Product Catalogue 2007
FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically
Installer Guide smart connect
Installer Guide smart connect TM 7330 Wireless Remote Humidity Sensor Please read all instructions before proceeding. The wireless remote humidity sensor monitors the humidity passing through the return
MAKING MODERN LIVING POSSIBLE. living connect. Installation and User Guide. Danfoss heating
MAKING MORN LIVING POSSIBLE Danfoss heating living connect Installation and User Guide Contents 1.0 System overview... 3 2.0 Overview of display and control buttons... 3 3.0 Installation - step by step...
HE-6800 Series Humidity Transmitters with Temperature Sensor
HE-6800 Series Humidity Transmitters with Installation Instructions HE-68xx-xN00WS Applications The HE-6800 Series Humidity Transmitters with provide both humidity and temperature sensing in room wall-mount
EBDSPIR-PRM, EBDSPIR-PRM-IP
Product Guide EBDSPIR-PRM, EBDSPIR-PRM-IP Ceiling PIR presence/absence detector Overview The EBDSPIR-PRM PIR (passive infrared) presence detector provides automatic control of lighting loads with optional
Wireless Indoor/ Outdoor Thermometer
Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...
GSM-EXT Cable Assembly Installation Guide
GSM-EXT Cable Assembly Installation Guide For Documentation and Online Support: http://www.security.honeywell.com/hsc/resources/mywebtech General Information The GSM-EXT cable assembly is used to connect
Wireless Alarm System. Panic Button. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location
Wireless Alarm System Panic Button User s Manual Choice ALERT Control all sensors, accessories and remote transmitters from one location Table of Contents Important Safeguards 4 Introduction 5 Activating
Model 70A00-1. GSM Cellular Communications Center
Home Automation, Inc. Model 70A00-1 GSM Cellular Communications Center Operation Manual Document Number 70I00-1 Rev A August, 2009 Contents Description... 1 Use with security systems...1 Everyday use...2
Energy Smart Electric Water Heater Controller
Installation, Operation and Troubleshooting Instructions Energy Smart Electric Water Heater Controller Table of Contents Installation and Setup, 2 Operation, 5 Troubleshooting, 7 Regulatory Notices, 11
T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control
T Series arge CD Digital Thermostat 0/0 VAC -pipe/-pipe fan coil control Data sheet Application T digital thermostats are designed for application of -speed fan and s in fan coil system. Including: -pipe
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
A99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
Radiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
WIRELESS STATUS MONITOR
INSTALLATION INSTRUCTIONS WIRELESS STATUS MONITOR (WSM or AUWSM) The most current version of this document is available for download at: http://www.ir-swa.com P/N: M053-032-D Schlage 245 W. Roosevelt Road,
Power Supply Guide Version 1.0 for D-Show
Power Supply Guide Version 1.0 for D-Show Digidesign 2001 Junipero Serra Boulevard Daly City, CA 94014-3886 USA tel: 650 731 6300 fax: 650 731 6399 Technical Support (USA) tel: 650 731 6100 fax: 650 731
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
TC-9102 Series Surface Mount Temperature Controllers
TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may
PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS
PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000
PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE
Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface
Product Catalog. Small Building Systems. www.viconics.com
Product Catalog Small Building Systems www.viconics.com Table of Contents VBZS - Viconics BACnet Zoning System VZ1 VZ7200F5000B Bacnet Zone Thermostat... VZ5 VZ7656B1000B Bacnet Rooftop Unit Thermostat...
EBDSPIR-DD, EBDSPIR-DD-IP
Product Guide EBDSPIR-DD, EBDSPIR-DD-IP Ceiling PIR presence detector DALI / DSI dimming Overview The EBDSPIR-DD PIR (passive infrared) presence detector provides automatic control of lighting loads with
Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature
T-100-R Installation Guide
T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard
Class 2 transformer (TBT) Low Tension Conform to EN 60742. A LED turns ON when the current exceeds 1 A at the 14V output connector
Technical notice TECHNICAL CHARACTERISTICS Power Class 2 transformer (TBT) Low Tension Conform to EN 60742 Rechargeable battery 16 Vac, 50-60Hz 50 Va min. 250 Va max 12 V, 7AH Protection A LED turns ON
4.3-inch Back-Up Camera
TM 4.-inch Back-Up Camera Model No.: PKC0BU4 Owner s Manual and Warranty Information Read these instructions completely before using this product. Retain this Owner s Manual for future reference. INTRODUCTION
AXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM
TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution
Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.
Install Guide CT100 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
RADIO CONTROLLED DIGITAL CLOCK MODELS 88905 / 88906
RADIO CONTROLLED DIGITAL CLOCK MODELS 88905 / 88906 QUICK SETUP GUIDE IMPORTANT! INSTALL BATTERIES IN THE OUTDOOR TRANSMITTER BEFORE INSTALLING BATTERIES IN THE RADIO-CONTROLLED CLOCK. ALKALINE BATTERIES
HMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
System 350 A350R Electronic Temperature Reset Control (with Relay)
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350R Issue Date 0899 System 350 A350R Electronic Temperature Reset Control (with Relay) The A350R Electronic Temperature Reset Control is designed
Technical support is also available by email or by phone: [email protected] 1.877.932.6233 (North America) 1.647.428.2220 (International)
Installation guide Welcome! If you have questions, we have answers. Visit ecobee.com/support/ecobee3 for tutorials, how-to videos and FAQs. Technical support is also available by email or by phone: [email protected]
evohome Wireless Radiator Zoning Kit Installation & User Guide
evohome Wireless Radiator Zoning Kit Installation & User Guide Getting the most from your evohome system Installation & User Guide 1 Getting the most from your evohome system Thanks for choosing an evohome
HLWLAN 802.11b/g/n Transceiver Kit
092524 RevB HLWLAN 802.11b/g/n Transceiver Kit Wireless Communications for OmniLogic Owner s Manual Contents Introduction...1 Installation...2 Configuration...6 Operation...8 Troubleshooting...9 HLWLAN
e-4 AWT07MLED 7 Q TFT LCD MONITOR (LED Backlighted) USER MANUAL
Thank you for purchasing our product. Please read this User s Manual before using the product. Change without Notice AWT07MLED 7 Q TFT LCD MONITOR (LED Backlighted) USER MANUAL e-4 SAFETY PRECAUTIONS Federal
Table of Contents Function Keys of Your RF Remote Control Quick Setup Guide Advanced Features Setup Troubleshooting
Congratulations on your purchase of the AT&T U-verse TV Point Anywhere RF Remote Control. This product has been designed to provide many unique and convenient features to enhance your AT&T U-verse experience.
Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR
Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions
Install Guide 3M-50. Caution. Caution
PG 1 Install Guide 3M-50 aution Your thermostat is a precise instrument, handle it with care. Turn off electricity to the HVA system before installing or servicing thermostat or any part of the system.
Installation Instructions. Wireless Adapter/Repeater. Introduction. 30-3001-887 Rev C
/Repeater Installation Instructions 30-3001-887 Rev C Workstation Ethernet bcx Controller Repeater Repeater Introduction Schneider Electric has designed a device that allows Andover Continuum controllers
HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function
Specifications Supply Voltage 240VAC @ 0.07Amps or 24VAC @ 0.380Amps Relays 240V @ 12A max (resistive) / Comp1,2,3, Aux Ht, Rv O/B) Fuses (Equipment) 15 Amps Maximum 3AG Control Range Minus 10 to 50C Control
ST815 Illumination Sensor with LCD
ST815 Illumination Sensor with LCD The Illumination Sensor with LCD (refer to as Illumination Sensor hereafter) is a Z-Wave TM enabled device which is fully compatible with any Z-Wave TM enabled network.
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
Communicating Wall Control Installation Manual TSTAT0101SC
Communicating Wall Control Installation Manual TSTAT0101SC U.S. Patent No. 7,243,004 U.S. Patent No. 7,775,452 616 01 1017 02 08/07/12 Safety Considerations... 7 Introduction... 8 Quick Start... 9 Set
Digi-Motor Installation Guide
Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support
Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10. Programmable thermostat Thermostat programmable Termostato programable
Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10 Programmable thermostat Thermostat programmable Termostato programable Read and save these instructions. Veuillez lire le mode d
2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal
O N DS160/DS161 Installation Guide High Performance Request-to-Exit Sensors 1.0 Description The DS160/161 is a passive-infrared (PIR) detector designed for Request to Exit (REX) interior applications.
DPT-2015 Differential Pressure Transmitter for VAV Box Applications
FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential
PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator
3.635.5275.251 IM-P486-19 CH Issue 2 PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator Installation, Start-up and Operation Manual 1. Safety information 2. General product information 3.
TYXIA. *2702178_Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF 642-1 channel
Installation and User Guide TYXIA Wireless receiver TYXIA RF 642-1 channel DELTA DORE Bonnemain - 35270 COMBOURG - France E-mail : [email protected] Unit compliant with the requirements of directives:
PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual
PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code
its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.
Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please
WHITE-RODGERS COMFORT-SET 90 SERIES
INSTALLATI DESCRIPTI WHITE-RODGERS COMFORT-SET 90 SERIES MULTI-STAGE INSTALLATI/CFIGURATI This White-Rodgers Automatic Setback Digital Thermostat uses microcomputer technology to provide precise time and
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Mode Switch. Fan Switch Menu button Program button
Operation 3M-30 Day Time of day Target Temperature Time Slot Touch Screen Current Room Temperature Thermostat Mode Statement of use: The 3M-30 can be used with millivolt, 24VAC, single and 2 stage conventional
Wireless Thermostats 230v and Battery Operated Instruction Manual
Wireless Thermostats 230v and Battery Operated Instruction Manual For models: JGSTATW2W JGSTATW2B JGSTATW1W JGSTATW1B Contents Box contents: Wireless Thermostats 230v and Battery Operated Instruction Manual
