TEC2664Z-3 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Part No , Rev.
|
|
|
- Eugene Bishop
- 9 years ago
- Views:
Transcription
1 TEC2664Z-3 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Part No , Rev. Issued May 13, 2011 Applications The TEC2664Z-3 Rooftop Controller is a BACnet Master-Slave/Token-Passing (MS/TP) device that operates with a Johnson Controls TEC2647Z-3 or TEC2647Z-3+PIR (occupancy sensor model) Zone Controller to provide efficient space temperature control in constant volume zoning systems. This technologically advanced rooftop controller provides a proportional 0 to 10 VDC control output to the bypass damper of a rooftop unit based on the sensed pressure in the duct, and controls up to two stages of heating and two stages of cooling. The TEC2664Z-3, TEC2647Z-3+PIR, and TEC2647Z-3 Controller combination can operate as a stand-alone zoning system or it can operate with a Building Automation System (BAS) that enables remote monitoring and programming in networked zoning systems. The TEC2664Z-3 Rooftop Controller features an intuitive user interface with backlit display that makes setup and operation quick and easy. The rooftop controller also employs a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based rooftop controllers. IMPORTANT: The TEC2664Z-3 Rooftop Controller is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the rooftop controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the rooftop controller. Refer to the QuickLIT Web site for the most up-to-date version of this document. North American Emissions Compliance United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense. Canada This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. TEC2664Z-3 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems 1
2 Rooftop Controller MS/TP Bus Rooftop Unit Supply Return Bypass Damper Mixed Airflow Bypass Airflow Return Airflow MS/TP Bus Zone Controller Zone Damper Zone Controller Zone Damper Zone Controller Zone Damper FIG:typcl_znng_systm RS485 End-of-Line Terminator (MS-BACEOL-0) Figure 1: Typical Zoning Control System Installed on a Single MS/TP Bus Mounting Figure 1 illustrates a typical zoning control system installed on a single MS/TP Bus. This installation consists of a TEC2664Z-3 Rooftop Controller controlling a rooftop unit; and multiple Zone Controllers, each controlling a single zone damper. The TEC2664Z-3 Rooftop Controller can be wired to an optional supervisory controller. Location Considerations Follow these guidelines for locating the TEC2664Z-3 Rooftop Controller. Observe all environmental limits, and be sure that the rooftop controller mounting location maintains the ambient operating conditions as described in the Technical Specifications on page 25. Mount the rooftop controller indoors or in an approved enclosure, where the ambient operating conditions are always maintained. Do not mount the rooftop controller where it may be exposed to water, condensation, other liquids, or corrosive or flammable vapors of any kind. IMPORTANT: Before specifying the TEC2664Z-3 Rooftop Controller for plenum applications, verify acceptance of exposed plastic materials in plenum areas with the local building authority. Building codes vary by location. Some local building authorities accept compliance to UL 1995, Heating and Equipment, while others use different acceptance criteria. Mount the rooftop controller in an accessible location to allow for easy access to the user interface keys. Do not mount the rooftop controller on surfaces that are prone to vibration, or in areas where electromagnetic emissions, inductive interference, or radio frequency signals from other devices or wiring can interfere with operation or Field Bus communication. 2
3 To install the rooftop controller: 1. Pull the bottom edge of the rooftop controller cover and open the rooftop controller as illustrated in Figure 2. Note: If you need to install the rooftop controller on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures you have enough space for cabling and end-of-line devices, if needed. Note: For surface-mount applications, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface. FIG:cvr_rmvl Figure 2: Removing the Rooftop Controller Cover 2. Carefully pull the locking tabs on the right side of the rooftop controller mounting base, and unlock the Printed Circuit Board (PCB). Open the PCB to the left as illustrated in Figure 3. PCB Locking Tabs Figure 4: Securing the Rooftop Controller Mounting Base to the Wall 6. Swing the PCB back to the right and carefully snap it into the locking tabs on the rooftop controller mounting base. 7. Remove the screw terminal blocks that are attached to a disposable adhesive to the display. Figure 5 illustrates the locations of the screw terminal blocks on the rooftop controller. FIG:mntng_bs FIG:prntd_crct_brd Figure 3: Opening the Rooftop Controller PCB 3. Pull approximately 6 in. (152 mm) of wire from the wall, and insert the wire through the hole in the rooftop controller mounting base. 4. Align the rooftop controller mounting base on the wall, and use the base as a template to mark the two mounting hole locations. 5. Position the controller mounting base so that the arrow on the base points upward to indicate the top of the controller. Figure 5: Removing the Screw Terminal Blocks FIG:trmnl_blcks 3
4 Wiring When an existing rooftop controller is replaced, remove and label the wires to identify the terminal functions. When a TEC2664Z-3 Rooftop Controller is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement rooftop controller.!! CAUTION: Risk of Electric Shock. Disconnect power supply before making electrical connections to avoid electric shock. CAUTION: Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment. IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC2664Z-3 Rooftop Controller. To wire the rooftop controller: 1. Strip the ends of each wire 1/4 in. (6 mm), and connect them to the appropriate screw terminals as indicated in Table 1 and Figure 6. Note: For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT ). 2. Carefully push any excess wire back into the wall. IMPORTANT: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings. Table 1: Terminal Identification (See Figure 6.) Terminal Number Terminal Label Function 1 Y2 Stage II (Energizes on a Call for Second-Stage ) 2 Y1 Stage I (Energizes on a Call for First-Stage ) 3 G Fan Output (Energizes the Fan in Accordance with the Selected System Mode) 4 RC 24 VAC from Transformer 5 C 24 VAC (Common) from Transformer 6 RH 24 VAC for Heating Stages 7 W1 Heating Stage I (Energizes on a Call for First-Stage Heating) 8 W2 Heating Stage II (Energizes on a Call for Second-Stage Heating) 9 BPD Bypass Damper (0 to 10 VDC Actuator Output) 10 AU Auxiliary Output 11 SP Static Pressure 12 DI1 Configurable Digital Input RS Return Air Sensor 14 Scom Sensor Common 15 OS Outside Air Sensor 16 DS Discharge Air Sensor Blank +,, REF MS/TP Bus 1. If no sensor is connected to this terminal, then the rooftop controller uses the onboard temperature sensor as the return air sensor. 3. Reinsert the screw terminal blocks onto the PCB. 4. Attach the MS/TP communication wires to the terminal block. Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors. 5. Reattach the rooftop controller cover to the mounting base (top side first). 6. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the rooftop controller cover. 4
5 MS/TP Connector + REF Five-Pole Left Top Connector Y2 Y1 G RC C Eight-Pole Bottom Connector Three-Pole Right Top Connector RH W1 W BPD AU SP DI1 RS Scom OS DS Auxiliary Contact for: Lighting On/Off Actuation Exhaust Fan Y2 Y1 G RC C RH W1 W2 BPD AU SP DI1 Remote Inputs Stage II Stage I Fan Output Jumper J1 Heating Stage I Heating Stage II 0 to 10 VDC 24 VAC Common Aux 0 to 5 VDC 24 VAC Common RS Scom OS If the same power source is used for the rooftop controller and the heating loads, install a jumper across RC and RH. 24 VAC Rooftop Controller Power Return Air Sensor Outside Air Sensor Discharge Air Sensor + REF Supervisory Controller FIG:wrng Figure 6: Wiring the TEC2664Z-3 Rooftop Controller (See Table 1.) 5
6 Connecting the MS/TP Bus To connect the MS/TP Bus: 1. Set the device address of the TEC2664Z-3 Rooftop Controller per the engineering drawings, and test for bus voltage, polarity, and isolation prior to wiring the MS/TP Bus. (See the RTC MAC parameter in Table 2 to set the device address for the rooftop controller.) Note: Pressing and holding the YES and NO keys simultaneously displays the assigned device address. Note: The wiring rules for the MS/TP Bus differ from the wiring rules for the N2 Bus. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT ). 2. Observe the polarity when connecting the bus wires to the rooftop controller. 3. After the bus wires are connected to the first rooftop controller, continue in a daisy-chained fashion to the next device on the MS/TP Bus. Note: The bus wiring must be twisted-pair lines. Do not run the bus wiring in the same conduit as line voltage wiring (30 VAC or above) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators). The MS/TP Bus requires proper termination and biasing at each end of a segment (a segment is a physically continuous length of wire). Because the rooftop controller is not equipped with end-of-line termination, a Johnson Controls MS-BACEOL-0 End-of-Line Terminator (see Table 6; ordered separately) or similar device is recommended to provide this end-of-line termination. An end-of-line terminator is required if a supervisory controller is not at the end of the segment. If a supervisory controller is at the end of the segment, then the end-of-line terminator switch on the supervisory controller must be set in the ON position. Note: See Table 6 for end-of-line terminator ordering information. For applications with a supervisory controller on the MS/TP Bus, set the supervisory controller to establish the baud rate, and set the rooftop controller for automatic baud rate detection. For stand-alone applications where a supervisory controller is not present, at least one device on the MS/TP Bus must be set to establish the baud rate. It is recommended that the baud rate be set at only one rooftop controller, and all other devices be set for automatic baud rate detection. Doing so prevents duplicate devices from having mismatched baud rates. After the baud rate is set, recycle the power to the device that was used to set the baud rate. Do not exceed the maximum number of devices allowed on a Field Bus. Be sure that the wiring terminations are set correctly, and that all communication wiring is daisy-chained with no taps. A small green light under the rooftop controller cover (on the left edge, when facing the rooftop controller) indicates the communications mode when the rooftop controller is operating. The following blink codes may occur: Short-Short-Long: Indicates that the baud rate is known and communication is active. Short-Short: Indicates that the rooftop controller is scanning for the correct baud rate and there is no communication. Off: Indicates that there is no power to the rooftop controller or the MS/TP wiring polarity is reversed. Long: Indicates that the MS/TP communication daughter board is the wrong type for the main board. 6
7 Setup and Adjustments Rooftop Controller Operation Overview Figure 7: Front Cover of Rooftop Controller Rooftop Controller User Interface Keys The TEC2664Z-3 Rooftop Controller user interface consists of five keys on the front cover (Figure 7). The function of each key is as follows: Use the YES/SCROLL key to: - confirm display selections and to advance to the next display item - stop the Auto Scroll Display from automatically scrolling and to manually scroll to the next parameter on the display Note: When the rooftop controller is left unattended for 45 seconds, the rooftop controller display resumes scrolling. Use the NO key to decline a parameter change and to advance to the next display item. Use the MENU key to: - access the Main User Menu or to exit the menu (See Main User Menu on page 8.) - access the Installer Configuration Menu or to exit the menu (See Configuring the TEC2664Z-3 Rooftop Controller on page 8.) Use the UP/DOWN arrow keys to change the configuration parameters and to activate a setpoint adjustment. Light-Emitting Diodes (LEDs) Three LEDs are included to indicate the fan status, and to show a call for heating or a call for cooling: The LED is on when the fan is on. The LED is on when heating is on. The LED is on when cooling is on. Manual Scroll Display To initiate the Manual Scroll Display, press the YES key repeatedly. The last item viewed shows on the display for 30 seconds before Auto Scroll Display resumes. The manual scroll sequence is as follows: Clock Status (Day/Time) System Mode (Off/Auto) Schedule Status (Occupied/Occupied Hold/ Unoccupied/Unoccupied Hold/Override) Outside Temperature Alarms (Service/DAS Alrm/SetClock/Filter/Comm Lost) Current Zone Sequence (Off/Cool/Heat) Return Air Temp Discharge Air Temp Current Static Pressure 7
8 Effective PI Heat Effective PI Cool Highest PI Heat Zone Highest PI Cool Zone Main User Menu The Main User Menu is used to access and change the basic operating parameters of the rooftop controller. During normal rooftop controller operation, press the MENU key once to access the Main User Menu. This menu is most commonly used by the zone occupant, and includes the following parameters: Schedule Override/Cancel Override System Mode Set Schedule Set Clock The Main User Menu uses Auto Help. Auto Help is displayed automatically in the Main User Menu when there is a pause in programming activity. Configuring the TEC2664Z-3 Rooftop Controller The TEC2664Z-3 Rooftop Controller ships from the factory with default settings for all configurable parameters. The default settings are shown in Table 2. To reconfigure the parameters via the rooftop controller, follow these steps: 1. Press and hold the MENU key for approximately 8 seconds to access the Installer Configuration Menu. 2. Once the Installer Configuration Menu begins, press the NO key to scroll through the parameters listed in Table When the desired parameter displays, use the YES key to choose the desired selection option. 4. Press the YES key and then the NO key to continue scrolling through the parameters. When the rooftop controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the rooftop controller reverts to the Auto Scroll Display. Refer to the TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications Technical Bulletin (LIT ) for additional configuring and commissioning details. Configuring Input DI1 When DI1 is configured for an alarm condition, an alarm condition appears locally when the input is closed. An alarm message is included on the Auto Scroll Display, and when the message is displayed, the backlight momentarily lights up. The DI1 input can be configured to the selection options included in Table 2. Table 2: Installer Configuration Menu (Part 1 of 5) Parameter Description and Default Selection Options Appearing on Display RTC MAC 1 Sets a unique device address for the rooftop controller on the MS/TP network. Default: 4 Note: This parameter setting must be the same as the RTC MAC parameter setting for all zone controllers associated with this rooftop controller. Range: 004 to 127 Note: When setting the device address, press the UP/DOWN arrow keys to change the device address in increments of 1; press and hold the UP/DOWN arrow keys to change the device address in increments of 10. 8
9 Table 2: Installer Configuration Menu (Part 2 of 5) Parameter Appearing on Display Description and Default Selection Options RTC Baud Lockout Pwr del 3 CntrlTyp Dis HL 4 Dis LL 4 Anticycl Heat cph Cool cph Deadband Sets the baud rate of the rooftop controller on the MS/TP network. Default: Auto Selectable Lockout Levels for limiting end user keypad interaction. Default: 0 Sets the delay time period at rooftop controller powerup, or at each time power is removed and reapplied, before any operation (fan, heating, or cooling) is authorized. Also can be used to sequence the startup of multiple units in one location. Default: 30.0 sec Sets how the rooftop controller is controlled. Default: AV_H3 Sets the Discharge Air High Limit temperature value at which the heating stages are locked. Default: F/49.0 C Sets the Discharge Air Low Limit temperature value at which the cooling stages are locked. Default: 45.0 F/7.0 C Anti-Short Cycle timer sets the minimum on/off times for heating and cooling stages. Default: 2.0 min Sets the maximum number of Heating cycles per hour. Default: 4.0 Sets the maximum number of cycles per hour. Default: 4.0 Sets the minimum deadband between the heating and cooling setpoints. Default: 2.0F /1.0C (9600): 9600 bps (19200): 19,200 bps (38400): 38,400 bps (76800): 76,800 bps (Auto): Auto Baud Lockout Level Function Local Unocc Override 2 System Mode Setting Schedule Setting Clock Setting (0): Level 1 Access Access Access Access (1): Level 2 Access No Access No Access Access (2): Level 3 No Access No Access No Access Access Range: 10.0 to sec (Highest): The highest PI Heating or demand controls the rooftop controller. (AV_H3): The average of the three highest PI Heating or demands controls the rooftop controller. (AV_H5): The average of the five highest PI Heating or demands controls the rooftop controller. Range: 70.0 F/21.0 C to F/65.5 C Range: 35.0 F/2.0 C to 65.0 F/18.0 C Range: 0.0 to 5.0 min adjustable in 1-minute increments Note: Set the anti-short cycle timer to 0.0 min for equipment that already has its own anti-short cycle timer. Range: 3.0 to 8.0 cycles per hour Range: 3.0 or 4.0 cycles per hour Range: 2.0F /1.0C to 4.0F /2.0C adjustable in 1.0F /0.5C increments 9
10 Table 2: Installer Configuration Menu (Part 3 of 5) Parameter Appearing on Display Description and Default Selection Options Units Fan del Sets the display scale of the rooftop controller. Default: Imp Fan delay extends fan operation after a heating or cooling cycle has ended. Default: off DI1 Configuration of Digital Input 1. Default: None TOccTime Cal RS Cal OS H stage Sets the duration of the Temporary Occupancy Time when the heating or cooling setpoints in the Occupied mode are established by: an Override Function enabled in the Main User Menu (when the rooftop controller is in the Unoccupied mode) a temporary heating or cooling setpoint Default: 3.0 hrs Sets the desired Room Air Temperature Sensor Calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature. Default: 0.0F /0.0C Sets the desired Outside Air Temperature Sensor calibration (offset). The offset can be added to or subtracted from the actual displayed outside air temperature. Default: 0.0F /0.0C Sets the number of Heating stages. Default: 2 (Si): Celsius/Pa (Imp): Fahrenheit/in. W.C. (on): Extends fan operation by 60 seconds after a heating or cooling cycle has ended. (off): No extension of fan operation after a heating or cooling cycle has ended. Note: The fan delay is only active when the GUI System Mode is set at Auto and the GUI Occupancy is set at Unoccupied. (None): No function is associated with an input. (RemNSB): Remote Night Setback (NSB) via a time clock input disables the internal scheduling of the thermostat. The scheduling is now set per the digital input. The time information still displays, but the menu information related to the schedule is disabled and no longer accessible. Contact open = Occupied; contact closed = Unoccupied (RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capacity of the rooftop controller. (Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter. (Service): A Service alarm is displayed on the rooftop controller when the input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction. Range: 0.0 to 12.0 hrs Note: When adjusting the TOccTime, press the UP/DOWN arrow keys to change the time in 1-hour increments; press and hold the UP/DOWN arrow keys to change the time in 10-hour increments. Range: -5.0F /-2.5C to 5.0F /2.5C adjustable in 1.0F /0.5C increments Range: -5.0F /-2.5C to 5.0F /2.5C adjustable in 1.0F /0.5C increments (1): One stage of heating (2): Two stages of heating Note: Two-stage rooftop controller operation reverts to one-stage operation only when the second heating step is not required. 10
11 Table 2: Installer Configuration Menu (Part 4 of 5) Parameter Appearing on Display Description and Default Selection Options C stage H lock 5 C lock 5 2/4event Aux cont Prog rec Occ CL 4 Occ HT 4 Unocc CL 4 Sets the number of stages. Default: 2 Discontinues Heating operation in response to the outside air temperature. Requires that an outside air temperature sensor be installed and connected. Default: F/49.0 C Discontinues operation in response to the outside air temperature. Requires that an outside air temperature sensor be installed and connected. Default: F/-40.0 C Sets the number and configuration of events. Default: 2 events Energizes peripheral devices (lighting equipment, exhaust fans, and economizers). Default: n.o. Enables Progressive recovery. Default: off Note: Progressive recovery is automatically disabled if DI1 is configured for remote NSB. If network communication is lost with the zone controller(s), the return air sensor controls the rooftop controller to maintain this setpoint. Default: 72.0 F/22.0 C If network communication is lost with the zone controller(s), the return air sensor controls the rooftop controller to maintain this Heating setpoint. Default: 70.0 F/21.0 C If network communication is lost with the zone controller(s), the return air sensor controls the rooftop controller to maintain this Unoccupied setpoint. Default: 82.0 F/28.0 C (1): One stage of cooling (2): Two stages of cooling Note: Two-stage rooftop controller operation reverts to one-stage operation only when the second cooling step is not required. Range: F/-26.0 C to F/49.0 C Range: F/-40.0 C to 95.0 F/35.0 C (2 events): Sets up programming for the following: Event 1 is for Occupied setpoints. Event 2 is for Unoccupied setpoints. (4 events): Sets up programming for the following: Event 1 is for Occupied setpoints. Event 2 is for Unoccupied setpoints. Event 3 is for Occupied setpoints. Event 4 is for Unoccupied setpoints. (n.c.): Contact open = Occupied; contact closed = Unoccupied (n.o.): Contact closed = Occupied; contact open = Unoccupied Note: The contact toggles with the internal Occupied/Unoccupied schedule (or the remote NSB contact if DI1 is used). (on): Progressive recovery enabled Note: The programmed Occupied schedule time is the time at which the desired Occupied temperature is attained. The rooftop controller automatically optimizes the equipment start time. (off): Progressive recovery disabled Note: The programmed Occupied schedule time is the time at which the system restarts. Range: 54.0 F/12.0 C to F/37.5 C Range: 40.0 F/4.5 C to 90.0 F/32.0 C Range: 54.0 F/12.0 C to F/37.5 C 11
12 Table 2: Installer Configuration Menu (Part 5 of 5) Parameter Appearing on Display Description and Default Selection Options Unocc HT 4 Sp range 6 Pressure 6 If network communication is lost with the zone controller(s), the return air sensor controls the rooftop controller to maintain this Unoccupied Heating setpoint. Default: 62.0 F/17.0 C Sets the static pressure transducer range. Default: 0 Sets the static pressure transducer setpoint maintained by the bypass damper. Default: 0.8 in. W.C./200 Pa Range: 40.0 F/4.5 C to 90.0 F/32.0 C (0): 0 in. W.C./0 Pa to 1.5 in. W.C./375 Pa (1): 0 in. W.C./0 Pa to 2 in. W.C./500 Pa (2): 0 in. W.C./0 Pa to 3 in. W.C./750 Pa (3): 0 in. W.C./0 Pa to 4 in. W.C./1,000 Pa (4): 0 in. W.C./0 Pa to 5 in. W.C./1,250 Pa Range: 0 in. W.C./0 Pa to 2 in. W.C./500 Pa 1. RTC MAC is the unique device address of the rooftop controller (from 004 to 127) on the MS/TP network. 2. Local Unocc Override appears only when in the Unoccupied mode. 3. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and hold the UP or DOWN arrow key to change the numeric value in increments of ten. 4. When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F /0.5C increments; press and hold the UP or DOWN arrow key to change the value in 5.0F /5.0C increments. 5. When adjusting the temperature, press the UP or DOWN arrow key to change the value in 5.0F /5.0C increments; press and hold the UP or DOWN arrow key to change the value in 50.0F /50.0C increments. 6. This value is adjustable in 0.1 in. W.C./25 Pa increments. 12
13 Sequence of Operation The sequence of operation of the zones is commanded from the TEC2664Z-3 Rooftop Controller on a Change of Value (COV) basis. The rooftop controller transmits its current sequence mode to the zones, depending on the highest or highest average PI demand. The available sequence values at the zones are heating and cooling. There is a 2-minute delay when toggling between the heating and cooling modes. This delay only applies when the system is switching over from the network demand. The delay is not active when working with the Comm Lost parameter using the return air temperature sensor or the room air temperature sensor. If the system mode of the rooftop controller is set to off, the sequence value at the zone is cooling by default. Note: If no return air sensor is installed and loss of communication occurs, control of the rooftop unit is based on the onboard sensor readings of the rooftop controller. The user can choose between a single highest PI demand, an average of the three highest PI demands, or an average of the five highest PI demands. Using the five highest PI demands as an example, five buffers are required in the BACnet module of the rooftop controller for the PI heating demand, and five additional buffers are required for the PI cooling demand. Each time a new zone sends its PI cooling demand, the rooftop controller compares it to the lowest of the five values already stored and buffers it (if required). The rooftop controller averages these five values, and the PI heating demand or PI cooling demand controls the rooftop controller. See Figure 8 through Figure 18 for sequence of operation examples. Stage 2 Stage 2 Stage 1 Stage 1 100% PI Demand Stage 2 Start/Stop (Approx.) PI Demand (Depends on Control Type Selected) Increase Heating Stage 1 Start/Stop (Approx.) 0% PI Demand Stage 1 Start/Stop (Approx.) Stage 2 Start/Stop (Approx.) PI Demand (Depends on Control Type Selected) Increase Figure 8: Rooftop Controller Sequence of Operation for Two-Stage Heating and Two-Stage 100% PI Demand FIG:tw_stg_htng_tw_stg_clg 13
14 Heating AO1 FIG:cntrl_crv_1 Figure 9: Zone Controller Set for No Reheat, AO2 = 0 VDC and BO5 = Off (Rooftop Controller in Mode) Heating AO1 FIG:cntrl_crv_2 Figure 10: Zone Controller Set for No Reheat, AO2 = 0 VDC and BO5 = Off (Rooftop Controller in Heating Mode) Heating AO2 AO1 * If AO2 stage is locked, then AO1 = minimum position. FIG:cntrl_crv_3 Figure 11: Zone Controller Set for Analog Duct Reheat Only, BO5 = Off (Rooftop Controller in Mode) 14
15 AO2 Heating AO1 FIG:cntrl_crv_4 Figure 12: Zone Controller Set for Analog Duct Reheat Only, BO5 = Off (Rooftop Controller in Heating Mode) Heating B05 A01 FIG:cntrl_crv_5 Figure 13: Zone Controller Set for On/Off Duct Reheat Only, AO2 = 0% and On/Off Reheat Time Base = 10 Seconds (Rooftop Controller in Mode) 15
16 B05 Heating AO1 FIG:cntrl_crv_6 Figure 14: Zone Controller Set for On/Off Duct Reheat Only, AO2 = 0% and On/Off Reheat Time Base = 15 Minutes (Rooftop Controller in Mode) B05 Heating AO1 FIG:cntrl_crv_7 Figure 15: Zone Controller Set for On/Off Duct Reheat Only, AO2 = Off (Rooftop Controller in Heating Mode) 16
17 Heating B05 AO1 AO1 FIG:cntrl_crv_8 Figure 16: Zone Controller Set for On/Off Peripheral Reheat Only, AO2 = 0% (Rooftop Controller in Mode) B05 Heating AO2 AO1 FIG:cntrl_crv_9 Figure 17: Zone Controller Set for Terminal Reheat on AO2 and Peripheral Heating on BO5 (Rooftop Controller in Mode) 17
18 B05 AO2 Heating AO1 FIG:cntrl_crv_10 Figure 18: Zone Controller Set for Terminal Reheat on AO2 and Peripheral Heating on BO5 (Rooftop Controller in Heating Mode) 18
19 Operation Main User Menu Access Modifications Each of the sections in the Main User Menu are accessed and programmed using the five keys on the cover of the TEC2664Z-3 Rooftop Controller. See Rooftop Controller User Interface Keys on page 7 for a description of the five user interface keys. Figure 19 shows a flow chart of the Main User Menu. The system mode can be set to either Off or Auto. The Auto mode allows the rooftop controller to determine, from the average PI demand (if a network is detected) or from the return air sensor PI demands (if a network is not detected), if the rooftop unit is in heating mode or cooling mode. Figure 19: Main User Menu 19
20 Sequence of Auto Status Display Scrolling The priority of alarms is as follows: The TEC2664Z-3 Rooftop Controller features a Comm Lost: This alarm indicates that two-line, eight-character status display. A low-level, communication is lost between the rooftop backlight is always active and can only be seen in the controller and the zone devices on the MS/TP Bus; dark. When the rooftop controller is left unattended, an however, the rooftop controller can remain online auto scroll status display indicates the actual status of with the supervisory controller. the system. SetClock: This alarm indicates that the clock Each item is scrolled one-by-one with the backlight in needs to be reset due to a power failure of more the low-level mode. Pressing any key causes the than 6 hours. low-level backlight to brighten to high-level mode. When left unattended for 30 seconds after changes are DAS Alrm: This alarm indicates a high or low made, the display resumes auto status display alarm at the discharge air sensor. If no discharge scrolling. air sensor is connected (-40.0 F/-40.0 C reading), the associated functions (such as lockouts and To brighten the low-level backlight to high-level mode, alarms) are disabled. If the discharge air sensor is simply press any key on the face of the rooftop shorted (122.0 F/50.0 C reading), the associated controller. The high-level backlight returns to low-level functions (such as lockouts and alarms) are mode when the rooftop controller is left unattended for enabled. 45 seconds. Service: This alarm indicates there is a service If alarms are detected, they are automatically displayed alarm, as per the configurable Digital Input DI1. at the end of the status display scroll. During an alarm message display, the backlight lights up at the same Filter: This alarm indicates that the filters are dirty time as the alarm message and shuts off during the and need to be replaced, as per the configurable remainder of the status display scroll. Two alarm Digital Input DI1. messages can appear at any given time. See Table 3 for the sequence of auto status display scrolling. Table 3: Sequence of Auto Status Display Scrolling Clock Status System Mode Schedule Status Outdoor Temperature 1 Alarms (If Detected) Monday 12:00 A.M. Sys Mode Off Sys Mode Auto Occupied Outdoor xx.x C or F Service 2 Unoccupied DAS Alm 3 Override SetClock 4 Filter 5 Comm Lost 6 1. The outdoor temperature displays only if an outside air temperature sensor is installed. If an outside air temperature sensor is not installed, an ambiguous outdoor temperature displays on the zone controller indicating that no outside air temperature sensor is installed. If no outside air temperature sensor is installed, the auto status display scrolling skips past the outdoor temperature. 2. This alarm is valid only if the DI1 parameter is configured and used as a service alarm. 3. This alarm is valid only if the Dis HL or Dis LL parameter is enabled. 4. This alarm is valid only if the power off clock time retention has expired. 5. This alarm is valid only if the DI1 parameter is configured and used as a filter alarm. 6. This alarm is valid only if communication is lost to the zones (not necessarily a BACnet communication failure). 20
21 Sequence of Manual Status Display Scrolling Manual scrolling of each menu item is achieved by pressing the YES key repeatedly. The last menu item viewed remains on the display for 30 seconds before auto status display scrolling resumes. The temperature reading is automatically updated when scrolling is held. See Table 4 for the sequence of manual status display scrolling. Table 4: Sequence of Manual Status Display Scrolling Clock Status System Mode Schedule Status Outdoor Temperature 1 Monday 12:00 A.M. Sys Mode Off Sys Mode Auto Occupied Outdoor xx.x C or F Alarms (If Detected) Service 2 Unoccupied DAS Alm 3 Override SetClock 4 Filter 5 Comm Lost 6 Current Zone Sequence Return Air Temperature Discharge Air Temperature Current Static Pressure Zone Seq Off RA Temp xx.x F or C DA Temp xx.x F or C Pressure x.x W.C. or Pa Zone Seq Cool Zone Seq Heat Effective PI Heat Demand at the Rooftop Unit Effective PI Cool Demand at the Rooftop Unit Highest PI Heat Demand Zone Address Highest PI Cool Demand Zone Address Heat Out xxx% Cool Out xxx% Heat MAC xxx Cool MAC xxx 1. The outdoor temperature displays only if an outside air temperature sensor is installed. If an outside air temperature sensor is not installed, an ambiguous outdoor temperature displays on the zone controller indicating that no outside air temperature sensor is installed. If no outside air temperature sensor is installed, the auto status display scrolling skips past the outdoor temperature. 2. This alarm is valid only if the DI1 parameter is configured and used as a service alarm. 3. This alarm is valid only if the Dis HL or Dis LL parameter is enabled. 4. This alarm is valid only if the power off clock time retention has expired. 5. This alarm is valid only if the DI1 parameter is configured and used as a filter alarm. 6. This alarm is valid only if communication is lost to the zones (not necessarily a BACnet communication failure). 21
22 FIG:byps_dmpr Sequence of Operation FIG:htng_clng Figure 20: Heating/ Stages Handling Start G Fan Output = On No Bypass Damper Loop = Disabled Bypass Damper Position = 100% Forced Open = 10 VDC Exit Yes Bypass Damper Output Based on Static Pressure Input Exit Figure 21: Bypass Damper Sequence FIG:systm_mde_fn_oprtn Figure 22: System Mode and Fan Operation 22
23 System Mode = Off? Zone Sequence = Cool NO Avg PI Heating Demand > Avg PI Demand? Zone Sequence = Heat NO Avg PI Demand > Avg PI Heating Demand? Zone Sequence = Cool NO FIG:zn_sqnc_slctn Avg PI Demand = Avg PI Heating Demand? Zone Sequence Stays in Existing Mode Figure 23: Zone Sequence Selection 23
24 Zoning Control System Components Table 5: TEC Zoning Control System Code Number Description TEC2647Z-3 Zone Controller for Proportional Zone Damper, On/Off, or Proportional Reheat Control TEC2647Z-3+PIR Zone Controller with Occupancy Sensor for Proportional Zone Damper, On/Off, or Proportional Reheat Control TEC2664Z-3 Rooftop Controller for Control of Up to Two Stages of Heating and Two Stages of in Rooftop, Proportional Bypass Damper, Fan, and Zone Demand Strategies Accessories All the accessories in Table 6 include mounting hardware; contact the nearest Johnson Controls representative to order any of these parts. Note: Review the technical specifications of the accessories prior to their use in an application. Repair Information If the TEC2664Z-3 Rooftop Controller fails to operate within its specifications, refer to the TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications Technical Bulletin (LIT ) for troubleshooting details. For a replacement rooftop controller, contact the nearest Johnson Controls representative. Table 6: Accessories (Order Separately) Code Number Description SEN Remote Inside Air Temperature Sensor TE-6361M-1 1 Duct Mount Air Temperature Sensor (Metal Enclosure) TE-6363P-1 1, 2 Outside Air Temperature Sensor (Plastic Enclosure) SEN Remote Inside Air Temperature Sensor with Occupancy Override and LED DPT D-AB Duct Static Pressure Transmitter, 24 VAC Power, 0 in. W.C./0 Pa to 5 in. W.C./1,245 Pa Input, 0to5VDCOutput MS-BACEOL-0 RS485 End-of-Line Terminator 1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT ) for more details. 2. An outside air temperature sensor is recommended to allow the H lock and C lock parameters of the rooftop controller to discontinue heating or cooling operation in response to the outside air temperature. If an outside air temperature sensor is not installed, an ambiguous outside air temperature displays on the zone controller unless its MenuScro parameter is set to off. 24
25 Technical Specifications TEC2664Z-3 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Power Requirements Analog Output Rating Auxiliary Triac Output Output Rating Digital Input Analog Inputs Temperature Sensor Type Wire Size TEC Zoning Control System Guidelines MS/TP Network Guidelines Temperature Range Backlit Display Heating Control Control Accuracy Minimum Deadband Ambient Operating Conditions Storage Compliance BACnet International United States Canada Europe 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or Safety Extra-Low Voltage (SELV) 0 to 10 VDC into 2k ohm Resistance (Minimum) 19 to 30 VAC, 15 ma to 1 A Continuous Current, 3 A Peak In-Rush Current Voltage-Free Contact across Terminal C to Terminal DI1 Resistive Inputs (RS, OS, and DS) for 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC) Thermistor Sensors Static Pressure: 0 to 5 VDC for Full Static Pressure Range Selected Local 10k ohm NTC Thermistor 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended 31 Zones Maximum per 1 Rooftop Controller 32 Devices Maximum; 4,000 ft (1,219 m) Maximum Cable Length F/-40.0 C to F/50.0 C in 0.5 Increments 40.0 F/4.5 C to 90.0 F/32.0 C 54.0 F/12.0 C to F/37.5 C ±0.9F /±0.5C at 70.0 F/21.0 C Typical Calibrated 2F /1C between Heating and 32 to 122 F (0 to 50 C); 95% RH Maximum, Noncondensing -22 to 122 F (-30 to 50 C); 95% RH Maximum, Noncondensing BACnet Testing Laboratories (BTL) Listed BACnet Application Specific Controller (B-ASC) UL Listed, File E27734, CCN XAPX Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A UL Listed, File E27734, CCN XAPX7 Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003 CE Mark - Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC. Shipping Weight Australia and New Zealand C-Tick Mark, AS/NZS CISPR 22 Compliant Supplier Code Number N lb (0.34 kg) The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Building Efficiency 507 E. Michigan Street, Milwaukee, WI Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners Johnson Controls, Inc. Published in U.S.A. 25
English plain text messages with constant backlight that brightens during user interaction. On/Off, Floating, or Proportional 0 to 10 VDC Control
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin Code No. LIT-12011587
Protects against unwanted thermostat controller tampering. Increases occupancy comfort by providing dehumidification.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin Code No. LIT-12011607 Issued
TEC2602-4 and TEC2602-4+PIR BACnet MS/TP Networked Heat Pump Thermostat Controllers
TEC2602-4 and TEC2602-4+PIR BACnet MS/TP Networked Heat Pump Thermostat Controllers TEC2602-4 and TEC2602-4+PIR Applications The TEC2602-4 and TEC2602-4+PIR Thermostat Controllers are BACnet Master-Slave/
TEC22x1-3 LONWORKS Networked Single Stage Thermostats
TEC22x1-3 LONWORKS Networked Single Stage Thermostats Installation Instructions Part No. 24-9890-463, Rev. Issued September 8, 2006 Applications The TEC2261-3 programmable and TEC2201-3 non-programmable
T600MEP-4 and T600MEP-4+PIR Multi-Stage Economizer Thermostat Controllers
T600MEP-4 and T600MEP-4+PIR Multi-Stage Economizer Thermostat Controllers Installation Instructions T600MEP-4, T600MEP-4+PIR Part No. 24-9890-943, Rev. Issued September 17, 2009 Applications The T600MEP-4
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers Product Bulletin T600HCx-4, T600HPx-4, T600MSx-4, T600MEP-4, T600HCx-4+PIR, T600HPx-4+PIR, T600MSx-4+PIR, T600MEP-4+PIR The T600xxN-4 and T600xxN-4+PIR
Installation Instructions. Applications. North American Emissions Compliance. Installation
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions Part No. 24-9890-1001,
FX07 Field Controller
Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions TEC2001-4 and TEC2001-4+PIR Part No. 24-9890-1125, Rev. B Issued July 13, 2010 Supersedes May 17, 2010
CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter
CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter Product Bulletin CD-Pxx-00-1 Code No. LIT-216525 Issued December 6, 2010 Supersedes September 12, 2008 Johnson Controls offers a complete line of Carbon Dioxide
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators Product Bulletin Code No. LIT-1201742 Issued February 12, 2015 The M9102 and M9104 Series Actuators are directmount,
FX07 Field Controller
Product Bulletin FX07 Field Controller Issue Date May 5, 2011 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,
I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
TEC Series BACnet MS/TP Network Temperature and Humidity Controllers
TEC Series BACnet MS/TP Network Temperature and Humidity Controllers Technical Bulletin Code No. LIT-12011592 Issued March 4, 2013 Supersedes May 13, 2011 Refer to the QuickLIT Web site for the most up-to-date
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM
TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution
Electronic Control Devices The European Product Catalogue 2007
FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically
T5000 T000 LCD Digital Fan Coil Thermostat
T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,
Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types
Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,
MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 852 Group: Controls Part Number: IM 852 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
Electronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Applications The T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers provide control
TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C
Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the
Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7
THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3
HEAT HEAT COOL HEAT PUMP COOL
OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control
INSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE
Installation Instructions. Wireless Adapter/Repeater. Introduction. 30-3001-887 Rev C
/Repeater Installation Instructions 30-3001-887 Rev C Workstation Ethernet bcx Controller Repeater Repeater Introduction Schneider Electric has designed a device that allows Andover Continuum controllers
TB7600 Series Communicating RTU Thermostats with Humidity Control
TB7600 Series Communicating RTU Thermostats with Humidity Control TB7600 Series Thermostat INSTALLATION INSTRUCTIONS APPLICATION The TB7600 Series PI thermostat family is specifically designed for single
MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 917-1 Group: Controls Part Number: IM 917 Date: October 2009 Supercedes: IM 917 MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module
Variable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
T775U Series 2000 Electronic Stand-Alone Controller
T775U Series 2000 Electronic Stand-Alone Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote
Installation Instructions
TP-PRH-A, TP-NRH-A Performance Series Edge Thermidistat Control Installation Instructions Programmable Control A07049 A07048 Non Programmable Control Designed and Assembled in the USA. NOTE: Read the entire
Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types
Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:
T7079A,B Solid State Remote Temperature Controllers
T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
System 350 A350E Electronic Cooling Control
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0899 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
HEAT PUMP PROGRAMMABLE THERMOSTAT
HEAT PUMP PROGRAMMABLE THERMOSTAT SA PM 3 COOL TEMP Form 44014-01 r010408 Model 43168 Owners Manual 1 Congratulations! Heat Pump Programmable Thermostat Model 43168 THERMOSTAT CONTROLS Switches & Buttons...15
T-100-R Installation Guide
T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps
HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps Operation and Maintenance Manual Model: 71028004 Applies to: Single Circuit Water-to-Water Twin Circuit Units Without DDC Controls MAMM WHSP
Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors
European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue 01/03/2013 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for
WHITE-RODGERS COMFORT-SET 90 SERIES
INSTALLATI DESCRIPTI WHITE-RODGERS COMFORT-SET 90 SERIES MULTI-STAGE INSTALLATI/CFIGURATI This White-Rodgers Automatic Setback Digital Thermostat uses microcomputer technology to provide precise time and
QUICK INSTALLATION GUIDE
QUICK INSTALLATION GUIDE Read Installer Notes before removing cover from Thermostat. 1F85RF-275 Wireless Remote Kit INSTALLER NOTES IMPORTANT Do not apply power to the thermostat or wireless sensor until
A99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)
Installation and Maintenance Manual IM 963-1 Group: Controls Part Number: IM 963 Date: July 2010 Supercedes: IM 963 Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)
Power Supply Guide Version 1.0 for D-Show
Power Supply Guide Version 1.0 for D-Show Digidesign 2001 Junipero Serra Boulevard Daly City, CA 94014-3886 USA tel: 650 731 6300 fax: 650 731 6399 Technical Support (USA) tel: 650 731 6100 fax: 650 731
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module
NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module 1. General Description 1 2. General Warnings 1 3. Interface 2 4. Temp Alarms Setting 3 5. Programming 3 6. Light Management 4 7. Installation and
About the HotWire 7900 10-Slot Standalone Shelf
TM HotWire Model 7900 10-Slot Standalone Shelf Installation Instructions Document Number 7900-A2-GN10-10 About the HotWire 7900 10-Slot Standalone Shelf The HotWire 7900 10-Slot Standalone Shelf is designed
Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions
Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions Preface Safety warnings To avoid injury, or damage to the Modbus interface, read all installation and configuration instructions in this
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:
GE Measurement & Control Ventostat Wall Mount Telaire Wall Mount, Humidity and Temperature Transmitters Features: Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low
User Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function
Specifications Supply Voltage 240VAC @ 0.07Amps or 24VAC @ 0.380Amps Relays 240V @ 12A max (resistive) / Comp1,2,3, Aux Ht, Rv O/B) Fuses (Equipment) 15 Amps Maximum 3AG Control Range Minus 10 to 50C Control
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
Energy Smart Electric Water Heater Controller
Installation, Operation and Troubleshooting Instructions Energy Smart Electric Water Heater Controller Table of Contents Installation and Setup, 2 Operation, 5 Troubleshooting, 7 Regulatory Notices, 11
Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual
Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com [email protected] TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting
AXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
AC-115 Compact Networked Single Door Controller. Installation and User Manual
AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.
Communicating Thermostats. Add More Flexibility to Building Automation with New. Communicating Thermostats
Communicating Thermostats Add More Flexibility to Building Automation with New Communicating Thermostats More Choices. More Possibilities. From zone control to rooftop units and nearly everything in between,
DPT-2015 Differential Pressure Transmitter for VAV Box Applications
FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)
MODEL NUMBER: ISC910-1-0-GB-XX ISC911-5-0-GB-XX IXP20 CONTROLLER SPECIFICATIONS Working Environment Plastic Housing... Power ImproX IXP20 Controller INSTALLATION MANUAL Designed to work in an indoor (dry)
How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.
Install Guide CT100 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the
MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.
its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.
Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please
Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT-1900349 Issued April 17, 2015
Code No. LIT-190039 Issued April 17, 015 Refer to the QuickLIT website for the most up-to-date version of this document. The Input/Output Module () Series Controllers are BACnet Application Specific Controllers
PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS
PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000
P66 Series Electronic Fan Speed Controls
P66 Series Electronic Fan Speed Controls Product Bulletin Code No. LIT-125465 Issued September 30, 2009 Supersedes March 23, 2006 The P66 Series Electronic Fan Speed Controls are refrigerant pressure actuated,
HMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
Model 5511 Filler Controller User s Manual Version 1.1 October 2011
Thompson Scale Company WEIGHING SYSTEMS & PACKAGING MACHINERY CONTROLS 2758 Bingle Road Houston, Texas 77055 Phone: 713/932-9071 Fax: 713/932-9379 www.thompsonscale.com Model 5511 Filler Controller User
Product Catalog. Small Building Systems. www.viconics.com
Product Catalog Small Building Systems www.viconics.com Table of Contents VBZS - Viconics BACnet Zoning System VZ1 VZ7200F5000B Bacnet Zone Thermostat... VZ5 VZ7656B1000B Bacnet Rooftop Unit Thermostat...
Single Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
Radiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
Hotwire 5620 RTU Installation Instructions. Contents. Hotwire 5620 RTU Overview. Document Number 5620-A2-GN11-40 September 2001
Hotwire 5620 RTU Installation Instructions Document Number 5620-A2-GN11-40 September 2001 Contents Hotwire 5620 RTU Overview... 1 Product Documentation Online... 4 Getting Started... 5 Installing the DSL
Triple Expansion Chassis
Triple Expansion Chassis AP9604 Installation Manual Contents Introduction............................. 1 Installation.............................. 2 Power Considerations...................... 5 Operations..............................
Wireless Multi-Zone HVAC Control
Refrigeration, Air Conditioning, Heating, and Ventilation Wireless Multi-Zone HVAC Control Courseware Sample 20588-F0 A First Edition Published July 2014 2014 by Lab-Volt Ltd. Printed in Canada All rights
Wireless Alarm System. Wireless Keypad. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location
Wireless Alarm System Wireless Keypad User s Manual 1 2 3 4 Choice ALERT Control all sensors, accessories and remote transmitters from one location Table of Contents Important Safeguards 4 Introduction
BACnet Automation Interface Module (Network Version)
Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP
Installation Instructions
TP --- PAC, TP --- PHP TP --- NAC, TP --- NHP Performance Series AC / HP Thermostat Installation Instructions A07049 Programmable Control A07048 Non-Programmable Control Designed and Assembled in the U.S.A.
TAC I/NETTM MR-AHU-HP. Application Specific Controller
TAC I/NETTM MR-AHU-HP Both the MR-AHU and MR-HP controllers are application specific controllers (ASCs). The intention of the design is to reduce total install cost through pre-engineered control algorithms
Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify
Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2
Install Guide CT101. Caution. Caution
Install Guide CT101 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the
Network Control Engine Product Bulletin
MS-NCE25xx-x Code No. LIT-12011283 Software Release 7.0 Issued December 5, 2014 The Metasys Network Control Engine (NCE) Series controllers provide a cost-effective solution designed for integrating central
GSM-EXT Cable Assembly Installation Guide
GSM-EXT Cable Assembly Installation Guide For Documentation and Online Support: http://www.security.honeywell.com/hsc/resources/mywebtech General Information The GSM-EXT cable assembly is used to connect
Mode Switch. Fan Switch Menu button Program button
Operation 3M-30 Day Time of day Target Temperature Time Slot Touch Screen Current Room Temperature Thermostat Mode Statement of use: The 3M-30 can be used with millivolt, 24VAC, single and 2 stage conventional
Broadband Telecommunications Drop Amplifier
INSTALL SHEET BDA Broadband Telecommunications Drop Amplifier Introduction The Broadband Telecommunications Drop Amplifier (BDA) is a two-way, 1 GHz amplifier designed for customer-premise amplification
