RR986 Research Report. Releases of unignited liquid hydrogen. Prepared by the Health and Safety Laboratory for the Health and Safety Executive 2014

Similar documents
Calculation of Liquefied Natural Gas (LNG) Burning Rates

LNG SAFETY MYTHS and LEGENDS

Control of legionella bacteria in water systems

Office for Nuclear Regulation

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

EXPLANATION OF WEATHER ELEMENTS AND VARIABLES FOR THE DAVIS VANTAGE PRO 2 MIDSTREAM WEATHER STATION

BCGA GUIDANCE NOTE GN 19. Cryogenic Sample Storage Systems (Biostores) Guidance on Design and Operation

RR749. Comparison of risks from carbon dioxide and natural gas pipelines

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

TECHNICAL SPECIFICATION. StirLIN-1 Economy Liquid Nitrogen System

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

MFP14, MFP14S and MFP14SS Automatic Pumps

The ADREA-HF CFD code An overview

The On-Board Refueling Vapor Recovery (ORVR) Evaporative Emission (EVAP) system.

The Behaviour Of Vertical Jet Fires Under Sonic And Subsonic Regimes

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

The paper addresses the boil-off in the cryogenic industry and details the specifics of it when applied to vehicle LNG tanks.

Portable petrol storage containers

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Nitrogen Blanketing for Methanol Storage and Transportation

Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service

This paper describes an instrumentation system concept which should be capable of early detection of a leak-before* break in main steam lines.

Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

Technical Guidance. Application of Portable Gas Detectors in the Petrochemical Industry. Made simple. Introduction

Economic and Social Council

Risk Assessment Data Directory. Report No March Ignition probabilities

Tipping Bucket Rain Gauge Models 6011-A 6011-B

AMTRON E-30 Compact heat and cooling meter

KNC Model 3666 Automatic Pressure Calibration System

INITIAL ASSESSMENT OF THE IMPACT OF JET FLAME HAZARD FROM HYDROGEN CARS IN ROAD TUNNELS AND THE IMPLICATION ON HYDROGEN CAR DESIGN

Newson Gale. Is it ever Safe to use Plastic Drums and Containers in Hazardous areas? White Paper. Author Details:

Fire & Explosion Risks in Service Stations

VAD Variable Area Desuperheaters

COMPARISON OF THE SUBSURFACE MIGRATION OF LPG AND NATURAL GAS

Continuous Thermal Monitoring to Minimise Slag Carry-Over in Steel Production. Slag Detection System

Developing NDE Techniques for Large Cryogenic Tanks Year 2 Report

Hot water supply, distribution and use

ENERGY CARRIERS AND CONVERSION SYSTEMS Vol. II - Liquid Hydrogen Storage - Takuji Hanada, Kunihiro Takahashi

REFRIGERATION (& HEAT PUMPS)

GAS LEAKAGE DETECTION & AUTO ON-OFF GAS SYSTEM

JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS

UNIT 6a TEST REVIEW. 1. A weather instrument is shown below.

Cooling Channel Optimization

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A

OT 40L / 90L. Laboratory Steam Sterilizers

Thermocline Management of Stratified Tanks for Heat Storage

PBX Series Quick Fit Connector Bimetallic Steam Traps

Thermal environments. Tel

A Practical Guide to Free Energy Devices

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Thermal Imaging Test Target THERMAKIN Manufacture and Test Standard

E-gas Instant Gas Water Heaters

The Versatile Differential Pressure Transmitter. By David Gunn Honeywell Process Solutions

THE NEWCASTLE UPON TYNE HOSPITALS NHS FOUNDATION TRUST SAFE USE AND STORAGE OF LIQUID NITROGEN AND SOLID CARBON DIOXIDE (DRY ICE)

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

FLAMMABLE LIQUIDS COMPLIANCE NOTE

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

CORONA E / FLYPPER ELECTRONIC METER MULTI-JET

Continuous flow direct water heating for potable hot water

APPENDIX H7: POOL SPREAD AREAS FOR INSTANTANEOUS TANK FAILURE

DIRECTED WATER DELUGE PROTECTION OF LIQUEFIED PETROLEUM GAS VESSELS

LNG Fuel Tank System LNG Tank overview

OPTIMASS 6000 Technical Datasheet

CHAPTER 4: OFFSITE CONSEQUENCE ANALYSIS

UNDERSTANDING CENTRAL HEATING SYSTEMS

Consequence Analysis: Comparison of Methodologies under API Standard and Commercial Software

Modular Glovebox Systems Gas Purifier Units Antechambers Accessories

RR887. Changes in shift work patterns over the last ten years (1999 to 2009)

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

Rusty Walker, Corporate Trainer Hill PHOENIX

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Flanged and Butt-= Weld Type

THE HUMIDITY/MOISTURE HANDBOOK

Fire and Rescue Service Operational Guidance. GRA 5.8 flashover, backdraught and fire gas ignitions

Determination of Thermal Conductivity of Coarse and Fine Sand Soils

Conservatory Roof Structural Information Guide

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Heating oven with mechanical control

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Heikki Turtiainen *, Pauli Nylander and Pekka Puura Vaisala Oyj, Helsinki, Finland. Risto Hölttä Vaisala Inc, Boulder, Colorado

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

HEAVY OIL FLOW MEASUREMENT CHALLENGES

RR839. A study of current working practices for refrigeration field service engineers

Description of functions

AIR CONDITIONING TECHNOLOGY

2010 Residential Water Heater Replacement Check List

Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems

A practical guide to restrictive flow orifices

RESULTS OF ICARUS 9 EXPERIMENTS RUN AT IMRA EUROPE

Ultrasonic Gas Leak Detection

VAD. Variable Area Desuperheaters

OREGON FIRE CODE Interpretations and Technical Advisories

Heating oven with mechanical convection

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Air Eliminators and Combination Air Eliminators Strainers

Hydraulic control unit series

Accurate Air Flow Measurement in Electronics Cooling

Transcription:

Health and Safety Executive Releases of unignited liquid hydrogen Prepared by the Health and Safety Laboratory for the Health and Safety Executive 2014 RR986 Research Report

Health and Safety Executive Releases of unignited liquid hydrogen M Royle and D Willoughby Health and Safety Laboratory Harpur Hill Buxton Derbyshire SK17 9JN In the long term the key to the development of a hydrogen economy is a full infrastructure to support it, which includes means for the delivery and storage of hydrogen at the point of use, eg at hydrogen refuelling stations for vehicles. As an interim measure to allow the development of refuelling stations and rapid implementation of hydrogen distribution to them, liquid hydrogen is considered the most efficient and cost effective means for transport and storage. The Health and Safety Executive (HSE) have commissioned the Health and Safety Laboratory (HSL) to identify and address issues relating to bulk liquid hydrogen transport and storage and update/develop guidance for such facilities. The second phase of the project involved experiments on unignited and ignited releases of liquid hydrogen (HSE RR987) and computational modelling of the unignited releases (HSE RR985). This position paper details the experiments performed to investigate spills of unignited liquid hydrogen at a rate of 60 litres per minute. Concentration of hydrogen in air, thermal gradient in the concrete substrate, liquid pool formation and temperatures within the pool were measured and assessed. The results of the experimentation will inform the wider hydrogen community and contribute to the development of more robust modelling tools. The results will also help to update and develop guidance for codes and standards. This report and the work it describes were funded by the Health and Safety Executive. Its contents, including any opinions and/or conclusions expressed, are those of the authors alone and do not necessarily reflect HSE policy. HSE Books

Crown copyright 2014 First published 2014 You may reuse this information (not including logos) free of charge in any format or medium, under the terms of the Open Government Licence. To view the licence visit www.nationalarchives.gov.uk/doc/open-government-licence/, write to the Information Policy Team, The National Archives, Kew, London TW9 4DU, or email psi@nationalarchives.gsi.gov.uk. Some images and illustrations may not be owned by the Crown so cannot be reproduced without permission of the copyright owner. Enquiries should be sent to copyright@hse.gsi.gov.uk. ii

CONTENTS EXECUTIVE SUMMARY... V 1. INTRODUCTION... 1 1.1 Background... 1 1.2 Aims... 1 1.3 Report... 1 2. TEST FACILITY... 2 2.1 Test facility... 2 2.2 LH2 tanker... 3 2.3 Release rig... 4 2.4 Test protocol... 6 3. INSTRUMENTATION AND DATA PROCESSING... 7 3.1 Visual records... 7 3.2 Meteorological monitoring... 7 3.3 Data logging... 7 3.4 Hydrogen detection... 8 3.5 Ground level pool thermocouples... 8 3.6 Thermocouples embedded in concrete... 9 4. TEST SETUP... 10 4.1 Concentration sensor locations for tests 5, 6 and 7... 10 4.2 Ground level pool thermocouples... 11 4.3 Embedded thermocouples... 11 4.4 Concentration sensor locations for test 10... 12 5. TEST PROGRAMME AND PARAMETERS... 13 5.1 Test parameters... 14 5.2 Weather conditions... 14 iii

6. RESULTS... 15 6.1 Test 5 horizontal ground release... 15 6.2 Test 6 vertically downward release 100 mm above the ground... 18 6.3 Test 7 horizontal release 860 mm above the ground... 20 6.4 Test 10 vertically downward release 100 mm above the ground... 21 7. DISCUSSION... 23 7.1 Release behaviour - general observations... 23 7.2 Hydrogen cloud dispersion... 23 7.3 Pool formation... 23 7.4 Pool extent... 24 7.5 Solid deposit... 24 7.6 Spills into free air... 25 7.7 Spill behaviour... 25 7.8 Hydrogen concentrations... 25 8. MAIN FINDINGS... 26 9. REFERENCES... 27 iv

EXECUTIVE SUMMARY If the hydrogen economy is to progress, more hydrogen fuelling stations are required. In the short term, in the absence of a hydrogen distribution network, these fuelling stations will have to be supplied by liquid hydrogen road tanker. Such a development will increase the number of tanker offloading operations significantly and these may need to be performed in close proximity to the general public. The aim of this work is to identify and address hazards relating to the storage and transport of bulk liquid hydrogen (LH2) that are associated with hydrogen refuelling stations located in urban environments. Experimental results will inform the wider hydrogen community and contribute to the development of more robust modelling tools. The results will also help to update and develop guidance for codes and standards. The first phase of the project was to develop an experimental and modelling strategy for the issues associated with liquid hydrogen spills; this was documented in HSL report XS/10/06 [1]. The second phase of the project was to produce a position paper on the hazards of liquid hydrogen which was published in 2009, XS/09/72 [2]. This was also published as a HSE research report RR769 in 2010 [3]. This report details experiments performed to investigate spills of liquid hydrogen at a rate of 60 litres per minute. Measurements were made on unignited releases which included concentration of hydrogen in air, thermal gradient in the concrete substrate, liquid pool formation and temperatures within the pool. Computational modelling of the unignited releases has been undertaken at HSL and reported in MSU/12/01 [4]. Ignited releases of hydrogen have also been performed as part of this project; the results and findings from this work are reported in XS/11/77 [5]. v

1. INTRODUCTION 1.1 BACKGROUND The 'Hydrogen Economy' is gathering pace internationally and now in the UK. Over the last year a number of vehicle related demonstration projects have appeared linked into the 2012 Olympics. While in the long term the key to the development of a hydrogen economy is a full infra structure to support it, a short bridging option for Hydrogen Refuelling Stations particularly, is the bulk storage and transport of cryogenic hydrogen, referred to in industry as LH2 (liquid hydrogen). LH2 storage and transport are currently the most efficient and cost effective means of rapidly implementing hydrogen distribution. This will result in a moderately large inventory (e.g. 3 tonnes) local storage of LH2. Although cryogenic liquid storage has been used safely for many years in secure and regulated industrial sites, its use in relatively congested, highly populated urban areas presents a new set of problems in relation to security, safety and associated planning. Although there is previous work by NASA [6] on LH2 relating to its spill behaviour, it is old and was performed in low humidity desert environment. In addition, it does not cover issues around leakage and combustion behaviour thoroughly as these problems were managed by the controls that can be put in place in an isolated specialist facility on the large remote sites used. Research is needed to identify and address issues relating to bulk LH2 storage facilities associated with hydrogen refuelling stations located in urban environments. The existing guidance requires updating and developing for new LH2 storage facilities that are beginning to appear in new challenging environments. 1.2 AIMS Particular issues relating to LH2 include its spill behaviour both as a liquid and vapour, its general combustion properties including flame speed and ignition behaviour as a cool/dense vapour and the complications of this associated with layering effects. LH2 has a low boiling temperature and associated ability to condense out and even solidify oxygen from air to produce a potentially self igniting energetic cocktail of LH2 & liquid or solid oxygen. This series of experiments was intended to determine the range of hazards from a realistic release of LH2, for example, spill rates which are consistent with a hose transfer operation. A number of distinct areas of spill behaviour were investigated: Hydrogen dispersion from unignited spills On ground liquid pool formation Spills into free air Pool formation with respect to storage conditions 1.3 REPORT This report is a factual record of the tests undertaken and of the measurements recorded. 1

2. TEST FACILITY 2.1 TEST FACILITY This section provides a description of the test facility and LH2 supply system. The location of the facility was situated at the Frith Valley site at the Health and Safety Laboratory in Buxton; see Figures 1 and 2. Figure 1 Spill area and release facility Figure 2 Test area and surrounding terrain 2

The facility included: Concrete pad, measuring 32 m in diameter Liquid hydrogen tanker containing 2.5 tonnes of hydrogen 20 metre long, 1 vacuum insulated flexible liquid line Liquid bypass line to vent Nitrogen and hydrogen packs for system purge and tanker operation Local instrument cabin containing the signal conditioning units and data logging system and control plc; Remote control room (300 m from the firing pad) with video displays of the trials area and the networked control system. 6 metre high vent stack to vent excess hydrogen A P&ID of the release system can be seen at Figure 3. N2 Purge supply H2 Vent stack Note: Valves in tanker subsystem greatly simplified full system specification property of BOC Vapour line to vent Liquid bypass line to vent LH 2 Tanker Water drain Vacuum insulated flexible liquid line PI Valve remote PLC Release point (1" nominal bore) All remote valves nitrogen actuated Figure 3 P&ID of the release facility 2.2 LH2 TANKER The liquid hydrogen release system comprises a 2.5 tonne liquid hydrogen tanker, 20 metres of one inch vacuum insulated hose, a release valve station with bypass purge and release valves, a liquid hydrogen bypass hose and a 6 metre high vent stack to vent excess hydrogen. 3

The tanker is an ISO tank container provided by BOC, the tanker contains up to 2.5 tonnes of liquid hydrogen in a vacuum insulated internal tank surrounded by an outer jacket containing liquid nitrogen see (Figure 4). The tanker is fitted with vent valves such that the pressure within the tanker can be lowered. It is also provided with a liquid hydrogen / air heat exchanger such that the pressure in the tanker can be raised. In use, LH2 is allowed to flow into the heat exchanger where it vapourises, the vapour is then fed into the vapour space in the tanker in order to pressurise the liquid hydrogen. The tanker is fitted with a bursting disc rated at 12 bar(g) to protect against overpressurisation. Figure 4 Liquid hydrogen tanker 2.3 RELEASE RIG As delivered, the hydrogen within the tanker is normally at around 4 bar(g) pressure and as such it is super heated relative to its atmospheric boiling point of 20K. To achieve a liquid spill of the contents at atmospheric pressure without excessive flash vaporisation thereby encouraging pooling, the tanker is first depressurised to atmospheric pressure by venting hydrogen from the vapour space above the liquid. This cools the remaining liquid hydrogen within the tanker to its atmospheric boiling point. Some liquid hydrogen is then allowed to flow into the hydrogen / air heat exchanger where it vaporises, this hydrogen vapour is fed to the top of the tanker in order to pressurise the liquid hydrogen such that it will flow out of the tanker when the release valve is opened. Releases of liquid hydrogen made using this system at approximately 1 bar(g) gave a flow rate of approximately 60 litres per minute. Photographs showing the release pipework, vent stack and LH2 tanker can be seen at Figures 5(a) through to 5(c) respectively. 4

Figure 5(a) Connection to liquid hydrogen trailer Figure 5(b) 20 m of 1 nominal bore vacuum line (release pipework) 5

Figure 5(c) Remotely operated valves to deliver hydrogen to the release point 2.4 TEST PROTOCOL After purging all the liquid hydrogen pipe-work with nitrogen and then warm hydrogen, the manual valve on the tanker is opened fully, the actuated valve on the tanker is then opened and the connection between the tanker and the vacuum hose is checked for leaks. The bypass valve to the vent stack is opened and when the pipe-work has sufficiently cooled (as evidenced by liquid air running off the surfaces of the un-insulated portions of the vent pipe), the release valve is opened allowing liquid hydrogen to flow out of the release pipe onto the concrete pad. 6

3. INSTRUMENTATION AND DATA PROCESSING A brief description of the general instrumentation is given in this section. Specific information regarding sensor details, mode of operation and location can be found in section 4 under test set up. 3.1 VISUAL RECORDS Video cameras at standard video speed of 25 frames per second were used to monitor and record selected trials. Two cameras were used one to give a cross wind view and the other to give an alternative view at 90 to the first camera. 3.2 METEOROLOGICAL MONITORING The wind speed and direction was recorded at close proximity to the release point using an ultra-sonic anemometer. Air temperature and relative humidity were also measured at the edge of the release pad by a Vector Instruments weather station. 3.3 DATA LOGGING The weather station outputs and were logged on a laptop connected via the USB port to a Datashuttle USB56 manufactured by IOtech Inc. This system is capable of measuring up to 28 channels at a resolution of up to 22 bits. During the trials, the computer was programmed to record data at a frequency of 0.5 Hz. Multipliers and offsets were programmed into the data collection software such that the recorded sensors read in engineering units. The thermocouples were logged on a laptop connected via the USB port to a Datashuttle USB3005 manufactured by IOtech Inc. This system is capable of measuring up to 32 differential channels at a resolution of up to 16 bits. During the trials the computer was programmed to record data at a frequency of 100 Hz. Multipliers and offsets were programmed into the data collection software such that the recorded sensors read in engineering units. 3.3.1 Data logger calibration The data shuttles were supplied from new with a factory calibration certificate traceable to NIST standards. 7

3.4 HYDROGEN DETECTION 3.4.1 Hydrogen concentration sensors Two methods were used to measure hydrogen concentrations, one method via oxygen depletion and the other via temperature within the cloud using thermocouples, see Figure 6. The oxygen depletion sensors were severely affected, initially by the condensed water vapour within the hydrogen cloud and subsequently by the low temperatures experienced. Therefore the use of these sensors was discontinued for subsequent trials. For the rest of the tests only temperature measurements were made within the cloud and an adiabatic mixing assumption was used to derive the H2 concentration from the temperatures. This calculation was corrected for relative humidity for each test. The thermocouples used were type E, 1 mm diameter stainless steel sheathed with insulated junctions. Figure 6 O2 sensor and thermocouple used for temperature measurement in cloud 3.5 GROUND LEVEL POOL THERMOCOUPLES The thermocouples were type E, 1 mm diameter, 10 cm long stainless steel sheathed with insulated junctions. They were mounted into a frame and spaced 100 mm apart in a horizontal line. The frame was placed in line with the release with the first thermocouple 500 mm from the release point. The tips of the thermocouples were in contact with the surface of the concrete, see Figures 7 and 8. 8

Figure 7 Pool thermocouples Figure 8 Tip of thermocouple in relation to concrete surface 3.6 THERMOCOUPLES EMBEDDED IN CONCRETE Three type E, 1.5mm diameter, stainless steel sheathed thermocouples were embedded into the concrete at depths of 10mm, 20mm and 30mm (see Figure 9) at a distance of 150cm from the release point and offset 20cm from the centre line of the release. Figure 9 Embedded thermocouples 9

4. TEST SETUP 4.1 CONCENTRATION SENSOR LOCATIONS FOR TESTS 5, 6 AND 7 Thirty sensors were positioned at a range of heights and distances from the release point in line with the wind direction, the wind direction for each test is detailed in section 6. The exact positions (distance, heights and thermocouple numbers) can be seen at Table 1. A drawing showing the test layout can be seen at Figure 10. Height (m) 0.25 0.75 1.25 1.75 2.25 2.75 Mount Distance (m) TC No TC No TC No TC No TC No TC No number from release 1 1.5 10 11 12 16 17 18 2 3.0 7 8 9 22 23 24 3 4.5 1 2 3 28 29 30 4 6.0 4 5 6 21 19 20 5 7.5 13 14 15 25 26 27 Table 1 Sensor locations 32 metre concrete pad 16.5m 0 N Concentration sensor mount numbers. Release point 9m Embedded thermocouples 1 Pool thermocouples 2 3 4 5 Concentration sensors were moved round to aline with the wind direction at the time of each release NOT DRAWN TO SCALE Figure 10 Test layout 10

4.2 GROUND LEVEL POOL THERMOCOUPLES The thermocouples were mounted into a frame 100mm apart in a horizontal line and the frame placed in line with the release. The number and positions of the thermocouples are detailed below. TC No Distance from release point (m) 1 0.5 2 0.6 3 0.7 4 0.8 5 0.9 6 1.0 7 1.1 8 1.2 9 1.3 10 1.4 11 1.5 12 1.6 13 1.7 14 1.8 15 1.9 16 2.0 17 2.1 18 2.2 19 2.3 20 2.4 21 2.5 22 2.6 23 2.7 24 2.8 4.3 EMBEDDED THERMOCOUPLES Three thermocouples were embedded into the concrete at depths of 10mm, 20mm, and 30mm at a distance of 150cm from the release point and 20cm offset from centre line. TC No Depth (mm) 1 10 2 20 3 30 11

4.4 CONCENTRATION SENSOR LOCATIONS FOR TEST 10 4.4.1 Sensor locations Thirty sensors were positioned at a range of heights and distances and at compass points around the release point. The exact positions (distance, heights and thermocouple numbers) can be seen at Table 8. A drawing showing the test layout can be seen at Figure 11. Height (m) 0.25 0.75 1.25 1.75 2.25 2.75 Mount Distance (m) TC No TC No TC No TC No TC No TC No number from release 1 0.2 10 11 12 16 17 18 2 1.0 7 8 9 22 23 24 3 1.0 1 2 3 28 29 30 4 1.0 4 5 6 21 19 20 5 1.0 13 14 15 25 26 27 Table 8 Sensor locations 32 metre concrete pad 16.5m 0 N Release point Concentration sensor mount numbers. 270 2 4 1 3 9m 5 180 Figure 11 Test layout 12

5. TEST PROGRAMME AND PARAMETERS The work plan involved releases of liquid hydrogen at a fixed rate of 60 litres per minute for different durations. The release height and orientation was varied see Figures 12, 13 and 14. Table 9 gives the test numbers and details (test numbers 8 & 9 were aborted due to adverse weather and equipment failure). The sensor positions were changed to reflect the release conditions see sections 4.1 and 4.4. Initially a large number of scoping tests were performed to see if a pool formation could be established, to validate operating procedures, check instrumentation location and function and to train personnel in the operation of the facility. These tests do not form part of this report. Test number Release height Release orientation Test Duration (s) 5 Onto ground Horizontal 248 6 100 mm above ground Vertically downwards 561 7 860 mm above ground Horizontal 305 10 100 mm above ground Vertically downwards 215 Table 9 Test number and release orientation Figure 12 Horizontal ground release Figure 13 Horizontal release 860 mm above ground 13

Figure 14 Vertical release 100 mm above ground 5.1 TEST PARAMETERS The nominal storage pressure was measured immediately upstream of the release valve with the tanker valve open and the release valve closed. The nominal release pressure was measured immediately upstream of the release valve with the release valve open. The release rate, nominal storage pressure and release pressure for all the tests are given below in Table 2. Release rate Nominal storage Nominal release (l/m) pressure (barg) pressure (barg) 60 1 0.2 Table 2 Test parameters 5.2 WEATHER CONDITIONS The weather conditions at the time of the release for each test were recorded, see Section 6. The wind direction and speed were measured at close proximity to the release, 86 cm from the ground. The wind direction is relative to north 0, see Figures 10 and 11 (test layout). Tests were not carried out during periods of precipitation, high winds or in the event of the wind direction taking the hydrogen plume back over the tanker. 14

6. RESULTS 6.1 TEST 5 HORIZONTAL GROUND RELEASE The hydrogen was released along the ground (see Figure 12). The weather conditions during the release are summarised below. Relative humidity (%) Temperature ( C) Wind speed m/s Wind direction 68 10.3 2.7 274* * Wind direction in degrees from the North = 0 Wind direction from the south = 180 The temperatures at various depths into the concrete can be seen at figure 15. Figure 15 Embedded thermocouples Temperatures recorded at the surface of the concrete for the first eight thermocouples during the release can be seen at figure 16. The thermocouple measurements taken in contact with the ground show a degree of sub-cooling is occurring as the hydrogen is released and evaporates with temperatures as low as 16K being recorded. In addition steps are evident in the temperature traces as the temperature increases after the release has ended. This is indicative of the melting and boiling of the condensed air. 15

Figure 16 Temperatures at concrete surface (pool thermocouples) The pool dimensions (pool spread) following the release can be estimated from Figure 17, the pool measured approximately 4 metres in length and 1 metre in width. Figure 17 Liquid pool spread 16

A plot showing measured concentrations at varying distances and at a fixed height of 0.25m from the release point can be seen at Figure 18. Note that the hydrogen sensors are positioned for each test such that they were in line with the wind direction see section 4.1 and section 6. 60l/m release Date: 17/09/10 File: lh2unig05.xls Volume % hydrogen 60.0 50.0 40.0 30.0 20.0 Valve open 1.5m 3.0m 4.5m 6.0m 7.5m Valve closed 10.0 0.0 100 200 300 400 500 600 Time (s) Figure 18 Hydrogen concentrations at varying distances from the release at a fixed height of 0.25 m Figure 19 shows the hydrogen cloud passing through the sensors during the release. Figure 19 Hydrogen cloud passing through the sensors 17

6.2 TEST 6 VERTICALLY DOWNWARD RELEASE 100 mm ABOVE THE GROUND The hydrogen was released at a height of 100 mm vertically downwards to provide a release configuration where the momentum of the jet was removed on contact with the ground. The weather conditions during the release are summarised below. Relative humidity (%) Temperature ( C) Wind speed m/s Wind direction 68 10.4 4.0 280* * Wind direction in degrees from the North = 0 Wind direction from the south = 180 Figure 21 shows the liquid hydrogen during the release and the build up of a solid deposit. Figure 21 Liquid hydrogen during the release After the release, the size and spread of the pool could easily be seen on the concrete pad, see Figure 22. The pool was estimated to be about 2.14 m wide and 1.3m long. 18

Figure 22 Pool extent and spread following the release A plot showing measured hydrogen concentrations at varying distances and at a fixed height of 0.25m from the release point can be seen at Figure 23. 60l/m release Date: 17/09/10 File: lh2unig06.xls 30.0 Volume % hydrogen 25.0 20.0 15.0 10.0 tc10-1.5m tc7-3.0m tc1-4.5m tc04-6m tc13-7.5m 5.0 0.0 300 400 500 600 700 800 900 1000 1100 1200 Time (s) Figure 23 Hydrogen concentrations at varying distances from the release at a fixed height of 0.25 m 19

6.3 TEST 7 HORIZONTAL RELEASE 860 mm ABOVE THE GROUND This test arrangement was used to check whether rain out occurred when liquid hydrogen was released as a free jet. The weather conditions during the release are summarised below. Relative humidity (%) Temperature ( ) Wind speed m/s Wind direction* 65 11.5 2.9 297 * Wind direction from the North = 0 Wind direction from the south = 180 A photo of the free jet during the release can be seen in Figure 24. Figure 24 Liquid hydrogen free jet A plot showing the measured hydrogen concentrations at varying heights and at a fixed distance of 1.50 m from the release point can be seen at Figure 25. The momentum of the free jet at the release point keeps the hydrogen jet buoyant at around one metre above the ground. Further away from the release point at approximately 1.5 m the hydrogen begins to move closer to the ground (see figure 24). When the valve is closed the hydrogen begins to rise again which accounts for the increase in concentration measured at the 0.75m sensor position after the release was terminated. 20

60l/m release Date: 17/09/10 File: lh2unig07.xls 70.0 Volume % hydrogen 60.0 50.0 40.0 30.0 20.0 Valve open 0.25m 0.75m 1.25m 1.75m 2.25m 2.75m Valve closed 10.0 0.0 300 400 500 600 700 Time (s) Figure 25 Hydrogen concentrations at varying heights and at a fixed distance of 1.50 m from the release 6.4 TEST 10 VERTICALLY DOWNWARD RELEASE 100 mm ABOVE THE GROUND As the orientation of the release was directed down onto the ground it was decided to change the sensor arrangement (see Figure 11) so that hydrogen concentrations could be measured omnidirectionally rather than uni-directionally. The weather conditions during the release are summarised below. Wind speed Wind direction * Relative Temperature m/s humidity (%) ( C) 1.4 65 87 4.3 * Wind direction from the North = 0 Wind direction from the south = 180 A plot showing measured hydrogen concentrations at fixed distance of 1.0 metre from the release point and at a height of 0.25 metres can be seen at figure 26, the sensor located at position 200 mm from the release was faulty for this test. A plot showing measured hydrogen concentrations at fixed distance of 1.0 metre from the release point and at a height of 2.75 metres can be seen at figure 27. TC 18 was located at a distance of 200 mm from the release and at a height of 2.75 metres. 21

60l/m release Date: 17/09/10 File: lh2unig10.xls 70.0 Volume % hydrogen 60.0 50.0 40.0 30.0 20.0 tc04-1.0m 0 tc1-1.0m 90 tc13-1.0m 180 tc7-1.0m 270 10.0 0.0 100 200 300 400 500 600 Time (s) Figure 26 Hydrogen concentrations at a height of 0.25m and at a fixed distance of 1.0 m from the release 25.0 60l/m release Date: 17/09/10 File: lh2unig10.xls Volume % hydrogen 20.0 15.0 10.0 tc20-1.0m 0 tc30-1.0m 90 tc18-200mm 180 tc25-1.0m 180 tc24-1.0m 270 5.0 0.0 100 200 300 400 500 600 Time (s) Figure 27 Hydrogen concentrations at a height of 2.75 m and at a fixed distance of 1.0 m and 0.2 m (tc 18) from the release The plots show that at one metre from the release point the maximum concentrations were recorded are at a height of 0.25 m. 22

7. DISCUSSION 7.1 THE EFFECT OF STORAGE CONDITIONS ON RELEASE BEHAVIOUR The releases were intended to replicate the type of release that could occur during transfer of LH2 from a road tanker to a fixed storage tank. All the reported releases were made after the tanker had been depressurised to atmospheric pressure and then re-pressurised to 1 bar (g) using hydrogen gas produced by the hydrogen vaporiser built in to the tanker. It could be argued that this is an unrealistic condition from which to release liquid hydrogen and that this condition favours the formation of a pool. In practice it is very unlikely that a release of the type investigated here will occur whilst the tanker is in transit and at a considerable pressure above ambient, and therefore at a considerable super heat relative to its atmospheric boiling point. The releases investigated in this work were intended to replicate the type of release that could occur during transfer of LH2 from the tanker to a fixed storage tank. In practice transfers from a tanker to a fixed storage tank should occur with the hydrogen in the tanker at a similar temperature to that already in the fixed tank. For this reason it is expected that a tanker arriving at site will be at least partially depressurised prior to being re-pressurised to the pressure required to facilitate the transfer, this will result in the LH2 being at a similar degree of super heat as tested here. Results from earlier (unreported) scoping trials indicated that, as would be expected, at a significant level of super heat, thermodynamic flashing of the liquid hydrogen occurs before contact with the ground, and hence at the flow rates investigated here no pooling or solid deposit is formed. 7.2 RELEASE BEHAVIOUR - GENERAL OBSERVATIONS On releasing liquid hydrogen onto the ground, initially the liquid flashes to gas instantaneously due to the large differential temperature between the liquid and the surface of the concrete. As the release continues and the surface of the concrete cools (approximately 150 seconds) the surface becomes sufficiently cool to allow a pool of liquid hydrogen to form. Further into the release a solid deposit was seen to accumulate on the ground, see Figures 28 and 29. The pool shape and spread clearly depends on the release orientation. 7.3 HYDROGEN CLOUD DISPERSION The cloud of hydrogen vapour is visible during the release due to condensation of water within the cloud. The scoping tests (not reported) showed that cloud dispersion is extremely dependent on wind speed, in wind speeds above 5 m/s the cloud stayed close to the ground. The cloud became more readily buoyant in wind speeds of 3 m/s and below. The concentration measurements were greatly influenced by the wind direction and the wind speed but it was noted that in general the flammable envelope approximates to a cone shape with its origin at the release point. 7.4 POOL FORMATION A liquid pool formed on the ground after several minutes into the release. However, it is extremely unlikely that all the liquid present on the ground is liquid hydrogen. A proportion of it is most probably liquid air, further evidence for this is provided by the formation of a solid 23

deposit. This deposit is thought to consist of either solid oxygen, nitrogen or a combination of the two with liquid hydrogen trapped within the matrix. This phenomenon will be investigated further during the ignited phase of the project. 7.5 POOL EXTENT Once the pool was established the extent of the pool remained constant throughout the release. This could be an equilibrium effect at this flow rate. To establish more information regarding pool extent releases with different flow rates would need to be investigated. The vertical releases resulted in an approximately circular pool around the impact point whereas the horizontal release resulted in an elongated pool commensurate with the release direction and momentum. 7.6 SOLID DEPOSIT The tests which impinged hydrogen onto the ground all produced a pool of liquid once the ground had cooled sufficiently, usually about 2.5 minutes into the release. In addition a large solid deposit, which had the appearance of snow, was produced see Figures 28 and 29. Figure 28 Solid deposit showing extent and quantity after LH2 release Figure 29 Close up of centre of solid deposit This solid persisted for some time after the release, appearing to co-exist with a boiling pool of liquid. The solid deposit appeared to sublime rather than melt, possibly due to the relatively close melting and boiling points compared to ambient temperature. After one of the tests an attempt was made to ignite the vapour above the snow deposit, ignition occurred and a vigorous flame ensued. Initial thoughts are that the solid deposit is a mixture of solid nitrogen and oxygen with some liquid hydrogen trapped within the matrix similar to that observed when butane forms hydrates with water Allen 2000 [7]. 24

7.7 SPILLS INTO FREE AIR A release was made into free air in order to determine whether rain out occurred under these conditions. No rain out was evident from the free jet however, when the jet impinged on one of the instrument supports a small amount of liquid was observed to fall to the ground. This liquid may have been liquid air. 7.8 SPILL BEHAVIOUR The storage conditions for the LH2 reported releases were manipulated to create the best conditions for pool formation to occur. To achieve these, the tanker was depressurised to atmospheric pressure in order to cool the liquid hydrogen to its atmospheric boiling point. The tanker was then repressurised to 1 bar(g) with cold hydrogen vapour to enable the releases to be made. During the scoping trials some releases were made from the tanker in its delivery state, i.e at a pressure of 3.5 bar(g). Under these conditions with the hydrogen superheated relative to its atmospheric boiling point no liquid pool or solid deposit was formed. 7.9 HYDROGEN CONCENTRATIONS The concentration contour graph shown in Figure 30 represents a snapshot of experimental data from a typical horizontal release at ground level. The graph was generated using measured hydrogen concentration data at various heights and distances from the release point. The red line represents the 4% concentration contour (LFL) and the green line the 30% concentration contour (stoichiometric). The graph gives an estimate of hydrogen concentrations at a specific time during the release when the wind direction was such that the hydrogen cloud passed through the sensors. Figure 30 Liquid hydrogen free jet 25

8. MAIN FINDINGS The release of liquid hydrogen in contact with a concrete surface can give rise to pooling of liquid once the substrate is sufficiently cooled. Release of liquid hydrogen in close proximity to a concrete surface can result in subcooling due to vapourisation. The release of liquid hydrogen at a rate consistent with the failure of a 1 inch transfer line produces a flammable mixture at least nine metres downwind of the release point. The release of hydrogen at its atmospheric boiling point onto a concrete surface produces a solid deposit of oxygen and nitrogen once the substrate is sufficiently cooled. The solid deposit of oxygen/nitrogen/air appears to trap liquid hydrogen within its matrix producing a potentially hazardous mixture. A release of 60 litres per minute of liquid hydrogen into free air 860 mm above the ground results in total evaporation, i.e there is no rain-out of liquid. 26

9. REFERENCES (1) Willoughby D, Royle M, 2010. Experimental / modelling strategy for issues associated with liquid hydrogen spills, HSL report XS/10/06 (2) Pritchard D K, Rattigan W M, 2009. Hazards of liquid hydrogen: Position paper, HSL report XS/09/72 (3) Pritchard, D.K., 2010. Hazards of liquid hydrogen position paper. HSE 2010 Research Report RR769, Sudbury: HSE Books. (4) Batt, R, Webber D.M, 2012 Modelling of Liquid Hydrogen Spills HSL report MSU/2012/01 (5) Hall, J. 2012 Ignited releases of liquid hydrogen, HSL report XS/11/77 (6) Witcofski, R.D. Experimental Measurements of the Clouds Formed by Liquid Hydrogen Spills, CPIA-Publication 348. In JANNAF Safety and Environmental Protection Subcommittee Meeting, Kennedy Space Centre, Florida, November 1981, 191-206 (7) Allen, J.T. 2000 Characteristics of impinging flashing jets, HSL report FS/00/02 27

Published by the Health and Safety Executive 02/14

Health and Safety Executive Releases of unignited liquid hydrogen In the long term the key to the development of a hydrogen economy is a full infrastructure to support it, which includes means for the delivery and storage of hydrogen at the point of use, eg at hydrogen refuelling stations for vehicles. As an interim measure to allow the development of refuelling stations and rapid implementation of hydrogen distribution to them, liquid hydrogen is considered the most efficient and cost effective means for transport and storage. The Health and Safety Executive (HSE) have commissioned the Health and Safety Laboratory (HSL) to identify and address issues relating to bulk liquid hydrogen transport and storage and update/develop guidance for such facilities. The second phase of the project involved experiments on unignited and ignited releases of liquid hydrogen (HSE RR987) and computational modelling of the unignited releases (HSE RR985). This position paper details the experiments performed to investigate spills of unignited liquid hydrogen at a rate of 60 litres per minute. Concentration of hydrogen in air, thermal gradient in the concrete substrate, liquid pool formation and temperatures within the pool were measured and assessed. The results of the experimentation will inform the wider hydrogen community and contribute to the development of more robust modelling tools. The results will also help to update and develop guidance for codes and standards. This report and the work it describes were funded by the Health and Safety Executive. Its contents, including any opinions and/or conclusions expressed, are those of the authors alone and do not necessarily reflect HSE policy. RR986 www.hse.gov.uk