HEAT AND MASS TRANSFER IN AN INDIRECT CONTACT COOLING TOWER: CFD SIMULATION AND EXPERIMENT



Similar documents
Keywords: Heat transfer enhancement; staggered arrangement; Triangular Prism, Reynolds Number. 1. Introduction

ME6130 An introduction to CFD 1-1

Lecture 3 Fluid Dynamics and Balance Equa6ons for Reac6ng Flows

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

Department of Chemical Engineering, National Institute of Technology, Tiruchirappalli , Tamil Nadu, India

Effect of Aspect Ratio on Laminar Natural Convection in Partially Heated Enclosure

EXPERIMENTAL ANALYSIS OF HEAT TRANSFER ENHANCEMENT IN A CIRCULAR TUBE WITH DIFFERENT TWIST RATIO OF TWISTED TAPE INSERTS

CFD Application on Food Industry; Energy Saving on the Bread Oven

Basic Equations, Boundary Conditions and Dimensionless Parameters

Design of heat exchangers

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra***

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions

Natural Convection. Buoyancy force

Integration of a fin experiment into the undergraduate heat transfer laboratory

Theoretical and Numerical Analysis of Heat Transfer in Pipeline System

CHAPTER 4 CFD ANALYSIS OF THE MIXER

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW

Correlations for Convective Heat Transfer

Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology

International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No , March-April 2015

Design and Pressure Loss Reduction in the Hydrogen Flow Heat Exchanger with Tube Bundles

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics

Numerical Investigation of Heat Transfer Characteristics in A Square Duct with Internal RIBS

Turbulence Modeling in CFD Simulation of Intake Manifold for a 4 Cylinder Engine

Convection heat transfer from tube banks in crossflow: Analytical approach

Dr.A.K.Shaik Dawood. N.V.Kamalesh. Department of Mechanical Engineering, Associate Professor, Karpagam University, Coimbatore , India.

CHEMICAL ENGINEERING AND CHEMICAL PROCESS TECHNOLOGY - Vol. I - Interphase Mass Transfer - A. Burghardt

Effect of air humidity on the convective mass transfer coefficient in a rectangular duct

Effect of Pressure Ratio on Film Cooling of Turbine Aerofoil Using CFD

Laminar Flow and Heat Transfer of Herschel-Bulkley Fluids in a Rectangular Duct; Finite-Element Analysis

Introduction to CFD Analysis

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET)

FLUID FLOW Introduction General Description

COMPUTATIONAL FLOW MODEL OF WESTFALL'S 4000 OPEN CHANNEL MIXER R1. By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY

Heat Transfer Prof. Dr. Ale Kumar Ghosal Department of Chemical Engineering Indian Institute of Technology, Guwahati

INTERNATIONAL JOURNAL OF RESEARCH IN AERONAUTICAL AND MECHANICAL ENGINEERING

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center

Mathematical Modelling and Design of an Advanced Once-Through Heat Recovery Steam Generator

AN EXPERIMENTAL STUDY OF EXERGY IN A CORRUGATED PLATE HEAT EXCHANGER

Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution

Introduction to CFD Analysis

The Effect of Mass Flow Rate on the Enhanced Heat Transfer Charactristics in A Corrugated Plate Type Heat Exchanger

FREESTUDY HEAT TRANSFER TUTORIAL 3 ADVANCED STUDIES

A comparison of heterogenous and homogenous models of two-phase transonic compressible

A COMPUTATIONAL FLUID DYNAMICS STUDY ON THE ACCURACY OF HEAT TRANSFER FROM A HORIZONTAL CYLINDER INTO QUIESCENT WATER

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number R1D1. 13 January 2015

AN EFFECT OF GRID QUALITY ON THE RESULTS OF NUMERICAL SIMULATIONS OF THE FLUID FLOW FIELD IN AN AGITATED VESSEL

THERMAL STRATIFICATION IN A HOT WATER TANK ESTABLISHED BY HEAT LOSS FROM THE TANK

Heat transfer in Flow Through Conduits

CFD Simulation of Subcooled Flow Boiling using OpenFOAM

NUMERICAL SIMULATION OF GAS TURBINE BLADE COOLING FOR ENHANCEMENT OF HEAT TRANSFER OF THE BLADE TIP

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

A heat pipe heat recovery heat exchanger for a mini-drier

Theoretical and Experimental Investigation of Heat Transfer Characteristics through a Rectangular Microchannel Heat Sink

Engine Heat Transfer. Engine Heat Transfer

HEAT TRANSFER ENHANCEMENT AND FRICTION FACTOR ANALYSIS IN TUBE USING CONICAL SPRING INSERT

Flow Physics Analysis of Three-Bucket Helical Savonius Rotor at Twist Angle Using CFD

Heat Transfer Analysis of Cylindrical Perforated Fins in Staggered Arrangement

MAXIMISING THE HEAT TRANSFER THROUGH FINS USING CFD AS A TOOL

International Journal of Heat and Mass Transfer

A Comparison of Analytical and Finite Element Solutions for Laminar Flow Conditions Near Gaussian Constrictions

DEVELOPMENT OF HIGH SPEED RESPONSE LAMINAR FLOW METER FOR AIR CONDITIONING

International Journal of Food Engineering

CFD Application on Food Industry; Energy Saving on the Bread Oven

Experimental investigation of heat transfer and flow friction in a circular tube fitted with regularly spaced twisted tape elements

2. CHRONOLOGICAL REVIEW ABOUT THE CONVECTIVE HEAT TRANSFER COEFFICIENT

Exergy Analysis of a Water Heat Storage Tank

Condensation of Moist Air in Heat Exchanger Using CFD

Energy Efficient Process Heating: Insulation and Thermal Mass

Heat Transfer Enhancement in a Heat Exchanger using Punched and V-cut Twisted Tape Inserts

Sizing of triple concentric pipe heat exchanger

Use of OpenFoam in a CFD analysis of a finger type slug catcher. Dynaflow Conference 2011 January , Rotterdam, the Netherlands

NUMERICAL INVESTIGATIONS ON HEAT TRANSFER IN FALLING FILMS AROUND TURBULENCE WIRES

Comparative Analysis of Gas Turbine Blades with and without Turbulators

International Journal of ChemTech Research CODEN (USA): IJCRGG ISSN: Vol.7, No.6, pp ,

EFFECT ON HEAT TRANSFER AND THERMAL DEVELOPMENT OF A RADIATIVELY PARTICIPATING FLUID IN A CHANNEL FLOW

CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM

Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data Centers

Fired Heater Design and Simulation

Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres

Dynamic Process Modeling. Process Dynamics and Control

Analysis of Heat Pump Condenser's Performance using the Mathematical Model and a Numerical Method

RAISED-FLOOR DATA CENTER: PERFORATED TILE FLOW RATES FOR VARIOUS TILE LAYOUTS

Differential Relations for Fluid Flow. Acceleration field of a fluid. The differential equation of mass conservation

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

AIR STREAMS IN BUILDING FOR BROILERS

OpenFOAM simulations of the Turbulent Flow in a Rod Bundle with Mixing Vanes

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Free Convection Film Flows and Heat Transfer

Effect of design parameters on temperature rise of windings of dry type electrical transformer

Abaqus/CFD Sample Problems. Abaqus 6.10

Chapter 28 Fluid Dynamics

COMPARISON INVESTIGATION ON THE HEAT TRANSFER CHARACTERISTICS FOR SUPERCRITICAL CO 2 FLUID AND CONVENTIONAL REFRIGERANTS ABSTRACT 1.

CFD SIMULATION OF IPR-R1 TRIGA SUBCHANNELS FLUID FLOW

MODELING OF CAVITATION FLOW ON NACA 0015 HYDROFOIL

Dimensional analysis is a method for reducing the number and complexity of experimental variables that affect a given physical phenomena.

Customer Training Material. Lecture 2. Introduction to. Methodology ANSYS FLUENT. ANSYS, Inc. Proprietary 2010 ANSYS, Inc. All rights reserved.

Transcription:

Numerical Heat Transfer, Part A, 54: 933 944, 2008 Copyright # Taylor & Francis Group, LLC ISSN: 1040-7782 print=1521-0634 online DOI: 10.1080/10407780802359104 HEAT AND MASS TRANSFER IN AN INDIRECT CONTACT COOLING TOWER: CFD SIMULATION AND EXPERIMENT Jorge Facão and Armando C. Oliveira Department of Mechanical Engineering, Faculty of Engineering, University of Porto, Portugal The present work is focused on the computational analysis of heat and mass transfer in an indirect contact cooling tower. The main objectives of the study are to contribute to the understanding of heat and mass transfer mechanisms involved in the problem and to check the possibility of making use of a commercial computational fluid dynamics (CFD) code for simulating mass and heat transfer phenomena occurring in indirect cooling towers. The CFD model uses as boundary conditions the temperatures of the tubes obtained by a correlation model developed by Mizushina. The available mass transfer correlations for indirect cooling towers are presented and compared with a correlation obtained from CFD simulations. The assumption of analogy between heat and mass transfer is also discussed. 1. INTRODUCTION Computational fluid dynamics (CFD) has been greatly developed over recent years, mostly due to the rapid advance of computer technology. It is now possible to solve scientific problems in complex geometries. Gan and Riffat [1], Gan et al. [2], and Gan and Hasan [3] have published several works about CFD simulation of indirect contact cooling towers, but they have only simulated the sensible heat transfer between the heat exchanger and air. They also have simulated the spray water trajectory. Kloppers and Kröger have presented Poppe, Merkel, and e-ntu methods for direct contact cooling towers operating in counterflow [4] or in crossflow [5]. The mass transfer coefficient was calculated using the analogy between convective heat and mass transfer. Recently, Ren and Yang [6] have presented an analytical model for different flow arrangements in indirect evaporative coolers, considering non-unity of the Lewis number. The mass transfer coefficient was calculated with the help of a Lewis factor. The present study investigates the major mechanisms of coupled heat and mass transfer in an indirect contact cooling tower, namely in the evaporation cooling process. The mass Received 10 March 2008; accepted 11 July 2008. The authors wish to thank Fundação para a Ciência e a Tecnologia for the post-doc scholarship for Jorge Facão. Address correspondence to Jorge Facão, Department of Mechanical Engineering, Faculty of Engineering, University of Porto, Rua Dr. Roberto Frias, 4200-465 Porto, Portugal. E-mail: jfacao@ fe.up.pt 933

934 J. FACÃO AND A. C. OLIVEIRA NOMENCLATURE a surface area per unity heat exchanger volume, m 2 =m 3 A surface, m 2 c p specific heat capacity at constant pressure, J=kg C D binary diffusion coefficient m 2 =s (water vapor through air) D 0 tube outside diameter, m G air mass velocity in narrowest cross section, kg=sm 2 h heat transfer coefficient i enthalpy, J=kg k thermal conductivity, W=mK k eff effective conductivity, W=mK k m mass transfer coefficient, kg=sm 2 L length of tube bundle, m Le Lewis number _m mass flow rate, kg=s Nu Nusselt number n tubes number of tubes in a row perpendicular to air flow P pressure, Pa Pr Prandtl number Re Reynolds number Sc Schmidt number Sh Sherwood number T temperature, C U overall heat transfer coefficient based on outside tube area W=(m 2 C) w water mass fraction in air, kg=kg a thermal diffusivity, m 2 =s e dissipation rate of turbulent kinetic energy, m 2 =m 3 g cooling tower efficiency j turbulent kinetic energy, m 2 =s 2 m viscosity, kg=ms m t turbulent viscosity, kg=ms q density, kg=m 3 Subscripts air air i air-water interface in inlet LM logarithmic mean out outlet sat saturation spray spray water v vapor water water transfer coefficient was calculated using boundary conditions at the interface between spray water and air supplied by a correlation model. A previous work [7] shows that the mass transfer coefficient has an influence on the rate of change of cooling tower efficiency (qg=qk m )of0.7to1.4. The indirect contact cooling tower in analysis was designed in order to be used with chilled ceilings with a nominal cooling capacity of 10 kw, [8]. The cooler has a section of 0.6 m 1.2 m and a height of 1.55 m. Tube bundle has 228 staggered tubes of 10 mm outside diameter, with transverse tube spacing of 60 mm, longitudinal tube spacing of 30 mm, and a total transfer area of 8.6 m 2. The ratio between heat transfer surface and heat exchanger volume is 25 m 2 =m 3. Figure 1 shows schematically the evaporative cooler and main variables involved. The air flow was forced by a fan located at one tower side. The mass transfer coefficient, k m, can be obtained using enthalpy difference or using water mass fraction difference [7], assuming that the Lewis number is equal to 1 and neglecting the term (c p T) v in calculating the enthalpy of water vapor. _m air ði air;out i air;in Þ¼Ak m Di LM ð1þ with Di LM ¼ i air;out i air;in ln i i i air;in i i i air;out ð2þ

HEAT AND MASS TRANSFER IN A COOLING TOWER 935 Outlet air enthalpy could be calculated considering that all the heat goes from water to air. i air; out ¼ i air; in þ _m water c pwater ðt water;in T water;out Þ _m air Equation (1) was used to calculate the mass transfer coefficient (average value) from experimental measurements and from CFD simulations. Another alternative is to use the analogy between convective heat and mass transfer [9]. or Figure 1. Indirect contact cooling tower and main variables. Sh Nu ¼ k m k qd h ¼ Sc m Pr ¼ a m¼ Le m D ð3þ ð4þ k m ¼ qha k Lem 1 ð5þ Here m 1=3 [9] and the dimensionless quantity Le ¼ a=d is called Lewis number, which for water vapor in air is about 0.87. The mass transfer coefficient for evaporative coolers was correlated by several authors as a function of air mass flow rate. Parker and Treybal [10] were the first to publish a correlation for the mass transfer coefficient in evaporative coolers. They have used a staggered tube bundle with an external diameter of 19 mm and a pitch of 2D 0. The correlation spans the interval 0.68 < G air < 5. k m ¼ 0:049ðG air Þ 0:9 ð6þ

936 J. FACÃO AND A. C. OLIVEIRA where G air is the mass velocity in the narrowest cross section. Parker and Treybal also measured the heat transfer coefficient for the tube bundle (no spray water flow) and found that the mass transfer coefficient predicted by Lewis relationship (Eq. (5)) was 50% smaller than the measured coefficient. Mizushina et al. [11] developed a correlation for mass transfer coefficient based on their experimental tests of four staggered bundles having a pitch of 2D 0 with diameters of 12.7, 19.05, and 40 mm. They have found a spray mass flow rate and diameter dependence. Their data spanned 50 < Re spray < 240 and 1.2 < Re air 10 3 < 14. The correlation may be written in form of k m a ¼ 5:02710 8 ðre air Þ 0:9 ðre spray Þ 0:15 ðd 0 Þ 2:6 ð7þ where a is a surface area per unity of heat exchanger volume and the Reynolds number is defined by, _m spray Re spray ¼ n tubes Lm spray If we assume a tube bundle with an outside diameter of 19 mm, a ¼ 44.8 m 1 and the maximum spray mass flow rate, i.e., Re spray of 240, we may simplify Eq. (7) to k m ¼ 0:036ðG air Þ 0:9 Niitsu et al. [12] have tested bundles with and without fins and they have concluded that for high spray mass flow rates the mass transfer was independent of the spray Reynolds number. The correlation for tubes without fins, with an outside diameter of 16 mm, a longitudinal pitch of 2.38D 0, and a transverse pitch of 2.34D 0 was k m ¼ 0:076ðG air Þ 0:9 Equation (10) is valid for 1.5 < G air < 5. Figure 2 presents the dimensionless correlations presented above as a function of Reynolds number. ð8þ ð9þ ð10þ 2. CORRELATION-BASED MODEL In order to know the temperature of the tubes in the exchanger a correlation based model was implemented. The model was first presented by Mizushina et al. [13] and applied by several researchers. In this model, the variation of spray water temperature could be evaluated; however, the spray water temperature was considered equal to the temperature at the interface water film=air. The temperature variation of the water inside the tubes can be calculated through the thermal balance between water and spray. dt water da ¼ U _m water c pwater ðt water T spray Þ ð11þ

HEAT AND MASS TRANSFER IN A COOLING TOWER 937 Figure 2. Sherwood number as a function of air Reynolds number using different existing correlations. The air enthalpy variation was calculated with the definition of enthalpy potential. di air da ¼ k m _m air ði i i air Þ The model may use previous correlations (Eqs. (5) (10)) to calculate k m,therefore being called a correlation based model. The evolution of spray water temperature was calculated neglecting the water evaporation. dt spray da ¼ _m air di air _m spray c pspray da _m water c pwater dt water _m spray c pspray da To calculate the outlet air temperature, the evolution of water mass fraction in air could be calculated, ð12þ ð13þ dw air da ¼ k m _m air ðw i w air Þ ð14þ The temperatures and enthalpy field in the cooling tower were evaluated through the numerical integration of differential Eqs. (11) (13). The integration was done in the direction of the air flow by the finite differences method. The known boundary conditions were the inlet water temperature, the inlet air enthalpy, and inlet spray water temperature equal to outlet spray water temperature. At the extreme points, the derivatives were approximated by forward or backward differences and in the interior of the grid the derivatives were approximated by central differences. This discretization transforms the differential equations into finite difference equations, whose solutions approximate the solution of the differential equations at discrete points.

938 J. FACÃO AND A. C. OLIVEIRA 3. CFD MODEL The mathematical formulation of the problem was simplified by approximating the three-dimensional geometry by a two-dimensional one. The flow length is more than double the width. The system was considered in steady-state condition. On a cross-section of the tube bundle for two-dimensional simulation the tubes become separate entities. The two-dimensional governing equations for steady-state turbulent flow adopted in the FLUENT code [14] were those related to the balance of mass, momentum, energy, species, turbulent kinetic energy, and turbulent energy dissipation rate. The j-e model with two equations was adopted to simulate turbulence. The flow field (calculated through the momentum equation) was considered to be independent of the temperature field. 4. BOUNDARY CONDITIONS The temperature of the tubes was evaluated by the correlation model. The water mass fraction was calculated to a relative humidity of 100% (i.e., saturation condition) with the help of a user defined function programmed in FLUENT. The water mass fraction at air=water interface is a function of local temperature and local pressure. w i ¼ 0:62198 P sat P P sat The saturation water pressure was evaluated with a correlation published by Hyland and Wexler [15], for the temperature range of 0 to 200 C. where lnðp sat Þ¼C 1 =T þ C 2 þ C 3 T þ C 4 T 2 þ C 5 T 3 þ C 6 lnðtþ C 1 ¼ 5:8002206E3 C 2 ¼1:3914993 ð15þ ð16þ C 3 ¼ 4:8640239E 2 C 4 ¼4:1764768E 5 C 5 ¼ 1:4452093E 8 C 6 ¼6:5459673 The tube bundle was divided into 12 rows, as presented in Figure 3. Table 1 presents tube temperatures evaluated by the correlation model which were used as

HEAT AND MASS TRANSFER IN A COOLING TOWER 939 Figure 3. Boundary conditions. boundary conditions for the CFD model. The conditions are similar to experimentally-tested conditions. Note that water film temperatures and air temperatures at air-spray water interface were assumed to be the same. The conditions used in the correlation model were an inlet water temperature of 21 C, a water mass flow rate Table 1. Boundary conditions at interface air spray water in tubes _m air ½kg=sŠ 1.7 1.3 0.56 Tube T i [ K] T i [ K] T i [ K] 1 290.53 292.62 293.20 2 290.85 292.76 293.29 3 291.02 292.83 293.34 4 291.09 292.86 293.36 5 291.09 292.86 293.36 6 291.05 292.84 293.35 7 290.97 292.81 293.33 8 290.88 292.78 293.31 9 290.77 292.73 293.28 10 290.66 292.68 293.25 11 290.53 292.62 293.21 12 290.40 292.57 293.17 Water mass flow rate of 0.8 kg=s, inlet water temperature of 21 C, and spray water mass flow rate of 1.37 kg=s.

940 J. FACÃO AND A. C. OLIVEIRA of 0.8 kg=s, and a spray water mass flow rate of 1.37 kg=s. In the CFD model at inlet, the air=vapor mixture has a uniform velocity, temperature (20 C), and water concentration (0.007258). Outflow boundary conditions are used to model flow exit where the details of the flow velocity and pressure are not known prior to solution of the flow problem [14]. The sump temperature was equal to the wet bulb temperature. The density of the mixture was evaluated by considering it as an incompressible ideal gas and c p, k, and m were calculated for a typical air temperature in the cooling tower, around 20 C. The mass diffusivity and thermal diffusion coefficient were evaluated by the kinetic theory. The effects of radiation heat transfer in the overall heat transfer were neglected. 5. SPACE DISCRETIZATION A structured two-dimensional grid has been set up with FLUENT s grid generation package, Gambit. The structured grid has the advantage that convergence occurs more rapidly and, often, more accurately. The grid was refined near the tubes where the largest variations of the thermal and fluid dynamic variables occur. Figure 4 presents the structured grid adopted in numerical computation. The overall geometry has about 347,270 cells. To test the grid independence, a model with an increase in resolution with a factor of 2 in all directions was tested. This represents an increase of the number of cells by a factor of 4 and then the required computation time for the CFD simulation also increases by approximately a factor of 4 [16]. The difference in outlet water mass fraction was about 1%, which means that the solution was independent of the grid size. Figure 4. Short representation of the structured grid adopted in the numerical computation.

HEAT AND MASS TRANSFER IN A COOLING TOWER 941 6. RESULTS In CFD simulations the solution was considered as converged when residuals were lower than 10 7 for the energy equation and 10 4 for the other equations. The evolution of outlet water mass fraction as a function of the number of iterations was also checked. To check the influence of the inlet relative humidity, two CFD simulations were performed with 90% and 1% as inlet boundary conditions. The CFD simulations showed that the inlet relative humidity doesn t influence the mass transfer coefficient, as in the theory the Sherwood number was only a function of the air Reynolds number. The CFD average mass transfer coefficient correlation as a function of air mass flow rate is k m ¼ 0:0413ðG air Þ 1:11 The correlation obtained experimentally for the same cooler was [5] k m ¼ 0:064ðG air Þ 0:81 In order to compare these correlations and other existing ones, Figure 5 presents a dimensionless representation. For higher air flow rates CFD simulations are very close to the experimental correlation. For smaller air flow rates there was a small deviation. The CFD simulation underestimates the mass transfer coefficient, especially for lower values of Reynolds number. As mentioned in the introduction, the mass transfer coefficient could be calculated after the heat transfer coefficient using the analogy between heat and mass transfer. Figure 6 presents a comparison of the mass transfer coefficient evaluated ð17þ ð18þ Figure 5. Comparison of mass transfer coefficient correlations.

942 J. FACÃO AND A. C. OLIVEIRA Figure 6. Sherwood number evaluated from experimental results through CFD simulations and by analogy between heat and mass transfer. by CFD simulations, by experiment, and by the analogy between heat and mass transfer. Two heat transfer correlations were used: Zhukauskas correlation [17] for a cross flow across tube banks and a heat transfer correlation evaluated by CFD simulations for the cooling tower under analysis. The mass transfer coefficient Figure 7. Contours of air velocity inside the evaporative cooler in analysis.

HEAT AND MASS TRANSFER IN A COOLING TOWER 943 evaluated through analogy lies below the experimental and CFD correlations. The difference between the Zukauskas correlation and CFD results may be justified by the nonuniform flow distribution in the existing cooling tower (see Figure 7). The location of the fan air inlet (on one tower side) leads to a nonuniform flow pattern. Therefore, to improve flow distribution the fan should be located at tower exit or, with this configuration, baffles could be used to guide the air. 7. CONCLUSIONS This article presented an analysis performed with the FLUENT code, aimed at improving the understanding of heat and mass transfer mechanisms that occur in indirect contact cooling towers and evaporative coolers. The conclusions obtained can be summarized as follows.. The correlation for the mass transfer coefficient obtained through CFD was close to the experimental correlation, especially for higher air flow rates. The minimum deviation for Sherwood number was 4% and the maximum deviation was 32%, which is acceptable for a two-phase turbulent flow.. The use of analogy between heat and mass transfer to estimate the mass transfer coefficient revealed a deviation to experimental results of 53 and 90% (in Sherwood number), depending on the use of the heat transfer coefficient from the Zhukauskas correlation or from CFD simulations. The non-uniform flow distribution inside the cooling tower could be the explanation for the difference between the heat transfer coefficient evaluated from the Zhukauskas correlation and from CFD simulations. A limitation of the present numerical study regards neglecting the liquid film (spray) in the model. This aspect will be addressed in a future work. REFERENCES 1. G. Gan and S. B. Riffat, Numerical Simulation of Closed Wet Cooling Towers for Chilled Ceiling Systems, Appl. Thermal Eng., vol. 19, pp. 1279 1296, 1999. 2. G. Gan, S. B. Riffat, Li Shao, and P. Doherty, Application of CFD to Closed-Wet Cooling Towers, Appl. Thermal Eng., vol. 21, pp. 79 92, 2001. 3. Ala Hasan and Guohui Gan, Simplification of Analytical Models and Incorporation with CFD for the Performance Prediction of Closed-Wet Cooling Towers, Int. J. Energy Research, vol. 26, pp. 1161 1174, 2001. 4. J. C. Kloppers and D. G. Kröger, A Critical Investigation into the Heat and Mass Transfer Analysis of Counterflow Wet-Cooling Towers, Inter. J. Heat and Mass Transfer, vol. 48, pp. 765 777, 2005. 5. J. C. Kloppers and D. G. Kröger, A Critical Investigation into the Heat and Mass Transfer Analysis of Crossflow Wet-Cooling Towers, Numer. Heat Transfer A, vol. 46, no. 8, pp. 785 806, 2004. 6. Chengqin Ren and Hongxing Yang, An Analytical Model for the Heat and Mass Transfer Processes in Indirect Evaporative Cooling with Parallel=Counter Flow Configurations, Inter. J. Heat and Mass Transfer, vol. 49, pp. 617 627, 2006.

944 J. FACÃO AND A. C. OLIVEIRA 7. Jorge Facão and Armando C. Oliveira, Heat and Mass Transfer Correlations for the Design of Small Indirect Contact Cooling Towers, Appl. Thermal Eng., vol. 24, pp. 1969 1978, 2004. 8. Jorge Facão and Armando C. Oliveira, Thermal Behaviour of Closed Wet Cooling Towers for use with Chilled Ceilings, Appl. Thermal Eng., vol. 20, pp. 1225 1236, 2000. 9. Hans Dieter Baehr and Karl Stephan, Heat and Mass Transfer, 2nd ed., Springer, Berlin, 2006. 10. R. O. Parker and R. E. Treybal, The Heat Mass Transfer Characteristics of Evaporative Coolers, Chem. Eng. Progress Symp. Ser., vol. 57, no. 32, pp. 138 149, 1961. 11. T. Mizushina, R. Ito, and H. Miyashita, Experimental Study of an Evaporative Cooler, Inter. Chem. Eng., vol. 7, no. 4, pp. 717 732, 1967. 12. Y. Niitsu, K. Naito, and T. Anzai, Characteristics and Methods of Thermal Design of Evaporative Coolers, J. SHASE, vol. 43, no. 7, 1969. 13. T. Mizushina, R. Ito, and H. Miyashita, Characteristics and Methods of Thermal Design of Evaporative Coolers, Inter. Chem. Eng., vol. 8, no. 3, pp. 532 538, 1968. 14. FLUENT, FLUENT 6.3 User s Guide, 2006. 15. R. W. Hyland and A. Wexler, Formulation for Thermodynamic Proprieties of the Saturated Phases of H 2 O from 173.15 K to 473.15 K, ASHRAE Trans., vol. 89, no. 2A, pp. 500 519, 1983. 16. Yunus A. Cengel and John M. Cimbala, Fluid Mechanics: Fundamentals and Applications, McGraw-Hill, Boston, 2004. 17. A. Zhukauskas, Convective Heat Transfer in Cross Flow, in S. Kakaç, R. K. Shah, and W. Aung (eds.), Convective Heat Transfer, Wiley, New York, 1987.