12 Appendix 12 Earth Electrodes And Earth Electrode



Similar documents
A practical guide to earth resistance testing

SOIL RESISTIVITY MEASUREMENTS

Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria

ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

Earth Ground Resistance

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

User Guide. 4 wire Earth Resistance Tester Model GRT300

Coupling Effect in Substation Ground Measurements

UNDERSTANDING GROUND RESISTANCE TESTING. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-on Measurements E I

Chapter 22: Electric motors and electromagnetic induction

GroundRod AC Substation Earthing Tutorial

Elementary circuits. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Introduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory

Earth electrode. and. earth loop impedance testing. Theory and applications

Understanding Soil Resistivity Testing

104 Practice Exam 2-3/21/02

Video Camera Installation Guide

PART 1 - INTRODUCTION...

Designing For A Low Resistance Earth Interface (Grounding) Roy B. Carpenter, Jr. Joseph A. Lanzoni

DET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers

Lightning Protection Introduction

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

CATHODIC PROTECTION SYSTEM DESIGN

Digital Ground Resistance Tester. Models 4620 & Digital Ground Resistance Tester

ELECTRICAL FUNDAMENTALS

DET3 and 4 Contractor Series Earth/Ground Resistance Testers

Objectives 200 CHAPTER 4 RESISTANCE

Substation Grounding Study Specification

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Electrical Fundamentals Module 3: Parallel Circuits

Just a Dipole. Gary Wescom N0GW July 16, 2007

DET3 Contractor Series

environment briefing02

The Electrical Properties of Materials: Resistivity

Module 1, Lesson 3 Temperature vs. resistance characteristics of a thermistor. Teacher. 45 minutes

Theory of Heating by Induction

Ground Resistance Clamp On Tester

ElectroMagnetic Induction. AP Physics B

Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

NEGRP TEST SUMMARY. Joseph A. Lanzoni, November 2005

V out. Figure 1: A voltage divider on the left, and potentiometer on the right.

Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Z +

1. The diagram below represents magnetic lines of force within a region of space.

TABLE OF CONTENT

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Chapter 13: Electric Circuits

Georgia Performance Standards Framework for Physical Science 8 th Grade. Powering Satellites

7. What is the current in a circuit if 15 coulombs of electric charge move past a given point in 3 seconds? (1) 5 A (3) 18 A (2) 12 A (4) 45 A

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.

EARTHING SYSTEM CALCULATION

Chapter 9. Bonding and Grounding

METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS

Application Note: PCB Design By: Wei-Lung Ho

Measuring Impedance and Frequency Response of Guitar Pickups

INTERNATIONAL STANDARD

I = V/r P = VI. I = P/V = 100 W / 6 V = amps. What would happen if you use a 12-volt battery and a 12-volt light bulb to get 100 watts of power?

Thermistor Basics. Application Note AN-TC11 Rev. A. May, 2013 Page 1 WHAT IS A THERMISTOR?

Application Note. So You Need to Measure Some Inductors?

Modeling of Transmission Lines

Selecting Receiving Antennas for Radio Tracking

Detection of Pipe Leaks Connection of Pulse Monitoring System in Thermal Utilities

AP Physics Electricity and Magnetism #4 Electrical Circuits, Kirchoff s Rules

Seven. Easy Steps. Your Own Walkway, Without Mortar. or Concrete. to Installing. Driveway and Patio

Chapter 11. Inductors ISU EE. C.Y. Lee

Application Guide for Equipotential Earth Mat Installation on Substation Structure Mounted Switches

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

Fault location on power cables. Fault location on power cables

What Really Is Inductance?

Insulation Resistance Testing of Low Voltage Cables in the Field

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples

Earthing Guidance Notes

Operating Instructions

Everline Module Application Note: Round LED Module Thermal Management

Electrical Safety Tester Verification

1. A wire carries 15 A. You form the wire into a single-turn circular loop with magnetic field 80 µ T at the loop center. What is the loop radius?

4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is:

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

V=5 L 3 GROUNDING ELECTRODES EXPLAINED

Earthing Techniques 1. SOIL RESISTIVITY TESTING THEORY OF SOIL RESISTIVITY INTERPRETATION AND MODELLING OF RESULT...

DESIGNING STRUCTURES IN EXPANSIVE CLAY

REINFORCED CONCRETE. Reinforced Concrete Design. A Fundamental Approach - Fifth Edition. Walls are generally used to provide lateral support for:

PL-277x Series SuperSpeed USB 3.0 SATA Bridge Controllers PCB Layout Guide

DATA SHEET THICK FILM CHIP RESISTORS Introduction

Voltage Loss Formula s

METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS

An equivalent circuit of a loop antenna.

PTC-Resistor Temperature-Sensors MINIKA to DIN and DIN

SECTION 5: SANITARY SEWER SYSTEM DESIGN

STUDY GUIDE: ELECTRICITY AND MAGNETISM

Antenna Basic Concepts

A99B Series Temperature Sensors

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

Multi-Function Ground

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Force on Moving Charges in a Magnetic Field

Attachment G-1: Pit Latrine Diagram. Fig E.1a: Pit Latrine. Fig E.1b: Plan View of Twin Pits

Transcription:

12 Appendix 12 Earth Electrodes And Earth Electrode Testing 12.1 Introduction This appendix provides guidance and background information an earth electrode testing and some limited information on earth electrode design and improvement. It is not intended to cover the design of large complex earth systems, soil resistivity tests or test methods such as the clamp-voltage earth testers (e.g. the attached rod and similar methods). More information on these subjects can be found in BS 7430 (for electrode design, earth design, soil resistivity testing) and various manufacturers for various testing instruments using clamps. This appendix has been based on information kindly provided by Megger. 12.2 Earth resistance Broadly speaking, earth resistance is the resistance of soil to the passage of electric current. Actually, the earth is a relatively poor conductor of electricity compared to normal conductors like copper wire. But, if the area of a path for current is large enough, resistance can be quite low and the earth can be a good conductor. It is the earth s abundance and availability that make it an indispensable component of a properly functioning electrical system. Earth resistance is measured in two ways for two important fields of use: 1. Determining effectiveness of ground grids and connections that are used with electrical systems to protect personnel and equipment. 2. Prospecting for good (low resistance) ground locations, or obtaining measured resistance values that can give specific information about what lies some distance below the earth s surface (such as depth to bed rock). 12.3 Nature of an earth electrode Resistance to current through an earth electrode actually has three components: Resistance of the electrode itself and connections to it. Contact resistance between the electrode and the soil adjacent to it. Resistance of the surrounding earth. 21 12

Guide to the Wiring Regulations Electrode Resistance Rods, pipes, masses of metal, structures, and other devices are commonly used for earth connections. These are usually of sufficient size or cross section that their resistance is a negligible part of the total resistance. Electrode-earth contact resistance This is much less than you might think. If the electrode is free from paint or grease, and the earth is packed firmly, contact resistance is negligible. Rust on an iron electrode has little or no effect; the iron oxide is readily soaked with water and has less resistance than most soils. But if an iron pipe has rusted through, the part below the break is not effective as a part of the earth electrode. Figure 12.1 Interface of earth and electrode Resistance of surrounding earth An electrode driven into earth of uniform resistivity radiates current in all directions. Think of the electrode as being surrounded by shells of earth, all of equal thickness (see Figure 12.1). The earth shell nearest the electrode naturally has the smallest surface area and so offers the greatest resistance. The next earth shell is somewhat larger in area and offers less resistance. Finally, a distance from the electrode will be reached where inclusion of additional earth shells does not add significantly to the resistance of the earth surrounding the electrode. 12 22

12.4 Basic test method for earth resistance The resistance to earth of any system of electrodes theoretically can be calculated from formulas based upon the general resistance formula: R = ρ L A where ρ is the resistivity of the earth in ohm-cm L is the length of the conducting path A is the cross-sectional area of the path The theory behind resistance measurement gets quite involved but is simplified by assuming that the earth s resistivity is uniform throughout the entire soil volume under consideration. The earth tester generates an ac signal, which is fed into the system under test. The instrument then checks the status of the circuits for good connection and noise. If either of these variables is out of specification then the operator is informed. Having checked that the conditions for test are met, the instrument automatically steps through its measurement ranges to find the optimum signal to apply. Measuring the current flowing and the voltage generated the instrument calculates and displays the system or electrode resistance. There are three basic test methods as noted below. The first two are shown schematically in Figures 12.2 and 12.3. 1. Fall of potential method, or three-terminal test. 2. Dead earth method (two-point test). 12.5 Fall of potential method 12.5.1 Introduction and method This three-terminal test is the method that can be carried out with three or four terminal earth testers. Although four terminals are necessary for resistivity measurements, the use of either three of four terminals is largely optional for testing the resistance of an installed electrode. The use of three terminals is more convenient because it requires only one lead to be connected. 23 12

Guide to the Wiring Regulations Figure 12.2 Fall of potential method With a three-terminal instrument, connect X to the earth electrode. With a four-terminal tester, P1 and C1 terminals on the instrument are jumpered and connected to the earth electrode under test. The driven reference rod C should be placed as far from the earth electrode as practical; this distance may be limited by the length of extension wire available, or the geography of the surroundings. Leads should be separated and snaked, not run close and parallel to each other, to eliminate mutual inductance. Potentialreference rod P is then driven in at a number of points roughly on a straight line between the earth electrode and C. 12.5.2 Simplified analysis for fall-of-potential test This reading with P at 50% of the distance from the earth electrode to C is noted as R1. Reference probe P is then moved to a location 40% of the distance to C. The reading at this point is noted as R2. A third reading, R3, is made with P at a 60% distance. The average of R1, R2 and R3 is calculated as RA. You determine the maximum deviation from the average by finding the greatest difference between individual readings and the average. If 1.2 times this percentage is less than your desired test accuracy, RA can be used as the test result. An example of this technique is as follows: R1 = 58 Ω, R2 = 55 Ω, R3 = 59 Ω RA = 58 + 55 + 59 = 57.3 Ω 12 24

RA R2 = 57.3 55 = 4.0% 4.0% 1.2 = 4.8% If your desired accuracy was 5%, 57.3 Ω (RA) could be used as the result. This is usually more than accurate for most applications. If the result is not within the required accuracy, probe C has to be placed farther away and the tests repeated. There are many variations on the fall of potential method. For example, resistance readings are logged for each of the points. A curve of resistance vs. distance is then drawn. Correct earth resistance is read from the curve for the distance that is about 62% of the total distance from the earth electrode to C. The detail of further analysis of these methods is outside the scope of this book. 12.5.3 Lazy spikes The problem with three or four electrode methods is often the ability to drive test electrodes. The latest designs of digital earth testers can operate with very high temporary spike resistances and still give reliable and accurate results. Because the current and voltage are measured separately, it enables electrode measurements to be carried out with test spike resistances up to 400 kω. However, in urban situations, tests can be carried out using street furniture such as sign posts, metal fences and bollards. Where this is not possible, results have been obtained by laying the temporary electrodes on a wet patch of concrete. Coiled metal chains or metallized ground mats, with water poured over them, make an even better electrode because they conform more intimately to the earth s surface than does a rigid spike. This technique has led to measured values of spike of less than 10 kω, well inside the maximum value that will cause an error to the reading. With modern instruments, any problem with the temporary spikes will usually be indicated on the display to show that a reading may not be valid. A more suitable position for the spike may have to be used such as along the gap between paving stones, a crack in concrete, or in a nearby puddle. As long as warning indicators do not appear, sufficient contact has been made and a reliable test may be performed. 12.6 Dead earth method When using a four-terminal instrument, P1 and C1 terminals connect to the earth electrode under test; P2 and C2 terminals connect to an all-metallic metal system (e.g. a water pipe system). The water system could be any suitable metal structure 25 12

Guide to the Wiring Regulations or similar.with a three-terminal instrument, connect X to the earth electrode, P and C to the pipe system, see Figure 12.3. If the water system is extensive (covering a large area), its resistance should be low and is usually much less than one ohm. You can then take the instrument reading as being the resistance of the electrode under test. Figure 12.3 Dead earth (two-electrode) method The dead earth method is the simplest way to make an earth resistance test. With this method, resistance of two electrodes in series is measured (the driven rod and the water system). It is, however important to note the limitations to this test method as follows: The dead earth metal (e.g. water pipe) system must be extensive enough to have a negligible resistance The dead earth metal (e.g. water pipe) system must be metallic throughout The earth electrode under test must be far enough away from the dead earth (e.g. water pipe) system to be outside its sphere of influence. In some locations, your earth electrode may be so close to the dead earth system (e.g. water pipe system) that you cannot separate the two by the required distance for measurement by the two-terminal method. Under these circumstances, you can connect to the water pipe system and obtain a suitable earth electrode. 12 26

12.7 How to improve earth resistance When you find that your earth electrode resistance is not low enough, there are several ways you can improve it as follows Lengthen the earth electrode in the earth. Use multiple rods. Treat the soil. 12.7.1 Effect of rod depth As you might suspect, driving a longer rod deeper into the earth, materially decreases its resistance. In general, doubling the rod length reduces resistance by about 40%. The curve of Figure 12.4 shows this effect. Figure 12.4 Effect of vertical depth on resistance to earth 27 12

Guide to the Wiring Regulations The subject of stability of single, vertical earth electrodes often causes confusion. The depth of a vertical rod is the decisive factor for stability as the effects of drying out or freezing effect the upper part of the rod most significantly. Therefore a 3 m rod with installed resistance of say 300 ohms will be more stable than a 1.2 m rod with resistance of say 100 ohms. 12.7.2 Use of multiple rods Two well-spaced rods driven into the earth provide parallel paths. They are, in effect, two resistances in parallel. The rule for two resistances in parallel does not apply exactly; that is, the resultant resistance is not one-half the individual rod resistances (assuming they are of the same size and depth). Actually, the reduction for two equal resistance rods is about 40%. If three rods are used, the reduction is 60%; if four, 66% as shown in Figure 12.5. Figure 12.5 Effect of rod spacing on overall resistance When you use multiple rods, they must be spaced further apart than the length of their immersion. 12 28

12.7.3 Treatment of the soil Chemical treatment of soil is a good way to improve earth electrode resistance when you cannot drive deeper ground rods because of hard underlying rock, for example. It is beyond the scope of this book to recommend the best treatment chemicals for all situations. One popular approach is to backfill around the electrode with a specialized conductive concrete. A number of these products, like bentonite, are available on the market. This subject does become specialist and it is worth discussing treatment with a specialist earthing design or installation organisation. 29 12