Model KGS/KGP. Automatic Transfer Switches Bypass/Isolation. Transfer Switch Standard Features. Controller. Standard Transition Models (KGS) Ratings



Similar documents
Model KSS. Transfer Switch Standard Features. Available Controllers. Ratings. Automatic Transfer Switches Standard Specific-Breaker Rated

Model: RXT. Model RXT Automatic Transfer Switch. Standard Features. Standard Interface Board. Available Models

MPAC 1500 Controller

Controller Features. Modbus link to define inputs and outputs. Programmable Outputs Auxiliary switch fault Common fault.

RXT. Model: Model RXT Automatic Transfer Switch

Model: RDT. Automatic Transfer Switch Amps. 200 amp load center models use up to 24 circuit breakers

Automatic Transfer Switch Controller

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Decision-Maker Paralleling System. Power Distribution Switchboards and Circuit Breakers. Standard Features

GTEC transfer switch open transition

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, (210) 16 (407) 5.5 (140) (283) 16 (407) 5.5 (140)

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

ASCO SERIES 185 Power Transfer Switches

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Power Meter Series 700

How To Operate A Gec Transfer Switch Open Transition Amp Power Supply

Applications. Remote Display Mounting Kits

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Series TS Amp. Automatic Transfer Switches

STRATO LED Drivers 70W, Single output

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Transfer switch BTPC open, closed or delayed transition

38 Series - Relay interface modules A

Bulletin 150 SMC Flex Smart Motor Controller Specifications

SmartOnline V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 Series - Relay interface modules A

OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

Uninterruptible Power Supply

Thyristor-controlled power supplies and battery chargers

3500/62 Process Variable Monitor

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches

MAJORSINE Power Inverter

Continuous Power... Continuous Protection

PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial

CTS SERIES AUTOMATIC TRANSFER SWITCH

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

Low Voltage Products. Switches Automatic Transfer Switches

SECTION DETECTION AND ALARM

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Internet Office 750VA Ultra-compact Standby 120V UPS with USB port

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog

Cisco Unified IP Phone Power Injector

Redundancy Module QUINT-DIODE/40

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial

SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial

TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

CPS Y S K CPS Y S C

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Model #: SMART2200CRMXL

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Bimetallic Overload Relay Specifications

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Electronic overload relay EF19 and EF45

SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting

CompactLogix Power Supplies Specifications

Always On UPS Systems Inc., # Campion Road, Kelowna, BC Canada V1X 7S8

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

MCR1900 Media Converter 19-Slot Chassis

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

RM4TG20 three-phase network control relay RM4-T - range V

Chassis, Power Supply, and Element Management

Telephone- and leased line modem for industrial applications TD-36

SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

Diesel Engine Driven Generators Page 1 of 6

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Secondary Unit Substations

Rack mounted telephone- and leased line modem for industrial applications

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

MasterINTERFACE 39 Series - Relay interface modules

Analog signal converters CC-E I/I Current / current isolators

Agilent 87421A/87422A Power Supply

SmartOnline V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Transcription:

Model KGS/KGP Automatic Transfer es Bypass/Isolation Controller D Decision-Makerr MPAC 1500 Ratings Model Current Voltage, Frequency Transfer Standard Features D UL 1008 listed at 480 VAC, file #E108981 D CSA certification available D IBC seismic certification available (NEMA 1 enclosures only) D Bypass/isolation switches for uninterrupted power to the load during switch maintenance and testing D Standard-transition or programmed-transition modes of operation D Ratings of bypass switch and automatic transfer switch identical D Available in 2, 3, or 4 pole configurations D Electrically operated, mechanically held mechanism D Double-throw, interlocked operation with mechanical and electrical interlocks D Drawout mechanism to facilitate maintenance D Quick-make, quick-break bypass switch operation for load transfer between live sources D Silver tungsten alloy contacts D Silver-plated, copper bus interconnection for the automatic transfer switch and bypass switch D Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 D NEMA type 1 enclosure D Exceeds UL 1008 requirements for temperature rise after overload and endurance tests in unventilated enclosure D Main shaft auxiliary position-indicating contacts rated15a@240vac D Engine start contacts rated 10 A @ 32 VDC D Solid or switched neutral D Standard one-year limited warranty. Extended warranties are available. Standard Transition Models (KGS) D Standard-transition transfer time less than 100 milliseconds (6 cycles @ 60 Hz) KGS KGP 150--3000 208--600 VAC 50/60 Hz Programmed Transition Models (KGP) D Programmed-transition operation provides a center OFF position that allows residual voltages in the load circuits to decay D Programmable OFF time D Dual DC solenoid drive G11-132 (Model KGS/KGP Transfer ) 3/14 Page 1

Automatic Transfer Controller The Decision-Makerr MPAC 1500 Automatic Transfer Controller is used on bypass/isolation transfer switch models. Decision-Makerr MPAC 1500 Controller D LCD display, 4 lines x 20 characters, backlit D Complete programming and viewing capability at the door using the keypad and LCD display D LED indicators: Source available, transfer switch position, service required (fault), and not in auto D Modbus communication is standard D Programmable voltage and frequency pickup and dropout settings D Programmable time delays D Programmable generator exerciser D Time-based load control D Current-based load control (current sensing kit required) D Two programmable inputs and two programmable outputs D Up to four I/O extension modules available D RS-485 communication standard D Ethernet communication standard D Three-source system D Prime power For more information about Decision-Makerr MPAC 1500 features and functions, see specification sheet G11--128. Codes and Standards The ATS meets or exceeds the requirements of the following specifications: D CSA C22.2 No. 178 certification at 600 VAC available, file # LR58301 D EN61000-4-4 Fast Transient Immunity Severity Level 4 D EN61000-4-5 Surge Immunity Class 4 (voltage sensing and programmable inputs only) D IEC Specifications for EMI/EMC Immunity: d CISPR 11, Radiated Emissions d IEC 1000-4-2, Electrostatic Discharge d IEC 1000-4-3, Radiated Electromagnetic Fields d IEC 1000-4-4, Electrical Fast Transients (Bursts) d IEC 1000-4-5, Surge Voltage d IEC 1000-4-6, Conducted RF Disturbances d IEC 1000-4-8, Magnetic Fields d IEC 1000-4-11, Voltage Dips and Interruptions D IEC 60947-6-1, Low Voltage gear and Control Gear; Multifunction Equipment; Automatic Transfer ing Equipment D IEEE Standard 446, IEEE Recommended Practice for Emergency and Standby Power Systems for Commercial and Industrial Applications D IEEE 472 (ANSI C37.90A) Ring Wave Test D NEMA Standard ICS 10--2005, Electromechanical AC Transfer Equipment D NFPA 70, National Electrical Code D NFPA 99, Essential Electrical Systems for Health Care Facilities D NFPA 110, Emergency and Standby Power Systems D Underwriters Laboratories UL 508, Standard for Industrial Control Equipment D Seismic certification in accordance with the International Building Code is available. (Accessory kit is required for seismic certification.) d IBC 2000, referencing ASCE 7-98 and ICC AC-156 d IBC 2003, referencing ASCE 7-02 and ICC AC-156 d IBC 2006, referencing ASCE 7-05 and ICC AC-156 d IBC 2009, referencing ASCE 7-05 and ICC AC-156 d IBC 2012, referencing ASCE 7-10 and ICC AC-156 D Underwriters Laboratories UL 1008, Standard for Automatic Transfer es for Use in Emergency Standby Systems, file # E108981 G11-132 (Model KGS/KGP Transfer ) 3/14 Page 2

Application Data Environmental Specifications Screw-Type Terminals for External Power Connections Operating Temperature -- 20 C to70 C (--4 F to 158 F) Range of Wire Sizes * Storage Temperature Humidity Component -- 40 C to85 C (--40 F to 185 F) 5% to 95% noncondensing Input and Output Connection Specifications Main board I/O terminals I/O module terminals Amps Wire Size Range #12--24 AWG #14--24 AWG Auxiliary Position Indicating Contacts (rated 15 @ 240 VAC) Number of Contacts Indicating Normal, Emergency KGS KGP 150--400 3, 3 3, 3 600--3000 2, 2 2, 2 Amps 150--400 Normal, Emergency, and Load Terminals (per phase) (2) 1/0 to 250 KCMIL or (1) #4 AWG to 600 KCMIL Neutral (2) 1/0 to 250 KCMIL or (1) #4 AWG to 600 KCMIL 600 (2) #2 AWG to 600 KCMIL (6) #2 AWG to 600 KCMIL 800--1200 (4) #2 AWG to 600 KCMIL (12) #2 AWG to 600 KCMIL 1600--2000 (8) 1/0 to 750 KCMIL (24) 1/0 to 750 KCMIL 2600--3000 (12) 1/0 to 750 KCMIL (36) 1/0 to 750 KCMIL * Use 60 C minimum wire for #14 to #1 AWG. Use 75 C minimum wire for 1/0 AWG and larger. Note: Use copper wire only. Weights and Dimensions Weights and dimensions are shown for standard-transition bypass/isolation switches in NEMA type 1 enclosures. Consult the factory for other available enclosures. Note: Weights and dimensions are provided for reference only and should not be used for planning installation. See your local distributor for submittal drawings. Bypass/Isolation es in NEMA 1 Enclosures Number of Poles 2, 3 Amps Height Dimensions, mm (in.) Width Depth Weight, kg (lb.) 150, 225, 260, 400 2261 (89.00) * 762 (30.00) 787 (31.00) 340 (750) 600 2362 (93.00) * 914 (36.00) 718 (28.25) [ 553 (1220) 800 2362 (93.00) * 1016 (40.00) 718 (28.25) [ 615 (1355) 1000, 1200 2362 (93.00) * 1016 (40.00) 718 (28.25) [ 615 (1355) 3 1600, 2000 2286 (90.00) 1016 (40.00) 1552 (61.12) 1406 (3100) 2600, 3000 2286 (90.00) 1016 (40.00) 1857 (73.12) 1769 (3900) 150, 225, 260, 400 2261 (89.00) * 762 (30.00) 787 (31.00) 386 (850) 600 2362 (93.00) * 1016 (40.00) 718 (28.25) [ 619 (1365) 4 800, 1000, 1200 2362 (93.00) * 1168 (46.00) 718 (28.25) [ 712 (1570) 1600, 2000 2286 (90.00) 1270 (50.00) 1552 (61.12) 1815 (4000) 2600, 3000 2286 (90.00) 1270 (50.00) 1857 (73.12) 2268 (5000) * Height includes removeable 76 mm (3 in.) lifting eyes on 150--1200 amp models. [ Optional adapter bay for bottom cable entry adds 356 mm (14.0 inches) to the depth. (600--1200 amp models only.) G11-132 (Model KGS/KGP Transfer ) 3/14 Page 3

Withstand and Close-On Ratings (WCR) Withstand Current Ratings, Current in RMS Symmetrical Amperes When Coordinated with: Current-Limiting Fuses Molded-Case Circuit Breakers @ 480 VAC @ 600 VAC Specific Manufacturers (see separate tables) Any Breaker Ratings Fuse Size, Class Class Amps @ 480 VAC Amps @ 600 VAC Amps @ 480 VAC Amps @ 600 VAC Time Duration (sec. max.) 150 225 260 400 600 200,000 J 600 100,000 600 750 200,000 800 1000 1200 1600 2000 2600 3000 RK5, RK1 J, L, RK1, RK5 N/A N/A 50,000 42,000 35,000 35,000 150,000 J, L, RK1, RK5 65,000 50,000 3000 200,000 L N/A N/A 85,000 65,000 2500 4000 200,000 L L 50,000 42,000 N/A N/A N/A N/A 100,000 85,000 0.050 * UL 1008 and CSA listed at 480 VAC and 600 VAC. Withstand and Close-On Ratings with Coordinated Circuit Breakers, 480 V, UL Listed and CSA Certified The following chart lists contactor withstand and close-on ratings (WCR) with specific manufacturer s circuit breakers. Rating 150, 225, 260, 400 Molded-Case Circuit Breakers WCR, RMS Symmetrical Amperes Manufacturer Type or Class Size, FDC, HFD 225 HJD, JDC, JGC, JGH, JGU, JGX 250 50,000 CHKD, CHLD4, CHMDL4, CLDC4, CMDL4, HKD, HLD4, HMDL4, KDC, LDC4, MDL4, NB TRI-PAC 400 CHLD6, CHMDL6, CMDL6, HLD6, HMDL6, LCDC6, LDC6, MDL6, NB TRI-PAC 600 CHMDL8, CMDL8, HMDL8, MDL8, NB TRI-PAC 800 HJ, HL, HR 150 JJ, JL, JR 250 LJ, LL, LR 400 LJ, LL, LR 600 MJ,PJ,PK,PL,RJ,RK,RL 800 CFD6, HFD6, HFXD6, HHFD6, HHFXD6 250 CJD6, HHJD6, HHJXD6, HJD6, HJXD6, SCJD6, SHJD6 400 CLD6, HHLD6, HHLXD6, HLD6, HLXD6, SCLD6, SHLD6 600 CMD6, HMD6, HMXD6, MD6, MXD6, SHMD6, SCMD6, SMD6 800 SEL, SEP, TEL, TEML, THLC1 150 FEH, FEL, FEN, SFL, SFP 250 FGH4,FGL4,FGP4,SGL4,SGP4,TB4,THLC4,TJL4,TLB4 400 FGH6, FGL6, FGN6, FGP6, SGL6, SGP6, TB6, TJL6 600 SKH8, SKL8, SKP8, TB8 800 G11-132 (Model KGS/KGP Transfer ) 3/14 Page 4

Molded-Case Circuit Breakers Rating WCR, RMS Symmetrical Amperes Manufacturer Type or Class Size, HLD, CHLD, LDC, CLDC 600 HMDL, CHMDL, NB TRI-PAC, DSL206 800 LC, LE, LI, LX, LXI 600 ME, MH, MX, NC, NE, NX 800 600 65,000 CLD6, SCLD6, HLD6, SHLD6 600 CMD6, SCMD6, HMD6, SHMD6 800 TB6, TJL, SGL6, SGP6 600 TB8, TP, THP, TC, THC, SKL8, SKP8 800 NB TRI-PAC 800 NDC, CNDC 1200 RDC, CRDC, PC, PCC, PB TRI-PAC 1600 NC, NE, NX 1200 PCF, PEF, PHF, PXF 1600 CMD6, SCMD6 800 800, 85,000 CND6, SCND6 1200 1000 CPD6 1600 THP, THC, TB8, SKP8 800 SKP12 1200 THP, THC, TRP 1600 Merlin Gerin CK1000L 1200 CM1600 1600 NDC, CNDC 1200 RDC, CRDC, PC, PCC, PB TRI-PAC 1600 NC, NE, NX 1200 PCF, PEF, PHF, PXF 1600 1200 85,000 CND6, SCND6 1200 CPD6 1600 SKP12 1200 THP, THC, TRP 1600 Merlin Gerin CK1000L 1200 CM1600 1600 1200 65,000 MASTERPACT NW 1600 SHD16 1600 G11-132 (Model KGS/KGP Transfer ) 3/14 Page 5

Withstand and Close-On Ratings with Coordinated Circuit Breakers, 600 V, CSA Certified The following chart lists contactor withstand and close-on ratings (WCR) with specific manufacturer s circuit breakers. 150 225 260 400 Molded-Case Circuit Breakers WCR, RMS Symmetrical Amperes Manufacturer Type or Class 42,000 600 50,000 800 1000 65,000 1200 65,000 Size, JGU, JGX 250 CLDC6,KDC, LDC4, NB TRI-PAC 400 CLDC6, LDC6, NB TRI-PAC 600 NB TRI-PAC 800 HL, HR 150 JL, JR 250 LL, LR 400 LL, LR 600 PK, RK, RL 800 CFD6 250 CJD6, HHJD6, HHJXD6, SCJD6 400 CLD6, HHLD6, HHLXD6, SCLD6 600 CMD6, HMD6, HMXD6, SCMD6, SHMD6 800 THLC1 150 FGL4, FGP4, SGL4, SGP4, TB4, THLC4, TJL4, TLB4 400 FGL6, FGP6, SGL6, SGP6, TB6 600 SKL8, SKP8, TB8 800 LDC, CLDC 600 NB TRI-PAC, DSL206 800 LI, LXI 600 NC, NE, NX 800 CLD6, SDLD6 600 CMD6, SCMD6, HMD6, SHMD6 800 TB6, SGL6, SGP6 600 TB8, THP, THC, SKP8 800 NB TRI-PAC 800 RDC, CRDC, PC, PCC, PB TRI-PAC 1600 NC, NE, NX 1200 PCF, PEF, PHF, PXF 1600 CMD6, SCMD6 800 CND6, SCND6 1200 CPD6, HPD6, HRD6 1600 THP, THC, TB8, SKP8 800 SKP12 1200 THP, THC, TRP 1600 Merlin Gerin MP16H1, MP16H2, MC16H1 1600 RDC, CRDC, PC, PCC, PB TRI-PAC 1600 NC, NE, NX 1200 PCF, PEF, PHF, PXF 1600 CND6, SCND6 1200 CPD6, HPD6, HRD6 1600 SKP12 1200 THP, THC, TRP 1600 Merlin Gerin MP16H1, MP16H2, MC16H1 1600 G11-132 (Model KGS/KGP Transfer ) 3/14 Page 6

Accessories Accessories are available either factory-installed or as loose kits, unless otherwise noted. - Adapter Bays D Available for 600--1200 amp models - CSA Certification - Digital Meter D Measure and display voltage, current, frequency, and power for both sources D Programmable visual alarms for high voltage, low voltage, and high current D Three digital outputs D Serial port for optional network connections D Password-protected programming menus D Joystick operation D Factory-installed - Extended Warranties D 2-year basic D 5-year basic D 5-year comprehensive D 10-year major components - Export Packaging - Heater, Anti-Condensation D Hygrostat-controlled 120 VAC strip heater (customer-supplied voltage source required) D 100 or 250 watts (sized for enclosure) D Protective 15 Amp circuit breaker - Literature Kits D Production literature kit (one kit is included with each transfer switch) D Overhaul literature kit - Neutral Assembly D Available as loose kit for open units - RSA III Remote Serial Annunciator D Monitors the generator set D Monitors Normal and Emergency source status and connection D Monitors ATS common alarm D Allows remote testing of the ATS D For more information, see specification sheet G6--139. - Pull Box D Optional for 150--260 amp units D Required for bottom cable entry on 400--600 amp units - Seismic Certification D Certification depends on application and geographic location. Contact your distributor for details. D Available for 150--3000 Amp KGS and KGP models with NEMA 1 enclosures - Surge Protection Device (SPD) D SPD available for the normal source supply D Surge protection reduces transient voltages to harmless levels D Protection modes: L-L / L-N / L-G / N-G D Replaceable phase and neutral cartridges for service D Frequency: 50--60 Hz D Operating Temperature Range: --40 to 176_F (--40to80_C) D Remote contacts for customer-supplied status indicators: Contacts: 1 NO, 1 NC Min Load: 12VDC / 10 ma Max. Load: 250 VAC / 1 A Wire Size (max.): 16AWG D Fuse protection: 30 / 600 V D UL 1449, 3rd Edition for Type 2 applications D IEC 61-643-1, 2nd Edition T2/11 D See additional specifications below Additional Controller Accessories See the controller specification sheet for more information. - Accessory Modules D Alarm Module D External Battery Supply Module D Input/Output Module D High-Power Input/Output Module - Controller Disconnect - Current Sensing Kit - Line-to-Neutral Voltage Monitoring - Padlockable User Interface Cover - Supervised Transfer Control Nominal Voltage (V ±15%) Max. Discharge Current (ka) Phase Poles UL VPR 3rd Ed (L-N/N-G/L-G) (kv) SPD Specifications Limiting Voltage, (L-N/N-G/L-G) (kv) Short Circuit Withstand Current (ka) Continuous Operating Voltage (VAC) at 3kAmps at 10kAmp 240 / 120 40 Split 3 0.6 / 1.2 / 0.7 0.6 / 0.4 / 0.6 0.8 / 0.7 / 0.8 200 175 / 350 208 / 120 40 Wye 4 0.6 / 1.2 / 0.7 0.6 / 0.4 / 0.6 0.8 / 0.7 / 0.8 200 175 / 350 480 / 277 40 Wye 4 1.0 / 1.2 / 1.1 1.0 / 0.4 / 1.0 1.2 / 0.7 / 1.2 200 320 / 460 240 / 120 40 HLD 4 1.0 / 1.2 / 1.1 1.0 / 0.4 / 1.0 1.2 / 0.7 / 1.2 200 320 / 460 600 / 347 40 Wye 4 1.3 / 1.2 / 1.4 1.3 / 0.4 / 1.3 1.5 / 0.7 / 1.5 200 440 / 880 G11-132 (Model KGS/KGP Transfer ) 3/14 Page 7

KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455 Model Designation Model Mechanism Transition Controls Voltage Poles Enclosure Current Rating Miscellaneous Record the transfer switch model designation in the boxes. The transfer switch model designation defines characteristics and ratings as explained below. Sample Model Designation: KGS-DCTA-0400S Model K: Kohler Mechanism G: Bypass/Isolation Transition S: Standard P: Programmed Controller D: Decision-Makerr MPAC 1500, Automatic Voltage/Frequency C: 208 Volts/60 Hz K: 440 Volts/60 Hz D: 220 Volts/50 Hz M: 480 Volts/60 Hz F: 240 Volts/60 Hz N: 600 Volts/60 Hz G: 380 Volts/50 Hz P: 380 Volts/60 Hz H: 400 Volts/50 Hz R: 220 Volts/60 Hz J: 416 Volts/50 Hz Number of Poles/Wires N: 2 Poles/3 Wires, Solid Neutral T: 3 Poles/4 Wires, Solid Neutral V: 4 Poles/ 4 Wires, ed Neutral Enclosure A: NEMA 1* * Contact the factory for other enclosure types. Current, Amps [ 0150 0600 1600 0225 0800 2000 0260 1000 2600 0400 1200 3000 [ Some selections are not available on all models. Connections S: Standard F: Front (800 amp only) Note: Some selections are not available on all models. Contact your Kohler distributor for availability. DISTRIBUTED BY: Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohlerr Power Systems distributor for availability. 2014 by Kohler Co. All rights reserved. G11-132 (Model KGS/KGP Transfer ) 3/14 Page 8