CommercialComplete Wall System NFPA 285 Tested Wall Assemblies



Similar documents
s ation lic app ntial Foamular sideor RE uide F Ily G am ation F sul In

Fiberglas, Exterior Wall Thermal Insulation

EcoTouch Insulation with PureFiber Technology

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

GreenGuard Housewrap Installation Guide

SECTION PRE-ENGINEERED BUILDING BLANKET INSULATION

Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver

Fire Resistance of Brick Masonry

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

PART 1 GENERAL 1.1 SECTION INCLUDES

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2B Energy & IAQ (2009) Related TEK: 6-1B, 6-11, 6-12C INTRODUCTION

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

THE DOW CHEMICAL COMPANY Issued: August 1, LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN (989)

Built to Last. Built for Beauty. Good. Solid. Logix. TM

) and air spaces (R a

R-Value and Densities Chart

RESIDENTIAL MASONRY A BEST PRACTICES GUIDE

The Prefab Package. Modular EIFS construction offers benefits to today s busy jobsites. Building Envelope. Roland Serino, P.E., of Dryvit Systems Inc.

Tremco Fire Protection Systems Group Technical Bulletin

UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS

DEFAULT HEAT LOSS COEFFICIENTS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

COMMERCIAL BUILDING APPLICATIONS

LEGACY REPORT. (800) (562) A Subsidiary of the International Code Council RETAINED ON U.S.

Meeting the Fire Code with Continuous Foam Plastic Insulation

Cost Comparisons for Common Commercial Wall Systems

The better way to build TM. Installation Manual. EXTERIOR WALL SIPs

ISO Types 1-6: Construction Code Descriptions

Fire Barrier Duct Wrap 15A

ICC-ES Evaluation Report Reissued September, 2010 This report is subject to re-examination in one year.

Gypsum Board Systems Manual

ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.

Continuous Insulation Using Polyiso Wall Sheathing

Avoiding Air Barrier Pitfalls

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: TEC-WOOD ( )

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2C Energy & IAQ (2013) Related TEK: 2-5B, 6-1C, 6-4B, 6-11A, 6-12C, 6-12D, 6-12E

Window Installation Instructions

Renovating Your Basement

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

The Optimum Basement Wall

Sun Windows General Information Sun New Construction Window Installation Instructions

March 14, Installation of Bay, Bow and Garden Windows

Heating Load Calculation

THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY

A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA

INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)

Atlas Roofing Corporation insulating sheathing

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

VA25014B0516 VA CINCINNATI PROJECT NO INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION GYPSUM BOARD

Introduction...COMB-2 Design Considerations and Examples...COMB-3

WELCOME. Recommended Window Installation. 1.5 credits Minnesota Department of Labor and Industry

FOAMULAR Tapered Roofi ng Products Extruded Polystyrene (XPS) Rigid Foam Insulation

Colorado State University. Durrell Center Roof Repair

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

Product Information Sheet

INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS

INSTALLATION INSTRUCTIONS IMPERVIA (Vent and Fixed) AWNING, CASEMENT, and LARGE AWNING WINDOW WITH FINS

AUTHORIZATION TO MARK

ROXUL Board Insulation Section Master Guide Specification (CAVITYROCK ) Page 1 April 2016

Underwriters Laboratories Testing Information

GYPSUM AREA SEPARATION FIREWALLS GA

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP APPLIED WOOD COATINGS SECTION: SHEATHING REPORT HOLDER:

Barewood Octagon and Elongated Windows Installation Instructions

From the popularity of building

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

H-Stud Area Separation Wall System

Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

Williamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, (68 pages)

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

Excerpts from the Canadian National Building Code (NBC)

Clad Direct Glaze Window Installation Instructions

2.18 INTERIOR & EXTERIOR FINISHES VAPOR & AIR BARRIERS

The Case for Cross Laminated Timber: Part 2

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

SECTION ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

Supplement to IRC Wall Bracing Guide: Design Examples

DuPont Tyvek Water-Resistive and Air Barriers Installation Guidelines

CHAPTER 7: Building Systems ROOFING SYSTEMS

The Difference Between Cast Stone and Adhered Manufactured Stone Masonry Veneer

Ver. 2. Guide to. Inspecting Residential Brick Veneer

LAYING BLOCK AND BRICK

Tundra Series Windows January 2016

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.

If you are a web registered user of ArlingontPermits.com you may also request an inspection at:

Building Envelope Design. ComfortBoard IS. Exterior Insulated Sheathing for High-Performance Residential Wall Systems

GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER

WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING

MOLD AND MOISTURE RESISTANT PAPERLESS SOLUTIONS FOR AREA SEPARATION WALLS

Additions and Alterations

LEGACY REPORT. (800) (562) A Subsidiary of the International Code Council. *Corrected March 2014

Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.

Manufactured Stone Veneer Installation Instructions

Technical Data Sheet W13. Edition Knauf Fire Walls

Transcription:

XPS Insulation, JointSealR Foam Joint Tape, EcoTouch Flame Spread 5, EcoTouch Thermal Batt FIBERGLAS Insulation NFPA 85 Fire Tested Wall Assemblies Owens Corning s CommercialComplete Wall System has successfully passed the NFPA 85 * fi re test in many variations giving architects options in exterior wall design. The system is approved with extruded polystyrene continuous insulation under a variety of masonry veneer exterior fi nishes, over either steel stud frame or masonry back-up walls. This brochure summarizes NFPA 85 approved assemblies. See Table and the family of CommercialComplete Wall System publications for more information. *NFPA 85, Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load Bearing Wall Assemblies Containing Combustible Components; National Fire Protection Association, 1 Batterymarch Park, Quincy, Massachusetts 0169 The Purpose of NFPA 85 The test is required in the International Building Code (IBC) when foam plastic insulation is used in the exterior walls of construction types I, II, III or IV. Those construction types, by code defi nition, have exterior walls constructed of non-combustible materials. The test is to determine that combustible foam plastic insulation, when exposed to fi re on the exterior face of the wall, does not spread fl ame over the surface or through the core of the otherwise non-combustible wall assembly. Owens Corning CommercialComplete Wall Systems EcoTouch FLAME SPREAD 5 INSULATION (5 flame spread facer for exposed use or for Types I or II construction) EcoTouch THERMAL BATT FIBERGLAS INSULATION (unfaced) FOAMULAR 50 XPS continuous insulating sheathing (directly over steel studs or over exterior gypsum sheathing) JOINTSEALR FOAM JOINT TAPE (optional joint seal) Brick, CMU, Stone, or Terra-Cotta Veneer EcoTouch FLAME SPREAD 5 INSULATION (5 flame spread facer for exposed use or for Types I or II construction) EcoTouch THERMAL BATT FIBERGLAS INSULATION (unfaced) 50 XPS continuous insulating sheathing Pre-Cast Concrete Panel The test standard NFPA 85 is referenced in IBC Section 60.5.5. That standard, or a variation of it, has been referenced in each edition of the IBC since its fi rst edition in 000, and since the 1980 s in the three model codes that preceded it. The now defunct ICBO Uniform Building Code fi rst included the concept in the 1988 edition, requiring testing in accordance with the UBC Standard 17-6, a predecessor of NFPA 85. EcoTouch FLAME SPREAD 5 INSULATION (5 flame spread facer for exposed use or for Types I or II construction) EcoTouch THERMAL BATT FIBERGLAS INSULATION (unfaced) 50 XPS continuous insulating sheathing PM EIFS (EIFS system by others) HIGH-R CW PLUS (alternative XPS insulation with a higher R per inch) JOINTSEALR FOAM JOINT TAPE (optional joint seal) CW15 OR CW5 50 XPS INSULATION Brick, CMU, Stone, or Terra-Cotta Veneer over CMU 1

The other two national model building codes of that era also required full scale testing of this type for exterior walls. The 198 SBCCI Standard, and the 1984 BOCA National (Basic) Building Codes stated in their foam plastics chapters, Results of diversifi ed or full scale fi re tests refl ecting an end use condition shall be submitted to the building offi cial demonstrating that the (wall) assembly in its fi nal form does not show any tendency to propagate fl ame over the surface or through the core when exposed on the exterior face to a fi re source. The intent was that a predecessor of NFPA 85 be utilized, the Full Scale Multi-Story Test as it was called at the time. The NFPA 85 Methodology The 0 minute test is conducted on a full scale two story wall assembly, built as it would be in the fi eld, on the front side of a three sided test structure. (See Figures 1 and that are excerpts from NFPA 85) The test wall, has a window in the center of the lower fl oor. (Figure ) The test scenario is that a fl ashover fi re, unrelated to the foam plastic insulation, has occurred in the lower story room emitting a fi re plume out of the room of origin through the window. Early in the 0 minute exposure the fi re plume wraps around the window head, extending up the exterior surface of the wall. (Figure 4) Figure 1: Elevation of test rig, test wall side To pass, the wall assembly must demonstrate limited fi re spread vertically and horizontally away from the window. The extent of fi re spread is determined visually, measured in feet, and by temperature that is measured by thermocouples placed throughout the wall assembly. Figure 5 shows a successful CommercialComplete Wall System test with the brick veneer stripped away just above the window lintel. Note the very limited fi re spread and melting of the foam. Figure : Section of test rig Figure : Test wall under construction Figure 4: Fire emitting from the test window Figure 5: showing limited damage above the test window with brick veneer stripped away after the fire test

Table 1 Owens Corning CommercialComplete Wall System Product Selection Guide Extruded Polystyrene Continuous Insulation Product Name Application CC Steel Stud Framing 50 Steel Stud Framing CC High R Steel Stud Framing CW15 Concrete Masonry CW5 Concrete Masonry High R CW Plus Concrete Masonry Thickness ½ ¾ 1 1½ ½ 4 1¾ 1 8 1 1½ ½ 1 1½ ½ 1¾ 1 8 @75 F mean temp. 1 4.0 7.5 1 0.0 1.0 17.0 7.5 1 7.5 1 1.0 17.0 R-Value 1 (180 Day) @40 F mean temp. 1.5 4. 5.4 8.1 1.5 1.6 1 18.4 5.4 8.1 1.5 5.4 8.1 1.5 1.0 18.4 R-Value 1 (LTTR) @75 F mean temp. 10.6 1.4 10.6 1.4.0 10. 10.6 1.4 10.6 1.4 10. Size x 48 x 96 ½ x 48 x 96 x 48 x 96 ¾ x 48 x 96 1 x 48 x 96 1½ x 48 x 96 x 48 x 96 ½ x 48 x 96 x 48 x 96 4 x 48 x 96 ( 50 also in 4" wide) 1¾ x 48 x 96 1 8 x 48 x 96 x 48 x 96 1 x 16 x 96 1½ x 16 x 96 x 16 x 96 ½ x 16 x 96 x 16 x 96 1 x 16 x 96 1½ x 16 x 96 x 16 x 96 ½ x 16 x 96 x 16 x 96 1¾ x 16 x 96 1 8 x 16 x 96 x 16 x 96 Compressive Strength (psi) ASTM C578 Type Edge Type 16 X Ship-lap long edge 5 lv Square (or T&G up to " thick only) 5 lv Ship-lap long edge 15 X Square 5 lv Square 5 lv Square 1. R-values vary depending on many factors including the mean temperature at which the test is conducted, and the age of the sample at the time of testing. Because rigid foam plastic insulation products are not all aged in accordance with the same standards, it is useful to publish comparison R-value data. The R-value for XPS is provided from testing at two mean temperatures, 40 F and 75 F, and from two aging (conditioning) techniques, 180 day real-time aging (as mandated by ASTM C578), and, a method of artifi cially accelerating aging sometimes called Long Term Thermal Resistance (LTTR, CAN/ULC S770). The R-value at 180 day real-time aged, and 75 F mean temperature, is commonly used to compare products. It is recommended that the specifi er verify testing and conditioning methods with the manufacturer before comparing the R-value of rigid foam plastic insulation products.. Availability may vary depending on sizes, edge confi guration, and/or region. Some items are made to order. Check with your local representative for specifi c information. EcoTouch Fiberglas Insulation Product Name Application EcoTouch Thermal Batt Unfaced EcoTouch Flame Spread 5 Faced Facer Types: FSK (foil) faced PSK (white) faced Thickness ½ ½ 6¼ ½ ½ 6¼ 9½ R-Value @75 F mean temp. 11.0 1.0 19.0 11.0 1.0 19.0 0.0 Perms maximum NA NA NA Depends on Facer Type Width 16 or 4 (Specify full width for steel stud) 16 or 4 (Specify full width for steel stud) Length 48 or 96 48 or 96 48 or 96 JointSealR Foam Joint Tape for the CommercialComplete Wall System 0.0 0.0 Roll Widths Roll Length Function (feet) Backer Foam board joint sealing.5 90 Acrylic 96 96 96 48 ASTM C665 Type Type 1 Type 1 Type 1 Depends on Facer Type Type 111, Class A Type 11, Class A

Architects Guide to NFPA 85 Tested Owens Corning CommercialComplete Wall Systems Table summarizes CommercialComplete Wall System options that are approved for use in NFPA 85 tested wall assemblies. The table provides information on approved variations including with and without FIBERGLAS Batt Insulation in the steel stud cavities, options for air barriers, foam thickness, window head closure details and other important system details. 4 Table * Wall Component Base Wall System: Select one Owens Corning CommercialComplete Wall System Specification Guide to Accepted NFPA 85 Options Material Options Floorline Firestopping: Select one If a fi re resistance rated fl oor or fl oor/ceiling assembly IS required use option 1. If a fi re resistance rated fl oor assembly IS NOT required use option. Concrete (cast-in-place, or, pre-cast) Concrete Masonry Units Steel Stud Framing, minimum 5 8" depth, minimum 0 gauge, maximum 16 inches on center spacing, with lateral bracing every 4 ft. vertically. Cover on the interior with 1 layer of 5 8" thick, Type X, gypsum wallboard. 1. Install an ASTM E07 tested and rated fi re stop joint assembly.. Install mineral wool fi re stop, 4 pcf density, attached with Z-clips or equivalent, continuously at each fl oor line and/or in each stud cavity if the stud framing is continuous past the fl oor line. Stud Cavity Insulation: Select one See Table 1 for product properties, sizes, and facer confi gurations. None Complete product data is available in related Owens Corning publications. Any non-combustible insulation EcoTouch Flame Spread 5 Batt Insulation (faced) EcoTouch Thermal Batt FIBERGLAS Insulation (unfaced) Spray Polyurethane Foam, Demilec Sealection 500 (0.5 pcf maximum, used only with gypsum exterior sheathing) Exterior Sheathing: Select one None Gypsum Sheathing, ½", exterior grade Gypsum Sheathing, 5 8", Type X, exterior grade Air & Weather Resistive Barrier Layer Over Base Wall System: Select one All barriers are to be installed at recommended application rates and in None strict accordance with the manufacturer s installation instructions. Wall Guardian FW-100A, STS Coatings Barritech VP, Carlisle Coatings & Waterproofi ng Fire Resist Barritech NP, Carlisle Coatings & Waterproofi ng CCW-705FR with CCW-70 WB adhesive, Carlisle Coatings & Waterproofi ng Air-Bloc 1MR, Henry Company (approximate thickness mil) Backstop NT, Dryvit Systems Inc. Air-Shield LMP (black only), W.R. Meadows Perm-A-Barrier, VPS, W.R. Grace & Co. Tyvek CommercialWrap, Dupont GreenGuard Max, Building Wrap, Pactiv Continuous Insulation: Select one See Table 1 for recommended product applications, and product properties, CC ASTM C578 Type IV sizes, and edge confi gurations. Complete product data is available in related 50 ASTM C578 Type IV Owens Corning publications. CC High-R ASTM C578 Type IV Options: joints may be sealed with JointSealR Foam Joint Tape. High-R CW Plus ASTM C578 Type IV may be installed directly over steel stud framing. CW15 ASTM C578 Type X CW5 ASTM C578 Type IV Thickness: ½" minimum, to " maximum, use Window & Door Opening Detail 1. ½" minimum to 5" maximum, use details, or 4.

*DISCLAIMER: The sole purpose of the information provided in Table is to identify certain Material Options, in assemblies, that have been shown by independent testing, as of the initial date of this publication, to be compliant with the NFPA 85 fire test. By providing this information, Owens Corning is not making, and specifically disclaims, any recommendations, warranties, or guarantees with respect to any of the listed Material Options. Complete product data for the Owens Corning products is available in related Owens Corning publications. Product data for non-owens Corning products, including verification that such products continue to meet the NFPA 85 standards, must be obtained directly from the relevant manufacturer. Table * Continued Wall Component Material Options Air & Weather Resistive Barrier over Continuous Insulation: Select one Install in accordance with manufacturers instructions. None JointSealR Foam Joint Tape, Owens Corning Tyvek CommercialWrap, Dupont GreenGuard Max, Building Wrap, Pactiv Exterior Cladding, Veneer: Select one Brick Veneer: Nominal 4" thick, clay brick. Veneer anchors, standard types, installed maximum 4" o.c. vertically on each stud, or, continuous ladder tie type if CMU backup is utilized. Maximum " air space between continuous insulation and brick. Concrete Panels: Minimum thick. Maximum " air space between continuous insulation and concrete. Insulated Concrete Sandwich Panels: Minimum " thick outer face wythe. Concrete Masonry Units: Minimum 4" thick. Maximum " air space between continuous insulation and CMU. Stone Veneer: Minimum " thick, limestone or natural stone veneer, or minimum 1½" thick manufactured stone veneer. May use any standard closed joint installation technique such as ship-lap, etc. Terracotta Panels: Terracotta cladding system, minimum 1¼" thick, with closed joint installation such as ship-lap, etc. Stucco: Minimum 7 8" thick, exterior cement plaster and lath. Lath mechanically attached. EIFS: Polymer Modifi ed (PM) Exterior Insulation Finish Systems, with XPS base. Details as NFPA 85 tested and specifi ed by PM EIFS manufacturer. Window and Door Opening Details See Table for window and door opening details. Detail 1: Window and door header openings must be fi restopped with mineral safi ng as shown. Maximum " thick continuous insulation. Detail : Window and door header openings must be fi restopped with a continuous steel lintel or shelf angle as shown. Maximum 5 thick continuous insulation. Detail : Steel stand-off window lintel or shelf angle. The void behind the lintel must be tightly fi lled with 4 pcf density mineral wool fi re safi ng packed to 5% compression inside standoff shelf angle. Maximum 5" thick continuous insulation. Detail 4: Same condition as detail, but, may be located at a fl oor line as shown. Maximum 5" thick continuous insulation. Jambs and Sill: For details, and 4, must be solid masonry returned to the face of the gypsum sheathing or the face of the steel stud if gypsum sheathing is not used. EIFS: Details as required by EIFS manufacturer. Stucco: Heads and Jambs must be stucco backwrapped to gypsum sheathing or steel framing. 5

Table Window and Door Opening Details 1,,, NFPA 85 Detail 1: Steel Lintel/Shelf Angle with Mineral Wool over and Safi ng Detail : Continuous Steel Lintel/Shelf Angle on Steel Framing 1. The base wall is shown in Table, Details 1 through 4, as a steel stud assembly for illustration purposes only. Note that it may be any of the Base Wall System options described at the beginning of Table.. Window unit details such as glass type, extruded aluminum shapes and foam fi lled voids are not critical to NFPA 85 compliance. The actual NFPA 85 test is conducted with no window unit in the opening. However, it is critical to match the approved insulation thickness with approved details for the opening head (continuous steel, or, steel with mineral wool fi re safi ng), and, jamb/sill details (not solid in Detail 1, solid masonry in Details, and 4).. As an option, fl ash window, door and other exterior penetrations with limited amounts of acrylic, asphalt or butyl based fl ashing tape, maximum 1" width. 6

Table Continued Window and Door Opening Details 1,, NFPA 85 Detail : Standoff Lintel/Shelf Angle on Steel Framing Detail 4: Standoff Shelf Angle at Floor Line 7

Owens Corning CommercialComplete Wall Systems Resources: For additional information see the complete set of Owens Corning CommercialComplete Wall System literature. Visit www.foamular.com or www.owenscorningcommercial.com, or call 1-800-GET-PINK. OWENS CORNING INSULATING SYSTEMS, LLC ONE OWENS CORNING PARKWAY TOLEDO, OHIO, USA 4659 1-800-GET-PINK www.owenscorning.com Pub. No. 10015478-H. Printed in U.S.A. June 01. THE PINK PANTHER & 1964 01 Metro-Goldwyn-Mayer Studios Inc. All Rights Reserved. The color PINK is a registered trademark of Owens Corning. 01 Owens Corning. All Rights Reserved. Trademarks are the property of their respective owners.