Supplement to IRC Wall Bracing Guide: Design Examples
|
|
|
- Adela Gordon
- 9 years ago
- Views:
Transcription
1 Supplement to IRC Wall Bracing Guide: Design Examples Introduction This supplement to the IRC Wall Bracing Guide presents two case studies or wall bracing design examples to illustrate the various bracing methods and the provisions in Section R of the International Residential Code (IRC). Both case studies demonstrate the use of a simple step-bystep design method as explained in the IRC Wall Bracing: A Guide for Builders, Designers and Plan Reviewers ( Guide ). (Refer to Section 2 and the bracing worksheet in Appendix A.) Case Study #1 illustrates a very simple, affordable home application that presents few challenges in using the IRC wall bracing provisions. Three bracing methods are featured for comparison purposes and to illustrate differences and similarities in requirements. Case Study #2 represents a more complicated building plan that requires some effort to achieve code compliance, regardless of the IRC bracing method used. This example also illustrates how to implement some of the more advanced recommendations found in the Guide to address difficult conditions or challenging design objectives. For example, combining multiple bracing methods or techniques on the same plan clearly highlight the design flexibility in selecting wall assemblies that best serve structural, cost, durability and energy performance objectives of a given project. Because each building plan may present unique challenges or design objectives that require a careful consideration of code compliance in a variety of ways, it is impossible to illustrate every conceivable application or solution for wall bracing. While these examples apply concepts that are appropriate to a variety of applications, it is advisable to refer to additional resources and use a design professional when in doubt. For additional information and design details, refer to the IRC Wall Bracing: A Guide for Builders, Designers and Plan Reviewers with Supplemental Information on Appropriate Use of Foam Sheathing. Foam Sheathing Coalition (FSC) Copyright 2006 Version 1.0
2
3 Supplement: Bracing Design Examples Page 1 CASE STUDY #1 One Story Home (Simple Building Plan) Objectives Evaluate bracing requirements for commonly used wall bracing methods Allow wall systems to be compared with respect to first cost, energy efficiency (monthly cost), and requirements (depends on local climate, materials costs, etc.). (Refer to Section 4 in the Guide for information on bracing strategies for energy efficient wall assemblies.) Given Typical one-story entry-level (starter) home with floor plan per Figure 1 Design wind speed < 110 mph per IRC Table R301.2(1) Seismic Design Category C Required wall system R-value of R15 or greater per energy code (northern, heating climates) Wall Assemblies & Bracing Methods Considered Wall Option #1 Option #2 Option #3 Components Bracing Method Method 1 (use USP WBT12 45 o Method 3 (wood structural panel) Method 4 (fiberboard) steel T-brace) Framing 2x4 studs at 16 oc or 2x6 studs at 16 oc or 2x6 studs at 16 oc only Exterior Sheathing 24 oc ½ foam backer panels (R3) installed as a combined air/thermal/water barrier 24 oc 7/16 OSB wood flake sheathing covered with building wrap for waterand air-barrier ½ fiberboard panels covered with building wrap for water- and air-barrier Siding Vinyl Vinyl Vinyl Interior Finish ½ gypsum wall board ½ gypsum wall board ½ gypsum wall board Cavity Insulation & warm-inwinter side vapor retarder R13 kraft-faced batts (plastic vapor retarder can be eliminated) R19 kraft-faced batts (plastic vapor retarder may be required) R19 kraft-faced batts (plastic vapor retarder may be required) Comments Requires least materials and layers on wall to achieve code compliance Provides energy efficiency comparable to 2x6 walls, but using standard thickness 2x4 wall Check local supply for material costs Uses thicker wall system and larger studs (structurally unnecessary for this plan) Requires thicker door/window jambs Check local supply for material costs Same as Option #2 Check local supply for material costs
4 Supplement: Bracing Design Examples Page 2 Application of IRC Bracing Requirements Due to the small plan size of this home and adequate space for bracing on exterior walls, no interior lines are required for this plan. As shown in the floor plan below (Figure 1), four exterior lines are identified. The rear line is drawn to split the offset in the rear wall line. (Refer to Section 1 of the Guide, in particular the definition for line and Figure 2c). Note that even though interior walls are not specifically designed as lines, they will contribute substantially to the racking strength of the whole building. In addition, portions of the exterior walls where panels (or braces) are not located, but which include interior gypsum wall board finishes, also contribute additional racking strength to the building. This, however, is not directly considered when applying the IRC wall bracing provisions. These non-structural systems (from the standpoint of how the code defines bracing) may actually provide adequate bracing of this particular home plan even in the absence of specified panels on the exterior walls. However, always ensure that the required bracing is provided in compliance with the IRC Braced Wall Lines F = front line B = back line L = Left line R = Right line Figure 1: House Plan for Case Study #1 with Designated Braced Wall Lines 1 1 House plan #3435VL: Starter Home with Two Covered Porches courtesy of
5 STEP 1 - Braced Wall Line ID Supplement: Bracing Design Examples Page 3 Table 1: Wall Bracing Worksheet for Case Study #1 A B C D E F G H I J Support STEP 3 Condition Bracing Method F (three options for front line) B (three options for back line) Maximum Offset in Braced Wall Line 4? Roof only OK 31 Roof only OK 31 STEP 2 Braced Wall Line Spacing (feet) Method 1 (use USP WBT12 45 o T-Brace) Method 3 (use 7/16 OSB) Method 4 (use ½ fiberboard) Method 1 (use USP WBT12 45 o T-Brace) Method 3 (use 7/16 OSB) Method 4 (use ½ fiberboard) STEP 3 Braced Wall Line Length (inches) STEP 3 Required Bracing Percentage (Table 3) 44 N/A (amount based on columns K & L) 44 16% (see Table 3b in Guide ) STEP 3 Required Total Length of Braced Wall Panels (inches) STEP 4 Total Length of Braced Wall Panels Provided (inches) N/A Minimum of 2 braces needed to meet brace location requirements per columns I & J 44 x 0.16 = % 44 x 0.25 = N/A (amount based on columns K & L) 44 16% (see Table 3b in Guide ) Minimum of 2 panels required if spaced as above for Method 1 braces Minimum of 3 panels required N/A Minimum of 2 braces needed to meet brace location requirements per columns I & J 44 x 0.16 = % 44 x 0.25 = 11 Minimum of 2 panels required if spaced as above for Method 1 braces Minimum of 3 panels required STEP 4 Value in Column F Value in Column E? STEP 5 Brace wall panels begin within 12.5 of ends of line? STEP 5 Braced wall panels spaced along braced wall line at 25 oc maximum? COMMENTS N/A OK OK Place each of 2 braces to inside of left and right windows on front wall line starting no more than 12.5 from ends of wall (results in spacing between braces < 25 oc). 8 min. OK 12 min. OK OK OK Place minimum of two 4 Method 3 panels as above for Method 1 braces; if panels placed at corners, three panels are required. OK OK Place two 4 Method 4 panels within 12.5 of ends of wall and one additional panel to right of entry door. N/A OK OK Requirements same as front wall. Brace locations differ. May require a 60 o brace (e.g., USP S365 T- brace) at bedroom #2 if 45 o brace angle can t fit. Alternatively, substitute a Method 3 panel. 8 min. OK 12 min. OK OK OK See comment for front line. OK OK Place three 4 panels similar to direction in comment for front line.
6 Supplement: Bracing Design Examples Page 4 R (three options for right line) L (left braced wall line) Roof only Roof only Roof only OK 44 Method 1 (use USP WBT12 45 o T-Brace) OK 44 Method 3 (use 7/16 OSB) OK 44 Method 4 (use ½ fiberboard) 35 N/A (amount based on columns K & max 20 oc spacing per Table 3b in Guide ) 35 21% (see Table 3b in Guide for 45 braced wall line spacing) 35 32% (see Table 3b in Guide for 45 braced wall line spacing) N/A Minimum of 2 braces needed to meet brace location requirements per Columns K & L 35 x 0.21 = x 0.32 = 11-2 Minimum of 2 braced panels required Minimum of 3 braced panels required N/A OK OK Max 20 oc per Table 3b in Guide 8 min. OK 12 min. OK Place each of two braces starting no less than 3.5 from each end of right side wall and no more than This arrangement results in brace spacing of < 20 oc. OK OK If two panels used start each panel no less than 3 from each end of right side wall and no more than 12.5 to provide a panel spacing of no more than 25 oc. OK OK Place 4 brace panels at ends and at center of right side wall. The bracing amounts and location determined for line R may be used for line L. The required bracing can be located completely in the 27 long side wall and not along the 8 segment of wall that is offset due to the projection of bedroom #2 at the rear of the plan. Notice that in taking this approach, the length of wall used to determine the amount of bracing in the 27 long left side wall is the overall length of the building side including the 8 extension of bedroom #2 (e.g., = 35 ). Some may interpret the 8 wall segment at bedroom #2 as a separate line which is not necessarily the intent of the IRC bracing provisions. Such an interpretation reflects the difficulty of developing prescriptive code language that adequately explains bracing requirements for buildings that have even a minor variation from a perfectly rectangular floor plan. Always use sound judgment when using the 4 offset criteria to define separate lines to ensure the code intent is met.
7 Supplement: Bracing Design Examples Page 5 CASE STUDY #2 Two-Story Home (Complex Building Plan) Objectives Code compliant wall bracing and energy efficiency Minimize cost to comply with energy and structural requirements in base plan Maximize energy savings in base plan without requiring dual sheathing (foam sheathing over structural sheathing) Provide a wall bracing strategy to permit an optional plan upgrade for energy efficiency and moisture protection: Include ½ water-resistant foam sheathing continuously over ½ structural panels and 1 foam sheathing where appropriate Detail foam sheathing to serve as secondary weather-barrier (eliminating building wrap/paper because foam sheathing serves a three-fold purpose as water barrier, air-barrier and thermal barrier) Maximize use of 1 foam sheathing coverage by using Method 1 bracing where possible in lieu of Method 3 or continuous structural panel bracing Given Typical model house plan Two-story with basement and attached garage (including several architectural plan options) Wind Speed 100 mph or less per local jurisdiction and IRC Table R301.2(1) Seismic Design Category SDC A or B per local jurisdiction and IRC Table R301.2(1) Bracing Methods Used on Plan Method 1 (indicated locations and lines only) USP S365 T-brace (60 o angle) installed per manufacturer instructions and as shown on plans (NER Report #505). Method 3 (indicated locations only) 7/16 OSB panels installed in accordance with IRC Section R R Continuous Structural Sheathing (indicated lines only) 7/16 OSB panels installed in accordance with Section R on all sheathable areas of indicated lines (i.e., street-facing lower and upper story wall lines) Narrow Braced Wall Panels for Garage Opening Supporting Roof Only Garage is braced as a continuous structural sheathed wall except panel width of 24 for garage opening panels is used in accordance with footnote b of Table R (Refer to Figure 6a in the Guide.) Application of IRC Bracing Requirements As shown in Figure 2 and Figure 3, a number of lines are required for this plan, including two interior lines on the first floor in the left-to-right and front-toback plan directions.
8 Supplement: Bracing Design Examples Page 6 Figure 2: First and Second Story Floor Plans For Case Study #2 with Designated Braced Wall Lines
9 Supplement: Bracing Design Examples Page 7 Figure 3: Plan Elevations Showing Front and Rear Braced Wall Line Conditions and Optional Plan Features.
10 Supplement: Bracing Design Examples Page 8 Figure 4: Plan Elevations Showing Side Exterior Braced Wall Line Conditions and Optional Plan Features.
11 Supplement: Bracing Design Examples Page 9 Table 2: Wall Bracing Worksheet for Case Study #2 A B C D E F G H I J STEP 1 Braced Wall Line ID / Description A (rear wall) STEP 1 Support Condition 0-roof 1- one st 2- two st. Maximum Offset in Braced Wall Line 4? STEP 2 Braced Wall Line Spacing (feet) STEP 3 Bracing Method STEP 3 Braced Wall Line Length (inches) STEP 3 Required Bracing Percentage (Table 3) Lower Story Longitudinal Braced Wall Lines (Parallel To Left-To-Right Plan Direction) 1 OK = Method oc and 15 (Use USP S365 start no more (see Steel T-Braces) than 12.5 comments) from ends B (interior wall) B-alt (alternate bracing for interior wall) C1 (front entry wall) 1 OK 18.2 (measured to front entry wall) Method 5 (one side and two side as indicated) 1 OK 18.2 Interior partition wall with ½ GWB on both sides installed per IRC Table R OK (4 offset between C1 and C2) 34 R Continuous Structural Sheathing 50 25% (based on both sides) STEP 3 Required Total Length of Braced Wall Panels (inches) STEP 4 Total Length of Braced Wall Panels Provided (inches) N/A Minimum of 3 braces needed to meet brace location requirements (both sides) at rear garage wall, plus 8 (one side) at left side stair well to meet 25 oc and 12.5 from ends of wall 50 50% (along entire braced wall line, excluding door openings and any segments less than 4 long) STEP 4 STEP 5 Value in Brace wall Column F panels Value begin in within Column 12.5 of E? ends of line? STEP 5 Braced wall panels spaced along braced wall line at 25 oc maximum? COMMENTS N/A OK OK For purpose of determining bracing amount, the braced wall line location for rear wall line is shifted 0.5 outward which increases the braced wall line spacing, but reduces the effective offset of the bump-out to 4 (e.g., not required to be braced as a separate braced wall line within the rear wall. OK OK OK Lap interior braced wall line top plates with exterior wall top plate or use equivalent strap. OK OK OK See Bracing Guide, Part 3 for justification to use interior partition wall as bracing; engineering approval may be required % OK OK OK Use 48 Method 3 panel on side walls at corners at ends of BWL C1 and C2 (minimum 2 corner return panels are required at ends of R walls).
12 C2 (garage opening wall) Supplement: Bracing Design Examples Page 10 A B C D E F G H I J 0 OK 20 (measured to rear wall of garage) 1 (left exterior side wall) Table R , footnote b, minimum 24 wide wood structural panels Lower-Story Transverse Braced Wall Lines (Parallel To Front-To-Back Plan Direction) 1 OK 29.4 Method oc and (measured start no more to garage than 12.5 left side from ends interior wall) 2 (garage left interior side wall) 3 (right side wall) 1 OK 29.4 (measured to left exterior side wall) 1 OK 21 (measured to garage left side interior wall) Method 5 (one side) ½ GWB on garage interior face also required for fire separation from living area. Method 3 and Method N/A 4 4 OK OK OK See comment above for BWL C1 with regard to sheathing panels at ends/corner on flanking lines. 34 (see comments) N/A Minimum 2- braces required; use 2 USP S365 braces in V shape between middle two optional window locations plus an additional Method 3 brace at front corner for end restraint of BWL C1 N/A OK, except when both options for windows and fireplace are used (see comment 4 below on plan options) OK 1. Method 3 panel provides additional bracing to this wall and gives mounting surface for electric service meter. 2. When window and fireplace option executed, the brace closest to rear corner will be 14.5 from the corner Design Required regardless of bracing method used. 50% OK OK OK Length of line is based on the depth of the building, not just the length of the garage interior wall line. Even though BWL 2 does not extend across building to rear wall, it effectively does so through connection to the floor/roof diaphragm that ties together the first story walls oc and start no more than 12.5 from ends N/A Minimum 3- braces required; use 1 USP S365 at rear end of wall and Method 3 panels at front corner and next to garage exterior egress door N/A OK OK Number of braces required is based on Method 1 bracing requirements. Method 3 braces are substituted for 2 of the required braces based on equivalency.
13 Supplement: Bracing Design Examples Page 11 A B C D E F G H I J Upper Story Longitudinal Braced Wall Lines (Parallel To Left-To-Right Plan Direction) 0 OK 34 Method oc and N/A Minimum 3- start no more braces than 12.5 (same as BWL from ends 3 for 1 st story rear wall) A (2 nd story rear wall) B (2 nd story front wall) B (2 nd story front offset at rear of garage) 0 OK 34 R (same as BWL C1 on first story) N/A OK OK NOTE: Can use Method 3 braces for all 2 nd story walls (except BWL A) as a complete substitute for Method 1 braces or just at corners. However, best to use Method 1 at corner where Tub/Shower is located to allow for exterior foam insulation for warmer wall and comfort % OK OK OK Inadequate space for Method 3 or Method 1 bracing to work (may be able to use Method 3 with approval of partial credit for narrower than 48 panel widths); use 48 Method 3 panels at corners on flanking walls. 0 OK 34 Method N/A N/A Place one brace near center of this short offset wall segment at rear of garage on second story N/A OK OK
14 Supplement: Bracing Design Examples Page 12 A B C D E F G H I J Upper Story Transverse Braced Wall Lines (Parallel To Front-To-Back Plan Direction) 0 OK 29.4 Method oc and start no more than 12.5 from ends 1 (2 nd story left exterior side wall) 2 (2 nd story center wall to left of garage roof) 3 (2 nd story right side wall) 0 OK 29.4 Method 1 and Method 3 0 OK 20 Method 1 or Method 3 34 (see comments) 17.8 depth) 25 oc and start no more than 12.5 from ends 25 oc and start no more than 12.5 from ends N/A Minimum 2- braces required; use 2 USP S365 braces in V shape between middle two optional window locations plus an additional Method 3 brace at front corner for end restraint of BWL B N/A N/A 2-braces, one each end (substitute Method 3 brace required at front corner of BWL 2 as restraint to BWL B R method) 2 braces, one at each corner N/A OK OK, except when both options for windows and fireplace are used (see comments) When window and fireplace option executed, the brace closest to rear corner will be 14.5 from the corner Design Required (same comment for BWL 1 on first story). N/A OK OK The length used for the line for purpose of determining bracing amount is based on the entire depth of the building as thought the wall line extended completely through the building. However, the bracing amount is placed only on the wall portion adjacent to the garage. N/A OK OK
15 Supplement: Bracing Design Examples Page 13 Comments on Plan Options Affecting Bracing Strategy 9 first story walls in lieu of standard 8 walls (applies to lower story walls only): This plan option is problematic for all Method 1 bracing used on the lower story unless window and door placement is modified in some locations. Method 3 bracing would still work as a substitute for all Method 1 braces, but where required braces cannot be located within 12.5 from ends of walls (e.g., installing windows and a fireplace on the left side wall), an engineered solution is required. This same issue also applies if the left side wall was braced with continuous structural sheathing because of the window location closer than 2 from the corner. The front walls with R continuous structural sheathing will not be affected. Method 1 bracing manufacturer s data appears limited to 8 or 10 wall heights unless RWB style flat straps are used, making intermediate wall heights difficult unless a different product is specified for the 9 wall height option. However, the RWB strap brace requires a 45 o angle and a double-v configuration which requires much more wall space than the S o T-brace selected for this example design problem. Finally, Method 5 bracing for interior lines is unaffected by this option. In summary, if the 9 first story wall height option is used, all Method 1 bracing on the first story level should be switched to Method 3 braces. Front walls with continuous structural sheathing will be unaffected, but the garage opening bracing panels will need to be increased in width from 24 to 27 to not exceed the maximum permitted 4:1 aspect ratio (panel height : panel width), in accordance with Table R , footnote b of the IRC. (Refer to Figure 6a in the Guide.) Alternatively, the portal framing approach for bracing of the garage opening wall may be used in accordance with footnote c in Table R of the IRC Side load and three car garage option (lower story, front wall and right side wall): In this case, the garage opening is part of a much longer line on the right side of the building. However, the garage door is located at one end of the wall such that a panel must be placed approximately 18 from the end of the wall line (exceeding the 12.5 prescriptive limit). This can be resolved simply by designing the garage door header and wall top plate to act as a drag-strut by ensuring that these members are adequately tied together at joints and splices to drag shear load into the rest of the wall line where the required amount of wall bracing is located. This is a simple task, but requires the services of an engineer. However, a standard detail for repetitive use should be feasible. (Refer to Section 3 of the Guide for additional information.) Window and Fireplace Option (left, lower-story wall): These optional plan features are adequately addressed in the bracing requirements detailed in Table 2 above, except when both options (windows and fireplace) are included. If both are included, engineering will be needed to approve a 14.5 distance of the brace from rear end of BWL #3 on the first and second story. If a design is required, follow the same procedure for drag struts as described above. In many cases, the resulting solution may require a modest increase in nailing of top plate splices for the affected wall portion. Note that this applies when either Method 1 or Method 3 braces are used. Also, if a continuous structural panel sheathed wall is used, a similar designed solution will be required because the
16 Supplement: Bracing Design Examples Page 14 minimum 2 panel required at ends cannot be achieved with the corner window option. (Refer to Section 3 of the Guide for additional information.) Bump-out bay window (4.5 wall line offset created in rear wall line at bump-out): Care should be taken when applying the 4 offset rule when identifying wall lines that are considered to be separate lines. In this case, if line A is located on an imaginary line 0.5 outward from rear wall, then the bump out does not create more than 4 offset from the indicated line location. To allow for this approach and the optional use of the bump-out bay window, the amount of bracing for BWL A should be based on the actual line spacing to the interior line B plus 0.5. This situation does not require that the bump-out walls be considered as a separate line. (Refer to Figure 2 in the Guide.) Therefore, the bump-out can be considered as a part of the rear line without requiring separate bracing of the bump-out portion. In fact, this meets the intent of the IRC code a maximum 8 out-to-out offset in any given line. Foam Sheathing Coalition (FSC) 4223 Dale Boulevard Woodbridge, VA Tel: Be sure to visit the FSC Website (available Oct. 06) for a downloadable copy of this Supplement and for other important information. Alliance for the Polyurethanes Industry (API) 1300 Wilson Boulevard Arlington, VA Tel: Fax: Extruded Polystyrene Foam Assn. (XPSA) 4223 Dale Boulevard Woodbridge, VA Tel: Fax: Polyisocyanurate Insulation Manufacturers Assn. (PIMA) 7315 Wisconsin Avenue Suite 400E Bethesda, MD Tel: Fax: Disclaimer The information contained herein is provided for educational purposes only. FSC does not assume any warranty, expressed or implied or assumes any liability. Always consult with a design professional and/or local building code officials for additional support.
THE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials.
ICC EVALUATION SERVICE, INC. EvaluateP InformP Protect Los Angeles Business/Regional OfficeP 5360 Workman Mill RoadP Whittier, CA 90601 (562) 699-0543 phonep (562) 695-4694 fax DIVISION: Section: 6 WOOD
POST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
Section A Roof Truss
Section A Roof Truss Truss Types Wisconsin Truss, Inc. can build a variety of truss types, pictured below are some common examples. Common Bobtail Scissor Mono Studio Dual Slope Cathedral Tray Vault Parallel
Chapter 6 ROOF-CEILING SYSTEMS
Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;
Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction
T e c h n i c a l n o t e Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction Number J450 February 2009 Controlling against moisture damage in structures depends upon proper system
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
GreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
6 RETROFITTING POST & PIER HOUSES
Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This
Roof Tutorial. Chapter 3:
Chapter 3: Roof Tutorial The majority of Roof Tutorial describes some common roof styles that can be created using settings in the Wall Specification dialog and can be completed independent of the other
*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.
Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.
Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise
Baltimore, Maryland NOISE-CON 2010 2010 April 19-21 Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise Scott Harvey
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Renovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces
center for the polyurethanes industry October 2009 Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces One of the largest growing uses of spray polyurethane foam (SPF) insulation is in
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
8/18/14. Introduction to. Framing. Terminology and Concepts
8/18/14 Introduction to Framing Terminology and Concepts Terminology: Framing Level Two points on exactly the same horizontal plane. Square Intersecting lines or faces that form an exact 90 angle. Plumb
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
R-Value and Densities Chart
R-Value and Densities Chart Material R-Value Per Inch R-Value Per Unit Inside Air Film 0.68 Air Space between Studs 0.95 Building Pa 0.06 ½ in. Fiberboard Sheathing 1.52 Gypsum Wallboard or Drywall 0.90
The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs
The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................
ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill
ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses
DESIGN GUIDE. Thermal Design and Code Compliance for Cold-Formed Steel Walls. 2015 Edition
DESIGN GUIDE Thermal Design and Code Compliance for Cold-Formed Steel Walls 2015 Edition Steel Framing Alliance 25 Massachusetts Avenue, NW Suite 800 Washington, DC 20001 Thermal Design and Code Compliance
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
LP OSB Sheathing & Structural 1 Sheathing
Rated OSB Sheathing Roof Panels Span Ratings Max. Live Load Thickness Span Rating for Roofs (lbs)** 3/8" 24/0 30 7/16" 24/16 40 15/32" 32/16 70 1/2" 32/16 70 19/32" 40/20 130 23/32" 48/24 175 1-1/8" 48
The Case for Cross Laminated Timber: Part 2
Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction
Introduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
H-Stud Area Separation Wall System
12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic
Sample Drawing Package for One and Two Family Dwelling Applications
Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx
Residential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: [email protected] Planning and Development Services Department Residential Decks
4. ANCHOR BOLTS AND STRAPS a. ½" anchor bolts shall be embedded 7" into concrete a maximum of 6' on center and 12" from corners and ends of plates.
GENERAL CODE REQUIREMENTS (BASEMENTS) 1. FOOTINGS a. Footings shall be below frost line depth (42"). b. For an 8" foundation wall, footings shall be no less than 8" deep and 16" wide. c. Steel reinforcement
TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION
TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006
December 24, 2008. [email protected]. SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216
December 24, 2008 [email protected] SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216 RE: Georgetown Community 2C - Revised Assessment Date: October
STANDARD OPEN PATIO COVER
STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
Comment Form on Proposed Gut Rehabilitation Alternatives
Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to [email protected] by October 10 th, 2012 with the subject line
Single Family Residential Building Permit Questions & Answers
Single Family Residential Building Permit Questions & Answers Prepared by Dept. of Public Works Revised 07/01/13 200 East Park Street Edwardsville, IL 62025 (618) 692-7535 (618) 692-7505(Fax) Hours: Monday
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 STAIRWAYS 46. LANDINGS. Section R311 IRC 2009 R311.7.5 Landings for stairways. There shall be a floor or
Pre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
2009 IECC Update. Scope. Content. International Energy Conservation Code
2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are
CONSTRUCTION DETAILS & LOAD DESIGN CHARTS
Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description
Guidelines for Earthquake Bracing Residential Water Heaters
Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the
Rehab Inspection Report Page 1
Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation
Automatic Door Selection Guide
Automatic Door Selection Guide AAADM 1300 Sumner Avenue Cleveland, OH 44115 P: 216-241-7333 F: 216-241-0105 [email protected] Automatic Door Selection Guide General: The members of AAADM manufacture an assortment
research highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
Insulating Basements: Part 3 Basement Wall Systems
The Pennsylvania Housing Research Center Insulating Basements: Part 3 Basement Wall Systems Builder Brief: BB0710 Brian Wolfgang, PHRC Fellow INTRODUCTION The perception of a basement has changed significantly
Roof Tutorial. Chapter 3:
Chapter 3: Roof Tutorial The first portion of this tutorial can be completed independent of the previous tutorials. We ll go over some common roof styles that can be created using settings in the Wall
The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A
TechSpecs A builder s blueprint for construction technologies January 2013 The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A C B A E D H G F A. Wood Floor Framing - p. 2 B. Foundation
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
Page & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
Foundation. Foundation
Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
Residential Foundations and Basements
Residential Foundations and Basements Disclaimer All of the following information is based on the 2006 International Residential Code with Kentucky Amendments. As some information is paraphrased, article
Development Services City of Lawrence, KS
Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.
CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST
CITY OF BERKELEY DETAILED CHECKLIST This checklist will assist you in preparing plans for submittal with a building permit application. Alterations, additions and remodeling projects may not require all
Underwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
Residential Plan Routing Information
Residential Plan Routing Information BUILDING INSPECTIONS 800 4th AVENUE EAST WEST FARGO, ND 58078 PHONE: 701-433-5480 The building Inspection s Department receives and issues all applications for building
Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014
TOWNSHIP OF HILLSBOROUGH COUNTY OF SOMERSET Hillsborough Township Municipal Complex The Peter J. Biondi Building 379 South Branch Road Hillsborough, NJ 08844 P: (908) 369-4313 F: (908) 369-3954 Building
TYPICAL PATIO COVERS 111
City of Laguna Niguel Building Division 30111 Crown Valley Pkwy Laguna Niguel, CA 92677 (949) 362-4360 FAX 362-4369 www.cityoflagunaniguel.org TYPICAL PATIO COVERS 111 PLEASE NOTE: This information Bulletin
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.
Section 9.8. Stairs, Ramps, Handrails and Guards 9.8.1. Application 9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Heating Load Calculation
Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of
DEFAULT HEAT LOSS COEFFICIENTS
DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables
Bracing Webs in Trusses that have Dissimilar Configurations
Bracing Webs in Trusses that have Dissimilar Configurations Released April 25, 2006 Issue: Truss Design Drawings (TDD) that are prepared in accordance with ANSI/TPI 1, National Design Standard for Metal
Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996
CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed
THERMAL DESIGN AND CODE COMPLIANCE FOR COLD-FORMED STEEL WALLS. Steel Framing Alliance 1201 15th Street, NW, Suite 320 Washington, DC 20005
THERMAL DESIGN AND CODE COMPLIANCE FOR COLD-FORMED STEEL WALLS Steel Framing Alliance 1201 15th Street, NW, Suite 320 Washington, DC 20005 August 2008 Acknowledgements This report updates the Thermal Design
Garden Window. Montecito Series Vinyl Garden Window Architectural Manual
Montecito Series Vinyl The offers the outstanding insulating properties, low maintenance, and contemporary aesthetic appeal only vinyl can provide. Available in White and Tan homogenous window frames,
Timber Frame Construction
Timber Frame Construction Introduction Design and Detailing What is timber? Failure modes History of timber frame construction Forms of timber frame construction Live and dead loads Wind loads Roof construction
Best Barns USA Assembly Book
Best Barns USA Assembly Book Revised November 27, 2013 the Easton - R 12'x 20' Manufactured by Reynolds Building Systems, Inc. 205 Arlington Drive Greenville, PA 16125 724-646-3775 This manual is copyrighted.
first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel
first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel What is GigaCrete GigaCrete is a family of products based on low carbon footprint Green ceramic binders
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein
Structure Survey Findings:
Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,
STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663)
HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: 1-800-TEC-WOOD (832-9663) Fire-Retardant-Treated Wood Framed Wall Assemblies GENERAL INFORMATION Fire-resistant construction
Built to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
Common Errors in Truss Design
In today s competitive world of trusses, component manufacturers are always looking for ways to generate more efficient truss designs. Occasionally, truss designs need to be changed in order to be sealed
Performance of 8 Passive House Envelopes in Cold Climates
7 th Annual North American Passive House Conference September 27-30, 2012 Denver CO Performance of 8 Passive House Envelopes in Cold Climates Rolf Jacobson, LEED AP CSBR, University of Minnesota ZEB, Norwegian
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
Featuring TJ Rim Board and TimberStrand LSL
#TJ-8000 SPECIFIER S GUIDE TRUS JOIST RIM BOARD Featuring TJ Rim Board and TimberStrand LSL Multiple thicknesses, grades, and products to cover all your rim board needs 1¼" Thickness matches lateral load
2.9 WINDOW & DOOR BUCKS
2.9 WINDOW & DOOR BUCKS Bucks provide attachment surfaces for windows and doors while holding back concrete from these openings during concrete placement. Mark the center and edges of openings as you place
BUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction
EcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
Lightweight Partition Design for Residential and Commercial Buildings
Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation
Guidelines for Earthquake Bracing of Residential Water Heaters
Guidelines for Earthquake Bracing of Residential Water Heaters Department of General Services Division of the State Architect 1102 Q Street, Suite 5100 Sacramento, CA 95814 Phone: (916) 324-7099 Fax: (916)
RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS
RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS Johnson County Building Officials Association January 2008 Residential Foundation Guideline Foundation designs for one-and two-family dwellings may use
CHAPTER 6 CONSTRUCTION TYPES
CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use
Discipline: Structural Issued 04-26-06
California Department of General Services. Division of the State Architect. Product Acceptance Report STRUCTURAL SHEAR PANEL SURE-BOARD SERIES 200 PANELS PA-132 Discipline: Structural Issued 04-26-06 This
REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS
UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS Executive Summary: There is a proposal at the Joint Committee on Administrative