OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.



Similar documents
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

Data Sheet. Electro-mechanical counters Hengstler 800 series

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Lab 8: DC generators: shunt, series, and compounded.

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

F B = ilbsin(f), L x B because we take current i to be a positive quantity. The force FB. L and. B as shown in the Figure below.

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.

Circuit Breakers. NRC Series. NRC Series

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

MEASURING INSTRUMENTS. By: Nafees Ahmed, Asstt, Prof, EE Deptt, DIT, Dehradun

Transmission Protection Overview

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

DIRECT CURRENT GENERATORS

DISTRIBUTION TRANSFORMER OVERLOAD PROTECTION TRIPPING CIRCUIT

The purposes of this experiment are to test Faraday's Law qualitatively and to test Lenz's Law.

SYNCHRONOUS MACHINES

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

Current Transformers Ratio / Polarity / Types

Power Plant Electrical Distribution Systems

Pilot-wire differential relay for lines with two or more terminals

UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING.

Physics 221 Experiment 5: Magnetic Fields

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

1. The diagram below represents magnetic lines of force within a region of space.

Induced voltages and Inductance Faraday s Law

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

NATIONAL CERTIFICATE (VOCATIONAL)

T Substation Maintenance and Commissioning Test Equipment

Unit 24: Applications of Pneumatics and Hydraulics

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear. rated voltage 15, 27 and 38 kv rated current 630 A

45. The peak value of an alternating current in a 1500-W device is 5.4 A. What is the rms voltage across?

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

Sentron Series Circuit Breakers

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

VOLTAGE REGULATOR AND PARALLEL OPERATION

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Eaton s E-Series protective relay family

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Data Bulletin. Circuit Breaker Characteristic Trip Curves and Coordination Class 0600 TRIP CURVES AND COORDINATION CIRCUIT BREAKER TRIP CURVES

Line Reactors and AC Drives

Power Quality Paper #3

Generator Differential Relay Electrical Apparatus

Electromagnetic Induction Experiment

Current and voltage measuring relays

Principles and Working of DC and AC machines

Lab 14: 3-phase alternator.

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

EET272 Worksheet Week 8

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

Current & Instrument Transformers

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

FIT TIER 2 Application

ABB Power T&D Company Inc. Power Automation and Protection Division Coral Springs, FL 33065

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21,

Transfer Equipment Controls

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Type SA-1 Generator Differential Relay

ε: Voltage output of Signal Generator (also called the Source voltage or Applied

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

AP/UP, AP/MIL Series. Magnetic Circuit Protectors

Magnetic Field of a Circular Coil Lab 12

Alternate Methods to Short Circuit Breaker Coordination

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

Relays High Capacity 50 Amp Mini Relays Standard Mini Relays Micro Relays Power Relays Connector Modules

Three-phase AC circuits

Nu-Lec Training Modules

Motor Fundamentals. DC Motor

Candidate Number. General Certificate of Education Advanced Level Examination June 2014

ElectroMagnetic Induction. AP Physics B

Industrial Automation Commonly-Used Terms

GE Protection and Control Business Department. Page 1 Date 5/11/99

Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Lesson 3 DIRECT AND ALTERNATING CURRENTS. Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks.

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

Low voltage circuit breakers. Working with trip characteristic curves

Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.

WINDING RESISTANCE TESTING

5. Measurement of a magnetic field

CSDPR. Multi Powered Over-Current Relay

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Local Back-up Protection for an Electric Power System

R438 A.V.R. Installation and maintenance R 438. This manual is to be given to. the end user T10. Armature 6- Field X2 Z1 X1 Z2 E+ E- 0V

Mounting instructions. Acceleration Transducer B12. B 26.B12.10 en

Synchronous motor. Type. Non-excited motors

8 Speed control of Induction Machines

SELECTION OF FINAL CIRCUIT PROTECTION

Tuning Up DC Motors and Generators for Commutation and Performance

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

Design and Analysis of Switched Reluctance Motors

Residual Current Circuit Breaker

Fundamentals of Power

Transcription:

OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in the system and to initiate through appropriate circuit breakers the disconnection of faulty circuits so that interference with the general supply is minimised. Relays are of many types. Some depend on the operation of an armature by some form of electromagnet. A very large number of relays operate on the induction principle. When a relay operates it closes contacts in the trip circuit which is normally connected across 110 V D.C. supply from a battery. The passage of current in the coil of the trip circuit actuates the plunger, which causes operation of the circuit breaker, disconnecting the faulty system. In the laboratory, a 3-phase contactor simulates the operation of the circuit breaker. The closure of the relay contacts short-circuits the 'no-volt ' coil of the contactor, which, in turn, disconnects the faulty system. The protective relaying which responds to a rise in current flowing through the protected element over a pre-determined value is called 'overcurrent protection' and the relays used for this purpose are known as overcurrent relays. Earth fault protection can be provided with normal overcurrent relays, if the minimum earth fault current is sufficient in magnitude. The design of a comprehensive protection scheme in a power system requires the detailed study of time-current characteristics of the various relays used in the scheme. Thus it is necessary to obtain the timecurrent characteristics of these relays. The overcurrent relay works on the induction principle. The moving system consists of an aluminium disc fixed on a vertical shaft and rotating on two jewelled bearings between the poles of an electromagnet and a damping magnet. The winding of the electromagnet is provided with seven taps (generally0, which are brought on the front panel, and the required tap is selected by a push-in -type plug. The pick-up current setting can thus be varied by the use of such plug multiplier setting. The pick-up current values of earth fault relays are normally quite low. The operating time of all overcurrent relays tends to become asymptotic to a definite minimum value with increase in the value of current. This is an inherent property of he electromagnetic relays due to saturation of the magnetic circuit. By varying the point of saturation, different characteristics can be obtained and these are 1. Definite time 2. Inverse Definite Minimum Time (IDMT) 3. Very Inverse 4. Extremely Inverse

The torque of these relays is proportional to φ1φ2 Sinα, where φ1 and φ2 are the two fluxes and α is the angle between them. Where both the fluxes are produced by the same quantity (single quantity relays) as in the case of current or voltage operated, the torque T is proportional to I2, or T = K I 2, for coil current below saturation. If the core is made to saturate at very early stages such that with increase of I, K decreases so that the time of operation remains the same over the working range. The time -current characteristic obtained is known as definite -time characteristic. If the core is made to saturate at a later stage, the characteristic obtained is known as IDMT. The time-current characteristic is inverse over some range and then after saturation assumes the definite time form. In order to ensure selectivity, it is essential that the time of operation of the relays should be dependent on the severity of the fault in such a way that more severe the fault, the less is the time to operate, this being called the inverse-time characteristic. This will also ensure that a relay shall not operate under normal overload conditions of short duration. It is essential also that there shall be a definite minimum time of operation, which can be adjusted to suit the requirements of the particular installation. At low values of operating current the shape of the curve is determined by the effect of the restraining force of the control spring, while at high values the effect of saturation predominates. Different time settings can be obtained by moving a knurled clamping screw along a calibrated scale graduated from 0.1 to 1.0 in steps of 0.05. This arrangement is called Time Multiplier Setting and will vary the travel of the disc required to close the contacts. This will shift the time-current characteristic of the relay parallel to itself. By delaying the saturation to a further point, the Very Inverse and Extremely Very Inverse time current characteristics can be obtained. Pre-experimental quiz 1. What do you understand by Primary relay Secondary relay Auxiliary relay? 2. What do you understand by Single quantity relay Double or multiple quantity relay? 3. What is the purpose of shaded pole structure? 4. Can both a.c and d.c actuate the overcurrent & earth fault relays? 5. What is meant by Pick-up current Drop-out current Dropout ratio?

6. In systems with low ground fault current is there a necessity to provide an earth fault relay? 7. Where do you connect overcurrent & earth fault relays in a power system? 8. What do sensitivity & selectivity of a relay mean? Material & equipment Overcurrent relay, Earth fault relay, Current transformer, 3-phase contactor, 1-phase load, Ammeter, Digital timer. Procedure: Overcurrent Relay: 1. Study the construction of the relay and identify the various parts. 2. Connect as in FIG.1 FIG.1 Overcurent or Earth -fault Relay TRIP COIL RELAY COIL 3 4 9 10 No-Volt Coil 400 ohms C.T R 230V 50 Hz K N A 3-phase Contactor Load Timer

3. Set the pick-up value of the current marked 1 A(100 % f. l current) by inserting the plug in the groove. 4. Set the Time Multiplier Setting (TMS) initially at 1.0. 5. Adjust the load current to about 1.3 times the f.l current by shorting the switch K. Open the switch K to permit this adjusted current to flow through the relay and record the time taken for this overload condition. 6. Vary the value of the load current in steps and record the time taken for the operation of the relay in each case with the help of the timer. 7. Repeat steps 5 and 6 for TMS values of 0.2, 0.4,0.6 and 0.8. 8. Repeat the above experiment with different pick up current values using the plug setting bridge. Earth-fault Relay 1. Replace the overcurrent relay by the earth fault relay. 2. Set the pick-up value of the current to full load current using the plug setting bridge. 3. Set the TMS to 1.0 4. Vary the load current in different steps and record the operating current value and the time of operation in each case. 5. Repeat step 4 for different TMS values as in the overcurrent relay case. 6. Repeat with different pick-up current values, using the plug-setting bridge Data Sheet: Type of Relay: Pick-up current (plug setting multiplier) = ----- Amps S.No Current, A Current(A) times the plug setting multiplier Operating time in sec. for TMS of 0.2 0.4 0.6 0.8 1.0 Data Processing & analysis: 1. Plot operating time versus the multiples of plug setting values for different TMS on the same graph for overcurrent relay. 2. Plot on a log -log sheet operating time versus the multiples of the plug setting value for different time multiplier settings on the same graph sheet for the overcurrent relay. 3. Plot the curves for earth fault relay as in steps 1 and 2 respectively. 4. Observe the Inverse nature of the characteristics as well as the definite time required for the operation of the relay in either case. Post experimental Quiz: 1. When is it necessary to add a direction feature for overcurrent protection?

2. Can the overcurrent and earth fault relays be made to operate instantaneously and how? 3. What are the equations of IDMT, very Inverse and Extremely Inverse overcurrent relays?