1756 ControlLogix Chassis Specifications



Similar documents
1756 ControlLogix Power Supplies Specifications

1788 Linking Device Specifications

CompactLogix Power Supplies Specifications

1756 ControlLogix I/O Specifications

Bimetallic Overload Relay Specifications

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

1756 ControlLogix Integrated Motion Modules Specifications

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P

USB-to-Data Highway Plus Cable

PanelView Component Specifications

PanelView 800 Terminals

Micro800 Programmable Controller Family. Bulletin 2080 Selection Guide

1756 ControlLogix Communication Modules Specifications

Compact I/O End Caps/Terminators

Stratix Ethernet Switch Specifications

NI NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module

Rotary Disconnect Switch Specifications

Micro800 Programmable Controllers. Bulletin 2080 Selection Guide

1442 Eddy Current Probe Systems Specifications

Redundancy Module QUINT-DIODE/40

Telephone- and leased line modem for industrial applications TD-36

Foxboro Evo Process Automation System

SMC -3 Specifications

DeltaV SISnet Repeater

ControlNet Standard and High-flex Coax Cable

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

S-series Mass Connection Solutions

Waveguide Access Point WGA631. Product Guide

Power Supplies 3. SDN-P DIN Rail Series

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Legacy PanelView to PanelView Plus 6 Catalog Number Conversions

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

3500/15 Power Supply Bently Nevada* Asset Condition Monitoring

STRATO LED Drivers 70W, Single output

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Terminal Boxes in Glass Fiber Reinforced Polyester (GRP)

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Isolating Barriers for our sensors A5S1 in Ex-areas Series D461

S-series SQ Controller

3500/62 Process Variable Monitor

CompactRIO crio-9052

CompactLogix Communication Modules Specifications

Rack mounted telephone- and leased line modem for industrial applications

Universal Serial Bus (USB) to DH-485 Interface Converter

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

Hard Disk Drive (HDD)

Plug and Socket Devices CES 63 A Series 8579

1769 Compact I/O Modules Specifications

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Series 8146/5-V37 and Series 8150/5-V37

Ammeter / Voltmeter Series 8402, 8403, 8405, 8404

Floodlight Range Installation Guide

PanelView Plus 7 Performance Terminals

ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide

CQM1-SF200/CS1W-SF200

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

ZS25 Screw Clamp Terminal Blocks Feed-through

MCR1900 Media Converter 19-Slot Chassis

PanelView Plus to PanelView Plus 6 Catalog Number Conversions

Relés e Contatores de Estado Sólido SIRIUS

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date:

Three-phase monitoring relay CM-PFE

MicroLogix 1100 Embedded Web Server

Stainless Steel and Mild Steel Enclosures. Stainless Steel and Mild Steel Enclosures

RM4TG20 three-phase network control relay RM4-T - range V

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

3500/25 Enhanced Keyphasor*Module

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

PXI Express Chassis with Integrated MXI-Express Remote Controller

HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5" - TFT - 96 MB

XPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment

Safety Function: Door Monitoring

Installation Instructions. Before Installation. Read these installation instructions carefully before commissioning the pressure transmitter.

Ammeter / Voltmeter Series 8402, 8403, 8405, 8404

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket

Stratix 5700 Switch Configuration

Manual motor starter MS116

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Logix5000 Controllers Nonvolatile Memory Card

How To Power A Power Supply Shelf With A Power Unit (Hp 2920)

ST Series POWER SUPPLIES USER INSTRUCTIONS

3DLevelScanner II TECHNICAL DATA SHEET

LOGO!Power. Power supply. LOGO!Power. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/disassembly

LOGO!Power. Power supply. LOGO!Power. Overview. Description, device design, dimension drawing. Mounting/Disassembly 2

and Accelerometers

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Plug and Socket Devices SolConeX 16 A Series 8570

Energy Management Energy Meter Type EM23 DIN

SMART Board interactive flat panel with appliance Model 8055ie-SMP

Transcription:

Technical Data 1756 ControlLogix Chassis Specifications Catalog Numbers 1756-A4/B, 1756-A4K/B, 1756-A4/C, 1756-A4K/C, 1756-A7/B, 1756-A7K/B, 1756-A7/C, 1756-A7K/C, 1756-A10/B, 1756-A10K/B, 1756-A10/C, 1756-A10K/C, 1756-A13/B, 1756-A13K/B, 1756-A13/C, 1756-A13K/C, 1756-A17/B, 1756-A17K/B, 1756-A17/C, 1756-A17K/C, 1756-A4LXT/B, 1756-A5XT/B, 1756-A7LXT/B, 1756-A7XT/B, 1756-A7XT/C Topic Page Standard ControlLogix Chassis Specifications 2 ControlLogix-XT Chassis Specifications 4 Spacing Requirements 6 ControlLogix Chassis with Standard Power Supplies Mounting Dimensions 8 (Series B) ControlLogix Chassis with Standard Power Supplies Mounting Dimensions 12 (Series C) ControlLogix Chassis Accessories 20 Additional Resources 21 The ControlLogix system is a modular system that requires a 1756 ControlLogix chassis. The chassis are designed for only horizontal back-panel mounting. Place any module into any slot. The backplane provides a high-speed communication path between modules. AutoCAD product drawings are available at http://www.rockwellautomation.com/en/e-tools/drawings.html.

Standard ControlLogix Chassis Specifications The chassis backplane provides a high-speed communication path between modules and distributes power to each of the modules within the chassis. Table 1 - Technical Specifications - ControlLogix Standard Chassis (Series B) Attribute 1756-A4/B 1756-A7/B 1756-A10/B 1756-A13/B 1756-A17/B Backplane current, chassis/slot max @ 1.2V DC 1.5 A/- Backplane current, chassis/slot max @ 3.3V DC 4 A/4 A Backplane current, chassis/slot max @ 5.1V DC 15 A/6 A Backplane current, chassis/slot max @ 24V DC 2.8 A/2.8 A Power dissipation, max 4 W 4.5 W 5 W 5.4 W 6 W Isolation voltage Determined by installed power supply and modules Slots 4 7 10 13 17 Mounting method Only horizontal Cabinet size (HxWxD), min 50.8 x 50.8 x 20.3 cm (20 x 20 x 8 in.) 50.8 x 60.9 x 20.3 cm (20 x 24 x 8 in.) 50.8 x 76.2 x 20.3 cm (20 x 30 x 8 in.) 60.9 x 76.2 x 20.3 cm (24 x 30 x 8 in.) 76.2 x 91.4 x 20.3 cm (30 x 36 x 8 in.) Weight, approx 0.75 kg (1.7 lb) 1.10 kg (2.4 lb) 1.45 kg (3.2 lb) 1.90 kg (4.2 lb) 2.20 kg (4.8 lb) Location Panel Wire size Functional Earth Ground - 8.3 mm 2 (8 AWG) solid or stranded copper wire rated at 90 C (194 F) or greater Protective Earth Ground - 2.1 mm 2 (14 AWG) solid or stranded copper wire rated at 90 C (194 F) or greater North American temperature code T5 IEC temperature code T4 T5 Enclosure type rating None (open-style) Table 2 - Technical Specifications - ControlLogix Standard Chassis (Series C) Attribute 1756-A4/C 1756-A7/C 1756-A10/C 1756-A13/C 1756-A17/C Backplane current, chassis/slot max @ 1.2V DC 1.5 A/- Backplane current, chassis/slot max @ 3.3V DC 4 A/4 A Backplane current, chassis/slot max @ 5.1V DC 15 A/6 A Backplane current, chassis/slot max @ 24V DC 2.8 A/2.8 A Power dissipation, max 4 W 4.5 W 5 W 5.4 W 6 W Isolation voltage Determined by installed power supply and modules Slots 4 7 10 13 17 Mounting method Only horizontal Cabinet size (HxWxD), min 50.8 x 50.8 x 20.3 cm (20 x 20 x 8 in.) 50.8 x 60.9 x 20.3 cm (20 x 24 x 8 in.) 50.8 x 76.2 x 20.3 cm (20 x 30 x 8 in.) 60.9 x 76.2 x 20.3 cm (24 x 30 x 8 in.) 76.2 x 91.4 x 20.3 cm (30 x 36 x 8 in.) Weight, approx 0.75 kg (1.7 lb) 1.10 kg (2.4 lb) 1.45 kg (3.2 lb) 1.90 kg (4.2 lb) 2.20 kg (4.8 lb) Location Panel Wire size Functional earth ground - 8.3 mm 2 (8 AWG) solid or stranded copper wire rated at 90 C (194 F) or greater Protective earth ground - 2.1 mm 2 (14 AWG) solid or stranded copper wire rated at 90 C (194 F) or greater North American temperature code T4 IEC temperature code T4 Enclosure type rating None (open-style) 2 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

Table 3 - Environmental Specifications - ControlLogix Standard Chassis Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 1756-A4/B, 1756-A7/B, 1756-A10/B, 1756-A13/B, 1756-A17/B 1756-A4/C, 1756-A7/C, 1756-A10/C, 1756-A13/C, 1756-A17/C 0 60 C (32 140 F) -25 60 C (-13 140 F) 60 C (140 F) -40 85 C (-40 185 F) 5 95% noncondensing 2 g @ 10 500 Hz Emissions IEC 61000-6-4 ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 30 g 50 g 30 g 6 kv contact discharges 8 kv air discharges 10V/m with 1 khz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 khz sine-wave 80% AM from 2000 2700 MHz Table 4 - Certifications - ControlLogix Standard Chassis Certification (1) 1756-A4/B 1756-A7/B, 1756-A10/B, 1756-A13/B, 1756-A17/B 1756-A4/C, 1756-A7/C, 1756-A10/C, 1756-A13/C, 1756-A17/C c-ul-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA FM CE RCM Ex CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations. European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex na IIC T4 Gc X European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex na IIC T5 Gc X CSA Certified Process Control Equipment. See CSA File LR054689. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA FileLR069960. European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex na IIC T4 Gc DEMKO13ATEX1325026X Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 3

Table 4 - Certifications - ControlLogix Standard Chassis Certification (1) 1756-A4/B 1756-A7/B, 1756-A10/B, 1756-A13/B, 1756-A17/B 1756-A4/C, 1756-A7/C, 1756-A10/C, 1756-A13/C, 1756-A17/C IECEx N/A IECEx System, compliant with: IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" IEC 60079-0; General Requirements II 3 G Ex na IIC T4 Gc IECExUL008X KC EAC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation (1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. ControlLogix-XT Chassis Specifications The ControlLogix-XT chassis support extreme temperature environments. The chassis are conformally coated for increased survivability in ISA G3 environments. Table 5 - Technical Specifications - ControlLogix-XT Chassis Attribute 1756-A4LXT/B 1756-A7LXT/B 1756-A5XT/B 1756-A7XT/B 1756-A7XT/C Backplane current, chassis/slot max @ 1.2V DC 1.5 A/- Backplane current, chassis/slot max @ 3.3V DC 4 A/4 A Backplane current, chassis/slot max @ 5.1V DC 10 A/6 A 15 A/6 A 10 A/6 A Backplane current, chassis/slot max @ 24V DC 2 A/2 A 2.8 A/ 2.8A 2 A/2 A Power dissipation, max 3.7 W 4.1 W 4.4 W Isolation voltage Determined by installed power supply and modules Slots 4 7 5 7 Mounting method Horizontal only Cabinet size (HxWxD), min 50.8 x 50.8 x 20.3 cm (20 x 20 x 8 in.) 50.8 x 60.9 x 20.3 cm (20 x 24 x 8 in.) 50.8 x 76.2 x 20.3 cm (20 x 30 x 8 in.) 50.8 x 60.9 x 20.3 cm (20 x 24 x 8 in.) Weight, approx 0.75 kg (1.7 lb) 1.1 kg (2.4 lb) 1.45 kg (3.2 lb) 1.09 kg (2.4 lb) Location Panel Wire size Functional earth ground - 8.3 mm 2 (8 AWG) solid or stranded copper wire rated at 90 C (194 F) or greater Protective earth ground - 2.1 mm 2 (14 AWG) solid or stranded copper wire rated at 90 C (194 F) or greater North American temperature code T5 T4A T4 IEC temperature code T5 T4 Enclosure type rating None (open-style) 4 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

Table 6 - Environmental Specifications - ControlLogix-XT Chassis Attribute 1756-A4LXT/B, 1756-A7LXT/B 1756-A5XT/B, 1756-A7XT/B 1756-A7XT/C Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -25 60 C (-13 140 F) -25 70 C (-13 158 F) Temperature, surrounding air 60 C (140 F) 70 C (158 F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) -40 85 C (-40 185 F) 5 95% noncondensing 2 g @ 10 500 Hz 30 g 50 g 30 g Emissions IEC 61000-6-4 ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 6 kv contact discharges 8 kv air discharges 10V/m with 1 khz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 khz sine-wave 80% AM from 2000 2700 MHz Table 7 - Certifications - ControlLogix-XT Chassis Certification (1) 1756-A5XT/B, 1756-A7XT/B, 1756-A7XT/C c-ul-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) RCM Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex na IIC T4 Gc X DEMKO13ATEX1325026X IECEx IECEx System, compliant with: IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" IEC 60079-0; General Requirements II 3 G Ex na IIC T4 Gc IECExUL008X KC EAC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation 1756-A4LXT/B, 1756-A7LXT/B IECEx System, compliant with: IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" IEC 60079-0; General Requirements II 3 G Ex na IIC T5 Gc IECExUL008X (1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 5

Spacing Requirements When you mount a ControlLogix chassis with a standard power supply in an enclosure, follow these spacing requirements (series C chassis depicted). 15.3 (6.0) 10.2 (4.0) 15.3 (6.0) 10.2 (4.0) Dimensions are in cm (in.). The 10.2 (4.0) measurement to the side of the enclosure can include the wireway. W I R E W A Y WIREWAY 7.7 (3.0) 5.1 (2.0) 5.1 (2.0) W I R E W A Y 15.3 (6.0) 6 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

IMPORTANT The 1756-CPR2 cable has a bend radius of 12.7 cm (5.0 in.). The chassis must have a minimum clearance of 12.7 cm (5.0 in.) on the left side to route and connect the 1756-CPR2 cable. The redundant power supplies must have a minimum clearance of 12.7 cm (5.0 in.) below the supply to route and connect the 1756-CPR2 cable. When you mount a ControlLogix chassis with a redundant power supply and a chassis adapter in an enclosure, follow these spacing requirements (series C chassis depicted). 10.2 (4.0) 12.7 (5.0 2.55 (1.0) 5.1 (2.0) WIREWAY 5.1 (2.0) 10.2 (4.0) 15.3 (6.0) 15.3 (6.0) 12.7 (5.0) 12.7 (5.0) 15.3 (6.0) 12.7 (5.0) WIREWAY 5.1 (2.0) 10.2 (4.0) W I R E W A Y Dimensions are in cm (in.). The 10.2 (4.0) measurement to the side of the enclosure can include the wireway only on the right side of the chassis. 12.7 (5.0) 15.3 (6.0) 12.7 (5.0) 15.3 (6.0) 15.3 (6.0) Series C chassis offer: Improved slot guidelines Improved ventilation Stronger mounting tabs Additional hole in mounting tab Additional ground screw Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 7

ControlLogix Chassis with Standard Power Supplies Mounting Dimensions (Series B) Dimensions are in cm (in.). Figure 1 - Chassis Common Dimensions 0.55 (0.217) Top Mounting Hole Diameter 0.55 (0.217) 1.1 (0.433) Bottom Mounting Hole Diameter Right-side View of All Standard Chassis Right-side View of All ControlLogix-XT Chassis (5.71) 14.9 (5.87) Figure 2-1756-A4/B Chassis and Power Supply 7.0 (2.76) 4.71 (1.85) 26.3 (10.34) 8 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

Figure 3-1756-A7/B Chassis and Power Supply 17.5 (6.89) 4.71 (1.85) 36.7 (14.47) Figure 4-1756-A10/B Chassis and Power Supply 5.7 (2.25) 48.3 (19.02) Figure 5-1756-A13/B Chassis and Power Supply 10.5 (4.13) 5.7 (2.25) 58.8 (23.13) Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 9

Figure 6-1756-A17/B Chassis and Power Supply 13.3 (5.22) 13.3 (5.22) 4.7 (1.85) 73.8 (29.04) Figure 7-1756-A4LXT/B Chassis and Power Supply 7.0 (2.76) 6.3 (2.48) (5.72) 27.8 (10.96) Figure 8-1756-A5XT/B Chassis and Power Supply 7.3 (2.87) (5.72) 49.8 (19.62) 10 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

Figure 9-1756-A7LXT/B Chassis and Power Supply 17.5 (6.89) 6.3 (2.48) (5.72) 38.3 (15.10) Figure 10-1756-A7XT/B Chassis and Power Supply 7.3 (2.87) 49.8 (19.62) Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 11

ControlLogix Chassis with Standard Power Supplies Mounting Dimensions (Series C) Dimensions are in cm (in.). Figure 11 - Chassis Common Dimensions 0.55 (0.217) Top Mounting Hole Diameter 0.55 (0.217) 1.1 (0.433) Bottom Mounting Hole Diameter Right-side View of All Standard Chassis Right-side View of All ControlLogix-XT Chassis (5.71) 14.9 (5.87) Figure 12-1756-A4/C Chassis and Power Supply 7.0 (2.76) 4.71 (1.85) 26.3 (10.34) 12 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

Figure 13-1756-A7/C Chassis and Power Supply 17.5 (6.89) 4.71 (1.85) 36.7 (14.47) Figure 14-1756-A10/C Chassis and Power Supply 5.7 (2.25) 48.3 (19.02) Figure 15-1756-A13/C Chassis and Power Supply 10.5 (4.13) 5.7 (2.25) 58.8 (23.13) Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 13

Figure 16-1756-A17/C Chassis and Power Supply 13.3 (5.22) 13.3 (5.22) 4.7 (1.85) 73.8 (29.04) Figure 17-1756-A7XT/C Chassis and Power Supply 7.3 (2.87) 49.8 (19.62) 14 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

ControlLogix Chassis with Redundant Power Supplies Mounting Dimensions (Series B) IMPORTANT The 1756-CPR2 cable has a bend radius of 12.7 cm (5.0 in.). The chassis must have a minimum clearance of 12.7 cm (5.0 in.) on the left side to route and connect the 1756-CPR2 cable. The redundant power supplies must have a minimum clearance of 12.7 cm (5.0 in.) below the supply to route and connect the 1756-CPR2 cable. Dimensions are in cm (in.). Figure 18 - Redundant Power Supplies 7.0 (2.76) Top Mounting Hole Diameter Bottom Mounting Hole Diameter 17.5 (6.88) 0.55 (0.217) 1.1 (0.433) 14.4 (5.66) Figure 19 - Chassis Common Dimensions Right-side View of All Chassis Top Mounting Tab Diameter Bottom Mounting Tab Diameter 0.55 (0.217) 1.1 (0.433) 0.78 (0.31) (5.71) Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 15

Figure 20-1756-A4/B Chassis and Chassis Adapter Module 7.0 (2.76) 4.7 (1.85) 18.6 (7.32) Figure 21-1756-A7/B Chassis and Chassis Adapter Module 17.5 (6.89) 4.7 (1.85) 29.1 (11.46) Figure 22-1756-A10/B Chassis and Chassis Adapter Module 5.71 (2.25) 40.6 (15.98) 16 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

Figure 23-1756-A13/B Chassis and Chassis Adapter Module 10.5 (4.13) 5.71 (2.25) 51.1 (20.12) Figure 24-1756-A17/B Chassis and Chassis Adapter Module. 13.3 (5.22) 13.3 (5.22) 4.7 (1.85) 66.1 (26.02) Figure 25-1756-A4LXT/B Chassis and Chassis Adapter 7.0 (2.76) 6.29 (2.48) 20.1 (7.91) Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 17

Figure 26-1756-A5XT/A7XT/B Chassis and Chassis Adapter 7.3 (2.87) 42.1 (16.57) 18 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

ControlLogix Chassis with Redundant Power Supplies Mounting Dimensions (Series C) IMPORTANT The 1756-CPR2 cable has a bend radius of 12.7 cm (5.0 in.). The chassis must have a minimum clearance of 12.7 cm (5.0 in.) on the left side to route and connect the 1756-CPR2 cable. The redundant power supplies must have a minimum clearance of 12.7 cm (5.0 in.) below the supply to route and connect the 1756-CPR2 cable. Figure 27 - Redundant Power Supplies 7.0 (2.76) Top Mounting Hole Diameter Bottom Mounting Hole Diameter 17.5 (6.88) 0.55 (0.217) 1.1 (0.433) 14.4 (5.66) Figure 28 - Chassis Common Dimensions Right-side View of All Chassis Top Mounting Tab Diameter Bottom Mounting Tab Diameter 0.55 (0.217) 0.55 (0.217) 1.1 (0.433) 0.78 (0.31) (5.71) Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 19

Figure 29-1756-A7XT/C Chassis and Chassis Adapter 7.3 (2.87) 42.1 (16.57) ControlLogix Chassis Accessories Use a slot filler module to fill empty slots. Cat. No. Description 1756-N2 Slot filler module for empty slots in standard ControlLogix chassis 1756-N2XT Slot filler module for empty slots in ControlLogix-XT chassis 20 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource ControlLogix Selection Guide, publication 1756-SG001 ControlLogix Power Supplies Specifications Technical Data, publication 1756-TD005 ControlLogix System User Manual, publication 1756-UM001 Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http://www.ab.com Description Provides an overview of the ControlLogix system and its products. Provides technical specifications for ControlLogix power supplies. Provides information on how to install, configure, program, and use ControlLogix controllers. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 21

Notes: 22 Rockwell Automation Publication 1756-TD006E-EN-E - October 2014

Rockwell Automation Publication 1756-TD006E-EN-E - October 2014 23

Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, ControlLogix, ControlLogix-XT, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 1756-TD006E-EN-E - October 2014 Supersedes Publication 1756-TD006D-EN-E - March 2013 Copyright 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.