Transmission Protection Overview



Similar documents
INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Teleprotection Schemes and Equipment. James W. Ebrecht Young Power Equipment Scottsdale, AZ

Local Back-up Protection for an Electric Power System

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Directional Comparison Blocking System Fundamentals

Pilot-wire differential relay for lines with two or more terminals

ECE 586b Course Project Report. Auto-Reclosing

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Application of Overreaching Distance Relays

Assessment of power swing blocking functions of line protective relays for a near scenario of the Uruguayan system

Transmission Line Protection Principles

Relay-to-Relay Digital Logic Communication for Line Protection, Monitoring, and Control

Advanced Protection of Distribution Networks with Distributed Generators

Permissible ambient temperature Operation Storage, transport

MiCOM P432 and P439. Distance Protection and Control Units. Protection Relays

Electric utilities may vary in their application of end-to-end testing

EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK

SIPROTEC Protection Technology

15LINE PROTECTION WITH PILOT RELAYS

Power Quality Paper #3

Special Considerations in Applying Power Line Carrier for Protective Relaying

Loss of ac Voltage Considerations For Line Protection

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Test & Data Management Software

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

TDMS Test & Data Management Software

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Numerical Differential Protection

The Application and Benefits of Multi-phase Auto-reclosing

Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through Fault and Blackout

The following table shows approximate percentage wise the

Impact of Distributed Resources on Distribution Relay Protection

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Everything you need for protection scheme testing

APPLICATION CASE OF THE END-TO-END RELAY TESTING USING GPS-SYNCHRONIZED SECONDARY INJECTION IN COMMUNICATION BASED PROTECTION SCHEMES

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Evaluation of L-PRO 4000 for End-to-End Communication Using IEC Protocol With RFL IMUX 2000 Multiplexer

Study on Differential Protection of Transmission Line Using Wireless Communication

Fundamentals of Power

Low Cost Automatic Transmission Line Sectionalizing

Step Voltage Regulators

Advances in Series-Compensated Line Protection

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

Eaton s E-Series protective relay family

Multi-Terminal DC System line Protection Requirement and High Speed Protection Solutions

SYNCHRONOUS MACHINES

Experten System zur Koordination von Schutzsystemen

ABB PSPS Erich Steinmann; Generator control-2013

Industrial IT for Substation Automation & Protection

FIT TIER 2 Application

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Evolution of Control for the Smart Transmission Grid

Type SA-1 Generator Differential Relay

Bus Protection Considerations for Various Bus Types

Staged-Fault Testing of Distance Protection Relay Settings

Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards

Current and voltage measuring relays

SPECIFICATION COG-2007

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.

Generator Differential Relay Electrical Apparatus

Arc Terminator Active Arc-Resistant Switchgear

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Considering the effects of UPS operation with leading power factor loads

Numerical transformer protection in medium voltage networks Transformer Protection and Control RET620

DIGITAL COMMUNICATIONS FOR POWER SYSTEM PROTECTION: SECURITY, AVAILABILITY, AND SPEED

13 ELECTRIC MOTORS Basic Relations

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed

Eaton Automatic Transfer Switches

Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation

TABLE OF CONTENTS 1.0 INTRODUCTION PURPOSE DEVIATION INTERTIE PROTECTION REQUIREMENTS... 4

PRESENT PROBLEMS OF POWER SYSTEM CONTROL

40 Series - Miniature PCB/Plug-in relays A. Features

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Transmissão em Corrente Contínua

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.

Stanford University Installs Advanced Power System

Distribution Automation Handbook. Section 8.13 Backup Protection

Lesson 12 Sequential Circuits: Flip-Flops

AORC Technical meeting 2014

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents

Step Response of RC Circuits

CT Application Guide for the 489 Generator Management Relay

Data Bulletin. Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers. Introduction. Thermal-Magnetic or Electronic Trip Unit?

MAS.836 HOW TO BIAS AN OP-AMP

Federal Wage System Job Grading Standards for Electric Power Controlling, Table of Contents

Chapter 3 AUTOMATIC VOLTAGE CONTROL

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]

REAL-TIME MONITORING AND ASSESSMENT OF CIRCUIT BREAKER OPERATIONS FOR DIAGNOSTICS AND CONTROL APPLICATIONS

Transfer Equipment Controls

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

Transcription:

Transmission Protection Overview 2012 Hands-On Relay School Brian Smyth Schweitzer Engineering Laboratories Pullman, WA

Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes

Transmission Line Protection Topics Primary/backup protection Coordination Communication-based schemes Breaker failure protection Out-of-step relaying Synchronism checking

Primary Protection Function Trip for abnormal system conditions that may Endanger human life Damage system equipment Cause system instability

Protection Zones Primary protection first line of defense Backup protection operates when primary fails

How Can A Protection System Fail? Current or voltage signal supply Tripping voltage supply Power supply to the relay Protective relay Tripping circuit Circuit breaker

Two Types of Backup Remote backup Located at different station No common elements Local backup Located at same station Few common elements Separate relays Independent tripping supply and circuit Different current and voltage inputs

Remote vs Local Backup Speed Remote is slower Selectivity Remote disconnects larger part of the system Price Local requires additional equipment

Primary and Backup Coordination Best selectivity with minimum operating time Achieved through settings Pick up values Time delays

Coordination Types Considered Time-Overcurrent Time-Stepped Distance Communication-Aided Schemes

Time-Overcurrent Relays Definite-Time Overcurrent Operate in a settable time delay when the current exceeds the pickup value Instantaneous operation no intentional time delay Inverse-Time Overcurrent Operating curve defined by limiting the total fault energy (K d = I 2 t)

Time-Overcurrent Coordination Inverse-Time Overcurrent Pickup of relay A set low enough to see the fault shown and backup relay C Pickup should be above emergency load conditions (phase relays) Time delay of relay A should allow relay C to clear the fault first

Time-Overcurrent Coordination S - Selectivity time delay (aka CTI): Breaker operating time Overtravel (impulse) time (E/M relays) Safety margin 0.2s CTI 0.4s

Time-Overcurrent Coordination Looped Systems Directionality required for most relays 1-2-3-4-5 a-b-c-d-e Relays at 5 and e can be nondirectional

Instantaneous Overcurrent Protection Inverse-Time O/C coordination may result in long time delays Instantaneous O/C relays set to trip for faults for ~80% of the line section Significantly reduced tripping times for many faults

Time-Stepped Distance Protection Coordination similar to that of inverse-time O/C Relay at A set to trip instantaneous for faults in its Zone 1 (reaching ~80% of the line section) Relay at A backs up relay at C after Zone 2 timer times out Faults at the end of the line also cleared in Zone 2 time

Communication-Based Protection Rationale Distance protection can clear faults instantaneously for 60% to 80% of the line length Protection speed may be critical to maintain system stability High-speed autoreclosing application

Communication-Based Protection Communication Mediums Power Line Carrier Microwave Fiber-Optics Private and Leased Pilot Channels

Communication-Based Protection Scheme Types Permissive Overreaching Transfer Trip (POTT) Permissive Underreaching Transfer Trip (PUTT) Directional Comparison Blocking (DCB) Directional Comparison Unblocking (DCUB) Direct Underreaching Transfer Trip (DUTT) Direct Transfer Trip (DTT)

Permissive Overreaching TT Protective Zones

Permissive Overreaching TT Permissive signal must be detected from the remote end for the communicationaided trip Absence of communication channel disables the accelerated tripping

Permissive Overreaching TT Complications and Concerns Desensitization due to infeed Dependability issue failure to trip high speed Current reversal Occurs in parallel lines with sequential tripping Security issue coupled with long channel reset times may cause trip of the healthy parallel line

Current Reversal All Sources In Z2 at Breaker 1 picks up and sends permissive signal to Breaker 2 Z2 at Breakers 3 and 4 send permissive signals to each other Z1 at Breaker 4 trips instantaneously

Current Reversal System After Breaker 4 Opens Current reverses through the healthy line Z2 at Breaker 2 picks up If the permissive signal has not reset, Breaker 2 trips on POTT

Current Reversal Possible Solution Timer with instantaneous pickup and time delayed dropout, initiated on reverse Z3 Delay trip with POTT until the timer drops out

Permissive Underreaching TT Similar to POTT but permissive signal sent by underreaching Z1 elements At the receiving end, Z2 elements qualify the permissive signal No problems with current reversal since Z1 doesn t overreach

Directional Comparison Blocking Protective Zones Zone 2 elements cover the entire line Reverse Zone 3 elements must reach further than the opposite Zone 2 overreach

Directional Comparison Blocking Basic Logic In-section faults will not key transmitter and both ends trip high-speed Out-of-section fault will key the transmitter at the nearest end to block the trip at the opposite end

Directional Comparison Blocking Complications and Concerns Coordinating time at fault inception Z3 faster than Z2, but channel delay time reduces the margin Z2 must be slowed down External fault clearing Z3 and Z2 race to drop out, if Z3 drops out first Z2 overtrips Z3 operates faster and drops slower Channel reset time helps Slower transmitter key dropout time helps

Directional Comparison Blocking Complications and Concerns External fault clearing failure Local backup provided by time-delayed Z3 or external BF relay clears the near bus Remote backup provided by Z2 clears the line Stop preference over start

Directional Comparison Blocking Complications and Concerns Current reversal Reach Margin Z3 reaches farther back than remote Z2 by at least 50% of Z2 overreach

Directional Comparison Unblocking Essentially the same as POTT Requires FSK In-section fault may impede communication In case of channel loss, a 150 ms window is open when permissive signal is bypassed and Z2 allowed to trip high speed

Direct Underreaching TT Underreaching Z1 elements send direct transfer trip Noisy channel can cause false trip Very secure channel required

Pilotless Accelerated Trip Schemes Communication equipment not justifiable in lower voltage transmission applications In-section faults may be uniquely determined by system conditions Detecting these conditions is all that is needed for high speed tripping

Pilotless Accelerated Trip Schemes Faulted System with Breakers Closed After Breaker 2 opens the only current that can flow is the fault current

Pilotless Accelerated Trip Schemes Faulted System with Breaker 2 Open Tripping conditions: Three-phase load was present before the fault Three-phase current was lost Current above the threshold detected in at least one phase

Breaker Failure Relaying Minimize the damage when a breaker fails to clear a fault Trips all sources locally within the critical clearing time to maintain system stability

Breaker Failure Relaying Common Causes of Breaker Failure Main breaker poles failed to clear the fault due to inadequate insulating medium Open trip coil or trip coil circuit Loss of tripping dc Mechanical failure of the breaker trip mechanism

Breaker Failure Relaying Operating Philosophy Activated only when a trip signal is issued from protective relay If current is above threshold after a pre-set time period, breaker failure condition is declared

Breaker Failure Relaying Considerations Timer settings must take into account the clearing time of the slowest breaker and the reset time of the fault detector The effect of any opening resistors in the circuit breakers on the reset time of fault detector Substation bus configuration must be taken into account to trip minimum number of breakers In multi-breaker schemes, possible transfer trip to the remote end

Out-of-Step Detection and Blocking Causes of Out-of-Step Power swings result from faults, switching, or big changes in load or generation Magnitude of the swing depends on the system impedance change during such conditions Swings can be stable or unstable

Power Transfer Equation where:, sin δ P power transferred from the sending to the receiving end V V S R P= P = P = sending end voltage receiving end voltage δ angle by which V leads V S S R VV X total reactance between the sending and receiving end R S X R

Power Transfer Curves,

Electrical Quantities During Swing Apparent Impedance Trajectories

Electrical Quantities During Swing Apparent Impedance Trajectories Apparent impedance during power swings can enter into the reach of distance relays If the apparent impedance stays longer than the time delay in a given zone, that distance element will trip as for a fault To prevent such tripping, out-of-step blocking schemes are employed

Out-of-Step Blocking Distance Elements If the timer expires between the two zones, out-of-step condition is declared and selected distance elements are blocked

Synchronism Checking After clearing a fault, one end of the line will reclose to test the line If the test is good, the other end can be closed but only if voltages are close enough and there is a small phase angle difference If the conditions are not right, the system will undergo a mechanical and electrical shock with a possible unstable swing

Synchronism Checking Monitored Quantities Voltage magnitudes Phase angle difference Slip frequency

Synchronism Checking Synchronizer Window

Synchronism Checking Conditions Both voltage phasors are above 59V setting Phase angle difference is small The above conditions are maintained for a short time, ensuring that the slip frequency is small enough and measurements are valid

Synchronism Checking Relay Phasor difference setting 25DV = 59V sinθ Timer setting 2 θ 25T = 360 Δ f The measured phasor difference should be below the setting for the given time Different than a synchronizing relay

Questions?