Fire Alarm Engineering Best Practices. CFAA NCA Technical Seminar 2014



Similar documents
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group

CAN/ULC-S Installation of Fire Alarm Systems Amendment 1. Canadian Fire Alarm Association (CFAA) D. GOODYEAR FIRE CONSULTING

Fire. The Fire Installers Mate. A guide to fire alarm systems design

CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements

SECTION FIRE ALARM AND DETECTION SYSTEM

DTW Works Master Specification Version 2006

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager

HERNANDO COUNTY FIRE ALARM GUIDELINES

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

PARTICIPATION HOUSE 9 BUTTERNUT LANE, MARKHAM

PLAN REVIEW GUIDE FOR FIRE ALARM

Fire Alarm Trainee Log Book

Fire Alarm System Plans Review Checklist Property location Date of Review

City of Columbus Department of Building and Zoning Services

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Original Document 10/16/07 Revised 01/30/09 2 nd Revision rd Revision- 12/18/14

SECTION FIRE ALARM AND DETECTION SYSTEMS

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

The Benefits of ADDRESSABLE Fire Alarm Technology

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE

FIRE ALARM SYSTEM RECORD OF COMPLETION

CAN/ULC-S Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

Sprinkler and Fire Alarm Systems for the Building Official

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

Design Standards Fire Alarm Systems Division (1995 CMS); (2004 CMS) Amended Feb 2015

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) Fire Alarm Permit Application

University Design Standard. Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

Bold items are particular to the City of Euless

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

Fire Alarm Systems Permit Packet. City of Greer Fire Department

FIRE DETECTION AND ALARM

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.

FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST

EXHIBIT A SCOPE OF WORK

FIRE-FIGHTING DESIGN BRIEF REPORT

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

C. Conform to requirements of Americans with Disabilities Act (ADA).

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

City of Peterborough

2007 ICC FINAL ACTION AGENDA

I.S :2013 Fire Detection & Alarm Systems

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

FIRE CODE INTERPRETATION

Fire Alarm Systems Requirements by Occupancy Type

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

BUILDING DESIGN STANDARDS UNIVERSITY SERVICES ELECTRONIC SAFETY AND SECURITY - DIVISION 28 Fire Alarm Systems

Building Commissioning

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

City of Bettendorf Fire Alarm System Requirements

CHAPTER 9 FIRE PROTECTION SYSTEMS

I.S :2013 Fire Detection & Alarm Systems

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA

Fire Alarm Submittal Requirements and Acceptance Testing

Life Safety Code Enabling References

Overview of Fire Alarm Systems and Maintenance

Module 4, Lesson 12 Fire Alarm Systems

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

SECTION DETECTION AND ALARM

Fire Alarm Systems Certification

Fire Alarm system Installation Guide

Project No. 4 Analysis of Active Fire Alarm Systems in WTC 1 & 2. Robert J. Keough Rolf Jensen & Associates Raymond A. Grill, P.E.

New Ontario Building Code Highlights

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

BS5839 Part 1:2002 Overview

* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

CBD-233. Fire Alarm and Detection Systems

Electromagnetic Locks and Electrified Door Hardware. Paul Latreille, CET Branch Manager

The Mission Critical Fire Protection Experts

Module 5. Fire and Emergency Alarm System Part I- Basics

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

SPEECH INTELLIGIBILITY and Fire Alarm Voice Communication Systems

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado

Emergency Evacuation Plan: 232 King St.

Element D Services Plumbing

FIRE DETECTION AND ALARM SYSTEMS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals

Overview of Hotel Fire Safety Requirements

James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc.

Mobile Fire Rescue Department Bureau of Fire Prevention

ENGINEERING SPECIFICATIONS

Transcription:

Fire Alarm Engineering Best Practices CFAA NCA Technical Seminar 2014

2 Overview Code Compliance Equipment Selection and Layout Drawings, Specifications Commissioning and Acceptance Miscellaneous Goals To give attendees a wider view of issues affecting fire alarm engineering To share best practices To engage in conversation that allows us to share our experience Format Open format. Questions and comments are welcome during the presentation.

3 Code Compliance 2012 Ontario Building Code and/or 2010 National Building Code of Canada Standards Referenced CAN/ULC S524 Standard for the Installation of Fire Alarm Systems - Latest issue is 2014 CAN/ULC S537 Standard for the Verification of Fire Alarm Systems - Latest issue is 2013 Sections will be covered as we discuss specific components Use the latest version Notwithstanding which version is referenced by the Building Code Don t mix and match. Pick either the referenced version or the latest version in its entirety.

4 ULC S524 Standard for the Installation of Fire Alarm Systems The 2014 version has a number of new topics including: - Wireless devices - Expanded information on fault isolation - Suppression releasing equipment A large portion of the material intended to be presented here as best practice is in the new version of the standard. Details of the updated standard is the subject of the next seminar. Providing features required where large scale systems are installed should be considered even for smaller systems. - The benefits usually outweigh the costs.

5 Equipment Selection and Layout Topics Covered Display and Control Equipment - Control Panels - Annunciators - Power Supplies - Communications Initiating Devices Signalling Devices Control Devices

6 Equipment Selection and Layout Display and Control Equipment - Annunciators - Multi event display vs. zone indicators Let the complexity of the system decide More than 8 zones, use multi event display - Multiple annunciators Provide enough display equipment to allow for effective maintenance and event management Don t over do it. 5.2.11 Where more than one display and control centre is installed, they shall have the ability to request, grant and deny system control with provision for failsafe auto-transfer from one display and control centre to another. - Annunciator location Visible from the fire department entrance Specify display height for installation for the intended user» (suggest 1.6 m to centre of display)

7 Equipment Selection and Layout Display and Control Equipment - Annunciators - Zoning Fire alarm zone and fire alarm circuit not necessarily the same thing.» Zoning defined by OBC article 3.2.4.9.» Circuit may serve multiple zones Determine the system zoning, then determine circuit routing Isolator modules required to provide zoning requirements for addressable circuits serving more than one zone.

8 Equipment Selection and Layout Display and Control Equipment - Control Panels - Single panel Locate at main entrance to reduce cost for annunciator. - Multiple panels Locate in stacked electrical rooms for improved fire protection of communications trunk. If two stacked sets of service rooms are available, consider class A wiring with panels located alternately in each riser room. 5.8 LARGE SCALE NETWORK SYSTEMS 5.8.7 Each control unit and transponder shall be located in a suitable service room and/or central alarm and control facility, separated from the remainder of the building by a minimum 1 h fire separation.

9 Equipment Selection and Layout Display and Control Equipment Network Communications - DCLB, DCLA, DCLC Why choose anything but the most fault tolerant required for large scale systems despite the size of the system? - Redundant communication method Addressable loop from the DCC/CACF to each transponder with monitor and relay modules to provide near full operation even in degrade mode.

10 Equipment Selection and Layout Display and Control Equipment Power Supplies - Systems are being provided with larger power supplies to accommodate more visual devices, voice communication systems etc. - Remote power supplies are still the go-to solution for some equipment suppliers. Increase system complexity but also flexibility» Treat remote power supplies like transponders in terms of integrating them with the system (protection, supervision, testing etc.)» Make power and battery calculations part of the normal submittal and review requirements.» Make power supply and battery test data part of the acceptance criteria to ensure the remaining installed capacity is known when projects are completed. 5.5.6 A remote power supply serving a large scale network system shall be located in an electrical service room or a dedicated room separated from the remainder of the building by a 1 h fire separation.

11 Equipment Selection and Layout Initiating Equipment: - OBC and ULC S524 provide clear guidance to meet minimum requirements - Manufacturers do a good job of providing the latest technology available - Take a measured approach to detection device application Not taking advantage of current technology doesn t make sense as the benefits far outweigh the incremental cost Adding technology for the sake of it creates an overly complicated or sensitive system where it is not warranted or appreciated by the owner. - Consider multi-criteria detectors for everyday applications like electrical rooms, server rooms, public corridors etc... - Consider air aspirating detectors for difficult to access locations like atriums or elevator shafts - Consider lower sensitivity smoke detectors for dirty locations where early detection is beneficial to property or life safety - Consider beam array devices for large open spaces with high ceilings, obstructions and the like such as power plants, chiller rooms, etc. - Consider visual smoke detection for targeted detection in large open spaces to compliment other detection equipment.

12 Equipment Selection and Layout Initiating Equipment - Smoke detectors in high ceiling applications For ceilings up to 6 m in height, smoke detectors can be used with a reduced spacing of r 0.2H. 8.3.8.5 Spot type smoke detector spacing is not required to be reduced for ceiling height, but may be affected by beam construction. On ceilings above 3600 mm in room height, spot type smoke detector spacing shall be based on fire type, growth rate, engineering judgement and manufacturer s published installation instructions. - Smoke detectors in stair shafts Install at every 3 rd level in any stair shaft serving 6 or more stories At worse the cost is one extra detector 8.3.11.2 In exit stair shafts exceeding 18 m in height, measured from the lowest point to the highest point of the shaft, additional spot type smoke detectors shall be installed at every third floor.

13 Equipment Selection and Layout Initiating Equipment - Manual Stations Mounting heights used to be a problem to meet accessibility and ULC requirements but that has been resolved in the 2014 version of ULC 524. Install such that only one manual station is encountered along any egress pathway at the exit door. 8.1.1 Manual stations shall be installed 1050 mm to 1150 mm above the finished floor level measured from the centre of the manual station. Q. Is it a manual station, a pull station or a manual pull station?

14 Equipment Selection and Layout Signalling Equipment - Strobes and Horns/Bells/Speaker spacing is different - Select low output devices for small rooms Don t count on sound transmission through walls to meet requirements Low output devices to not produce sound levels above maximum permitted values (100 dba) - Software for design to meet voice communication intelligibility. Algebraic equations can be used as well. Develop a library of layout patterns with acceptable results. http://evac.afmg.eu/ T 0.16V Sα *Last year s presentation

15 Equipment Selection and Layout Control Equipment - Relays Use remote relays when possible» Reduces fire protection requirements for certain cables» Improves supervision of controlled equipment - Smoke Management Often done by BAS system but should be by FAS» Very few BAS systems are listed for smoke control functions Have the BAS relinquish control of equipment on fire alarm but allow the BAS control the return to normal operation after a fire event Where complicated control sequences are required involving system feedback, connect the FAS directly to the fan controller

16 Drawings and Specifications Separate fire alarm from other electrical drawings whenever possible - Combine reflected ceiling (lighting) and floor plan (power) into one Show interference elements from other systems - Diffusers, Bulkheads, Ceiling Heaters Coordinate notes with specification items - Eliminates duplication or worse contradictory information Drawing specifications or book specifications - Let the project complexity decide but don t mix and match Show zone boundaries and provide a zone schedule Provide a riser schematic for network communications Provide a sequence of operations chart for complicated signalling or automated smoke management. Don t ask for anything you don t want or need and check to ensure you get all of the items that you have asked for.

17 Commissioning and Acceptance Annunicators - Check communication between annunciator and control equipment (especially when the annunciator is not a network node) Integrated commissioning - Plan early, develop checklists with specific test scenarios and expected results. - Don t start until verification procedures are complete Verification reports and acceptance testing - Insist on and become familiar with proper verification reports - Don t rely on a certificate as proof of compliance - Conduct your own acceptance testing 3.2.4.6. Commissioning of Life Safety and Fire Protection Systems (1) Where life safety and fire protection systems are installed to comply with the provisions of this Code or the Fire Code made under the Fire Protection and Prevention Act, 1997, the commissioning of these integrated systems must be performed as a whole to ensure the proper operation and inter-relationship between the systems.

18 Commissioning and Acceptance Network communication testing - Do this first and pay it enough attention - Can usually be done as an interim step in acceptance

19 Miscellaneous Elevators - TSSA requirements of fire alarm systems are different than OBC/NBC requirements. - Seek clarification of requirements from elevator designer early on in project to avoid problems during acceptance of the elevator installation later on. Generators - Permitted to provide emergency power to fire alarm system with reduced requirement for batteries (2 hrs of supervision only) - Must be connected to FAS to report fault where used - Separate reporting requirements from CSA 282 can easily be covered by the FAS at the same time. Fire Pumps - Reporting requirements now include all NFPA 20 supervision items OBC 3.2.4.10.(4)

20 Miscellaneous Electromagnetic Locks - Ensure that enough attention is paid to the installation, modification or extension of a system - Ensure the existing system operates as required before modification - Don t forget the emergency lighting and signage requirements - Try to avoid electromagnetic locks unless control of the doorway in the direction of egress travel is required Monitoring - Compliance with both ULC 559 and ULC 561 is required for this aspect of the system installation Be a better designer - Develop and use design tools to help speed up design tasks and ensure proper spacing in all circumstances - Pay attention to industry updates and publications to keep your knowledge and skills up to date

21 William Kuffner, M.A.Sc, P.Eng, PMP Director Fire Protection Engineering william.kuffner@wspgroup.com (613-)729-2800 ext 19247