How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply



Similar documents
GTEC transfer switch open transition

Transfer switch BTPC open, closed or delayed transition

Diesel generator set C22D5T series

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

Transfer Equipment Controls

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

ATC-300 Automatic Transfer Switch Controller

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

MTS Power Products MIAMI FL ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

SECTION VARIABLE FREQUENCY DRIVES

Unified requirements for systems with voltages above 1 kv up to 15 kv

ASCO SERIES 185 Power Transfer Switches

PowerCommand Paralleling System Digital MasterControl

Conventional Fire Detection and Extinguishant Control System Specification

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SECTION DETECTION AND ALARM

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Continuous Power... Continuous Protection

Diesel Engine Driven Generators Page 1 of 6

Guidelines for ATS selection: How to choose the right transfer solution for your power application.

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Zenith Controls ISO R-1000C 5/99

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

Mobile Data Power Model: MDP-25

Thyristor-controlled power supplies and battery chargers

Automatic Transfer Switch Controller

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

, User s Manual

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Three-phase monitoring relay CM-PFE

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Eaton s E-Series protective relay family

RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu,

Cisco Redundant Power System 2300

ATS - Automatic Changeover

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Electronic Control Devices The European Product Catalogue 2007

Loc-1Tx/Loc-5Tx/Loc-10Tx Data Sheet V3.3

I.L T.K. Instructions for Cutler-Hammer MP1 Series Automatic Transfer Switches A

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Phase Modular Finally the benefits of Modular ups are for all

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x , 2CDG 110 1xx R0011

Bolted contact switches. Pringle switches

SENTRON Switching and Protection Devices Air Circuit Breakers

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Fundamentals of Power

BB800 Off-Grid Solar System

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

HM-W536 Install Guide

How To Test A Power Switch On A Power Supply

SURGE PROTECTIVE DEVICES

ABB central inverters PVI-55.0/ PVI-165.0/ PVI-275.0/ to 330 kw

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial

EGSTON Standard E2xFxWx 12W

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Gas Genset Controls. Genset Control Panel (GCP2) with PCS (PowerCommand Supervisor) Features. Description

FIREDEX Conventional Fire Panels

SECTION LOW VOLTAGE LIGHTING CONTROLS

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, W BASIC T5

Anti-blackout system for grid connected solar installations (Solsafe concept)

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

LOXONE 12 Channel Amplifier

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Tmax MCCBs. Molded case circuit breakers. Tmax

R.C.C.B. s two-pole LEXIC

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

Pow-R-Con Multi Function Control

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

MasterINTERFACE 39 Series - Relay interface modules

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

Automatic start of a generator

ADM1TE 5/30A DIN rail single phase two wire energy meter

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

Installation and Operation Back-UPS 1250, 1300, 1500

Automatic management of two different energy sources

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Automatic Transfer Switch-Controller ATS-C by Eaton. Automatic Transfer Switch- Controller ATS-C 96 and C 144

TOSHIBA G /100/160/225 kva

Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier

Transcription:

GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator set, or between two generators. The microprocessor control monitors utility and emergency standby generator power. When utility power fails or is unsatisfactory, the control starts the generator, then transfers the load from the utility to the generator. When stable utility power returns, the switch automatically transfers the load back to the utility. For genset-to-genset applications, the generator set that is connected to the utility side of the control is the lead genset. If the lead generator set goes down or is taken offline, the transfer switch starts the second generator set and transfers the load. The control can be programmed to alternate between the two generator set at a set interval up to 300 hours. The fully integrated controller is designed for practical functionality, with LED indicators and digital push-buttons for ease of operator use. 40-2000 amp switches are third-party certified as meeting IEC 60947-6-1 AC31A. All switches bear the CE mark. 40-1250 amp switches are CCC certified by the China Quality Certification Centre. This transfer switch is designed and manufactured in facilities certified to ISO9001. Features Microprocessor control: Easy-to-use, standard control. LED displays indicate transfer switch status. Pushbuttons allow operator to activate test, exercise timing and transfer mode. Programmed transition: Open transition timing can be adjusted to completely disconnect the load from both sources for a programmed time period. Recommended for inductive loads to prevent nuisance tripping. Advanced transfer switch mechanism: True transfer switch mechanism with break-before-make action. Manual operation: Standard removable handle can be used to manually operate the switch after the power source has been completely disconnected. Multi-voltage rating: The multiple selectable voltage setting is field adjustable, and allows GTEC to be applied to voltage ranging from 110V to 277V without using external transformers. Positive interlocking: Mechanical and electrical interlocking prevent source-to-source connection through the power or control wiring. Main contacts: Silver alloy contacts with multi-leaf arc chutes are rated for 100% load interruption. They require no routine contact maintenance and provide 100% continuous current ratings. Easy to service: Single-plug harness connection and compatible terminal markings simplify servicing. Access space is ample. Door-mounted controls are field-programmable; no tool is required. Complete product line: Cummins Power Generation offers a wide range of equipment, accessories and services to suit virtually any backup power application. Warranty and service: Products are backed by a comprehensive warranty and a worldwide network of distributors with factory-trained service technicians.

GTEC Open 2 Transfer switch mechanism A powerful, economical AC solenoid operates GTEC transfer switches. Independent break-before-make action is used for 2-pole, 3-pole and 4-pole switches. On 4-pole/switched neutral switches, this action prevents the objectionable ground currents and nuisance ground fault tripping that can result from overlapping designs. A mechanical interlock prevents simultaneous closing of normal and emergency contacts. Electrical interlocks prevent simultaneous closing signals to normal and emergency contacts and interconnection of normal and emergency sources through the control wiring. High-pressure silver alloy contacts resist burning and pitting. Separate arcing surfaces further protect the main contacts. Contacts are mechanically held in both normal and emergency positions for reliable, quiet operation. Contact wear is reduced by multiple leaf arc chutes that cool and quench the arcs. Barriers separate the phases to prevent interphase flashover. Protective covers for lugs are available. Specifications Voltage rating Arc interruption Neutral bar Auxiliary contacts Up to 480VAC, 50 or 60 Hz Multiple leaf arc chutes provide dependable arc interruption. A full current-rated neutral bar is Standard on enclosed 3-pole transfer switches. Two isolated contacts (one for each source) indicating switch position are provided for customer use. Contacts are normally open, and close to indicate connection to the source. Wired to terminal block for easy access. Rated at 5 amps continuous at 100VAC or 2.5 amps continuous at 200VAC. Operating temperature -30 C (-22 F) to 60 C (140 F) Storage temperature -40 C (-40 F) to 60 C (140 F) Humidity Altitude Total transfer time (source-to-source) Manual operating handle Up to 95% at 20 C Up to 2,000 m (6,561 ft) without derating Will not exceed 100 msec with normal voltage applied to the actuator and without programmed transition enabled. Transfer switches are equipped with a removable operating handle which allows operation during servicing to facilitate troubleshooting with sources of power disconnected.

Microprocessor control Simple, easy-to-use control provides transfer switch information and operator controls LED lamps for source availability and source connected indication, exercise mode, and test mode. LED status lamps also provided for control set-up and configuration Pushbutton controls for initiating test, overriding time delays and setting exercise time Field-configurable for open or programmed transition Integral exerciser clock Control is prototype-tested to withstand voltage surges per EN 60947-6-1 Gold-flashed generator start contacts GTEC Open 3 Control functions Under-voltage sensing: All phases on the normal source, and single phase on generator source. Normal source pickup: adjustable 80-95% Dropout: adjustable 70-90% of nominal voltage Generator source pickup: 90% Dropout: 75% of nominal voltage Over-voltage sensing: All phases on the normal source. Source pickup: 120% Dropout: 125% Under-frequency sensing: Default setting is OFF. Generator source pickup: 90% of nominal frequency Dropout: 85% of nominal frequency Normal source pickup: 80% Dropout: 70% Over-frequency sensing: Default setting is OFF Normal source pickup: 130% Dropout: 140%. Genset-to-genset sensing: Same functions as above, for lead and secondary generators. Exercise mode: The control exerciser clock can be set to operate on a 7, 14, 21 or 28-day cycle with a fixed exercise period duration of 20 minutes. A convenient 12-hour offset feature offsets the exercise time by 12 hours, without having to reprogram the timer. The control can be programmed to exercise the generator with or without load. Test mode: When manually or remotely activated from the control panel, the control will start the generator and run until stopped. Can be configured to test with or without load. Transition modes Open transition/programmed: Controls the time required for the device to switch from source to source, so load-generated voltages decay to a safe level before connecting to an energized source. Recommended method of dealing with significantly inductive loads to prevent nuisance tripping. Adjustable 0-10 seconds, default 0 seconds. Open transition/in-phase: Initiates open transition transfer when in-phase monitor senses both sources are in phase. Operates in a break-before-make sequence. Includes ability to enable programmed transition as a backup. If sources are not in phase within 120 seconds, the system will transfer using programmed transition. Time-delay functions Engine start: Prevents nuisance genset starts due to momentary power variation or loss. Adjustable 0-10 seconds, default 3 seconds. Transfer normal to emergency: Allows genset to stabilize before application of load. Prevents power interruption if normal source variation or loss is momentary. Allows staggered transfer of loads in multiple transfer switch systems. For genset-to-genset applications, delays transfer of load from lead to secondary generator. Adjustable 0-300 seconds, default 5 seconds. Re-transfer emergency to normal: Allows the utility to stabilize before re-transfer of load. Prevents needless power interruption if return of normal source is momentary. Allows staggered transfer of loads in multiple transfer switch systems. For genset-to-genset applications, delays re-transfer of load from secondary back to lead generator. Adjustable 0-30 minutes, default 10 minutes. Engine stop: Maintains availability of the genset for immediate reconnection if the normal source fails shortly after transfer. Allows gradual genset cool down by running unloaded. Adjustable 0-30 minutes, default 10 minutes. Elevator signal relay: Requires optional elevator signal relay (M032). Delays transfer for specified interval to prevent a power interruption during elevator operation. Options Elevator signal relay (M032): Provides relay output contacts for sending a load-disconnect warning signal to the elevator control. Transfer/re-transfer delay time is selectable for 0, 1, 2, 3, 5, 30, 120 or 300 seconds. Programmable exerciser clock (J030): Provides a fully-programmable 7-day clock to provide greater flexibility in scheduling exercise periods than standard integral exerciser. Peaking function feature allows for generator operation during periods of high utility rates. Manual restore (S006): Provides a key switch on the front door to allow the operator to control when the switch transfers to the available normal source.

GTEC Open 4 Electrical performance The transfer switches listed below must be protected by either circuit breakers or fuses. The following WCR ratings are available when protecting the transfer switch with a circuit breaker or fuse. Short circuit ratings are stated in symmetrical RMS ampere. Fuse protection Transfer switch ampere Overload current (make-break test) Endurance cycles at current (operational performance capability) WCR at 480V max with current limiting fuse 40, 63 95 amps 6000 at 63 amps 26,000 amps 100, 125 188 amps 6000 at 125 amps 26,000 amps 160, 200, 225, 250 375 amps 6000 at 125 amps 38,000 amps 350, 400, 500 750 amps 630, 800 1200 amps 1000, 1250 1875 amps 1600, 2000 3000 amps 1000 at 0 amps 2000 at 500 amps 1000 at 0 amps 2000 at 800 amps 1500 at 0 amps 1500 at 1250 amps 1500 at 0 amps 500 at 2000 amps 50,000 amps 55,000 amps 65,000 amps 120,000 amps Max fuse, size and type RT16NT-00 63 amp RT16NT-00 125 amp RT16NT-2 250 amp RT16NT-3 500 amp RT16NT-4 800 amp RT16NT-4 1250 amp KRP-C 3000 amp Class L Fuse type Transfer switch ampere 40, 63 63A 100, 125 125A 160, 200, 225, 250 250A 350, 400, 500 500A 630, 800 800A 1000, 1250 1250A 1600, 2000 2000A Max breaker rating Specified Circuit breaker protection manufacturer, model and type Schneider: NSX160FTM, EZD100, NSD100F, NSD100K Siemens: 3VU, 3RV1, 3VT1 ABB: Isomax S1, S2X80, Sim100 Schneider: NSX160FTM, NSD160K Siemens: 3VL, 3VT1 ABB: Isomax S2, Isomax S3, S3X, Sim250 Schneider: NSX250NTM, NSD250K Siemens: 3VL, 3VT2 ABB: Isomax S3, S4X, Sim250 Schneider: NSX630NTM, NSD630K Siemens: 3VL,3VT3 ABB: Isomax S4, S6X, Sim500 Schneider: MT08, MT10, NW08 Siemens: 3VL, 3WT, 3VT4 ABB: Isomax S6, E1B, E1N, E1S Schneider: MT12, NW16 Siemens: 3VL, 3WT, 3VT5 ABB: Isomax S7, E2B, E2L Schneider: MT20, MT25, NW20, NW25 Siemens: 3WT ABB: E1N, E2N, E2S, E3S

Enclosures GTEC Open 5 The transfer switch and control are mounted in a key-operated locked enclosure. Enclosures meet IEC 60947-6-1 standard. 40-500 amp switches are front-connected. 630-2000 amps are rear-connected. Standard enclosure is grey. Green is available as an option (P152). Cable tie bars are available to relieve stress on lugs for switches smaller than 500 amps. Dimensions: IP32 Amp rating Height Width Door closed Door open Weight Outline drawing in mm in mm in mm in mm lb kg 40, 63 31.4 800 23.6 600 8.8 226 31.4 800 101.4 46 0300-6004 100, 125 31.4 800 23.6 600 8.8 226 31.4 800 105.8 48 0300-6004 160, 200, 225, 250 39.3 1000 31.4 800 8.8 226 39.3 1000 125.6 57 0300-6005 350, 400, 500 39.3 1000 31.4 800 8.8 226 39.3 1000 143.3 65 0300-6005 630, 800 53.9 1370 29.2 742 24.8 631 53.0 1348 385.8 175 0300-6006 1000, 1250 53.9 1370 29.2 742 24.8 631 53.0 1348 405.6 184 0300-6006 1600, 2000 78.7 2000 39.4 1000 44.3 1126 83.7 2126 888.9 400 A0281839 Dimensions: IP54 Amp rating Height Width Door closed Door open Weight Outline drawing in mm in mm in mm in mm lb kg 40, 63 34.0 864 23.5 598 11.6 296 31.0 788 110 50 0300-4559 100, 125 34.0 864 23.5 598 11.6 296 31.0 788 110 52 0300-4559 160, 200, 225, 250 41.9 1064 31.6 804 11.6 296 39.0 991.8 143.3 65 0300-4560 350, 400, 500 41.9 1064 31.6 804 11.6 296 39.0 991.8 160.9 73 0300-4560 630, 800 53.9 1370 29.5 750 26.6 676 51.9 1319 188 0300-4561 1000, 1250 53.9 1370 29.5 750 26.6 676 51.9 1319 414.5 188 0300-4561 1600, 2000 78.9 2004 39.2 996 45.3 1150 83.7 2126 892.9 405 A026M050

GTEC Open 6 Submittal detail: options Current ratings 40 63 100 125 160 200 225 250 350 400 500 630 800 1000 1250 1600 2000 Voltage ratings R060* 110 to 139 R061* 220 to 240 R062* 255 to 277 R063 110 to 277 Pole configuration A027 Poles - 2 (solid neutral) A028 Poles - 3 (solid neutral) A029 Poles - 4 (switched neutral) Frequency A044 60 Hertz A045 50 Hertz A086-7 50/60 Hertz Application A035 Utility-to-genset A037 Genset-to-genset * Only available with L-L controller option. System Options A041 Single phase, 2-wire or 3-wire A042 Three phase, 3-wire or 4-wire Enclosure B004 Open construction: no enclosure - includes automatic transfer switch and controls (1600 2000 amp open construction not available) B901 IP32 general purpose indoor B014 IP54 general purpose outdoor P152 Optional paint colour: Onan green M048 Protective shield Control voltage M033 12V, Genset starting voltage M034 24V, Genset starting voltage Control options J030 Add-on programmable exercisor clock M032 Relay signal module S006 Manual restore switch Battery chargers K001 2 amps, 12/24 volts Auxiliary relays Relays are factory installed. All relays provide two sets of form C (DPDT) contacts rated 5 amps at 250VAC. Relay terminals accept one 0.75 mm to two 4 mm wires per terminal. L101 24 VDC coil: installed, not wired (for customer use). L102 24 VDC coil: emergency position - relay energized when GTEC in Source 2 (emergency) position. L103 24 VDC coil: normal position - relay energized when GTEC in Source 1 (normal) position L201 12 VDC coil: installed, not wired (for customer use) L202 12 VDC coil: emergency position - relay energized when GTEC in Source 2 (emergency) position L203 12 VDC coil: normal position - relay energized when GTEC in Source 1 (normal) position Warranty Warranty: 12 months from commissioning to a maximum 18 months after date of sale. Accessories AC-176 Specification sheet