OPTIMIZATION OF DATA CENTER CHILLED WATER COOLING SYSTEM ACCORDING TO ANNUAL POWER CONSUMPTION CRITERION



Similar documents
News in Data Center Cooling

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Elements of Energy Efficiency in Data Centre Cooling Architecture

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Improving Data Center Energy Efficiency Through Environmental Optimization

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

How to Build a Data Centre Cooling Budget. Ian Cathcart

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Analysis of data centre cooling energy efficiency

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Direct Fresh Air Free Cooling of Data Centres

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

STULZ Water-Side Economizer Solutions

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

AIRAH Presentation April 30 th 2014

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center Environments

Model-Based Approach for Optimizing a Data Center Centralized Cooling System

Legacy Data Centres Upgrading the cooling capabilities What are the options?

State of the Art Energy Efficient Data Centre Air Conditioning

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

Heat Recovery In Retail Refrigeration

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

The Different Types of Air Conditioning Equipment for IT Environments

How To Improve Energy Efficiency Through Raising Inlet Temperatures

Building HVAC Load Profiling Using EnergyPlus

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

- White Paper - Data Centre Cooling. Best Practice

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Impacts of Perforated Tile Open Areas on Airflow Uniformity and Air Management Performance in a Modular Data Center

Data Center Temperature Rise During a Cooling System Outage

Rate of Heating Analysis of Data Centers during Power Shutdown

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE ? SLIDE 1

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Data Center Equipment Power Trends

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

How To Design A Building In New Delhi

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

DataCenter 2020: first results for energy-optimization at existing data centers

Data Center Temperature Rise During a Cooling System Outage

Chapter 3.4: HVAC & Refrigeration System

Guide to Minimizing Compressor-based Cooling in Data Centers

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

Energy Efficient Cooling Solutions for Data Centers

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings

Energy Impact of Increased Server Inlet Temperature

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

CAE 331/513 Building Science Fall 2013

BICSInews. plus. july/august Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Centre Cooling Air Performance Metrics

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Energy savings in commercial refrigeration. Low pressure control

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Center Thermal Management Can Live Together

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES

Creating Efficient HVAC Systems

ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Code of Practice for Building Energy Audit

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

Heating, ventilation and air conditioning (HVAC) equipment. A guide to equipment eligible for Enhanced Capital Allowances

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

HVAC Efficiency Definitions

Technical Systems. Helen Bedford

Investigation into the energy consumption of a data center with a thermosyphon heat exchanger

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.

Transcription:

OPTIMIZATION OF DATA CENTER CHILLED WATER COOLING SYSTEM ACCORDING TO ANNUAL POWER CONSUMPTION CRITERION Piotr Kowalski 1, Mieczysław Porowski 2 1 Poznan University of Technology Piotrowo 5 60-695 Poznan, Poland piotr.kowalski@emerson.com 2 Poznan University of Technology Piotrowo 5 60-695 Poznan, Poland mieczyslaw.porowski@put.poznan.pl ABSTRACT The paper presents optimization model of the chilled water based data center cooling system. The optimization procedure includes system technological and mathematical model, limiting conditions and optimization criterion, which in this case is annual power consumption minimum. The cooling system model is defined by constant parameters and decision variables and consists of aircooled chiller, independent external freecooling heat exchanger (drycooler), computer room air handling unit (CRAH) and constant flow chilled water system with circulation pump. Influence of the server racks architecture (open or closed rack aisle), server inlet temperature and chilled water regime on the annual power consumption of the cooling system has been shown. Case study calculation based on the described model has been presented, including optimum variant designation and power usage effectiveness ratio of mechanical system calculation. KEYWORDS data center, efficiency, optimization, precision cooling, chilled water NOMENCLATURE c p specific heat, [kj/kgk] CRAH computer room air handler E CR CRAH unit fan power consumption, [kwh] E CWP chilled water pump power consumption, [kwh] E DX compressor power consumption, [kwh] E FC freecooling coil fan power consumption, [kwh] E IT server power consumption, [kwh] E K condenser fan power consumption, [kwh] E TOT cooling system power consumption, [kwh] h CRS, h CRR CRAH unit supply specific enthalpy, [kj/kg] h KA, h Ke condensing coil supply/return specific enthalpy, [kj/kg] h FA, h Fe freecooling coil supply/return specific enthalpy, [kj/kg] l hydraulic system length, [m] p absolute air pressure, [Pa] P CR CRAH unit fan power input, [kw] P CWP chilled water pump power input, [kw] P DX compressor power input, [kw] P FC freecooling coil fan power input, [kw] P IT IT systems power input, [kw] P K condenser fan power input, [kw] P TOT mechanical systems total power input, [kw] PUE(m) power usage effectiveness of mechanical systems, [-] Q CW chilled water cooling capacity, [kw] Q E evaporator cooling capacity, [kw] Q FC freecooling coil cooling capacity, [kw] Q IT server room cooling load, [kw] Q K condenser capacity, [kw] R pressure loss coefficient, [Pa/m] R p gas constant of air, 287,05 [J/kgK] t A ambient temperature, [ C] t Amax max amb. temperature for a given profile, [ C] t Amin min amb. temperature for a given profile, [ C] t CHR condensing coil return air temperature, [ C] 1

t CHS condensing coil supply air temperature, [ C] t CRR CRAH unit return air temperature, [ C] t CRS CRAH unit supply air temperature, [ C] t CWE chilled water temperature before evaporator, [ C] t CWR chilled water return temperature, [ C] t CWS chilled water supply temperature, [ C] t E evaporating temperature, [ C] t FA, t Fe freecooling coil supply/ return air temperature, [ C] t FC,0% freecooling start ambient temperature, [ C] t FC,100% full freecooling ambient temperature, [ C] t FCR freecooling coil return air temperature, [ C] t FCS freecooling coil supply air temperature, [ C] t KA, t Ke condensing coil supply/return air temperature, [ C] T E evaporating temperature, [K] T K condensing temperature, [K] V CR CRAH unit airflow volume rate, [m 3 /s] V CW chilled water flow volume rate, [m 3 /s] V FC freecooling coil airflow volume rate, [m 3 /s] V K condensing coil airflow volume rate, [m 3 /s] Δp CR CRAH unit pressure drop, [kpa] Δp CWP chilled water pump available pressure, [kpa] Δp E evaporator pressure drop, [kpa] Δp FC freecooling coil pressure drop, [kpa] Δp p hydraulic system pressure drop, [kpa] ΔQ FC freecooling coil capacity difference, [kw/ C] Δt CR CRAH unit air temperature difference, [ C] Δt E evaporating and chilled water supply temp. difference, [ C] Δt EXV min. evaporating and condensing temp. difference, [ C] Δt FC,100% 100% freecooling capacity temp. difference, [ C] Δt IT server air temperature difference, [ C] Δt K condensing and ambient temp. difference, [ C] Δτ duration of a given ambient temperature, [h] η CR CRAH unit fan efficiency, [%] η CWP chilled water pump efficiency, [%] η DX compressor efficiency, [%] η FC freecooling coil fan efficiency, [%] η K condenser fan efficiency, [%] ρ CRS mass density, CRAH unit supply air temperature [kg/m 3 ] 1 INTRODUCTION Data Center cooling is one of the most energy consuming mechanical systems available. There are several factors that contribute to high power demand including continuous operation independently of ambient conditions (cooling load depends mostly on IT equipment and external heat gains have minor impact on it), high expenditures on cooling and movement of load carriers (especially air and water) and constant growth of heat gains and density of servers. Power consumption of mechanical systems has large impact on total cost of ownership and carbon footprint of data center class buildings, so many different researches to minimize this impact have been carried and the problem is still valid. Application of optimization methods to design chilled water based HVAC systems have been presented by Lu (Lu, Cai, Chai, 2005; Lu, Cai, Xie, 2005), while Porowski (Porowski, 2011) presented composite strategy to select optimum ventilation and air-conditioning system based on energy consumption criterion. Research on data center cooling system optimization have been carried by i.e. Shah et al., (Breen, Walsh, Shah, 2010; Breen, Walsh, Punch, 2010; Breen, Walsh, Punch, Shah, Kumari, 2010) Iyengar et al. (Iyengar, 2009) and Demetriou et al. (Demetriou, 2011), who presented holistic, analytic models taking into account the heat flow from servers to ambient air with a watercooled chiller and cooling tower as a cooling source. The subject of presented paper is optimization model of the data center chilled water based precision cooling system with external, aircooled chiller and additional freecooling heat exchanger (water economizer) as a mechanical cooling source. 2

2 PROBLEM FORMULATION Data center cooling system optimization problem includes formulation of the system model (including constant parameters and decision variables), definition of the limiting conditions and optimization criterion. Simplified technological scheme of the analyzed system is shown on Fig. 1. Figure 1. Technological scheme of the chilled water based data center cooling system The data center cooling system model is described by the constant parameters and decision variables. Constant parameters, by definition, remain constant throughout optimization procedure (in general they can be a function of time). Decision variables, by definition, are changing throughout optimization procedure. Cooling system model described in this paper has following constant parameters: system structure, thermo-dynamical parameters of load carriers (air, water, refrigerant), ambient temperature distribution profile, server room heat load, mechanical efficiency of various components (pump, fans, compressor), difference between chilled water supply and evaporating temperature, minimum difference between refrigerant evaporating and condensing temperature, difference between ambient and refrigerant condensing temperature, length of the chilled water piping. There are two types of decision variables used in the described model: incommensurable variables - server rack architecture. There are two variables of this kind included in the model: closed aisle architecture (separation of the hot and cold aisle, cooling system control according to supply air temperature, mass flow of the CRAH air as a function of server temperature rise) or open aisle architecture (no cold/hot aisle separation, cooling system control according to the return air temperature and CRAH unit airflow 30% higher compared to closed aisle architecture), measurable variables: server air temperature raise, supply and return chilled water temperatures (thus chilled water mass flow), freecooling coil operation starting ambient temperature, temperature difference to reach full required capacity of the freecooling coil. There are following limiting conditions used in the optimization procedure: CRAH unit return air temperature (for open aisle option) or server inlet air temperature, thus supply air 3

temperature range according to ASHRAE 2011 A1 class recommended envelope for closed aisle architecture. The optimization criterion used in the described model was minimum annual electrical power consumption of the cooling system according to the below account: E TOT = min (E TOT1, E TOTj, E TOTj max ) (1) 3 MODEL ASSUMPTIONS AND SOLVING PROCEDURE For each of the components of the cooling system model (CRAH, freecooling coil, water chiller) balance equations have been formulated including power input of the components, i.e. cooling capacity delivered by the chilled water system includes the additional heat dissipated by the CRAH unit fans according to the equation: Q CW =Q IT +P CR (1-η CR ) (2) CRAH unit fan power input depends on the volume flow of the server room air, which further depends on the mass flow and supply air temperature. It has been calculated as a function of the reference values of the fan power input and volume airflow according to the following equations: P CR =P CR ref ( V CR ) 3 (3) V CR ref Q m IT CR= C P (t CRR -t CRS ) (4) V CR= m CR ρ CRS (5) p ρ CRS = (6) R p T CRS Cooling capacity of the external freecooling coil has been calculated in a simplified way, including decision variables Δt100%FC and ta,0%fc according to the equations: t FC,100% = t CWS+t CWR -Δt 2 FC,100% (7) 0, t A t A,0%FC Q FC = Q CW -(t A -t FC,100% )ΔQ CF, t FC,0% >t A >t FC,100% (8) { Q FC =Q CW, t A t FC,100% Q CW ΔQ FC = (9) t FC,0% -t FC, 100% 4

Power input of the freecooling coil fan has been calculated using equations (3,4,5,6) described for the CRAH unit, with the assumption of constant ambient temperature raise across the coil. Cooling load of the evaporator has been calculated according to the equation: Q E =Q CW -Q FC (10) Heatload of the aircooled condenser includes power input of the compressor and has been calculated according to the equation: Q K =Q E +P DX (11) Power input of the compressor has been calculated according to following equations: Q E P DX = (12) COP DX COP DX = ( T E T K -T E ) η DX (13) t E =t CWS -Δt E (14) t A +Δt K,(t K -t E ) Δt EXV t K = { (15) t E +Δt EXV, (t K -t E )<Δt EXV where η DX, Δt EXV, Δt K are decision variables based upon chiller manufacturer data. Power input of the aircooled condenser fan has been calculated using equations (3, 4, 5, 6) with the assumption of constant temperature rise of the ambient air. Power consumption of the circulating pump has been calculated using following equations: P CWP = V CWΔp CWP η CWP (16) Δp CWP =Δp P +Δp CR +Δp FC +Δp E (17) Δp P =1,3Rl (18) with the simplifying assumption, that local pressure drop is 30% of the linear. Pressure drop of the CRAH unit, freecooling coil and evaporator has been calculated using below equations: Δp CR =Δp CR ref ( V CW ) 2 (19) V CW ref Δp FC =Δp FC ref ( V CW ) 2 (20) V CW ref Δp E =Δp E ref ( V CW ) 2 (21) V CW ref where values of reference pressure drops have been taken from manufacturers datasheets. 5

To find optimum mix of the design parameters according to the given criterion a complete review optimization method was used. Starting point of the method was creation of the mathematical models of the particular components of the cooling system, which influence the total power consumption (CRAH, chiller, freecooling coil, hydraulic system and pump). For each of the components system of the equations for the load carriers and energy balance were created. After applying the limiting conditions, a set of permissible variants was formulated, including the mix of design parameters (aisle architecture, chilled water supply and return temperatures, supply and return CRAH unit air temperatures). For each of the permissible variants, according to the ambient air temperature profile in the <ta,min, ta,max> range with a step of 1 C and assigned duration (time) of each temperature, power consumption of the particular components has been calculated according to the following accounts: E TOT (t A )=E CR (t A )+E FC (t A )+ +E DX (t A )+E K (t A )+E CWP (t A ) (22) E CR (t A )=P CR Δτ (23) E FC (t A )=P FC (t A )Δτ (24) E DX (t A )=P DX (t A )Δτ (25) E K (t A )=P K (t A )Δτ (26) E CWP (t A )=P CWP Δτ (27) t E TOT = A max t A min E TOT (t A ) (28) For each of the permissible variants power usage effectiveness ratio of the mechanical systems has been calculated according to following equations: PUE(m)= E TOT+E IT E IT (29) E IT =8760P IT (30) Figure 2. General algorithm of the optimization procedure Optimum variant according to minimum annual power consumption criterion (1) has been determined. General algorithm of the optimization procedure is shown on figure 2. 6

4 CASE STUDY INPUT DATA AND RESULTS The permissible variants (mix of decision variables and limiting conditions) calculated for the case study purposes include: open aisle room architecture: chilled water regime range t CWS /t CWR = (5-10/13-15) C, CRAH unit return temperature t CRR =24 C, CRAH unit temperature difference ΔtCR= 11,5 C, closed aisle room architecture: chilled water regime range t CWS /t CWR = (12-21/20-26) C, temperature of the cold aisle (server inler) according to ASHRAE 2011 A1 Data Center class recommended range (A. T. C. TC 9.9., 2011), CRAH unit temperature difference ΔtCR= 15 C. There have been 24 permissible variants calculated. List of decision variables of the selected five calculations for the case study example is shown in Table 1. Table 1. Case study calculation selected input data Variant No. Architecture Q IT t CWS t CWR Δt CR Δt FC0% Δt FC100% [ - ] [ - ] [kw] [ C] [ C] [ C] [ C] [ C] 1 open 200 8 13 11,5 1 12 2 open 200 8 15 11,5 1 12 3 closed 200 15 22 15 1 12 4 closed 200 16 24 15 1 12 5 closed 200 18 26 15 1 12 The case study calculation results of the selected permissible variants are shown in Table 2., which includes annual power consumption of the respective components of the modelled system, total annual power consumption of the system and PUE(m) ratio. Energy consumption of the optimum variant (No. 5) based on the minimum annual energy consumption criterion (variant No. 5) is 60% lower compared to most energy consuming system (variant No. 5). Figure 3. shows energy consumption split of the optimum calculated system, while Figure 4. shows energy consumption split of the maximum calculated variant (No. 1). Table 2. Case study calculation selected results t CWS /t CWR E DX E K E FC E CWP E CR E TOT PUE(m) [ C] [kwh/year] [kwh/year] [kwh/year] [kwh/year] [kwh/year] [kwh/year] [-] 8/13 176020 26541 43332 50189 83134 379215 1,22 8/15 165007 23416 47376 22547 83861 342208 1,20 15/22 77413 10382 46793 22547 40514 197649 1,11 16/24 63051 7687 44699 16887 41108 173432 1,10 18/26 46337 5265 40973 16887 41958 151420 1,09 7

Power input [kw] Annual consumption [kwh/year] 41958, 28% 16887, 11% 40973, 27% 46337, 31% 5265, 3% Edx E DX [kwh/year; %] %] Ek E K [kwh/year; %] %] Efc E [kwh/year; %] FC [kwh/year; %] Ecwp [kwh/year; %] E CWP [kwh/year; %] Ecr [kwh/year; %] E CR [kwh/year; %] Figure 3. Cooling system energy consumption split (optimum variant No. 5) 83134, 22% 50189, 13% 176020, 46% Edx E DX [kwh/year; %] %] Ek E K [kwh/year; %] %] Efc E [kwh/year; %] FC [kwh/year; %] Ecwp E [kwh/year; %] CWP [kwh/year; %] Ecr [kwh/year; %] E CR [kwh/year; %] 43332, 12% 26541, 7% Figure 4. Cooling system energy consumption split (maximum variant No. 1) Figure 5. shows power input of the respective components of the cooling system, total power input and annual energy consumption of the optimum calculated system versus ambient temperature range. 70 60 50 40 30 20 10 9000 8000 7000 6000 5000 4000 3000 2000 1000 Pdx P DX Pk P K Pfc P FC Pcwp P CWP Pcr P CR P tot P TOT E tot E TOT 0 36 33 30 27 24 21 18 15 12 9 6 3 0-3 -6-9 -12-15-18-21-24 Ambient temperature [ C] 0 Figure 5. System components power input and total energy consumption versus ambient temperature optimum variant No. 5 8

5 CONCLUSIONS The presented paper shows universal model of the optimization procedure and partial results of the calculations of an example case study. Complete review of the permissible variants is used as an optimization method. Based on a case study calculations is has been shown, that presented algorithm can provide an energy-optimized mix of design parameters of the data center cooling system, including server rack architecture (open/closed), chilled water temperature regime, chilled water mass flow and server inlet air temperature. Example calculation results presented in this paper are showing big potential of possible energy conservation depending on design parameters mix. For the case study calculation the difference between maximum and minimum calculated annual power consumption of the cooling system is 60%. Authors are conducting further research on the discussed topic, purpose of the research is further refinement of the cooling system particular components and introduction of more complex optimization procedures. 6 REFERENCES A. T. C. TC 9.9. (2011). Thermal Guidelines for Data Processing Environments Expanded Data Center Classes and Usage Guidance. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Breen, T. J.; Walsh, E. J.; Punch, J.; Shah, A. J.; Bash, C. E. (2010). From chip to cooling tower data center modeling: Part II Influence of chip temperature control philosophy. IEEE. Breen, T. J.; Walsh, E. J.; Punch, J.; Shah, A. J.; Kumari, N.; Bash, C. E.; Lyon, G. (2010). From Chip to Cooling Tower Data Center Modeling: Validation of a Multi-Scale Energy Management Model. 13th IEEE ITHERM Conference. Breen, T. J.; Walsh, E. J. P. J.; Shah, A. J.; Bash. C. E. (2010). From chip to cooling tower data center modeling: Part I Influence of server inlet temperature and temperature rise across cabinet. IEEE. Demetriou, D. W.; Khalifa, H. E.; Iyengar, M.; Schmidt, R. R. (2011). Development and experimental validation of a thermo-hydraulic model for data centers. HVAC&R Research, vol. 17:4, pp. 540-555. Iyengar, M.; Schmidt, R. R. (2009). Analytical Modeling for Thermodynamic Characterization of Data Center Cooling Systems. Journal of Electronic Packaging, vol. 131, no. June, pp. 021009-1 - 021009-9. Lu, L.; Cai, W.; Chai, Y. S.; Xie, L. (2005). Global optimization for overall HVAC systems - Part I problem formulation and analysis. Energy Conversion & Management, vol. 46, pp. 999-1014. Lu, L.; Cai, W.; Xie, L.; Li, S.; Soh. C. (2005). HVAC system optimization - in-building section. Energy and Buildings, vol. 37, pp. 11-22. Porowski, M. (2011). Strategia wyboru energooptymalnego systemu wentylacyjnego lub klimatyzacyjnego. Wydawnictwo Politechniki Poznańskiej, Poznań. 9