Current Transformers Ratio / Polarity / Types



Similar documents
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Type SA-1 Generator Differential Relay

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21,

VOLTAGE REGULATOR AND PARALLEL OPERATION

Power Plant Electrical Distribution Systems

CURRENT TRANSFORMERS INSTALLATION GUIDE

Current Transformers

Hyperlinks are Inactive

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

The following components are common to most cubicles; this example is an ABB HK cubicle.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Tamura Closed Loop Hall Effect Current Sensors

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

How To Choose A Transformer

SECTION VARIABLE FREQUENCY DRIVES

Troubleshooting accelerometer installations

Table of Contents. TransformerIQ FAQs 1

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

Transformer circuit calculations

Pilot-wire differential relay for lines with two or more terminals

7CURRENT TRANSFORMERS

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

CT Application Guide for the 489 Generator Management Relay

Medium Voltage Electrical Distribution

Transformer Calculations

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

Inverter / Charger Installation General Operations and AC and DC Connections

Primary and Secondary Electrical Distribution Systems

Line Reactors and AC Drives

Unit/Standard Number. High School Graduation Years 2010, 2011 and 2012

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

What is a multimeter?

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA

Typical Data Requirements Data Required for Power System Evaluation

Using Current Transformers with the 78M661x

T Substation Maintenance and Commissioning Test Equipment

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Current & Instrument Transformers

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Short Circuit Current Calculations

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

THE INPUT/OUTPUT SYSTEM. Key Points

Multimeter measurements on variable frequency drives using the new Fluke 289 DMM

Three-phase AC circuits

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

ECEN 1400, Introduction to Analog and Digital Electronics

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

EET272 Worksheet Week 9

Current and voltage measuring relays

SYNCHRONOUS MACHINES

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

LOW-VOLTAGE CURRENT TRANSFORMERS

The Basics of Digital Multimeters

AMZ-FX Guitar effects. (2007) Mosfet Body Diodes. Accessed 22/12/09.

Automatic Voltage Regulator User s Manual

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

Balun Parameter Definitions & Measurement May 2004

NATIONAL CERTIFICATE (VOCATIONAL)

MODEL 2202IQ (1991-MSRP $549.00)

Motor Fundamentals. DC Motor

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

Reverse-feed applications for circuit breakers

City of Riverside Building & Safety Division Phone: (951)

Selection Guide to Clamp-On Current Probes

Safety technique. Emergency stop module BO 5988 safemaster

Power Supplies. 1.0 Power Supply Basics. Module

Physics 221 Experiment 5: Magnetic Fields

Advantages of Fixed Circuit Breaker Switchgear

Cable/Conduit Conversion

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Semiconductor Diode. It has already been discussed in the previous chapter that a pn junction conducts current easily. Principles of Electronics

FIT TIER 2 Application

Kit Watt Audio Amplifier

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Fitting/Installation Guide - UNIVERSAL

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.

Michelin North America

FREQUENCY CONTROLLED AC MOTOR DRIVE

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

ACCURACY OF POTENTIALTRANSFORMERS

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

Secondary Unit Substations

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Unified requirements for systems with voltages above 1 kv up to 15 kv

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

GenTech Practice Questions

High Voltage Power Supplies for Analytical Instrumentation

Transcription:

CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s provide isolation from the high voltage primary, permit grounding of the secondary for safety, and step-down the magnitude of the measured current to a value that can be safely handled by the instruments. Ratio The most common CT secondary full-load current is 5 amps which matches the standard 5 amp full-scale current rating of switchboard indicating devices, power metering equipment, and protective relays. CT s with a 1 amp full-load value and matching instruments with a 1 amp full-range value are also available. Many new protective relays are programmable for either value. CT ratios are expressed as a ratio of the rated primary current to the rated secondary current. For example, a 300:5 CT will produce 5 amps of secondary current when 300 amps flows through the primary. As the primary current changes the secondary current will vary accordingly. With 150 amps through the 300 amp rated primary, the secondary current will be 2.5 amps ( 150 : 300 = 2.5 : 5 ). When the rated primary amps is exceeded, which is usually the case when a fault occurs on the system, the amount of secondary current will increase but, depending on the magnetic saturation in the CT, the output may not be exactly proportional. Polarity All current transformers are subtractive polarity. Polarity refers to the instantaneous direction of the primary current with respect to the secondary current and is determined by the way the transformer leads are brought out of the case. On subtractive polarity transformers the H1 primary lead and the X1 secondary lead will be on the same side of the transformer (the left side when facing the low-side bushings). See the article Understanding Transformer Polarity in the Archive Catalog of the Kilowatt Classroom Web Site for more information on polarity. Donut or Window-Type CT Startco Engineering Ltd Photo White Lead is Secondary Polarity Primary Polarity Mark On the Window or Donut-type CT s, such as pictured on the left, the conductor, bus bar, or bushing which passes through the center of the transformer constitutes one primary turn. On Window-type units with low primary current ratings, where the primary conductor size is small, the ratio of the transformer can be changed by taking multiple wraps of the primary conductor through the window. If, for example, a window CT has a ratio of 100:5, placing two primary conductor wraps (two primary turns) through the window will change the ratio to 50:5. Some types of equipment employ this method to calibrate the equipment or to permit a single ratio CT to be utilized for several different ampacities of equipment. Bar-Type CT s have primary connections that bolt-up directly to the substation bus bars. Outdoor-rated versions of this equipment are used in pole-mounted primary metering installations. Primary Polarity Mark H1 Terminal Bar -Type CT This type of CT often has compensating windings which improve the accuracy across the full-load range of the transformer. X1 Terminal X1 Polarity Mark X2 Terminal H2 Terminal Sheet 1

CT2 Current Symbols Current Flow Analysis In analyzing the current flow in a system utilizing CT s the following observation can be made: When current flows in the CT primary from the H1 lead (polarity + ) to the non- polarity H2 lead, current will be forced out the secondary X1 (polarity + ) lead, through the burden (load), and return to the secondary X2 non-polarity lead. The next half-cycle the current will reverse, but for the purpose of analysis and for constructing phasor diagrams, only the above indicated one-half cycle is analyzed. Electrical Drawing Conventions The polarity marking on electrical drawings may be made in several different ways. The three most common schematic conventions are shown below. The drawing symbol for meters and relays installed in a draw-out case that automatically short the CT secondary is shown in the drawing at the lower right. CT One-Line Diagram Symbol Secondary Winding One-Turn Primary Secondary Conductors to Relays or Instruments Polarity Marks Shown as Dots Source Current Elements in Meters or Relays H1 Polarity Marks Shown as Squares Source Current Elements in Meters or Relays X1 X2 H2 Load Secondary Safety Ground Load Secondary Safety Ground Polarity Marks Shown with Slash Draw-Out Meter or Relay Case Source Current Elements in Meters or Relays Source Symbol for draw-out case with CT Shorting Load Secondary Safety Ground Load Secondary Safety Ground Sheet 2

CT3 Current Shorting Methods Caution: The secondary of a Current Transformer must always have a burden (load) connected; an opencircuited secondary can result in the development of a dangerously-high secondary voltage. Energized but unused CT s must be kept short-circuited. Startco MPU-16 Motor Protective Relay Retrofit installation in draw-out case. Startco Engineering Ltd Photo Draw-Out Instrument Cases Meters and protective relays are available in draw-out cases that automatically short-circuit the CT when the instrument is removed for testing and calibration. Voltage and trip-circuit contacts will be opened. See symbol for draw-out case on Sheet 2. CT Shorting Terminal Strips The illustration below shows the termination of a multi-ratio CT on a special shorting terminal strip. Insertion of shorting screw through shorting bar ties isolated terminal strip points together. Any shorted winding effectively shorts the entire CT. Multi-Ratio CT Spare Shorting Screw Stored for future shorting requirement. X1 X2 X3 X4 X5 Shorting Bar Shorting screw in any other locations shorts CT. Relay connected to CT tap which provides the desired ratio. Lead X3 becomes polarity. Shorting screw ties X5 CT lead to ground. Safety Ground Shorting screw ties shorting bar to ground. Terminal Strip Mounting Hole Auxiliary Current Startco Engineering Ltd has developed a system utilizing an Auxiliary CT (pictured at left) which permits safe removal of hard-wire protective relays from the system. The current transformers are permanently wired to the input of the Auxiliary CT and the output of the Auxiliary unit is wired to the protective relay current inputs. This arrangements keeps a burden on the CT secondary circuits and permits the protective relays to be removed for repair, calibration, or replacement. Startco Engineering Ltd Photo The Auxiliary CT is installed as close as possible to the current transformers. This reduces the CT burden by reducing the length of the CT secondary current conductors. Sheet 3

CT4 Current CT Accuracy Classes ANSI Accuracy Classes Current are defined by Accuracy Classes depending on the application. Metering Accuracy CT s are used where a high degree of accuracy is required from low-load values up to full-load of a system. An example of this application would be the current transformers utilized by utility companies for large capacity revenue billing. Relaying Accuracy CT s are used for supplying current to protective relays. In this application, the relays do not normally operate in the normal load range, but they must perform with a reasonable degree of accuracy at very high overload and fault-current levels which may reach twenty times the full-load amplitude. Notes: 1) Instrument (PT s & CT s) are defined in ANSI C57.13-1978. 2) The load on an instrument transformer (PT or CT) is referred to as the burden. Metering Accuracy Classifications Available in Maximum Ratio Error Classes of: + 0.3%, + 0.6%, + 1.2%, +2.4%. For Burdens (Loads) of: 0.1, 0.2, 0.5, 0.9, 1.8 ohms. Which equals 2.5, 5.0, 12, 22-1/2, 45 volt-amperes ( va ). Since Power = I 2 xr, use 5 amp secondary for I, and burden value for R. Typical Number 0.3 B 0.2 Max Ratio Error + % Burden Ohms (Burden) Relaying Accuracy CT s Class C (C for Calculated) is low leakage reactance type - typical of donut units - Formerly Class L ( L for Low Leakage). Class T (T for Tested) is high leakage reactance type - typical of bar-type units - Formerly Class H ( H for High Leakage). Typical Number 10 C 800 10% Max Ratio Error at 20 times Rated Current Low Leakage Unit Max secondary voltage developed at 20 times rated current without exceeding the +10% ratio error. Available secondary voltages: 10, 50, 100, 200, 400, 800. Will support burdens of: 0.1, 0.2, 1.0, 2.0, 4.0, 8.0 ohms. Sheet 4

CT5 Current Multi-Ratio CT s Westinghouse Multi-Ratio Bushing-Type CT For External Installation Installation Considerations This bushing CT is designed for use on existing circuit breakers and power transformers and is installed externally (See Sheet 11). It is housed in an aluminum case which provides electrostatic shielding. Care must be taken with the installation to insure that the mounting clamp bolts do not contact the case resulting in a one-turn primary short circuit. Also because the case is metal and is installed externally it can decrease the bushing strike distance. The circuit breaker or transformer manufacturer should be consulted to verify acceptability of the installation. Polarity Mark 600/5 CT Secondary Turns Diagram Diagram at the left shows the number of turns for each winding on a 600/5 multi-ratio CT. The full number of 120 turns, from X1 - X5, is used to obtain the 600/5 ratio. (Since there is one primary turn, 120:1= 600:5). Another example: X1 - X2 has 20 turns, so 20:1= 100:5. Any combination of adjacent turns can be utilized. The lowest lead number of the combination will be the polarity lead. See the CT shorting strip diagram on Sheet 7 for a typical termination arrangement. Selection Guide Shows ANSI Accuracy Classes, Dimensions, and Mfg Style Number Sheet 5

CT6 Current Typical Excitation Characteristics Excitation Curves The family of curves below describe the excitation characteristics for the 600/5 multi-ratio bushing current transformer shown on the previous sheet. This is a plot of the CT secondary current against secondary voltage. These curves illustrate how high the secondary voltage will in rise in order to force the rated secondary current through the burden. The effect of magnetic saturation is also illustrated by the knee of the curve. Next month s article will show how to perform a CT Saturation Curve Test. Sheet 6

CT7 Current Typical Installations Load-Side CT s Line-Side CT s Bushing CT s Bushing CT s may be mounted externally or internally on circuit breakers and transformers. Multi-ratio units are often used. Where single-ratio CT s are employed, the CT primary rating may match either the full-load ampacity of the circuit breaker or of the feeder. In the latter case, upgrading the feeder ampacity will require replacement of the CT s. The CT secondary leads land on a termination strip in the breaker or transformer control cubicle. Siemens SF6 Circuit Breaker With externally mounted bushing CT s External Portion of Bushing Note Petticoats which shed moisture and increase creepage distance. Multi-Ratio CT Bushing Internal Porcelain This section is submerged in oil. Westinghouse Oil-Filled Vacuum Recloser With tank dropped showing internally mounted CT s on line-side bushings. In this configuration the protective relays fed by the CT s are said to look through the breaker. Control Circuit Contact Block Mates with breaker control block. Bus Bars Breaker Bus-Side Stabs With single donut CT on B-Phase General Electric 480 Volt Metal-Clad Switchgear Cubicle with generator breaker racked out. Breaker Machine-Side Stabs With donut CT on A and C Phases Sheet 7

CT8 Current Types Hall Effect CT s Hall-Effect CT s are not current transformers in the conventional sense, rather they are electronic circuit transducers which can be applied in the measurement of either AC or DC circuit currents. These devices have many applications; they are commonly used in Variable Frequency Drives (VFD s) to measure the DC link current and are also employed in AC/DC instrument probes such as the TPI-A254 Current Adapter shown at the right. Hall-Effect devices contain an null-balance type amplifier circuit. The magnetic flux (field) produced by the current flow through the primary (usually one-turn) results in an output voltage which is balanced by an equal and opposite output from the control or measuring circuit. Because the circuit is an amplifier, it requires external operating power which is supplied by the control circuit power supply, or in the case of a portable instrument probe, batteries are used. As with conventional current transformers, Hall-Effect devices provide isolation from the high voltage circuit and reduce the measured current to a proportional value which can be safely measured by the control or instrument circuit. Hall-Effect devices do not pose the same danger as conventional bus-bar or donuttype CT s with regard to an open circuited secondary. (Note: some instrument current probes are conventional CT s; these usually have a burden resistor within the probe or may be protected from an open circuit with back-to-back zener diodes.) However, good practice dictates that instrument current probes should not be disconnected from the meter while current is passing through the device primary. TPI AC/DC Current Probe Probe employs the Hall- Effect principle and produces a millivoltage output that is applied to a TPI Digital Multimeter. The meter interprets the probe voltage as a current value. Batteries are used in the probe to power the amplifier circuitry. Test Products International Photo Hall-Effect CT Used on the DC Link of a 5000 H.P. VFD. Heat Sink Control Circuit Connections Tubular High Voltage Bus Bar Passes through Hall-Effect CT Power Transistors Typical VFD Block Diagram Showing Hall-Effect CT (HCT) Connections DC Link 3-Phase AC Motor Single or Three-Phase AC Input Rectifier HCT Inverter Speed Reference HCT Output Signal Regulator HCT Power Frequency Control Signal Sheet 8 Motor Voltage Feedback