IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Similar documents
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

R.C.C.B. s two-pole LEXIC

NEW RANGE OF CABINETS DRIVIATM. Innovation at your service. THE GLOBAL SPECIALIST in electrical and digital building infrastructures

IEC & 2 standard. The reference for safe and reliable LV switchboards

Application Switchgear for industrial and commercial applications. U e V AC 230/ (per pole)

The power distribution board that sets new standards

P System Cubicles. Certified for more safety

Securing your electrical installations Prisma,

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

FAQs-Main switchboard design criteria

know-how Giant in distributing electricity for industry Prisma GK

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

Unified requirements for systems with voltages above 1 kv up to 15 kv

The easy way to build switchgear and controlgear assemblies in compliance with the regulations

IEC specifications for LV assembly switchboards

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

Distribution Boards & Consumer Units

Low Voltage Switchboards The Best Technical Solution for Your Ship

5SV Residual Current Protective Devices

DEVICES OF PROTECTION AND COMMAND

KAM A Lighting Busbar System KAP A Plug-in Busbar Distribution System

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

MNS is Switchgear System Technical Overview

Standard-compliant switchgear and controlgear production

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

SIVACON The Versatile Low-Voltage Switchboard

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Technicaldata General

ADM1TE 5/30A DIN rail single phase two wire energy meter

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

The Intelligent AX1 Switchgear for Medium Voltage

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

RM4TG20 three-phase network control relay RM4-T - range V

Dlp-s & WIRING DEVICES. THE MAXIMUM FReeDOM OF ChOICe. SNAP-ON AND UNIVERSAL TRUNKING FOR high AND LOW CURReNt DIStRIBUtION

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

Comparative study for cables and busbars

Industrial Process Plants. Residential & Commercial Buildings. Roads & Tunnels. Airports & Seaports

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Breaking and protection devices

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

SURGE PROTECTIVE DEVICES

Linkeo 19" freestanding cabinets

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS

SIVACON Low Voltage Switchboard

The complete range of consumer switchboards and switchgear

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Technical Application Papers No.11 Guidelines to the construction of a low-voltage assembly complying with the Standards IEC Part 1 and Part 2

White Paper IK code: Impact protection in line with the IEC standard. By Sven Schnautz

NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c Erlangen Germany.

Data Center Integrated solutions

SERVER ROOM CABINET INSTALLATION CONCEPTS

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Voltage Regulator SPAU 341 C. Product Guide

Low Voltage Products. Switches Automatic Transfer Switches

UFES Active protection for switchgear

Redundancy Module QUINT-DIODE/40

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation

About the BitStorm 6051 POTS Splitter

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Instructions for Safe Use

Installation. Smart-UPS VT MGE Galaxy Maintenance Bypass Panel kva 400 V

Explosion proof enclosures

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

How To Build A Low Voltage Capacitor Lvcp

Nothing s BetterThan the Original MODAN Power Distribution Systems

IT infrastructure Efficiency-boosting solutions. nextlevel. for data centre

LightingEurope EU Compliant Requirements Products Sheets for LIGHTING COMPONENTS

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Climasys Thermal Management System. Schneider Electric Universal Enclosures 2009

Technical data. RCBO s DS 261 / DS 271 Residual current operated circuit breakers with integral overcurrent protection

vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall-mounted drives

Cisco TelePresence MCU 4500 Series safety and compliance information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Guidance for upgrading to GB (IEC : 2005, MOD)

Switchboard system. NorLine 800

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

Rack Installation. Unpacking the System. Choosing a Setup Location. General Server Precautions. Barracuda Appliances

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Project files. Customer copy Legrand copy

ECOCIAT. Domestic hot water heat recovery unit

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

Secondary Unit Substations

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

Transcription:

xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439 This document only deals with distribution enclosures for advanced users (authorised persons), i.e. parts 1 and 2 of the new standard. Summary of use Part 3 of standard IEC 61439 discusses DBO (Distribution Boards intended to be operated by Ordinary persons) only up to 250 A. One of the new features of this standard is that the table in appendix D (checking the design) covered later in this document does not apply in 61439-3. In addition in its new version, standard 61439-3 takes account of domestic normative references.

Contents 1-2 The standard, what's changed Definition of standard IEC 61439-1 2 Extract from standard IEC 61439-1 3 4-7 The Legrand range and certification The XL 3 range 4-5 Certification of pre-equipped XL 3 enclosures 6-7 8-13 The 13 standardsbased tests The 13 tests 8 Response to the tests 9 The type tests in detail 10-13 14-16 The panel builder s response Documentation 14 Example of declaration of conformity 15 List of operations 16 www.legrand.com XL 3 GUIDE TO MIGRATION 1

Standard IEC 61439-1 what's changed IEC 60439 IEC 61439 IEC 60439-1 Standard assemblies and assemblies derived from the standard IEC 61439-1 General rules Old 1992 series IEC 60439-2 Busbar trunking systems IEC 60439-3 Distribution boards IEC 60439-4 Assemblies for construction sites IEC 60439-5 Assemblies for power distribution IEC 61439-2 Power switchgear and controlgear assemblies IEC 61439-3 Distribution boards IEC 61439-4 Assemblies for construction sites IEC 61439-5 Assemblies for power distribution IEC 61439-6 Busbar trunking systems IEC 61439-7 Electric vehicles new 2012 series PUBLICATION DATES IEC 61439-1: 19/08/2011 (DOW (1) 2014) IEC 61439-2: 19/08/2011 (DOW (1) 2014) IEC 61439-3: 16/02/12 (DOW (1) 2015) IEC 61439-4: 2012-10 IEC 61439-5: 29/11/10 (DOW (1) 2013) IEC 61439-6: 2012-05 IEC 61439-7: 2013-03 Definition of an assembly "Complete system of electrical and mechanical components (enclosures, busbars, functional units, etc) as defined by the Original Manufacturer and intended to be assembled in accordance with these instructions " Example: pre-equipped distribution enclosure. (1) Date of withdrawal 2

Extract from standard 61439-1 This edition of IEC 61439-1 includes the following technical modifications compared to the last edition of IEC 60439-1: The dual role of IEC 60439-1 as both a separate product standard and a general rules standard for assemblies covered by a subsidiary product part in the IEC 60439 series has been abandoned As a result, IEC 61439-1 is purely a "general rules" standard that should be invoked by subsidiary product parts in the IEC 60439 series The product standard replacing IEC 60439-1 is IEC 61439-2 The distinction between standard assemblies (SA) and assemblies derived from the standard (ADS) has been eliminated by the verification approach Three different but equivalent types for verifying requirements have been introduced: verification by a test, verification by calculation/ measurement, or verification by satisfying design rules The requirements concerning temperature rise have been clarified The rated diversity factor (RDF) is been discussed more comprehensively The requirements for empty enclosures that will be made into assemblies (IEC 62208) have been incorporated The whole structure of the standard has been aligned with its new function as a "general rules" standard. Original manufacturer Entity responsible for the original design and associated checking that an assembly conforms to this standard (IEC 61439-1). Example: Legrand. Note Assembly manufacturer Entity responsible for assembly, wiring and ultimately responsible for the finished assembly. Example: panel builder. The assembly manufacturer can be a different entity from the original manufacturer. Comment Unlike IEC 60439-1, conformity cannot be established simply on the basis of the general rules (IEC 61439-1). Assemblies must comply with the specific standards dedicated to them; in this case standards IEC 61439-2, IEC 61439-3, etc. www.legrand.com XL 3 GUIDE TO MIGRATION 3

XL 3 the range which can adapt to any Legrand offers ranges which comply with each part of standard IEC 61439: Zucchini busbars, pre-loaded/pre-wired consumer units, portable combined units, EV charging points, etc. requirement For sites up to 160 A For sites up to 400 A This document aims to focus on power distribution enclosures. xl 3 160 xl 3 400 Ready to use metal or plastic IP 30 enclosures, capacity of 24 modules per row. For various configurations, either surface-mounted or flush-mounted solutions. Supplied complete with rails and faceplates. Can be fitted with a metal or glass door (to be ordered separately). Surface mounting cabinets have an adjustable cable entry plate, removable side panels, and removable separable top and bottom for ease of wiring. The flush-mounting version is supplied with a metal flush-mounting box, removable chassis with rails fitted, terminal blocks for protective conductors, finishing frame and plastic faceplates. Take modular DPX³ 160 MCCBs, and Vistop devices up to 125 A in cabinets with dedicated space. Metal distribution cabinets and enclosures, IP 30 to IP 55, capacity of 24 modules per row. Reduced depth for optimum space saving Easy and reliable equipment installation thanks to the functional uprights integrated at the back of the cabinet Optimum use of wiring space: the cable ducts can take DPX 3 and DPX power circuit-breakers Possibility of pairing (between 2 enclosures or between the enclosures and the cable ducts) for more wiring capacity Perfect finish and protection index IP 40 to IP 43 thanks to the metal or glass doors IP 55 distribution cabinets available on request 4

For sites up to 800 A For sites up to 6300 A Our products Thanks to the XL 3 range we can provide you with a solution adapted to meet your site power distribution needs by offering a range between 160 and 6300 A. Each enclosure model from the XL 3 range offers a large selection of sizes, versions and equipment. xl 3 800 Metal distribution cabinets and enclosures, IP 30 to IP 55, 24 or 36 module capacity per row. Easy and reliable equipment installation thanks to the functional uprights integrated at the back of the cabinet Optimum use of wiring space: the cable ducts can take DPX 3 and DPX power circuit-breakers Enclosures with width for 36 modules can integrate an internal cable duct (by changing to 24 modules per row) Possibility of pairing (between 2 enclosures or between the enclosures and the cable ducts) for more wiring capacity Perfect finish and protection index IP 40 to IP 43 thanks to the metal or glass doors IP 55 distribution cabinets available on request All versions can be fitted with a busbar at the side or at the back of the enclosure xl 3 4000 and 6300 Configurable metal distribution enclosures, IP 30 to IP 55 (with door and waterproof seal only for XL 3 4000 enclosures). Can take all Legrand protection equipment up to 6300 A and multiple distribution solutions Numerous configurations capable of meeting highly diverse requirements. The enclosures are available in different configurations according to each range: 2 heights, 3 widths and 3 depths for XL 3 4000 and 1 height, 1 width and 3 depths for XL 3 6300 Reliable assembly using the mounting devices and the sectioned uprights Remarkable strength thanks to the specially designed structural elements for maximum stability Perfect finish: metal or glass doors (only for XL 3 4000 enclosures) www.legrand.com XL 3 GUIDE TO MIGRATION 5

Safety guaranteed by the certification of pre-equipped XL 3 enclosures The principles The standard The certification of distribution enclosures is defined by international standards IEC 61439-1 and IEC 61439-2. This formulates the definitions, operating conditions, structural provisions, technical characteristics and the tests for low-voltage wiring accessory assemblies. Obligations The construction of assemblies of representative configurations using products that have themselves been tested and comply with their own specific standards; these are the type tests carried out based on our enclosures with Legrand equipment. Compliance with the rules for selection and use of these products in accordance with the procedures defined by the standards, regulations, and good practice. The carrying out of individual tests (insulation, continuity of exposed conductive parts) and of a final inspection, are recorded in a simplified individual report (see example in the appendix). 6

The 13 tests for certification of pre-equipped enclosures The 13 tests described overleaf are an additional guarantee of the operation of pre-equipped enclosures in safe conditions, as well as of the safety of individuals and of the equipment installed downstream of the panel. This is the case for the entire period of service of the electrical panel. Different people's roles The original manufacturer produces the various elements that make up a distribution panel: the protection devices, enclosures, distribution system, etc. All these elements have been granted product certificates of conformity. The assembly manufacturer assembles the electric cabinet, installs the equipment, completes the wiring and should certify the finished assembly. Conformity Total compliance with this process can then be certified by a declaration of conformity (see example in the appendix) and the assembly can be marked accordingly. Compliance with standard IEC 61439-2 also enables the CE mark to be affixed, if required. www.legrand.com XL 3 GUIDE TO MIGRATION 7

The 13 standards-based Check performed on a sample of an assembly or on parts of assemblies to demonstrate that the design satisfies the requirements of the applicable assembly standard. tests no. Characteristic to be checked Items verification option Tests comparison evaluation 1 Strength of materials and parts 10.2 YES NO - 2 Degree of protection (IP) 10.3 YES NO YES 3 Clearance 10.4 YES NO NO 4 Creepage distance 10.4 YES NO NO 5 6 7 Electric shock protection and integrity of protection circuits Integration of connection devices and components Internal electrical circuits and connections 10.5 YES - NO 10.6 NO NO YES 10.7 NO NO YES 8 Terminals for external conductors 10.8 NO NO YES 9 Dielectric properties 10.9 YES NO - 10 Temperature rise 10.10 YES YES YES 11 Short-circuit resistance 10.11 YES YES NO 12 Electromagnetic compatibility 10.12 YES NO YES 13 Mechanical operation 10.13 YES NO NO Testing the check (3.9.1.1) Comparing the check (3.9.1.2) Evaluating the check (3.9.1.3) 3 options Test performed on a sample of an assembly or on parts of assemblies to check that the design satisfies the requirements of the applicable assembly standard (performed by Legrand). Structured comparison of a design proposal for an assembly, or parts of an assembly, with a benchmark design that has been subjected to the test (performed by Legrand). Design check of the design rules or strict calculations applied to a sample of an assembly or to assembly parts to demonstrate that the design satisfies the requirements of the applicable assembly standard (performed by the assembly manufacturer or the original manufacturer). 8

Response to the tests certificates, documentation Characteristic to be checked Original manufacturer (legrand) Assembly manufacturer (panel builder) Resistance of materials and parts LOVAG 10.2 certificate Degree of protection (IP) LOVAG 10.3 certificate Visual check 11.2 Clearance LOVAG 10.4 certificate Visual check 11.3 Creepage distance LOVAG 10.4 certificate Visual check 11.3 Electric shock protection and integrity of protection circuits Integration of connection devices and components Internal electrical circuits and connections Terminals for external conductors LOVAG 10.5 certificate Check by survey 11.4 Checked on tested configurations Legrand 10.6 Checked on tested configurations Legrand 10.7 Checked on tested configurations Legrand 10.8 Visual check 11.5 Check by survey 11.6 Visual check 11.7 Dielectric properties LOVAG 10.9 certificate(time 5 s) Test to be performed 11.9 (time 1 s) Temperature rise Short-circuit resistance Electromagnetic compatibility LOVAG 10.10 certificate LOVAG 10.11 certificate LOVAG 10.12 certificate Mechanical operation LOVAG 10.13 certificate Visual check 11.8 Wiring, functional performance and operation Functionality test or visual check 11.10 Legrand is committed to carrying out the 10 type tests on these XL 3 enclosures The type tests defined by standard IEC 61439-1 are carried out officially by neutral organisations on assemblies representative of the usual wiring and device configurations. These assemblies are called Standard assemblies. An additional action on top of the simple visual check. www.legrand.com XL 3 GUIDE TO MIGRATION 9

The type tests in detail Test 1 Resistance of materials and parts The mechanical, electrical and thermal capacities of construction materials and parts of the assemblies must be proved by checking the construction and performance characteristics. Tests are therefore conducted to check withstand to: heat, ultraviolet, lifting, mechanical impacts. test 3 Clearances and creepage distances The measurement procedures for clearances and creepage distances are accurately covered in appendix F of standard IEC 61439-1 derived from standard IEC 60664-1. The clearances and distances are measured between live parts with different polarities, and also between live parts and exposed conductive parts (example in the appendix). Test 2 Verification of the degree of protection (IP) The IP defines the ability to protect people against current-carrying hazardous parts and to prevent entry of solid bodies (first number) and liquids (second number). The additional letter indicates the protection against access to current-carrying hazardous parts. Legrand offers a solution that is perfectly suited to all environments. Test 4 Fitting devices and equipment When installed in accordance with the specified conditions, Legrand guarantees that clearance distances are observed for the insulation voltages of these devices. Experience has shown that the greatest risk is in the wiring. Connections, bundles of conductors and busbars must be meticulously checked. Unsuitable connectors, bolted connections, joints and metal supports can reduce the insulation values initially envisaged. 10

Test 5 Effectiveness of the protective circuit The continuity of the protective circuit is a decisive factor for safety. It is checked: firstly in accordance with standard IEC 61439-1 at a test current of 25 A between the terminal connecting the protective conductors and all the exposed conductive parts; secondly in accordance with an additional Legrand test, at a high fault current that could occur following accidental detachment of a conductor. Test 6 Integration of connection devices and Components These are rules concerning the installation of devices included in the assembly, whether fixed or removable parts, or compliance with the customer's wiring requirements. This also includes accessibility to regulation and reset devices; and all types of indication (LEDs, dials, etc). Test 7 Internal electrical circuits and connections This test consists of checking conformity with the design requirements for the power and control circuits. It includes correct sizing of the busbar and cables, earthing the control circuits, etc; it also includes identification of the various circuits by colour. Test 8 Terminals for external conductors This rule requires an indication of the terminal capacity and also whether aluminium or copper are possible options to be declared to the end user. It also includes checking all types of terminal that can be used for cable entries and outlets (Neutral, PEN, symbolic PE, etc). www.legrand.com XL 3 GUIDE TO MIGRATION 11

The type tests in detail continued Test 9 Dielectric properties The dielectric tests check the insulation performance levels for the maximum operating voltage. They are carried out at the industrial frequency of 50 Hz and in the form of voltage waves simulating a lightning strike. Test 10 Temperature rise limits Temperature rise test on assemblies This test checks that assemblies operate correctly under maximum operating conditions (current, number of devices, volume of enclosure). It is used to define the heat balance elements for an average temperature rise in the air in assemblies of less than 30 C and a temperature rise in the terminals of less than 70 C. Test 12 Electromagnetic compatibility This test consists of checking the assembly's electromagnetic interference when operating in its environment, the aim being for it to produce no interference. Test 11 Short-circuit resistance The tests carried out guarantee, in relation to thermal and electro dynamic stresses, the resistance of the busbars and their supports, the breaking devices (Vistop/DPX-IS) and protection devices (DMX 3 /DPX 3 /DX 3 ), and the enclosures. Test 13 Mechanical operation check In accordance with the provisions of the standard, tests are carried out on parts and devices that are not subject to any specific requirements. Correct mechanical operation is checked by 50 operating cycles on draw-out racks and faceplate fixings. 12

lovag certificate www.legrand.com XL 3 GUIDE TO MIGRATION 13

the panel builder s response documentation Information to be provided by the assembly manufacturer 1 Marking 2 Documentation The following information must be included on one or more of the designation labels: Name or trademark of the assembly manufacturer (responsible for the finished assembly), eg: Company Panel builder's name Type designation or an identification number ex : TD01-RDC or G18732 Means of identifying the manufacturing date, eg: 2012 or 2012-03 or 12W09 IEC 61439-X (the specific part X must be identified). eg: IEC 61439-2 Example of nameplate Panel builder's name TD01 - RDC 2012 IEC 61439-2 The following additional information must be included in the technical documentation supplied with the assembly (dossier or technical publication): Rated voltage for the assembly (Un), eg: Un = 400 V Rated operating voltage for a circuit (Ue), eg: Ue = 230 V (if different from Un) Rated impulse withstand voltage (Uimp), eg: Uimp = 6 kv Rated insulation voltage (Ui), eg: Ui = 800 V Rated current for the assembly (Ina), eg: Ina = 3100 A Rated current for a circuit (Inc), eg: Inc = 250 A Permissible rated peak current (Ipk), eg: Ipk =140 ka Permissible rated short-time withstand current (Icw), eg: Icw = 50 ka 1 s Conditional rated short-circuit current (Isc), eg: Isc = 70 ka Rated frequency (fn), eg: fn = 50 Hz Rated diversity factor (RDF) eg: RDF = 0.7 The additional information below must be provided where necessary Additional requirement depending on the specific operating conditions for an FU Degree of protection Assembly neutral earthing system type Installation inside and/or outside Fixed or mobile Degree of pollution Accreditation of personnel EMC classification Specific operating conditions External design Protection against mechanical impact Construction type: fixed or partially removable Short-circuit resistance and nature of protection devices Electric shock protection method Weight of assembly if more than 30 kg Electrical diagrams including component identification 14

Example of letter of conformity declaration of conformity Company: Address: Addressee: Document no: Assembly no: Date: Date: Standard IEC 61439-1 Standard IEC 61439-2 The assembly manufacturer certifies through this document that the low-voltage switchgear and controlgear assembly referred to above has been built in conformity with standard IEC 61439-1/ IEC 61439-2. Installation has been completed in accordance with the recommendations by the original manufacturer of the components used. The following product ranges were used: DPX, DPX 3 and DMX 3 power circuit-breakers complying with standard IEC DX, DX 3 secondary MCBs complying with standard IEC 60947-2 Distribution blocks and busbar supports with reference to the type tests conducted in accordance with IEC 61439-1: Verification of temperature rise limits Verification of the dielectric properties Verification of the short-circuit withstand strength Verification of the effectiveness of the protective circuit Verification of clearances and creepage distances Verification of mechanical operation Verification of the degree of protection Verification of the strength of materials and parts including: - verification of resistance to mechanical impact - verification of rust resistance - verification of resistance to heat and fire - verification of resistance to lifting The individual tests form the subject of individual inspection report no.... including, in conformity with the standard: Visual inspection of the assembly Verification of the insulation Checking of the continuity of the protective circuit The declarant: Signature: www.legrand.com XL 3 GUIDE TO MIGRATION 15

List of operations to be performed by the assembly manufacturer Item concerned Operations Completed Not applicable 1. Visual inspection 11.10 Wiring check 11.10 Compliance with the diagram 11.5 Wiring accessories check 11.5 Compliance with the specified wiring accessories 11.6 Busbar check 11.4 Verification of the effective connection of exposed conductive parts 11.4 Verification of the measurements associated with category II 11.10 Electrical operation (power) 11.10 Electrical operation (control) 11.10 Check of the measuring devices 11.10 Tests of residual current devices 11.8 Mechanical operation check 11.8 Compliance of the locking with specifications 11.4/11.6 Check of the tightening torques 11.10 Compliance of the handling devices 11.2 Verification that the degree of protection is maintained 2. Insulation check 11.9 Dielectric test: voltage... 11.9 Insulation resistance below 500 V minimum value measured:... 3. Verification of continuity of the protective circuit 11.4 Continuity measurement below 10 A 11.4 Check with signal controller 4. Final check 11.10 Nameplate present 11.10 Documentation present 16

FOLLOW US ON www.legrand.com www.youtube.com/legrand twitter.com/@legrand EXB 12074 - January 2013 Head office and International Management 128, av. du Maréchal-de-Lattre-de-Tassigny 87045 Limoges Cedex - France Tel: + 33 (0) 5 55 06 87 87 Fax: + 33 (0) 5 55 06 74 55