100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd



Similar documents
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

GE Multilin technical note

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21,

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.

INNOVATIVE INJECTION-BASED 100% STATOR EARTH-FAULT PROTECTION

Shunt Capacitor Bank Fundamentals and Protection

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

ABB PSPS Erich Steinmann; Generator control-2013

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

VOLTAGE REGULATOR AND PARALLEL OPERATION

Generator Differential Relay Electrical Apparatus

The following table shows approximate percentage wise the

Product Data Bulletin

Earth Fault Detection Basics in Theory

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

SYNCHRONOUS MACHINES

Typical Data Requirements Data Required for Power System Evaluation

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Paralleling Power Sources Which Share a Common Neutral

Pilot-wire differential relay for lines with two or more terminals

Eaton s E-Series protective relay family

CT Application Guide for the 489 Generator Management Relay

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Electrical Safety Tester Verification

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Basics of Electricity

Motor Protection Principles. Craig Wester GE Multilin

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

8 Speed control of Induction Machines

Transistor Characteristics and Single Transistor Amplifier Sept. 8, 1997

WIND TURBINE TECHNOLOGY

Physical Address: City: State: Zip Code:

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

S&C BankGuard PLUS Control

AC-Synchronous Generator

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TABLE OF CONTENTS 1.0 INTRODUCTION PURPOSE DEVIATION INTERTIE PROTECTION REQUIREMENTS... 4

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Chapter 24. Three-Phase Voltage Generation

UCI274C - Technical Data Sheet

UCI274H - Technical Data Sheet

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Lab 8: DC generators: shunt, series, and compounded.

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

FIT TIER 2 Application

Table of Contents. TransformerIQ FAQs 1

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unit 33 Three-Phase Motors

GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co.

WHITE PAPER GROUND FAULT. Lowering the Limits for Ground Fault Detection

Voltage Unbalance and Motors

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

Cahier technique no. 196

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Power Quality Paper #3

FREQUENCY CONTROLLED AC MOTOR DRIVE

Test & Data Management Software

Transmission Protection Overview

PM734F - Technical Data Sheet Winding 28

Advance Electronic Load Controller for Micro Hydro Power Plant

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

Application Note. So You Need to Measure Some Inductors?

PI734D - Technical Data Sheet

SX460. Generator Automatic Voltage Regulator Operation Manual

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

PI734B - Technical Data Sheet

T Substation Maintenance and Commissioning Test Equipment

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current

10A-C GENERATOR AND MOTOR PROTECTION

Using Current Transformers with the 78M661x

Tutorial on Safety Standard Compliance For Hipot Testing

Predictive Maintenance

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

Chapter 16. Current Transformer Design. Copyright 2004 by Marcel Dekker, Inc. All Rights Reserved.

1/29/2013. School. Generation Track. Overview Lecture. Generator Design, Connections, and Grounding

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

Application Note AN- 1095

Protection of Phase Angle Regulating Transformers

Physics 623 Transistor Characteristics and Single Transistor Amplifier Sept. 13, 2006

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Testing of Power Transformers. Routine tests, Type tests and Special tests

Open Phase Conditions in Transformers Analysis and Protection Algorithm

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transfer Equipment Controls

TDMS Test & Data Management Software

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HIGH VOLTAGE CALCULATIONS / EVALUATIONS. West Virginia Office of Miners Health, Safety & Training

DC/DC power modules basics

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

Specifying a Variable Frequency Drive s

7CURRENT TRANSFORMERS

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

General Thoughts on Generator Set - Acoustic Solutions & Noise Control

Transcription:

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman, WI. 53118 roger.a.hedding@us.abb.com Duluth, MN. 55811 sschoenherr@mnpower.com An undetected stator ground fault on a large turbine generator can cause millions of dollars in damage and a larger amount of lost operating revenue during the time the generator is out of service being repaired. As Minnesota Power has been upgrading the protection on their generating units the grounding has been being upgraded from low impedance grounding to high impedance grounding. 100% stator ground protection has been being implemented. From a past project of relay upgrades at Minnesota Power s Laskin Energy Center the two generators do not have 100% stator ground fault detection. Due to the design of the generators, the use of third harmonic voltage to detect the stator ground fault is not reliable. When it was time to upgrade Minnesota Power s Hibbard Energy Center Unit 3 and Unit 4 generators, which are similar in design and size as the units at Laskin Energy Center, it was decided that different options needed to be explored to achieve 100% stator ground protection. Minnesota Power services 143,000 retail costumers in northeastern Minnesota and wholesale electric service to 16 municipalities and some of the largest industrial customers in the country. MP operates five thermal power plants, and eleven Hydro Stations for a total production of 1500 Megawatts net 100% Stator Ground protection To understand the issue of ground fault protection for a generator, it s necessary to know the effect of grounding of the generator has on the amount of ground fault current available. There are several ways to ground a generator; Ungrounded, low impedance grounding, low impedance grounding, high impedance grounding, and solidly grounded. 1

Fig 1 Types of Grounding Ungrounded Generator is grounded through the winding and cable capacitance. Fault current is negligible. This type grounding rarely used for generators since neutral of generator must be insulated for full phase to phase voltage. On small generators this may not be problem. This grounding method is used in some industrial applications where the generator can still operate with a ground fault. Solidly grounded Generator neutral is directly tied to ground The high magnitude of fault current which results from solidly grounding a generator is unacceptable because of the fault damage it can cause. Shutting down the generator through tripping the generator breaker, field, and prime mover does not cause the fault current to immediately go to zero. The flux trapped in the field will result in the fault current slowly decaying over a number of seconds after the generator is tripped which substantially increases damage. This type connection is not commonly used. Stator windings on major generators are grounded in a manner that will reduce the fault current and overvoltages and provide a means of detecting the ground fault condition quickly enough to prevent iron burning. Two methods to accomplish this are low impedance and high impedance grounding. Low impedance grounding The grounding resistor or reactor is chosen to limit the generator contribution to a single line to ground fault current to between 200 amps and 150% of rated load current. The phase differential relaying can provide some ground fault protection for higher level ground faults, but additional protection is needed for lower level ground faults closer to the generator neutral. 2

High Impedance grounding This grounding method is mainly used on unit connected generators. A distribution transformer is utilized whose primary voltage is chosen to be slightly greater than the line to neutral rating of the generator so it doesn t saturate on single line to ground faults with the machine operating at 105% of rated voltage. The secondary rating is 120 or 240v. The secondary resistor is selected so that the fault current for a single line to ground fault at the terminals of the generator is limited to 3 25 primary amps. This level of fault current is not sufficient to pick up the generator differential relay for ground faults. Additional protection is needed to detect ground faults. Those generators that use low impedance or high impedance grounding will need to supplement the generator differential relay with some other protection to detect stator ground faults. There are several methods to detect stator ground faults The classical method to provide generator ground fault protection is a neutral overvoltage scheme. (59GN). A time delayed overvoltage relay is connected across the grounding resistor to sense zero sequence voltage. The relay is sensitive to fundamental frequency voltage and not sensitive to third harmonic voltage that is present at the generator neutral. Fig 2. 59GN For a single line to ground fault on the generator terminals, full phase to neutral voltage will impressed on the generator neutral. The voltage across the resistor will be a function of the transformer turns ratio and the location of the fault within the winding. As the fault moves from the terminal to the generator neutral, the voltage across the resistor becomes smaller. Typically, the minimum pick up setting for this relay is 5v. This limits the sensitivity of the relay, so it can detect faults only down to within 5% of the generator neutral. A time overcurrent relay can also be used for providing ground fault protection when using a distribution transformer grounding scheme with a secondary resistor. The current transformer can either be located in 3

the generator neutral or in the secondary of the distribution transformer. An inverse of very inverse overcurrent curve is used for this application. The relay must be set above the normal unbalance currents and the zero sequence harmonic currents that appear in the neutral. The pickup setting of the overcurrent relay should be greater than 135% of the maximum current in the neutral under non fault conditions. The time overcurrent relay provides less sensitive protection than the overvoltage relay that detects zero sequence voltage. Fig. 3 51GN The relaying described above does not yield 100% stator ground fault protection, only 95%. This is because faults near the neutral do not cause sufficient residual voltage and residual current to operate these relays. To achieve 100% ground fault protection two methods are used; third harmonic voltage, and neutral injection. Third harmonic voltages are present at the terminals of nearly every generator in some degree. They exist due to differences in generator design and manufacture. If there is adequate amount of third harmonic voltage, this voltage can be used to detect ground faults near the neutral. The third harmonic voltages measured at the generator terminals, or neutral, or both can be used to detect ground faults. 4

Fig. 4 3rd Harmonic Profile Figure 4 shows the third harmonic voltage at the terminal of the generator and the neutral of the generator during different load conditions, for a fault at the generator neutral, and a fault at the generator terminals. Several observations can be made from the voltage profile. The level of third harmonic voltage at the neutral and generator terminals is dependent of the operating conditions of the generator. The voltage is higher at full load than no load, although this could change with generator design. There is a point in the winding, depending on the generator design, where the third harmonic voltage is zero. For a fault at the generator neutral, the third harmonic voltage at the neutral is zero. For the same fault, the third harmonic voltage on the generator terminals is high and varies with load. For a fault at the generator terminal, the third harmonic voltage is zero, and the third harmonic voltage at the neutral is high. As the ground fault moves from the generator terminal toward the neutral, the third harmonic voltage at the generator terminal increases, and the third harmonic voltage at the neutral decreases. The amount of increase or decrease is a function of the generator operating conditions. The third harmonic voltage levels vary from one generator to another. There are three types of third harmonic voltage schemes employed for 100% stator ground fault protection; Third harmonic neutral overvoltage, third harmonic terminal voltage, and third harmonic comparator. Third Harmonic Undervoltage This method uses the fact that for a fault near the neutral of a generator the third harmonic voltage decreases. An Undervoltage relay operating from third harmonic voltage at the neutral could detect a fault at the neutral. 5

Fig. 5 Third Harmonic Undervoltage Relay An Undervoltage relay tunes to 180HZ is used in this application. The relay is placed across the resistor in the secondary of the neutral grounding transformer scheme. Generally, the third harmonic undervoltage relay can detect faults from 0 30% of stator winding as view from the neutral towards the machine terminals. This relay in combination with the overvoltage relay tuned to fundamental frequency will overlap in protection and give 100% ground fault protection for the stator. Third Harmonic Residual voltage This method relies on the fact that the third harmonic generator terminal voltage increases at the ground fault approaches the generator neutral. Therefore, an overvoltage relay at the generator terminal using third harmonic voltage can detect fault at the generator neutral. Residual voltage at the generator terminal is supplied by a wye grounded broken delta transformer. This voltage is passed to an overvoltage relay tuned to 180HZ. As the fault approaches the generator neutral the voltage received by the relay increases and operated the relay. For faults near the generator terminal, the third harmonic voltage as seen by the relay decreases and this protection does not operate. Thus, this relay needs to be sued in conjunction with the 59GN scheme to yield 100% protection of the stator winding for ground faults. Third harmonic comparator The third harmonic comparator relies on the fact that under normal conditions the ratio of the magnitude of the third harmonic voltage at the generator neutral to the magnitude of the third harmonic generator voltage at the generator terminals is almost constant. This ratio is upset for fault near the generator neutral or near the generator terminals. Ground fault midway in the stator winding are detected by the 59GN relay since the third harmonic differential relay sensitivity is minimal for these faults. For these faults the third harmonic voltage at the neutral and at the terminal is very near the relay setting. The setting for the relay is determined during field tests. 6

Fig 6. Third Harmonic Comparator Voltage injection In this method, an independent signal with a certain frequency, different from the generator rated frequency is injected into the stator circuit. The response of this injected signal is used to detect stator ground faults. To implement this, a separate injection box is required. The injection box generates a square wave which can be injected into a voltage transformer in the neutral of the generator, or grounding transformer. This signal propagates through the transformer into the stator circuit. The magnitude of the injected voltage signal is measured on the secondary of the grounding transformer. In addition, the injected current is measured via a resistive shunt located in the injection box. Based on these two measured quantities, the stator winding resistance to ground is calculated. The calculated resistance value is compared to a setting for alarm or trip. This technique not only measures the resistance to the generator neutral but also along the stator winding and at the generator terminals including connected components such as voltage transformers, excitation transformers, circuit breakers, and other equipment. The measuring principle is not influenced by the generator operating condition and is fully functional even when the generator is on turning gear, or at standstill. Fig 7. Stator Injection 7

Grounding Upgrade at Hibbard The existing grounding on Unit 3 and 4 at Hibbard was low impedance. With the relay upgrade it is MP s standard to upgrade the grounding of the unit to high impedance. The high impedance grounding was implemented by using a distribution transformer with a resistor connected on the low side. The transformer used is a 13,800V to 240V with a 6A primary. The resistor bank is 1.664A, 8154W this setup limits the fault current for a line to ground fault to 6A primary. Stator ground protection at Hibbard Traditionally to achieve 100% stator ground protection on MP s generators a neutral overvoltage scheme (59N) along with a third harmonic comparator (59D). When Laskin Units one and two were upgraded it was discovered that the machines did not produce enough third harmonic voltages, due to the pitch of the windings, to implement a third harmonic comparator scheme. The two Units at Hibbard are of the same vintage and design as Laskin, so it was decided that in the design it should be assumed that the machines would not produce enough third harmonics. Table 1 shows third harmonic reading from the metering after the new relaying was installed. The 59N overvoltage element covers 95% of the stator, and the third harmonic differential only covers the first 15% of the winding so there is 5% of the winding not covered as shown in Figure 8. GENREATOR LOAD 3 RD HARMONIC SECONDARY VOLTAGE TERMINAL SIDE 3 RD HARMONIC SECONDARY VOLTAGE NEUTRAL SIDE Off Line 1.753V 2.010V 0.364 MW 1.865V 2.154V 1.052 MW 1.943V 2.249V 5.163 MW 2.960V 3.609 8.679 MW 3.914V 4.801V Table 1 Third Harmonic Voltage Readings Stator Winding from Neutral 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 64G1 64G2 Element Element Coverage Dead Band Element Coverage 8

Achieving 100% Stator Ground Protect Figure 8 Element Coverage. To achieve 100% stator ground protection an overvoltage scheme (59N) was implemented along with injection through the secondary side of the grounding transformer see figure 9. The 59N element was set to 4% of the nominal primary line to ground voltage, 319V primary, and is only sensitive to the fundamental frequency. This value provides approx 95% of the stator protection while being secure enough not to trip on unbalanced currents. A time delay of 1 second is used to make the element more secure and allow for external system faults to be cleared. Due to there not being enough third harmonics produced to set a third harmonic voltage differential, injection through the grounding transformer was used as shown in figure 9. There are three main parts to the injection unit; the generator protection relay, the injection unit, and a shunt resistor. The injection unit injects a square wave voltage in to the secondary side of the grounding transformer at a frequency of 106 Hz and measures the resulting 106HZ current. The injection unit outputs two voltages to the generator relay which represent the voltage and measured current. The generator relay uses these values to calculate a reference resistance from the winding to ground. This measured value is then compared to predetermined values that are set during commissioning. The shunt resistor is installed in to the circuit to protect the injection unit which is designed to handle voltages of 120V not 240V which is present on the secondary side of the grounding transformer. IEC11000225.ai Fig 9. 100% Stator Connection To implement the injection protection the unit needed to be calibrated. The resistance of the stator is being measured at the generator relay which led to approximately 250 of cable to the grounding transformer of the generator. So the circuit has to be calibrated to account for the resistance in the cable. To calibrate the unit three steps need to be followed; a measurement with the injection circuit in its final 9

configuration, injection with a know resistance from the star of the generator to the ground, and injection with the neutral of the generator grounded. The three steps were done using the commissioning tool, a K1 value and K2 value was established. The K1 value is used to compensate for the transformer ratio and K2 compensates for series impedance from the cabling in the circuitry. See figure 10 and eq. 1 and eq 2 for further explanation of K1 and K2. Figure 10 Equivalent circuit for impedance measurement Where : Z Bare = V inj / I inj eq. 1 Z measured = Z Bare K 1 + K2 eq 2 Fig 11. Three steps for Calibration 10

With the injection unit calibrated reference values need to be established. This was done as the unit was brought on line. Various operating conditions were observed. Measurements were taken with the generator at stand still, with the voltage regulator on and the unit up to speed, and then at various loads. Table 2 shows the various values. The measured resistance stayed very constant through the loading of the generator. This was expected since the generator parameters stay constant throughout the loading STATOR READINGS LOAD (MW) REAL (OHM) IMAGINARY (OHM) VR OFF 1224.244-945.448 VR ON OFF LINE 1313.83-1020.388 3 1310.125-1023 10 1299.284-1022.067 15 1302.019-1023.031 19.5 1294.789-1024.84 27.7 1279.789-1026.547 32.9 1277.404-1028.37 37.5 1272.637-1029.127 A setting of 1000 ohm was set for tripping the unit off line. The logic for tripping the generator if a ground fault is detected by injection is to perform a soft shut down if the unit is online followed by tripping the unit lockout. If the unit is not online the lockout is tripped immediately. This tripping logic allows the unit be taken off line without stressing the turbine. If the overvoltage (59N) scheme picks up and times out the lock out is trip instantly even if the unit is online being the fault is not within the last 5% of the stator winding and more damaged can be caused the farther away from the neutral of the generator the fault is. Conclusion By using an overvoltage scheme and injection 100% stator protection was able to be achieved. With the installation of high impedance grounding and 100% stator ground protection, the risk of causing costly damage to Hibbard Energy Center s Unit 3 and 4 due to a stator ground fault was greatly reduced. References 1. ABB Inc. Generator Protection REG670 ANSI Application Manual, Document ID: 1MRK 502 030-UUS, April 2011 2. ABB Inc. Generator Protection REG670 ANSI Installation and Commissioning Manual, Document ID: 1MRK 502 029-UUS April 2011 3. ABB Inc. Generator Protection REG670 Technical Reference Manual, Document ID: 1MRK 502 027 UEN September 2011 4. Schweitzer Engineering Laboratories, Inc. SEL-300G Multifunction Generator Relay Instruction Manual, Date Code 20100830 11

5. J. Lewis Blackburn and Thomas J. Domin Protective Relaying Principles and Applications Third Addition CRC Press, 2007 6. IEEE C37.102 2006 Guide for AC Generator Protection 7. IEEE Tutorial on the Protection of Synchronous Generators, IEEE Catalog number 95 TP 102 12