RE-COMMISSIONING OF VAV BOXES



Similar documents
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Example of Functional Performance Test : FPT for VAV Ventilation Systems

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

HVAC Processes. Lecture 7

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

ASTACEA4 Inspect complex/central air conditioning systems

HVAC Systems: Overview

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Element D Services Heating, Ventilating, and Air Conditioning

Riverside City College. Math & Science Building HVAC Investigation. May 23, 2013

Energy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat

RKE. Heat recovery unit. heat recovery unit RKE. from 200 to 6800 m 3 /h. General features

EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE

Building Re-Tuning Training Guide: AHU Heating and Cooling Control

Benefits of Cold Aisle Containment During Cooling Failure

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

Dual Maximum VAV Box Controls

Testing methods applicable to refrigeration components and systems

VariTrane Duct Designer An in depth look...

Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview

CGC s Hybrid System Loop Control

Bring the fresh in. Dedicated Outside Air Systems

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Rev. No. 0 January 5, 2009

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Variable Air Volume - VAV

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

Enclosed Football Stadium Design History and Lessons Learned

Why and How we Use Capacity Control

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

Powers Controls TH 192 S Single Temperature Room Thermostat

S & P COIL PRODUCTS LTD SPC HOUSE, EVINGTON VALLEY ROAD, LEICESTER. LE5 5LU. Electrical layouts for EC Motors in Fan Convector units

Lesson 36 Selection Of Air Conditioning Systems

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

Attached is a link to student educational curriculum on plug load that provides additional information and an example of how to estimate plug load:

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore


Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How to Measure HVAC System Airflow

ELECTRIC CENTRAL HEATING FLOW BOILER

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

How To Get A Passive House

Condensing Boiler Efficiency

How To Control Humidity With A Humidifier

FAQs. Conserve package. Gateway... 2 Range Extender... 3 Smart Plug... 3 Thermostat... 4 Website... 7 App and Mobile Devices... 7

Accurate Air Flow Measurement in Electronics Cooling

HVAC Checklist - Long Form

APC APPLICATION NOTE #92

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.

Technical Concept. Filter Fan Unit COMPACT. Type COMPACT AC Type COMPACT EC

FAN COIL UNIT SOFTWARE User Manual

MP-4000 Alarm List (Software version or later)

Controls for fan coil units and cassettes

Case Study. Vermont Hospital: Advanced Analytics as a Preventative Maintenance Tool

T-100-R Installation Guide

February 1, Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure

Applying Schedules and Profiles in HAP

Benefits of. Air Flow Management. Data Center

HERZ-Thermal Actuators

Mistrale. Fusion Terminal

T-4000 Series Pneumatic Room Thermostats

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

Comparing Energy Savings of Different VAV Systems

3. AIR CONDITIONER CONTROLLER (UNIT)

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

Using Time-of-Day Scheduling To Save Energy

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium

KONRAD. Hybrid Fancoil Series

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

Impact of Control System Technologies on Industrial Energy Savings

DUCT TYPE AIR CONDITIONER

Dehumidification Design

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Example of audit of an air conditioning system

HVAC Characteristics. Test Space HVAC Characteristics

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

T7560A,B,C Digital Wall Module

Designed for multi-injector endurance testing, the

VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING

Mechanical Systems Proposal revised

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

PANDA SPRAY BOOTH FILTER INFORMATION

Radiant Temperature Sensor TY7321

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Transcription:

RE-COMMISSIONING OF VAV BOXES Authors: Cristian CUEVAS, Jean LEBRUN (ULg) Patrick LACOTE, Philippe ANDRE (FUL) September 2002 1

Table of contents Nomenclature...3 1. INTRODUCTION...4 2. DESCRIPTION OF THE SYSTEM TO BE COMMISSIONED...4 3. COMMISSIONING OBJECTIVES AND EVALUATION CRITERIA...7 4. MEASUREMENT PROTOCOL AND PROBES LOCATION...8 4.1. Global commissioning...8 4.1.1. Experimental protocol...8 4.1.2. Measured variables...9 4.2. Individual commissioning...10 4.2.1. Experimental protocol...10 4.2.2. Measured variables...10 5. RESULTS AND ANALYSIS OF THE MEASUREMENTS...11 5.1. Global analysis...12 5.2. Individual analysis...15 5.2.2. Flow rate verification (C02 testing)....17 5.2.3. VAV aeraulic characteristics...20 6. OPPORTUNITIES FOR AUTOMIZATION...22 7. CONCLUSIONS AND PRACTICAL RECOMMENDATIONS...22 8. REFERENCES...22 2

Nomenclature P : Pressure, Pa T : temperature, C V : Volumetric flow rate, m³/s X : Concentration, ppm Subscripts AHU : Air handling unit a : Air ex : Exhaust hx : Heat exchanger rad : Radiator st : Static su : Supply w : Water 3

1. INTRODUCTION This paper concerns the re-commissioning of the CA-MET Building located in Namur, which was designed for a one thousand occupants. The building is divided in 11 modules representing together 15 000 m 2 of gross floor area and is described in other IEA40 reports [1], [2]. The study is dealing with the verification of the performance of the VAV boxes and their control laws. 2. DESCRIPTION OF THE SYSTEM TO BE COMMISSIONED VAV principle. The air coming from the AHU is brought into the plenum of the air diffuser (A) and passes through the perforated sheet (b) towards the outlet path formed by the bellows (c) and the bellows stop (d), see Figure 1. The cross sectional area of the outlet path is varied by the changing control pressure from the control unit expanding and contracting the bellows. Figure 1 VAV diffuser in cross section 4

The air diffuser is essentially self-regulating. The air pressure, which is the controlling force, is itself derived from the primary air supply. This pressure acts on the bellows, which expand, and contract to regulate the rate of the airflow from the unit. The control system is presented in Figure 2; it works as explained hereafter. First, the air bleed passes through the filter that allows supplying clean air to the control system. Then the air passes through the variable orifice 1, which changes as the pressure at the controller inlet changes. The size of orifice 2, set manually by rotating a calibrated sleeve, determines the maximum airflow supplied by the unit. Finally, the thermostat keeps the room temperature constant by controlling the bleed rate across the variable orifice 3. An internal crank linked to a bi-metal strip moves the sliding plate. The bimetal strip is constantly exposed to the room airflow by means of a venturi, which creates a depression within the thermostat. Figure 2 Control schematic The VAV boxes are able to regulate the room temperature between 18 and 28 C thanks to the set point adjusting lever, which is accessible to the occupants. Figure 3 (a) shows the VAV tested during the measurement campaign and the position of the set point 5

adjusting lever. Figure 3 (b) shows the room temperature setting; according to the manufacturer the middle position correspond to a room temperature of 23 C. Set point adjusting l 18 C Summer 23 C 28 C Winter (a) (b) Figure 3 Position of the set point adjusting lever The control law, which is supposed to govern the operation of the VAV boxes, is shown by fig. 4. Airflow 2K 2K Max Min 20 C 28 C Summer (blue arrow) Winter (red arrow) Ambient temperature Figure 4: VAV control strategy 6

In summer condition (figure3), the lever should be positioned toward the blue arrow, which means a set point around 20 C. If the room temperature exceeds 21 C, the VAV boxes will be wide open, in order to supply a maximum of cool air In winter condition, the lever should be moved toward the red arrow. The offices being heated by radiators, the VAV boxes are then only used to renew the air in the office. In this position, the set point is around 28 C. In that case and with a normal ambient temperature, the VAV boxes are always closed. This means the airflow rate is minimal. VAV installed in CAMET. The CAMET building is equipped with 1248 VAV boxes, which are divided in two types: Nominal flow rate Range Type [m³/h] [m³/h] 1 200 68 280 2 350 170 850 The type 1 is the most used in the building and it is the VAV studied in this work. Normally, when a type 1 box is closed, there remains a minimal airflow of 68 m³/h. According to manufacturer, a minimum supply pressure of 250 Pa is necessary to guarantee a good performance of the VAV. At this pressure, the VAV covers the whole range of airflow, from the minimum (68 m³/h for type 1) to the maximum, which is fixed by the flow controller. The maximal plenum pressure is limited at 1250 Pa. 3. COMMISSIONING OBJECTIVES AND EVALUATION CRITERIA Commissioning of a VAV system can be carried out at two levels: - Global level: the objective is to check whether the operation as a whole of all the VAV boxes located in the building or in a part of it (for instance connected to a same AHU) is satisfactory - Individual level: the objective is to check individually the operation of some typical VAV boxes. The boxes to be tested are selected according to a global 7

analysis, to occupants complaints, or to specific observation made in some of the rooms. The properties of the VAV boxes, which deserve verifications, are: At global level: - The flow rate operating range: does the operation of the VAV boxes drive the corresponding AHU all across its operating range? - The operating pressure of the AHU: is the fan of the AHU able to maintain its nominal pressure for all configurations of the VAV boxes? At individual level: - The temperature control operation of each VAV box - The flow rate range provided by each VAV box 4. MEASUREMENT PROTOCOL AND PROBES LOCATION 4.1. Global commissioning 4.1.1. Experimental protocol As the specific objective of this commissioning is to check whether the AHU connected to the verified VAV boxes is able to provide the full range of flow rate (from minimum to maximum), the following protocol is proposed: 1. Launch data archiving. Are concerned the variables, which are useful for the exhaust air, flow rate control (see below). 2. Switch the AHU in automatic mode, Bring the offices temperatures somewhere between the two extreme set points (typically around 24 C) and wait for almost steady state conditions. 3. Go in each office supplied by the AHU and switch each thermostat at the end of scale of summer position (lowest temperature set point). 4. Hold on the stabilization of the fan modulation. 5. Measure the static pressure in, at least, one VAV box plenum, located far away from the AHU. 8

If that pressure is outside the tolerances, correct the pressure set point at AHU exhaust. When the advisable pressure is reached, note the airflow rate and the corresponding pressure set point: it will be kept for all further operations. 6. Individual VAV box checking For each office: i. The thermostat being on the summer position (VAV's wide open), note: 1. the VAV noise 2. the air speed close to the outlet (typically with a portable anemometer or simply with the hand) 3. the static pressure in the plenum ii. Put the thermostat at end of scale of winter position (highest temperature set point). The VAV boxes should then reach their minimal opening. This can be checked by: 1. a reduction of VAV noise 2. a lower air speed 3. a higher static pressure in the plenum iii. If nothing is happening, we may conclude that the thermostat is badly connected or deficient. 7. Go in each office supplied by the AHU and switch the thermostat to end of scale of winter position 8. Hold on the stabilization of the fan modulation. 9. Go in each office supplied by the AHU and switch back the thermostat to its normal position, according to the season: a. If we are in winter, let the thermostat in "winter" condition. Or else, switch back the thermostat in "summer" position and ask to the occupants to adjust more accurately, according to their requirements. Note: the here-above described procedure is easier to perform in winter:the 9 th step is then irrelevant. If, the procedure should be applied in summer, then first switch the thermostat on the "winter" position in order to finish with the "summer position". 10. Process the data. By moving all the set-points of the VAV boxes on summer position and then winter position, we force the VAV to be once at maximum flow rate and once at minimal flow rate. If all VAV's local control systems are well connected, we should be able to deduce from AHU monitoring results the maximal and minimal ventilation airflow rates and to compare them with as-built values. 4.1.2. Measured variables The variables archived are: supply pressure at the exhaust of the AHU 9

Heating/cooling coil pressure drop fan modulation pressure at the supply of verified VAV box 4.2. Individual commissioning 4.2.1. Experimental protocol In the offices concerned by verification, the following actions have to be carried out: - Loading of selected rooms with auxiliary heating system (radiators or electrical system) to generate response of VAV system - CO2 test to measure ventilation rate (injection of C02 and subsequent concentration measurement) - Test of VAV system at constant fan speed - Test of VAV system at constant exhaust pressure 4.2.2. Measured variables In order to study the performance of the VAV boxes, some measurements were performed in two offices located in the third floor of the building. The variables measured were, see figure 5: N T amb T a, su T return T return T a, su T w, su, rad B3708 T a B3508 T a T w, su, rad T w, ex, rad T w, ex, rad Atrium Figure 5 Office schematic measurements T w, su, rad : Radiator supply temperature, C 10

T w, ex, rad : Radiator exhaust temperature, C T supply : Supply room temperature, C T thermostat : Air diffuser thermostat temperature, C T return : Return temperature, C T room : Room temperature, C P plenum : VAV plenum pressure, Pa Figure 6 and Figure 7 show the temperature measurements in the offices and the heating system used to load the offices. Thermostat temperature Supply temperature Return temperature Figure 6 Temperature measurements Thermocouple Figure 7 Temperature measurements and auxiliary heating system 5. RESULTS AND ANALYSIS OF THE MEASUREMENTS 11

5.1. Global analysis A fan exhaust set point of 400 Pa may be typically required in order to get 250 Pa in the plenum of the most distant VAV boxes, when they are wide open (the most unfavorable condition). In this condition, there is about 150 Pa of pressure drop all along the air network. Pressure measured in the plenum of 2 offices (Pa). Office B3707 Office B3708 (thermostat badly connected) Summer position 260 150 Winter position 320 150 Control system disconnected 160 150 On summer position, when the VAV's should be fully open, we find the nominal plenum pressure (260Pa) for the boxes B3707, whereas the pressure is significantly lower for B3708. Moreover, this pressure doesn t change when the set point is moved to winter position. In this position, the pressure of B3707 increases normally, confirming that the VAV boxes are closed. We conclude that the B3708 thermostat is deficient or disconnected. Pressure in the plenum and noise measurements in 9 offices (AHU exhaust pressure: 675 Pa; thermostats in summer position) Office Pressure plenum (Pa) Noise level (db) B3708 B3508 B3509 C3513 C3713 C3512 K3358 K3361 K3363 260-530 - 660 680 755 690 690 60 51 37 38 42 37.5 - - - B3708 and B3508 are deficient. Indeed, the noise level is higher there than in the other offices and the plenum pressure is lower. The VAV boxes of the other offices are operating at maximal airflow rate, giving around 600 Pa in the plenum. On deficient VAV's, the pressure is lower because there is no more control of the maximum flow and the boxes are fully open. Here also, we can see that the local control system is either disconnected or deficient. 12

Pressures measured in several plena: Office C3713 C3512 B3720 K3361 K3363 K3368 Pressure plenum (Pa) 410 410 390 330 330 390 As the VAV boxes are closed, these pressures at the plenum are higher than in summer conditions. Figure 8, 9 and 10 show results of an overall commissioning procedure of the VAV boxes installed in the BS module (about 80 offices) of the CAMET building. The pressure difference Htg/Clg, measured between the inlet of the heating coil and the outlet of the cooling coil allows us (after calibration), to calculate the air flow rate. Figure 8: Time schedule of VAV testing phase 13

Figure 9: Response of AHU to all VAVs change of set point (from summer to winter position) Figure 10: response of AHU to all VAVs change of set point (winter to summer position 14

Figure 8 shows the development of the commissioning procedure: During the first phase (Figure 9), all VAV boxes are moving from open to closed positions and this makes the exhaust pressure to increase. Then, the AHU control makes the fan speed to decrease, in order to compensate the pressure elevation. That s what we can see on the graph: the fan modulation decreases, while the exhaust pressure is maintained to its set point (about 400Pa). The reverse situation is observed in Figure 10. The airflow rate varies from 18 879m³/h to 10 424m³/h in the first phase and from 9 582m³/h to 18 575 m³/h in the second phase. This is in accordance with the as-built data. Note: fan modulations at the end of the first phase and at the beginning of the second phase are not the same, while, in both cases, the VAV thermostats are in the same winter position. This can be explained by the very strong difference between both AHU exhaust temperatures (Figure 8): In the winter (red) position during the first phase, the AHU exhaust air temperature is about 27 C, whereas, in same position, but during the second phase, the AHU exhaust temperature is about 14 C. So, during the first case, VAV s are more likely to be entire closed, because of low exhaust temperature combined with a low return temperature. The effect is a little less easy to observe when the thermostats are in summer (blue) position, probably because steady states conditions are not reached yet. 5.2. Individual analysis 5.2.1. Temperature control operation. The air supplied by the VAV to the room is controlled by a thermostat, which acts according to the room temperature. So, in a normal functioning, the thermostat temperature should be the same as the room temperature. But, according to the measuring results available, this is not always the case: the thermostat temperature is highly influenced by the supply temperature and by the radiators. The measurements analyzed correspond to Wednesday 20 th (see Figure 11 and 12). Between 03:15 h and 00:05 h hot water at 80 C is supplied to the radiator, maintaining the VAV turned off. The office temperature increases from 21 C to 23 C and the thermostat temperature increases until 28 C, which is normal since hot air is stratified close to the ceiling, where the thermostat is located. At 05:00 h the AHU is turned on, supplying air at 18 C and the supply radiator temperature is decreased to 56 C. From that time, it is possible to see that the temperature measured by the thermostat is very close to the room temperature (23 C). 15

At 11:00 h the supply radiator temperature is again increased to 80 C and the supply temperature continues decreasing until 16 C. It disturbs the thermostat temperature, which at the beginning increases to 26 and then decreases to 21 C, which does not correspond to the room temperature (25.5 C). The VAV system sees a temperature lower than the room temperature. This one is then maintained according to a wrong set point. 100 B3508 90 80 Temperature [ C] 70 60 50 40 30 20 10 0 19.03.2002 21:00 20.03.2002 00:00 20.03.2002 03:00 20.03.2002 06:00 20.03.2002 09:00 20.03.2002 12:00 20.03.2002 15:00 20.03.2002 18:00 20.03.2002 21:00 Time 35 Tw,ex,rad Tw,su,rad Figure 11 Radiator entering and leaving water temperature B3508 33 31 Temperature [ C] 29 27 25 23 21 19 17 15 19/03/2002 21:00 0:00 3:00 6:00 9:00 12:00 15:00 18:00 21:00 Time Troom Tsupply Treturn Tthermostat Figure 12 Evolution of the room, thermostat and supply temperature 16

5.2.2. Flow rate verification (C02 testing). Two CO2 tests were performed in order to determinate the airflow rate supplied for the VAV system to the offices. The monitoring system device was used to measure the CO2 concentration, which is shown in Figure 13. As it is shown in Figure 14, one of these probes has a measuring offset. Comparing with the others devices installed in the other offices the probe installed in the office B3508 gives better results; so the values measured in the office B3708 must be corrected. Figure 13 Sensors installed in the monitored offices The first test was performed the Wednesday March 20 th at 13:20 h and the second the Thursday March 21 st at 15:10 h. 2400 CO2 concentration [ppm] 2000 1600 1200 800 400 0 19/03/02 00:00:00 19/03/02 12:00:00 20/03/02 00:00:00 20/03/02 12:00:00 21/03/02 00:00:00 21/03/02 12:00:00 Time CO2_B3708 CO2_B3508 17

Figure 14 Evolution CO2 concentrations in the offices B3508 and B3708 The air renovation can be determined using the following equation: X X X 0 0 X = 1 e τ / τ 0 where X 0 X τ τ 0 : is the initial concentration, ppm : is the final concentration, ppm : is the time, s : time constant (inverse of the air renovation), s The last equation can be expressed as: ln ( X ) = ln( X X ) n τ X 0 where n is the air renovation, 1/s. The nominal airflow rate of each VAV is 200 m 3 /h. In each office there are two VAV, so the nominal airflow rate supplied to each office must be 400 m 3 /h. In the first test the offices were heated with the radiators. The office temperatures increase up to 25 C, for an exhaust AHU temperature of 14 C, as is shown in Table 1. According to Figure 15 the VAV are not fully opened. In fact, the static pressure used to control the fan speed was not measured correctly during this test. The sensor scale was incorrect, the measured monitoring pressure was 600 Pa and in fact the real pressure was 120 Pa. So the pressure at the inlet of the VAV box was not sufficient to ensure its good performance. In the second test the offices were again heated with the radiators, but also by an additional heat load of 1500 W in B3508 and 1575 W in B3708. According to the results got in this case, the VAV boxes were fully opened, supplying the offices B3508 and B3708 with 445 m 3 /h and 485 m 3 /h respectively (see Figure 16). 18

The air temperatures were maintained at 22 C in both offices. 8 7 ln(x-xinf) 6 5 4 3 y = -0.0696x + 6.6896 V = 209 m³/h y = -0.0498x + 7.1695 V = 149 m³/h 2 1 0 0 10 20 30 40 50 60 70 80 Time [min] CO2_B3708 CO2_B3508 Figure 15 Airflow rate supplied to the offices (20.03.2002 13:20) 8 7 6 y = -0.1619x + 7.2717 V = 485 m³/h ln(x-xinf) 5 4 3 y = -0.1485x + 7.0393 V = 445 m³/h 2 1 0 0 5 10 15 20 25 30 35 40 Time [min] CO2_B3708 CO2_B3508 Figure 16 Airflow rate supplied to the offices (21.03.2002 15:20) Table 1 Summary of the CO2 tests Test P st, P hx T exhaust, T return, a AHU V, a,b 3508 V V a,b3708 T B3508 T B3708 19

AHU AHU AHU 1 120 19.5 14 23.6 7395 209 149 25 25 2 400 52.6 14 22.8 12720 445 485 22 22 5.2.3. VAV aeraulic characteristics. In order to observe the opening of the VAV boxes, two tests were performed: test at constant fan frequency and test at constant exhaust static pressure. The airflow rate supplied for the AHU is determined using the heat exchangers pressure drop and the model identified previously. With this information and with the temperatures measured in the offices is possible to analyze the performance of the VAV boxes installed in the modules B and C of the building. In the first test the Modules B and C were heated with the radiators and with the air supplied by the AHU. The fan frequency was kept fix at 40 Hz. According to Figure 7 the supplied temperature increases from 14 C to 40 C and the room temperature from 21 C to 27 C. The opening of the VAV increases slightly and the supplied air flow rate increases only of 8 % in 2 hour. Airflow [m3/h] 22000 20000 18000 16000 14000 12000 10000 8000 16:48 19:12 21:36 Test period B3708 21/03/2002 0:00 21/03/2002 2:24 21/03/2002 4:48 53 50 47 44 41 38 35 32 29 26 23 20 17 14 11 21/03/2002 7:12 Temperature [ C] Time Airflow T_supplyB3708 T_roomB3708 T_returnB3708 Tthermostat Figure 17 VAV behavior 20

Figure 8 shows the evolution of the AHU airflow rate against the AHU return temperature for the period where the VAV was tested. It can be seen that the AHU return temperature continues increasing, while the AHU airflow rate increases. This indicates that the VAV boxes are not still fully open. As it can be seen in Figure 9 the pressure at the exhaust of the AHU decreases while the airflow rate increases. The same behavior is observed for the plenum pressure measured in the VAV boxes. 19000 18500 18000 Airflow rate [m³/h] 17500 17000 16500 16000 15500 15000 20 21 22 23 24 25 26 27 28 29 Treturn,AHU [ C] Figure 18 AHU airflow rate against AHU return temperature 1200 Test period 30 1000 25 Presion [Pa] 800 600 400 20 15 10 200 5 0 16:48 19:12 21:36 21/03/2002 0:00 21/03/2002 2:24 21/03/2002 4:48 0 21/03/2002 7:12 Time PplenumB3708 PplenumB3508 Pexhaust,AHU Treturn,AHU Figure 19 Evolution of the pressure and return AHU temperature during the test 21

6. OPPORTUNITIES FOR AUTOMIZATION Automatization of such a procedure for commissioning of a VAV system entirely relies on the possibility to measure and to control the individual operation of each box. In the case presented in this report, the VAV boxes are essentially self-regulating devices: remote measurement of the thermostat temperature, remote adjustment of the set point and remote control of the VAV opening are not possible. As a consequence, automization of the procedure using that kind of device is difficult. If it were the case, the global checking would be the easiest to carry out. 7. CONCLUSIONS AND PRACTICAL RECOMMENDATIONS The methods presented in this report allow carrying out the checking if VAV boxes, both at a global level and at an individual level. In the case study presented here, they allowed to check that, as whole, the behavior of the VAV system was satisfactorily, while they identified the devices that are likely non-operating. The main recommendations would be to start from a global approach (in conjunction with a parallel verification of the Air Handling Units) to detect problems. If this global approach points out deficiencies, the analysis should carry over to a more detailed analysis of selected individual devices. The global verification can take place during normal operation of the building (passive testing), while the individual verification requires the generation of artificial (and forced) conditions (active testing). 8. REFERENCES [1] CUEVAS, C; LACÔTE, P.; LEBRUN, J. Recommissioning of an Air Handling Unit, IEA Annex 40 working document, University of Liège, May 2002 22