ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.
|
|
|
- Curtis Caldwell
- 9 years ago
- Views:
Transcription
1 1 ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS. - EXPERIENCE FROM A PLANT RECONSTRUCTION BASED ON A NEW SUPPLY AIR TERMINAL DEVICE CONCEPT. MARI-LIIS MARIPUU* and LENNART JAGEMAR* * Building Services Engineering, Chalmers University of Technology, Gothenburg, Sweden. Contact [email protected] Summary In commercial buildings a CAV (constant air volume) system is normally used for ventilation and air-conditioning. In order to keep the room temperature in required level during the summer period quite high airflow rates and higher amounts of energy for heating and distribution of air are needed. By changing the system to VAV operation, considerable energy savings can be achieved. However, such a change becomes meaningful only if the system as a whole is adapted to the new way of operation. The critical components are the supply air terminal devices, which must have good controlling properties, a low noise level and provide a comfortable air flow and temperature pattern in the room within the variable volume flow range in question. The paper accounts for experiences from a reconstruction from CAV to VAV in a 5000 m about 40 year old office building. Investigations were carried out with new type of supply air devices, which were installed in this office building. Keywords: CAV, VAV, supply air terminal devices, intelligent diffuser, climate control, energy efficiency, ventilation 1. INTRODUCTION In commercial buildings the need of energy for ventilation and air conditioning may account for a substantial part of the need of energy. There is, at least in Sweden, a large existing stock of 0 to 30 year old office buildings, which are supplied with centralized constant air volume flow (CAV) air conditioning systems with the primary function to keep the room temperature at an acceptable level summertime. At times high air flow rates are needed to master the loads from solar radiation, electrical equipment and people. However, the heat loads are only occasionally at the peak level, which means that in a CAV system the air flow rate is unnecessarily high most of the time. The need of energy for distribution and heating of air becomes high, although the systems are usually provided with heat recovery and are in operation mainly during working hours. If the system I changed to a air volume flow VAV system, the average air volume flow will be lower and need of electrical energy for of air distribution and heat for supply air heating is reduced. With a decreased average air volume flow the average efficiency of heat recovery will be improved, which also contributes to a decreased need of supply air heating. One cause of high need of energy may be that the air outlet devices need a quite high supply air temperature if disturbing draft should be avoided. This is the case e.g. when displacement ventilation was installed in quite small rooms, which was a quite frequent in Sweden when existing offices were rebuilt in the early 90ies. For acceptable thermal comfort in these rooms a supply air temperature of at least +19 C is needed in practice. This implies poor cooling capacity of the air supplied and a quite high need of energy for supply air heating. If this type of air supply devices could be replaced with devices, which enable a low supply air temperature without causing draught problems, the need of heat for supply air conditioning will decrease. At the same time the cooling capacity of the supply air will increase and the prerequisites for room temperature control will improve. However, a change of an existing CAV system to VAV is somewhat complicated from both technical and economic point of view. It is a simple task to change from constant speed fans to variable speed fans. The necessary changes in the rest of the system may be both complicated and costly. Here the availability of supply air devices with appropriate properties is the critical issue. The outlet air device must have good variable air volume flow properties: Demand based control by room temperature, by room air quality or by a combination of these should be possible. A high pressure difference over the device, at least 100 Pa, must be possible to master without noise problems The air movement pattern in the room must be stable independent of the supply air flow rate It should be possible to supply air with a low temperature, +15 C or lower, without risk of disturbing draught The cost must be acceptable from a life cycle point of view The paper accounts for experiences from a change from CAV to VAV, based on a new supply air device that fulfils the above criteria. The change is carried through in a 5000 m about 40 year s old office building. The plant was retaken in operation in September 003 and is now monitored regarding the energy needs, the function of the new VAV and the indoor climate. The paper accounts for the ideas behind the system change and for preliminary results from the monitoring project.
2 . METHODS.1. Energy savings A variable air volume system changes the supply air flow rate according to the need of the supported room or zone. By decrease of the average air flow the need of electrical energy for air distribution will decrease. The power demand will vary with the ventilation flow according to the cube fan law [1, ]: VAV 3 VAV VVAV p tot VVAV k1v k1v P(kW) = = = (1) ηtot ηtot ηtot Where P is the power use measured as power input to the fan engine (kw), p tot the total pressure drop in the system (kpa), η tot the total efficiency of the fan system (%), k 1 a constant and V VAV is the mechanical ventilation flow in a VAV-system (m 3 /s). Power demand for central heating and cooling can be determined as follows when humidity is regarded []: Ph / c ( kw ) = VVAV ρc p T () Where P h/c is the power needed for central cooling or heating, V VAV is the mechanical ventilation flow in VAV-system (m 3 /s), ρ is the density of air (kg/m 3 ), c p is the specific heat capacity for air (kj/(kg K)), T is the temperature change of airflow (between inlet and outlet) (K). According to presented formula by a decrease of the average air flow rate the amount of heat needed for supply air heating and cooling is decreased. If the supply air temperature can be decreased, the need of heat supply air heating will decrease substantially as shown in fig. 1 Q additional MWh/year m 3 /s 15 Stockholm t ex +5 C Op 3000 h/year η T = η T = η T = Supply air temperature t sp, C Figure 1. The annual additional energy needed for supply air heating in an air supply unit with different heat recovery temperature efficiencies. Diagram responds to the location of Stockholm. The plant is in operation 3000 hours/year. Temperature efficiency is calculated according to the formula: t t t t η t = rec o (3) e o The temperature efficiency of the heat recovery will increase when the air flow through the heat recovery decreases. By a decreased average air flow the average heat recover will increase.. Problems A VAV system consists of different components such are central ventilation aggregate with supply and exhaust fans with variable frequency inverters for fan speed control, duct system, variable air volume devices (most commonly VAV boxes on the duct line are used) and room air distribution system. When designing a VAV system for a building it is necessary to
3 3 understand the importance of those different components. Most common problems associated with VAV systems are most often due to improper design of different components and/or control of the system [3]. The limitations that influence the selection of the VAV system components and also energy savings are due to the indoor climate quality requirements. VAV devices tend to be too noisy in the situations with a high static pressure drop across the device. Problems occur also with the use of improper diffusers, which may induce uncomfortable conditions for occupants [3]. The most common reason for thermal complaints in office buildings is draft [4] and higher velocities with lower temperatures increase the percentage of occupants objecting to drafts [5]. It is desired that the chilled supply air should be rapidly mixed with the air within the space. The mixed airstreams temperature should have reached the design room temperature and air velocity should have met the required level by the time that it enters the occupied zone. For office-type applications, where occupants are seated for much of the time, this is nominally defined as an envelope extending from floor level to a height of 1,m, and to within 0,15 m of any other room surface [6]. The reason why most of the usual supply air diffusers are unsuitable for VAV systems is that they are meant for working under constant air flow conditions. All the types of air terminal devices that are used to supply air produce a discharge pattern in the form of a jet. After entering room the mixing between room air and supply air takes place. Supply air diffusers typically turn the air stream received from the supply air duct through 90 and discharge it horizontally across the ceiling. The natural tendency of a fluid in motion to cling to an adjacent solid surface is called the Coanda effect. It is defined as a apparent of a negative pressure or suction which pulls each layer of a air in the jet towards the ceiling. Since the chilled air is naturally denser it tends to cause the supply air stream to fall away from the ceiling towards occupied zone (negative buoyancy force). If the strength of the Coanda effect is weaker than the negative buoyancy force the supply air jet will dump or fall away from the ceiling and cause discomfort in the occupied zone. This tends to happen when the air flow rate supplied by the diffuser reduces till the certain point. According to the research and evaluations made this may occur at the supply velocities below 1,5 m s -1 [6]. In order to have the required thermal comfort in the room with the VAV system the chosen supply air diffuser must maintain the velocity of the supply air stream from the diffuser with the decreasing supply air flow rates. It means that the device must handle the pressure differences in different working situations. In order to save energy with the VAV system the supply air temperature must be quite low to handle the heat surplus with less amount of air flow rate. This is however limited parameter in most of the supply air devices due to the occurrence of dumping. The aim of this paper is to introduce the investigations that have been made with the new type of VAV supply air diffuser, which allows supplying the air into room with low temperature (around +15 C) without causing any thermal comfort problems. This diffuser also meets the noise requirements in different air flow rate conditions. The working principle of this diffuser is following. Diffuser varies the airflow rate according to the demand of the room, which is expressed by the room temperature. They contain advanced control- and regulating equipment. Sensors for measuring room temperature, supply air temperature and air flow rate and also presence sensor are built in to the device. If temperature raises above the set point the motor inside starts to open the distance between the lamella plates and gives more air flow in order to keep the room temperature in required level. In the minimum air flow rate the lamellas are nearly closed. Every supply air device can be programmed for two low air flow rates and maximum air flow rate. Programming can be handled by using palm-computer. A schematic picture of this diffuser is given in figure. Motor Supply duct connection V (l/s), t sp, v(m/s) Supply air jet discharge horizontally across ceiling Lamella plates Computer & sensors Fig.. VAV supply air diffuser.3 Investigated building This new type of VAV supply air diffuser has been tested in several different houses. This report describes the investigations that were carried out in the old building, where reconstructions were made two years ago. During these reconstructions the ventilation system was also changed from CAV (Constant air volume) to VAV system. Investigated building is a university building in Chalmers in Gothenburg, which was built in 1950-ies. In 003 reconstructions were made in one part of the building which consists of 5000 m office area (5 floors). An air handling
4 4 system was also rebuilt, except that more than 10 years old air handling unit and duct system was kept the same. Maximum air flow rate of this unit is 5, 6 m 3 /s. The main idea of renewing this old system was to make it from constant air volume system (CAV) to variable air volume system (VAV) in order to save expenses for the energy. Ordinary supply air devices were changed to the new type of variable air volume diffusers (Lindinvent) described above. Variable frequency inverters for fan speed control were installed to both supply and exhaust air fans in order to maintain a specific static pressure in the main duct near the air handling unit. Besides that a cooling coil was installed to the unit for cooling down the supply air during summertime. Cooling coil was connected to the local university cold water system. Supply and exhaust air flow rates in different floors are balanced by measuring respective air flow rate in the two main supply air branches and exhaust air branch on each floor and regulating the flow rates through the damper on the exhaust air brunch. Air handling system is working during normal working hours. The supply air temperature from the central unit is ca C. Because the air distribution ducts are not insulated the supply air temperature rises some degrees in the duct system. During the night time the ventilation system is switched off or running under minimum air flow rates. Air handling system has also a night cooling. When room temperature gets higher than +1 C and outdoor temperature decreases below +17 C, all the supply air devices will get a signal for full opening and central unit starts. After the room temperature gets lower than +3 C or if the outdoor temperature gets higher than +17 C the ventilation unit stops. 3. RESULTS 3.1 The Results of the energy consumption Investigated ventilation system has a rotating wheel type heat exchanger with a temperature efficiency ca 80 % at a maximum air flow rate. In VAV system a lower air flow rate will increase the temperature efficiency. In order to save energy for operating fans, variable frequency inverters for fan speed control were installed to both supply and exhaust air fans. Specific static pressure is maintained in the main duct after the ventilation unit. After reconstructions a cooling coil was installed to the ventilation unit. The main reason for this was to improve the temperature control in rooms. The supply air temperature in this system was +18 C and the cooling effect was certainly not enough to deal with the heat surplus in the rooms. Installing a cooling coil to the system gives an additional need of energy. Table 1 gives the comparison of the air handling system parameters before and after the reconstructions. Table 1. Comparison of the air handling system before and after the reconstructions. Temperature efficiency and specific fan power of the VAV system are given as an average over the year. *- to compare two different systems and different indoor climates, the annual cooling energy for CAV system was calculated, although there was no cooling before. System parameter Before rebuilding After rebuilding CAV system VAV system Heat recovery -temperature efficiency 75% av 78% Maximum air flow rate 6,5 m 3 /s 5,6 m 3 /s Operation time 3500 h/year 3500 h/year Supply air temperature 18 C 15 C Exhaust air temperature 1 C 1 C Outdoor climate Göteborg Göteborg Specific fan power- SFP,5 kw/m 3 /s av1, kw/m 3 /s Necessary annual heat energy 1,5 MWh heat 0 MWh heat Necessary annual electric energy 57 MWh el 1 MWh el Necessary annual cooling energy 44,0 MWh cooling * 56,7 MWh cooling 4.3 Measurements of the thermal climate Measurements of the thermal comfort and noise were made in different office rooms each floor. Rooms were selected on the basis of having at least one room each floor and also some rooms with two supply air devices in the same room. Selected rooms were typical office rooms. Figure 4 shows a typical room and the location of the measuring instrument.
5 3,6 m 5 t a, v a, t PRT V, t sp 5,0 m Fig. 4. Typical room and the location of the measuring instrument (location marked with X) Thermal comfort measurements were made in the conditions where the diffusers were working with maximum air flow rate (40 l/s) and with the minimum supply air temperature, since these are the conditions that may cause the sensation of draught. To measure the diffusers work in conditions, in some measured rooms the diffusers were forced to open in maximum mode by changing the set point of the room with the palm-computer. All the rooms had a set point +3 C. Measurement instrument Brüel & Kjaer Model 113 Thermal Climate Analyzer was used for this project. This instrument allows to measure following parameters: room temperature, plane radiant temperature in two opposite directions, air velocity, standard deviation of air velocity, air humidity. These indoor climate parameters were measured during ca 10 minutes time after simulating the diffuser for the maximum mode. Transducers were placed at the level of sitting person s head (1,1m above the floor) near the working place (See fig. 4). To avoid difficult and time consuming measurements for calculating mean radiant temperature, measurement was taken with plane radiant temperature sensor in two opposite surfaces, where one was the window direction in every measured room. Assumption was made that other surfaces temperatures in the room do not differ from the measured ones. Table below describes measurement results in different rooms. The values are given as an average over the measurement period (ca 10 minutes). Table. Thermal comfort parameters in measured rooms. Air temperatures are given as an average over the measurement period. Average air velocity and SD are given as an average over the 3 minutes before last measured minute. Diffusers were working with the maximum mode with supply air rate 40 l/s. Room Supply air Room Air Standard nr. temp. temp. velocity, deviation of air t sp, C t a, C v a, m/s velocity m/s, SD 1 14,7,7 0,1 0,04 15,0 3,4 0,08 0, ,7 1,4 0,0 0, ,6,6 0,10 0, , 3,5 0,10 0,03 For evaluating the draught rating it can be calculated by using following Eq. () [7]: DR=(34-t a )(v a -0,05) 0,6 (0,37 v a Tu+3,14) [%] (4) where Tu is turbulence intensity and expressed in Eq. (3) SD Tu = [%] (5) va In these formulas v a, local mean air velocity, is calculated as an average air velocity during 3 minutes before last measured minute, because during the last minute a lot of air movement was due to the people entering the room.
6 Figure 5 below expresses the draught rating in measured rooms DR, % measured room nr Fig. 5. Draught rating in measured rooms. Calculated according to eq.. According to thermal comfort standard [7], the draught rating DR, should not exceed 15% based on the model of draught for 15 % dissatisfied due to draught. According to the measurement results the DR values did not exceed 10% value in the conditions were supply air flow rate was maximum and supply temperature minimum. This gives the conclusion that investigated new type of variable air volume diffusers can be used with lower supply air temperatures. 4.4 Measurements of the Sound In order to investigate the sound pressure level generated by VAV device sound measurements in the rooms were carried out. Measurements were made during the full operation of the diffusers (with the maximum airflow rate 40 l/s). Measurement time was ca 10 minutes starting from the device simulation. Measurement instrument Brüel & Kjaer type 60, application BZ706 version.1 was used. Sound pressure levels were measured in different frequencies on one third of the octave band. Problems with the background noise occurred during the measurement time. To evaluate just the sound generated by the VAV device, an assumption was made that it can not exceed the minimum measured sound pressure level in the room. Also to avoid possible influence from the central ventilation unit rooms in the lower floor have only taken in to account. Measurements were made in two rooms in the lower floor and in both rooms the minimum sound pressure level was between 6 db(a) and 7 db(a). The diffusers producing company has made their own laboratory measurements about the sound levels produced by their VAV device. Noise level with different airflow rates and pressure drops dependent on the slot opening is given in figure 8. Pressure drop over device [Pa] db(a) Air flow rate [l/s] 30 db(a) 1,50 mm/slot 1,9 mm/slot Fig. 8. Laboratory measurements. Noise level with different airflow rates and pressure drops dependent on the slot opening. According to these laboratory measurements noise from the diffuser should not exceed 5 db(a) if the airflow rate is around 40 l/s. 4.5 Flow control properties Every supply air device is programmed for two low air flow rates and maximum air flow rate. If the room is empty and the room temperature is under +3 C, the supply air device is working with the minimum air flow rate 5 l/s. When somebody is in the room the air flow rate increases to 10 l/s. If the room temperature increases over +3 C increases the airflow rate from the diffuser to the maximum 40 l/s in order to keep the room temperature under the desired level. 4.6 General function
7 Air handling system of this test house is working during normal working hours. The office rooms in this building are quite small (ca 18 m ) and usually during working hours there is always some extra heat surplus due to office equipment and people in the room that exceeds the heat transmission of the room. The supply air temperature is therefore kept quite low ( ) all year around. If the heat surplus of the room is low or there is no heat surplus in the moment at all, the supply air devices work under the minimum air flow rate and the radiator system compensates the cooling effect of the supply air. The supply air diffusers in the rooms are functioning in the way that according to the measurements made, the low supply air temperature is not affecting the thermal comfort of the room occupants. This fact gives big advantage towards energy saving. Conclusions A lot of investigations have been made to prove that VAV (variable air volume) system is one of the most energy efficient ways for building air-handling system. Since there is still a problem with the high cost of this system, the possible effort of it should be maximized. While designing a VAV system for a building it is necessary to understand that different parts of this system have a significant role for the total functioning of it. Also costs of the different parts vary a lot. Installing variable frequency inverters for the fan speed control for both supply and exhaust air fans is one of the simplest and probably cheapest part of the total VAV system. Building air distribution parts however demand much bigger investments and they also play a significant role in the total functioning of the whole ventilation system. Therefore they must fulfil certain requirements. Providing good indoor climate with less use of energy is part of it. In this article a concept of energy savings and improving indoor climate was presented. VAV system with low supply air temperatures gives a big amount of energy savings. This was proven by the investigations and tests made in the reconstructed old building. Lower supply air temperatures also require diffusers that will maintain required indoor climate. The main problems that occur with VAV devices are noise and unsatisfied thermal comfort. Measurements that were made in our test house showed that these new type of supply air diffusers provide good climate control. They work quietly and do not cause any problems with the thermal comfort in the rooms even with low supply air temperatures. 7 Nomenclature η t temperature efficiency t rec supply air temperature after the recovery heat exchanger ( C) t o outdoor temperature ( C) t e exhaust air temperature ( C) V d air flow rate from the diffuser (l/s) h diffusers opening (%) t a,dif average room temperature according to the diffusers data ( C) t sp supply air temperature from the diffuser ( C) t a average room temperature t PRT average plane radiant temperature v a average air velocity in the measured zone (m/s) φ relative humidity, RH % DR draught rate in the measured zone (%) Tu Turbulence intensity in the measured zone L peq equivalent sound pressure level (db) L Smax maximum sound pressure level with slow time weighting (db) L Smin minimum sound pressure level with slow time weighting (db) L paeq A weighted equivalent sound pressure level (db(a)) C weighted equivalent sound pressure level (db(c)) L pceq References 1. American Society of Heating, R.a.A.-C.E.I., ASHRAE Handbook: HVAC Systems and Equipment M. Mysen, I.P.R., P.O. Tjelflaat, Demand controlled ventilation for office cubicles- can it be profitable? Energy and Buildings, : p Robert Linder, C.B.D., P.E., VAV Systems Work Despite Some Design and Application Problems. ASHARE Transactions, (p): p Achieving the Desired Indoor Climate. Energy Efficiency Aspects of System Design, ed. P.-E. Nilsson American Society of Heating, R.a.A.-C.E.I., ASHARE Handbook, Fundamentals (Chapter 31.6). 6. Shepherd, K., VAV Air Conditioning Systems, ed. B.S. Ltd ISO7730, Moderate Thermal Environments- Determination pf the PMV and PPD indices and specification of the conditions for thermal comfort
CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
Air Conditioning in Green Office Buildings?
Air Conditioning in Green Office Buildings? How to implement Demand Controlled Ventilation Stuttgart Rechte allein bei ICEBO 08 10.10.2008 CI / DrRo 1 Air Conditioning in Green Office Buildings ventilation
Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
Mistrale. Fusion Terminal
Mistrale Fusion Terminal PUBLICATION NATURAL VENT. 1 SEPT 2015 Features - Slimline energy efficient ventilation solution - Standard and high capacity terminals provide 128 or 256 L/s capacity - Compliant
How To Design A Room Air Conditioning System
Comparison of HVAC Technology in Buildings Conventional HVAC Technology Bauer Optimising Technology The Differences Room environment (Occupant Comfort) Energy Consumption Architecture Air flows in a room
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Energy Efficient HVAC-system and Building Design
Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: [email protected] SUMMARY This paper
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Displacement ventilation
General The displacement ventilation principle is the oldest form of ventilation and can be achieved without the use of fans. Air movement occurs by means of the density differences between supply air
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
Dual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How
DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple
CHAPTER SEVEN L. Glicksman and J. Lin (eds), Sustainable Urban Housing in China, 116-123 2006 Springer. Printed in the Netherlands. DESIGN OF NATURAL VENTILATION WITH CFD Qingyan Chen INTRODUCTION As the
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
AIR DISTRIBUTION FOR COMFORT AND IAQ
AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
plenum slot diffusers
light powered Redefine your comfort zone. www.titus-hvac.com dual-function smart logic light powered energy solutions Table of Contents PLENUM SLOT IFFUSERS products Plenum Slot iffusers Products... 4
MULTIZONE APPLICATION OF SOLUTION UNITS
MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Panu Mustakallio and Risto Kosonen Halton Oy, Haltonintie 1-3, 47400 Kausala, Finland E-mail: [email protected]
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
Performance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation
Performance Estimation of Water Thermal Energy Storage Tank by Using Simplified Simulation M. Kubota, K. Sagara, T. Yamanaka, H. Kotani Division of Global Architecture, Graduate School of Engineering,
Mechanical and Natural Ventilation
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.
SECTION EG Air Distribution Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. Space Air Diffusion AIR DISTRIBUTION ENGINEERING GUIDE Proper selection of air diffusion
Under sill units. Type FSL-B-ZAS
.1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering
Challenges and Failures in Green Building Design Using Under-Floor Air Distribution Ken Urbanek, PE, HBDP, LEED AP Director of Engineering Agenda UFAD Overview Challenges / Failures Steps for a Successful
How To Get A Passive House
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product
Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer
Fundamentals of Acoustics & Practical HVAC Design Considerations Demir Doken Acoustic Engineer What is sound? Sound is a mechanical wave that is an oscillation of pressure transmitted through some medium
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Comparing Energy Savings of Different VAV Systems
Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd [email protected] EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March
HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
Building Performance With District Cooling
Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint
HDA -----------------------------------------------------------
----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS
Flexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
SAM HOUSTON STATE UNIVERSITY
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
FAQ' s. Frequently Asked Questions. A1 Control Units. Pge 1 of 7 PUMPKIN HOOK ROAD PO BOX OGD VAN HORNESVILLE NY 13475 USA 315-858-1002
Frequently Asked Questions FAQ' s A1 Control Units Pge 1 of 7 Table of Contents Q-1 Who are OGD and V-HVAC? 3 Q-2 Why do I need the A1 Control Unit and what are the benefits? 3 Q-3 How is the A1 Control
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation
Element D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2
CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2 Eddy Rusly 1 and Mirek Piechowski 2 1,2 Meinhardt (VIC), Melbourne, Australia ABSTRACT
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of
CASE STUDY: NEW NCAA DIV. I COLLEGE BASKETBALL ARENA
CASE STUDY: NEW NCAA DIV. I COLLEGE BASKETBALL ARENA Stephen W. Duda, PE LEED AP Director, Mech Engineering Ross & Baruzzini, Inc. [email protected] Acknowledgements: Ellerbe Becket, Architects, Kansas
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015
EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW
Installation, operation and maintenance manual TX 35A
Installation, operation and maintenance manual TX 35A Rev.10 may 2012 Page 1 of 18 1.0.0 Table of contents INSTALLATION, OPERATION AND MAINTENANCE MANUAL...1 1.0.0 TABLE OF CONTENTS...2 2.0.0 ILLUSTRATIONS...2
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Kan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13
Kan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13 1 Kan behovsstyrt ventilasjon erstatte lokal varme? Principles Challenges VABAT Project 2 Principles Increased envelope
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
RE-COMMISSIONING OF VAV BOXES
RE-COMMISSIONING OF VAV BOXES Authors: Cristian CUEVAS, Jean LEBRUN (ULg) Patrick LACOTE, Philippe ANDRE (FUL) September 2002 1 Table of contents Nomenclature...3 1. INTRODUCTION...4 2. DESCRIPTION OF
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents
Fläkt Woods Building Future
Energy, Expertise and Environment with Fläkt Woods Fläkt Woods Building Future Saving energy in building ventilation You must save 20% on energy before 2020. Following the Kyoto protocol the European Union
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
Performance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Halton - Achieving Energy Efficiency in School Design
Halton - Achieving Energy Efficiency in School Design Enabling Wellbeing Halton Design Tools Drive Energy Efficient Kitchen Ventilation and Comfort Today, nutritional guidelines for school foodservice
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs Fan Performance (Paper I.D. 021) Mark Stevens Air Movement and Control Association International Abstract
CEN/TC 156. pren 15251. Date: 2006-07-31 CEN/TC 156. Secretariat: BSI ICS: Descriptors:
CEN/TC 156 Date: 2006-07-31 pren 15251 CEN/TC 156 Secretariat: BSI Indoor environmental input parameters for design and assessment of energy performance of buildingsaddressing indoor air quality, thermal
Noise in the Classroom
ASHRAE JOURNAL Copyright 2000, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission of ASHRAE Journal. This article may not be copied nor distributed
Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice
Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice A truly international certification The Eurovent Certification Programmes are managed by an autonomous
Building HVAC Load Profiling Using EnergyPlus
Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: [email protected] Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological
Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects
Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony
VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING
VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEFINITION OF VENTILATIVE COOLING VENTILATIVE COOLING IS APPLICATION (DISTRIBUTION IN TIME AND SPACE) OF VENTILATION AIR FLOW TO REDUCE COOLING LOADS IN
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Mechanical Systems Proposal revised
Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
AN APPLICATION MANUAL FOR BUILDING ENERGY AND ENVIRONMENTAL MODELLING
AN APPLICATION MANUAL FOR BUILDING ENERGY AND ENVIRONMENTAL MODELLING D. Bartholomew *, J. Hand #, S. Irving &, K. Lomas %, L. McElroy # F. Parand $, D. Robinson $ and P. Strachan # * DBA, # University
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances
Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL
CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER
International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)
Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov. 2003 to Mar. 15, 2004.
Proceedings World Geothermal Congress 2005 Antalya, Turkey, 24-29 April 2005 A Case Study of Ground Source Heat Pump System in China Jun Zhao, Chuanshan Dai, Xinguo Li, Qiang Zhu and Lixin Li College of
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
How To Control Humidity With A Humidifier
Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2
Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
Heating, ventilation and air conditioning zone controls
Technology information leaflet ECA762 Heating, ventilation and air conditioning zone controls A guide to equipment eligible for Enhanced Capital Allowances Contents Introduction 01 Background 01 Setting
AIR DISTRIBUTION ENGINEERING
AIR DISTRIBUTION ENGINEERING a1 a1-1 a1 Table of Contents Terms & Definitions...a1-...a1-3 Primary Jet...a1-3 Entrainment, Jet Interface, Primary Air, & Total Air...a1-4 Natural Convection Currents...a1-5
We have been working in an ideal climate for thirty years.
Underfloor cooling We have been working in an ideal climate for thirty years. A climate that has brought us to a position of leadership in Italy in the field of radiant heating and cooling. RDZ was the