Compact NSX Wiring diagrams Contents Functions and characteristics A-1 nstallation recommendations B-1 Dimensions and connection C-1 Compact NSX100 to 630 Fixed circuit breakers D-2 Plug-in / withdrawable circuit breakers D-4 Motor mechanism D-6 SDx module with Micrologic D-8 SDTAM module with Micrologic M D-9 Additional characteristics E-1 Catalogue numbers F-1 Glossary G-1 559E4000.indd version: 1.0 D-1
+ - + - Wiring diagrams Compact NSX100 to 630 Fixed circuit breakers Power Micrologic Remote operation Upstream CB DB115707 3P or 4P N L2 L3 BPO BPF H L D2 C2 MN MX ou U D1 C1 3P + N N L2 L3 Downstream CB Motor mechanism (MT) a (220/240 V) HL BSCM U EN ENCT H2 H1 Communicating motor mechanism (MTc) a Micrologic A or E A/E Communication H(), L(BL): data - (), + (): 24 V DC power supply A/E ZS (Zone Selective nterlocking) : ZS OUT SOURCE : ZS OUT : ZS N SOURCE : ZS N ST (short time) : ZS N GF (ground fault) Note:,, for NSX400/630 only. A/E E ENCT: external neutral current transformer: - shielded cable with 1 twisted pair (, ) - shielding earthed at one end only (CT end). Connection L = 30 cm max. - maximum length of 10 metres - cable size 0.4 to 1.5 mm 2 - recommended cable: Belden 41 or equivalent. EN: external neutral voltage tap for connection to the neutral via a 3P circuit breaker. Remote operation MN: undervoltage release or MX: shunt release Motor mechanism (MT) : opening order : closing order, : power supply to motor mechanism : al position () : interlocking (mandatory for correct operation) BPO: BPF: opening pushbutton closing pushbutton Communicating motor mechanism (MTc), : motor mechanism power supply BSCM: breaker status and control module D-2 version: 2.0 559E4100.indd
ndication contacts DB115708 Closed Closed OF4 41 42 44 OF3 31 21 32 34 22 24 OF2 OF1 11 12 14 SD 91 92 94 CAF2 CAF1 131 121 101 134 124 102 104 CAO1 SDV 71 72 74 Terminals shown in red O must be connected by the customer. ndication contacts OF2 / OF1: device ON/OFF indication contacts OF4 / OF3: device ON/OFF indication contacts (NSX400/630) : fault-trip indication contact (short-circuit, overload, ground fault, earth leakage) SD: trip-indication contact CAF2/CAF1: early-make contact (rotary handle only) CAO1: early-break contact (rotary handle only) SDV: earth leakage fault trip indication contact (add-on Vigi module) Colour code for auxiliary wiring : red : violet : white : grey : yellow OR: orange : black BL: blue : green 559E4100.indd version: 2.0 D-3
+ - Wiring diagrams Compact NSX100 to 630 Plug-in / withdrawable circuit breakers Power Micrologic Remote operation Upstream CB DB115709 3P or 4P N L2 L3 BPO BPF BL - + L H 24/34 22/32 D2 BL C2 OR OR BL D2 C2 MN MX or D1 C1 D1/C1 3P + N N L2 L3 HL a (220/240 V) 41 42 44 U Motor mechanism (MT) Downstream BSCM U EN ENCT H2 OR H1 a Communicating motor mechanism (MTc) D-4 version: 2.0 559E4100.indd
ndication contacts Carriage switches DB115710 Closed Closed Connected Disconnected OF4 41 42 44 OF3 31 21 32 34 22 24 OF2 OF1 11 12 14 SD 91 121 92 94 CAF2 CAF1 131 101 134 124 102 104 314 312 352 354 CAO1 SDV CE CD 41 31 21 11 91 71 71 311 351 72 74 42 44 32 34 22 24 12 14 92 94 72 74 Micrologic A or E A/E Communication H(), L(BL): data - (), + (): 24 V DC power supply A/E ZS (Zone Selective nterlocking) : ZS OUT SOURCE : ZS OUT : ZS N SOURCE : ZS N ST (short time) : ZS N GF (ground fault) A/E E Note:,, for NSX400/630 only. ENCT: external neutral current transformer: - shielded cable with 1 twisted pair (, ) - shielding earthed at one end only (CT end). Connection L = 30 cm max. - maximum length of 10 metres - cable size 0.4 to 1.5 mm 2 - recommended cable: Belden 41 or equivalent. EN: external neutral voltage tap for connection to the neutral via a 3P circuit breaker. Colour code for auxiliary wiring : red : violet : white : grey : yellow OR: orange : black BL: blue : green Terminals shown in red v / O must be connected by the customer. Remote operation MN: undervoltage release or MX: shunt release Motor mechanism (MT) : opening order : closing order, : motor mechanism power supply : al position () : interlocking (mandatory for matic or remote recharging) BPO: opening pushbutton BPF: closing pushbutton Communicating motor mechanism (MTc), : motor mechanism power supply BSCM: breaker status and control module ndication contacts OF2 / OF1: device ON/OFF indication contacts OF4 / OF3: device ON/OFF indication contacts (NSX400/630) : fault-trip indication contact (short-circuit, overload, ground fault, earth leakage) SD: trip-indication contact CAF2/CAF1: early-make contact (rotary handle only) CAO1: early-break contact (rotary handle only) SDV: earth leakage fault trip indication contact (add-on Vigi module) 559E4100.indd version: 2.0 D-5
Wiring diagrams Compact NSX100 to 630 Motor mechanism DB114666 Motor mechanism (MT) with matic reset After tripping initiated by the "Push to trip" button or by the undervoltage (MN) release or the shunt (MX) release, device reset can be matic, remote or al. BPO BPF Following tripping due to an electrical fault (with an contact), reset must be carried out ally. Motor mechanism (MT) with remote reset DB114667 BPO BPF Reset Motor mechanism (MT) with al reset DB114668 BPO BPF Symbols : circuit breaker : opening order : closing order, : motor mechanism power supply : al position () : interlocking (mandatory for correct operation) BPO: opening pushbutton BPF: closing pushbutton : fault-trip indication contact (short-circuit, overload, ground fault, earth leakage) D-6 version: 2.0 559E4100.indd
+ - Communicating motor mechanism (MTc) DB114669 H L BSCM a (220/240 V) a Schematic representation of the communicating motor mechanism (MT). DB115436 DB114670 RSU screen for the communicating motor mechanism (MTc) RSU utility setup screen for the communicating motor mechanism. 220 VAC Auto Manu command OF SD Close command OF Enable matic reset SD Enable reset even if Reset command motor Close motor Reset motor Single-line diagram of communicating motor mechanism ing, closing and reset orders are transmitted via the communication network. The "Enable matic reset" and "Enable reset even if " parameters must be set using the RSU software via the screen by clicking the blue text. "Auto/" is a switch on the front of the motor mechanism. Symbols : circuit breaker, : motor mechanism power supply BSCM: breaker status and control module Terminals shown in red O must be connected by the customer. 559E4100.indd version: 2.0 D-7
Wiring diagrams Compact NSX100 to 630 SDx module with Micrologic Symbols SD1, SD3: SD2: SD4: SDx-module power supply output 1 (80 ma max.) output 2 (80 ma max.) DB115711 Connection a (+) 24 à 415 V SDx SD3 STD or output 1 SD2 PAL r or SDG or output 2 SD4 SD2 SD4 Micrologic 2 SDT - Micrologic 5 SDT or output 1 PAL r or output 2 Micrologic 6 SDT or output 1 SDG or output 2 SD1 Terminals shown in red O must be connected by the customer. a (-) Operation DB115712 > 105 % r tr at 6 r > 90 % r PAL r SDG SDT Circuit breaker trip order Circuit breaker reset : charge current PAL r: thermal overload pre-alarm SDG: ground-fault signal SDT: thermal-fault signal : circuit breaker D-8 version: 2.0 559E4100.indd
SDTAM module with Micrologic M Symbols SD1, SD3: SD2: SD4: SDTAM-module power supply thermal-fault signal output (80 ma max.) contactor-control output (80 ma max.) SD2 SD4 Micrologic 2-M SDT K Micrologic 6 E-M SDT K DB115713 Connection KM1 a (+) 24 to 415 V Manual reset SDT K SD3 SDTAM 6 8 4 10 2 12 1 14 OFF 15 Auto reset (minutes) SD2 SD4 SD1 Closing order ing order K KM1 KM1 Terminals shown in red O must be connected by the customer. a (-) Operation DB115714 > 95 % T < 95 % T Class (tr) at 7.2 r 400 ms SDT K KM1 %T 400 ms before circuit-breaker tripping order Contactor closing order %T Manual or matic reset : charge current SDT: thermal-fault signal K: auxiliary relay (e.g. RBN or RTBT relay) KM1: motor contactor : circuit breaker 559E4100.indd version: 2.0 D-9