Interference in the ECG and its elimination



Similar documents
LUCCI AIRFUSION QUEST II CEILING FAN

Users Manual FA106 / FA306 version 1.0. Field Analyzer. FA106 and FA306. Users Manual

Electric Field Mapping Lab 3. Precautions

The Control of ph and Oxidation Reduction Potential (ORP) in Cooling Tower Applications By Charles T. Johnson, Walchem Corporation

TROUBLESHOOTING RECEIVERS

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE

A Versatile Audio Amplifier

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

Variety of Control Options Control is possible via wall switches, remote control systems or integration into building management systems.

MODEL 2202IQ (1991-MSRP $549.00)

Grounding Demystified

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.

NUCLEAR MAGNETIC RESONANCE. Advanced Laboratory, Physics 407, University of Wisconsin Madison, Wisconsin 53706

1. The diagram below represents magnetic lines of force within a region of space.

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

Current Probes. User Manual

HERZ-Thermal Actuators

3 IN 1 BATHROOM HEATER

Amplifier for Small Magnetic and Electric Wideband Receiving Antennas (model AAA-1B)

Section B: Electricity

BXR 300C BXR 300R. Owner, s Manual P/N

Technical Note Series

Rated Power(W) 8W 2. EG-LED W 3. EG-LED W

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

CX Zoner Installation & User Guide

Measuring Insulation Resistance of Capacitors

THE KW107 SUPERMATCH ATU manual, courtesy of Barry G0DWZ

Video Camera Installation Guide

Achat 115MA full-range speaker. user manual

289 SERIES FLOW METER TRANSMITTERS

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

ECEN 1400, Introduction to Analog and Digital Electronics

ElectroMagnetic Induction. AP Physics B

Introduction. Harmonics and IEEE 519 Page 1 of 19

Unit 24: Applications of Pneumatics and Hydraulics

VOLTAGE REGULATOR AND PARALLEL OPERATION

2. Remove rear cover of head lamp if bulbs are covered/sealed within the housings, and remove halogen bulb carefully.

1 Safety instructions. 2 Device components. 3 Function. Leader in Led solutions. Compact presence detector. Operating instructions

APPLICATION NOTE ULTRASONIC CERAMIC TRANSDUCERS

Troubleshooting accelerometer installations

Chapter 13: Electric Circuits

Rousseau 10. User Guide

Adding Heart to Your Technology

DIGITAL-TO-ANALOGUE AND ANALOGUE-TO-DIGITAL CONVERSION

Digital Active Indoor Antenna SRT ANT 10 ECO

ORIGINAL PROTOSOUND (PS1) TROUBLESHOOTING

Operating instructions IV / 2007

WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON.

AMPLIFIED HIGH SPEED FIBER PHOTODETECTOR USER S GUIDE

162 CB CABLE TRACER. Filter Probe & Tone Generator INSTRUCTION MANUAL

HID H4 BI-XENON FITTING GUIDE. Carefully read the following notes before starting work.

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Single-Phase AC Synchronous Generator

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2

DATA SHEET. TDA1510AQ 24 W BTL or 2 x 12 W stereo car radio power amplifier INTEGRATED CIRCUITS

Odyssey of the Mind Technology Fair. Simple Electronics

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Balanced vs. Unbalanced Audio Interconnections

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE

Lab E1: Introduction to Circuits

How To Read A Pipe From A Sensor

SELECTION, APPLICATION AND MAINTENANCE

S/PDIF D/A Converter. User Manual. Rev.B, December 2011 Audial d.o.o Belgrade, Serbia

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Air conditioning, electrical testing

The electrical energy produced at the gen

PART 1 - INTRODUCTION...

Electrical Fundamentals Module 3: Parallel Circuits

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Hands On ECG. Sean Hubber and Crystal Lu

Installation and instruction manual for Laing DDC pumps

Lecture 24. Inductance and Switching Power Supplies (how your solar charger voltage converter works)

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER

Using an Oscilloscope

Power Supply Unit (PSU)

Single Channel Loop Detector

Owner s Manual channel amplifier

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

Electrical Resonance

LiteAide OWNER'S MANUAL PREASSEMBLED AUTOMATIC SECURITY FLOODLIGHTS MOTION SENSOR SECURITY LIGHTING SYSTEMS

High Voltage Power Supplies for Analytical Instrumentation

This paper will explain some of the more important factors on how UTP wires work; specifically it will cover the following:

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin

BeoLab 1. User s guide

Control Box Wiring For PRSstandard Tool

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

Q1. The graph below shows how a sinusoidal alternating voltage varies with time when connected across a resistor, R.

Outer Diameter 23 φ mm Face side Dimension 20.1 φ mm. Baffle Opening. Normal 0.5 Watts Maximum 1.0 Watts Sine Wave.

OWNER S MANUAL. Permolock C3. Docking system for Power wheelchair in vehicle

Manual Ranging MultiMeter

Single Transistor FM Transmitter Design

Amplified High Speed Fiber Photodetectors

An equivalent circuit of a loop antenna.

SEISMIC VELOCITY TRANSDUCER T1-40

Name Class Date Laboratory Investigation 4B Chapter 4: Cell Structure

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series

METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS

Transcription:

Interference in the ECG and its elimination General points The signal voltages in ECG recording are known to be very small and are in the millivolt range, i.e. they have amplitudes of only a few thousands of a volt. The R wave is the curve segment with the greatest amplitude, i.e. approx. 0.5 4 mv depending on the lead. However, segments with considerably smaller voltages, sometimes within the range of 0.1 0.5 mv, are of greater diagnostic value. If we consider the ratios to all noise fields, we can see that the ratio of the mains voltage (230 V) to the ECG wanted signals is 230 V / 0.1 mv = 2.3 million: 1. This figure cannot be imagined. It would be like trying to find a thick hair measuring 0.1 mm in diameter in a car park 230 meters wide. Only when such parallels are drawn does it become clear just what demands are made on ECG equipment. Fortunately, modern circuiting techniques enable these extremely low voltages to be relatively effortlessly processed. However, the human as the source of ECG voltages also acts as an antenna for most varied of noise fields. The aim of this paper is to describe the types of interference which occur. Their causes will be detailed and advice given how to eliminate them. Types of interference The interference which occurs may be divided into five categories: - AC interference caused by other types of interference - AC interference due to earth circuit or incorrect earthing - AC interference due to potential differences - Shaking - Zero line fluctuations AC interference AC interference is interference which arises from superpositioning of the ECG wanted signal with sinusoidal voltages with the mains frequency. It may be recognised by its constant frequency of 50 Hz or 60 Hz depending on the country. Sometimes it can also be 16 2/3 Hz as this is the frequency used by trains. This constant frequency is often only recognised when the ECG recorder has a high rate of paper feed (100 mm/s). In this case, a full wave is approx. 2 mm at 50/60 Hz approx. 6 mm at 16 2/3 Hz clean ECG ECG superimposed with AC e-mail info@riemermed.de Postfach 1173 Seite 1 von 5

AC interference caused by other types of interference AC interference arises from interference of the mains frequency on the test people, on the electrodes and on the patient cable. Electrode hoses and patient cables normally have such a good shielding that there is little to fear in this respect. Exceptions to this are unshielded electrode cables which in many cases act as an antenna and absorb the interference. Interferences occur due to electric fields which are generated from - electric leads in the wall - chokes in fluorescent lamps - neighbouring units (e.g. diathermy units) - large units either in the vicinity of further away (X-ray, lifts). A commercial lead finder obtainable in a DIY store can be very useful in localising leads behind plaster. If such a lead is found in the wall behind the patient table for example, this can already be sufficient to switch off all consumers at the end of the lead and thus minimise the current conduction and thus the generated fields. However, the course of current conduction must be known exactly. Another possibility is the earthing of the patient table, the metal frame of the table being connected to the earthing pins of the ECG recorder by a sufficiently thick cable ( 4mm²). For a permanent solution the table should be contacted by firmly tightening the earthing cable. Other solutions such as crocodile clips or only even winding around a metal part (all already tried!) firstly do not guarantee sufficient contact of low impedance and secondly it is more than likely that cleaning staff or the like will tear them off. A good solution is the use of a ring terminal which is screwed to the screw on the table using a tooth lock washer. If the earthing of the table does not bring about success, mounting metal on the wall is often the only solution. This can take the form of metallized wallpaper or a fly screen. A good connection to the earthing pin of the ECG is necessary in both cases. Space permitting, simple moving of the equipment often leads to success. Interference generated by fluorescent lamps is magnetic in nature and are effective usually because they are near the ECG equipment. Simply switching on and off the lamp can determine whether such a lamp causes interference. This problem may be remedied by replacing the choke with a shielded version or by using a totally different kind of lamp. The effects of other units may also be determined by simply switching them off. In this case too, simply moving the units is often the easiest method. If interference is generated by large electrical units, moving the ECG room is usually the simplest and cheapest solution. In principle, every room may be shielded from external fields but the costs are considerable. It is very problematic when the fields are generated by large motors or transformers, i.e. when magnetic fields are involved. In this case mu-metal must be used which costs several hundred per square metre. e-mail info@riemermed.de Postfach 1173 Seite 2 von 5

AC interference due to earth circuit or incorrect earthing This occurs when the protective earth forms a closed ring. An interference voltage similar to a transformer is included in this loop. This can be remedied by interrupting the loop somewhere. Earth circuits may be avoided by connecting each unit only once with a central earthing socket (normally on the ECG recorder). Often, little attention is paid to earthing. You cannot depend on any socket outlet, especially not in old buildings where the earthing (connecting the grounded connection to the N-lead) was and is common. In the interests of the patients and personnel (and not least for liability reasons), installation should be carried out according to the appropriate IEC regulations. Earthings over heaters or water pipes may indeed bring about an improvement in AC problems but they are definitely not a permanent and safe solution as such installations are mostly only connected in the cellar to the house earhting and corrosion at the various sites can worsen electrical conductivity slowly but surely. AC interference due to potential differences Electrical consumers often cause a reduction in voltage along the power line which is often enough to generate interference in the ECG. This can also easily be resolved by connecting all units belonging to the ECG measuring station to one wall outlet. Shaking At first glance, shaking often appears to be AC interference. However, it may easily be distinguished if observed at a high paper feed rate. The frequency in this case is not constant, the amplitude and frequency of every wave is different. clean ECG shaky ECG Shaking comes from interference voltages from the patients themselves. For example, when the patient is cold, the musculature contracts. This contraction is controlled by currents from the brain which are, however, also taken up by the ECG electrodes. Another reason can be nervousness; in this case, interference voltage is generated by tensing of the muscles. The first problem mentioned can be successfully remedied by heating the investigation room. However, psychological methods must be used in the case of nervousness. e-mail info@riemermed.de Postfach 1173 Seite 3 von 5

The surroundings can often help: an undisturbed view of a park, flowers or even just pictures on the walls are proven methods. The impression of an investigational piece of machinery for patient processing should be avoided at all costs. It has been shown that even careful and invisible laying of the different cables helps to avoid the impression that it has something to do with electricity (most people are afraid of the electricity). The creation of a quiet, familiar atmosphere by personnel is also very helpful. Explaining the investigation and indicating that it is absolutely painless leads to the patient playing a cooperative part in the proceedings. Zero line fluctuations Zero line fluctuations are easily recognised by the movement of the curve upwards or downwards. zero line fluctuations stable zero line They always occur at the transition from the skin to the electrode. A capacitor is formed which has a contact medium as a dielectric. Skin A Electrode Contact medium As is known from physics, the voltage at a capacitor changes when the distance between the boards changes. This is the very effect which induces zero line fluctuations. If the distance of the electrode button to the skin changes, a voltage of several tens of millivolts is generated. The capacitor has a voltage because two different materials which touch each other directly or via a dielectric form a voltaic cell, i.e. a battery. This is also the reason why good electrodes exclusively use silver-silver chloride (Ag-AgCl) as a contact medium. This material is very sensitive to touch, sunrays, chemical decomposition, etc. but has an electrochemical voltage most similar to that of the skin. When this material is used, the voltage generated between the skin and the electrode is minimal. In principle, a constant DC voltage generated between the skin and the electrode is safe as it can be effortlessly compensated by the input amplifier of the ECG recorder. However, fluctuations in this DC voltage cannot be compensated as they are in the same frequency range as the ECG itself and these fluctuations are all the stronger the higher the voltage. e-mail info@riemermed.de Postfach 1173 Seite 4 von 5

D.C. voltage Fluctuation Absolute with constant by distance Fluctuation distance change in % 10 mv 10% 1 mv 50 mv 10% 5 mv Thus use of good electrode material and secure fastening of the electrode onto the skin is indispensable for stable zero-line leads. Troubleshooting As the types of interference described above have a different effect on all electrodes, the following analysis table is useful. It shows the disturbed electrode in connection with the disturbed leads. 1. Analysis of the limb electrodes using the lead diagram according to Einthoven. Lead I Lead II Lead III Disturbed electrode disturbed disturbed OK right arm disturbed OK disturbed left arm OK disturbed disturbed left leg greatly dist. disturbed disturbed right arm and left arm disturbed greatly dist. disturbed right arm and left leg disturbed disturbed greatly dist. left arm and left leg Identical interference in all three leads right leg 2. Analysis of the precordial electrodes. Before the precordial electrodes are analysed, the limb electrodes must be functioning perfectly as the leads according to Wilson refer to the limb electrodes. Then analysis is simple: if lead VI is disturbed, there is interference in electrode VI, etc. e-mail info@riemermed.de Postfach 1173 Seite 5 von 5