ULTRA-EFFICIENT HVAC DESIGN AND CONTROL



Similar documents
Agenda. Part I: Introduction to OptimumHVAC. Part II: Initial Energy Savings Analysis for MCO Main Terminal. Part III: Case Studies & Conclusion

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

Outline. CC objectives Site and building description Typical data floor overview CC measures Results Lessons learned

Continuous Energy Management at UC San Diego. Anna Levitt, P.E. Assistant Energy Manager June 13, 2013

Commissioning - Construction Documents (Page 1 of 6)

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

HVAC Systems: Overview

Heating, Ventilation & Air Conditioning Equipment

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Heating, Ventilation & Air Conditioning Equipment

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Section 2: Estimating Energy Savings and Incentives

*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, C arastro & A ssociates, C&A# 5747

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Continuous Commissioning of the Dallas/Fort Worth International Airport

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Impact of Control System Technologies on Industrial Energy Savings

What are the Carrier ChillerVu Energy Dashboards?

Wet Bulb Temperature and Its Impact on Building Performance

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates

Chapter 3.4: HVAC & Refrigeration System

Denver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian

Variable Refrigerant Flow Systems

Creating Efficient HVAC Systems


Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

Printing and Publishing Energy Savings Guide

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Direct Fresh Air Free Cooling of Data Centres

Retrofitting for Optimum HVAC Performance by Greg Jourdan Wenatchee Valley College

Second Place: Industrial Facilities or Processes, New

Xcel Business Customers: Program and Rebate Summary

CHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

The next generation of geothermal systems for school buildings

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Sustainable Smart Laboratories

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

Enclosed Football Stadium Design History and Lessons Learned

Building Performance With District Cooling

Optimizing Design & Control Of Chilled Water Plants Part 5: Optimized Control Sequences

National Grid Your Partner in Energy Solutions

How To Design A Building In New Delhi

Datacenter Efficiency Program

Tips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

Flexibility, Efficiency In San Antonio Arena

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Centrifugal Fans and Pumps are sized to meet the maximum

Drives and motors. A guide to using variable-speed drives and motors in retail environments

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

OEH Energy Efficient HVAC for Business Training Course

ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

High Altitude HVAC. Silvertip Integrated Engineering Consultants

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

HVAC Processes. Lecture 7

Appendix C. Minimum Equipment Efficiency Standards

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project

for Plans Examiners and Building Inspectors

Case Study. Commercial Building Energy Efficiency Retrofit 4 Mort Street, Canberra. Results. Background PEOPLE PRACTICES SYSTEMS

Heating & Cooling Efficiency

Water cooled chiller plant (cp/vs)

The sample report format is applicable to many different building types and systems and the examples provided cover a variety of applications.

Drives and motors. A guide to using variable-speed drives and motors in car parks

Seven Steps to Maximizing Central Plant Efficiency

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

Sample - Existing Building Commissioning Plan

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

CONTROL STRATEGIES FOR HVAC SYSTEMS

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

Hines Property Management, NYC

Benefits. Air-Cooled Systems

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Scope of Work. See for resources available

Tim Facius Baltimore Aircoil

Q Utility Rebate Report. Houston, TX

Demand Based Static Pressure Reset Control for Laboratories

3/29/2012 INTRODUCTION HVAC BASICS

Drives and motors. A guide to using variable-speed drives and motors in data centres

THERMAL STORAGE WITH ICE HARVESTING SYSTEMS

Transcription:

CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego, CA 92123 Tel: 858-244-1177 Fax: 858-244-1178 Web: www.sdenergy.org

Background The County of San Diego Crime Laboratory is a 102,000 sq ft facility that provides assistance to the criminal justice system by analyzing and evaluating physical evidence in criminal investigations and prosecutions. Needing additional lab space, but faced with an antiquated HVAC system and escalating energy costs, the County of San Diego Sheriff s Department began searching for ways to reduce electrical usage and demand, and at the same time increase the quantity, quality and reliability of their labs. Two areas of concern were the chilled water plant Figure 1: Rooftop ductwork and existing air-cooled chillers. and air-handling system. Seven original Variable Air Volume (VAV) airhandlers (with rusted guide vanes and economizers) were served by two 18 year old 130 ton aircooled reciprocating chillers (see Figure 1 above), one 40-ton air-cooled pony chiller, three constant speed primary pumps (3 x 3 hp) and three constant speed chilled water secondary pumps (10 hp each). An extensive energy audit conducted by the San Diego Regional Energy Office helped convince the County that a band-aid approach was not the way to go. A new oil-less ultra-efficient all variable speed central plant, new energy management control system, and new VAV air-handler system was installed to improve the facility s office and lab spaces while significantly reducing electrical power consumption. Figure 2: Crime Lab s new central plant design (courtesy of Alpha Mechanical) Page 2 of 10

Central Plant Energy Assessment A comprehensive energy assessment was performed on the facility. Based on spot measurements, site utility data, and a building simulation, the pre-existing air-cooled chiller plant operated at a wire-towater plant efficiency ranging from 1.4 to 1.7 kw/ton (averaged 1.48 kw/ton). The central plant savings were calculated based on two different scenarios: (1) The band-aid approach the County would install new air-cooled screw chillers and a constant speed primary / variable speed secondary chilled water loop; (2) Ultra-efficient water cooled central plant the County would install two 150-ton water cooled WMC McQuay / Turbocor chillers, primary-only chilled water pumps and condenser water pumps with variable frequency drives (VFDs), and two 200-ton stainless steel induced draft cooling towers with VFDs. The new plant would be controlled by the Hartman LOOP 1. Table 1 below outlines the savings and costs from each potential retrofit. Table 1. Estimated Energy Savings from Retrofit Tonnage (tons) Est. Annual Electrical Savings (kwh) Peak Demand Reduction (kw) Est. Annual Cost Savings Est. Implementation Cost Standard Practice - New air cooled chiller plant SDG&E Incentives Final cost after incentive Simple Payback (Years) Option 1 300 138,870 15.9 $16,491 $400,000 $0 $400,000 24.3 Water cooled McQuay WMC150 chillers, all variable speed controlled by the Hartman LOOP Option 2 300 509,190 83.0 $64,990 $650,000 $164,000 $486,000 7.5 After the utility incentive, the incremental cost of the new ultra-efficient plant (versus a like-for-like retrofit) was only $86,000. With an incremental energy savings of $48,499/yr, the new simple payback could be calculated at 1.8 years. With these numbers the County decided to move forward with the high efficiency option. Figure 3: One of the two new WMC150 McQuay Turbocor chillers 1 Hartman LOOP network-based control optimizes all-variable speed plants by taking advantage of the exclusive characteristics of variable-speed pumps, chillers and fans. For more information, see www.hartmanco.com. Page 3 of 10

Chiller Performance Data on the new McQuay WMC150 chiller was provided by McQuay. Table 2 below shows the operating conditions of the Turbocor chiller with 44 F leaving chilled water temperature and 80 F entering condenser water. Table 2. Manufacturer's Data - Operating Conditions of 150-ton McQuay WMC Chiller Size Input Efficiency RLA NPLV 75% Load 50% Load 25% Load Evaporator Condenser Tons kw kw/ton Amps kw/ton kw/ton kw/ton kw/ton Ft PD Temp in Ft PD Temp out 150 85.6 0.571 122 0.355 0.434 0.315 0.294 8.5 56 6.6 89.3 Spot measurements were taken on March 7, 2005 at the chiller. The entering condenser water was read at 69.2 F and the chilled water set point was 46 F. The lead compressor was putting out 70 tons and only consuming 25 kw (0.36 kw/ton). Figure 4 and 5 below show the actual monitored performance of the lead chiller during the month of November and August 2005. The chillers averaged 0.315 kw/ton during November 2005 and 0.376 kw/ton during August 2005 with a chilled water set point of 46 F. 0.8 Crime Lab Chiller 64 o F-68 o F entering condenser water November 2005 0.7 0.6 kw/ton 0.5 0.4 0.3 0.2 0.1 0 0 10 20 30 40 50 60 70 80 90 tons Figure 4: McQuay WMC150 efficiency during November 2005 Page 4 of 10

0.8 Crime Lab Chiller 66 o F-73 o F entering condenser water August 2005 0.7 0.6 kw/ton 0.5 0.4 0.3 0.2 0.1 0 0 20 40 60 80 100 120 tons Figure 5: McQuay WMC150 efficiency during August 2005 Central Plant Control Strategy The chiller and condensing circuit in all-variable speed designs employ coordinated variable speed chillers, variable flow condensing water, and optimized tower fan speed control. The Crime Lab central plant utilizes the following three control strategies. 1. Natural Curve Sequencing of Chillers, Pumps, and Towers In all-variable speed chiller plants, optimum performance is attained when the equipment is operating at a specific part load that depends on the current condenser and chilled water temperatures. The curve of the loading, at which each variable speed component achieves maximum efficiency as the external conditions (pressure or temperature) vary, is called the natural curve of that component. Central plant equipment is sequenced accordingly. 2. Power Based Speed Control of Variable Condenser Pumps and Tower Fans Conventional cooling tower control involves delivering a specific (sometimes reset) condenser water temperature to the chillers. This is usually delivered with constant speed condenser pumps. Contrary, a Hartman LOOP plant uses a straightforward patented demand based control methodology for tower fans and condenser pumps in which the speed of this equipment is based on chiller power [1]. 3. Network Control of Chilled Water Distribution Pumping Chilled water distribution pumps are usually operated to maintain a specific distribution differential pressure. Sometimes this pressure set point is reset based on the maximum position of one or several of the valves on the loads served by the system. However, the use of minimum pressure set points can contribute to substantial wasted pumping energy, especially during periods of low loads which are frequent in systems that operate on a 24 x 7 schedule. In the Crime Lab central plant, the speed of the distribution pumps is controlled according to the valve orifice area method [2]. The valve orifice method controls pump speed by using the percentage of total valve orifice area open to determine the required flowrate. This control method allows the head pressure to go to zero as flowrate goes to zero. Page 5 of 10

Figure 6 below shows the actual monitored performance of the entire central plant (wire-to-water plant efficiency) during the month of November 2005. The wire-to-water plant efficiency includes the power from all chillers, chilled water pumps, condenser water pumps, and cooling tower fans. The central plant averaged 0.538 kw/ton during November 2005. 0.80 Crime Lab Central Plant 64 o F-68 o F entering condenser water Novem ber 2005 0.70 0.60 kw/ton 0.50 0.40 0.30 0.20 0.10 0.00 0 10 20 30 40 50 60 70 80 90 tons Figure 6: Wire-to-water central plant efficiency during November 2005 Page 6 of 10

Air-Handling System Seven original Variable Air Volume (VAV) air-handlers (with rusted guide vanes and economizers) served the majority of the offices and labs. Again, the Sheriff s department was faced with two different retrofit/replacement options: (1) Band-aid approach Keep existing air-handlers and install VFDs, new economizer dampers, and electronic actuators. Also, install additional spot air-handlers for the newly installed labs or (2) Install all new properly designed VAV air-handlers, VAV boxes, and sophisticated DDC controls. Because of the state of the old air-handlers, the County decided to go with Option 2. Figure 7: Original VAV air-handler at the Crime Lab Figure 8: New penthouse for new VAV air-handlers Page 7 of 10

Air-handler Control Strategy Most VAV systems today are controlled by a constant (sometimes reset) static pressure set point. This type of simple stand-alone, single process feedback control limits the effectiveness and efficiency of modern HVAC systems. The Terminal Regulated Air Volume (TRAV) system used on the Crime Lab project is a network-based controls technology that employs the new capabilities of highperformance DDC systems that result in a VAV system that is more energy efficient and provides improved building comfort [3]. In TRAV systems, the central fan is regulated to meet terminal VAV box airflow requirements rather than a duct static pressure setpoint. When areas of the building are not experiencing design loads, significant static pressure reductions occur that bring corresponding energy reductions. TRAV systems regularly result in 30 percent to 50 percent less energy use than standard VAV systems. See Figures 9 and 10 below. Figure 9: Fan power curve comparisons for standard VAV systems [3] Page 8 of 10

Static Pressure - Air-handler #2 Monday (7-18-05) SP (inches H2O) 0.45 0.4 0.35 0.3 0.25 0.2 0.15 0.1 0.05 0 0 2 4 6 8 10 12 14 16 18 20 22 24 Hours Figure 10: Monitored static pressure for Crime Lab air-handler #2 in July 2005 These systems also achieve much more than lower fan power. The network based controls provide automatic demand based reset of the supply air temperature, automatic self-balancing of the terminal units, and better distribution of ventilation air. Savings Analysis The goals of the project have been met. Lab space and lab requirements increased significantly (building ton-hrs) while still decreasing the amount of energy the facility used. Comparing 2004 energy consumption to 2005 energy consumption, total building energy usage decreased by 21% and peak demand by 37%. The Crime Lab now has a building energy density of 16 kwh/ft 2 -yr while maintaining building environmental conditions 24 hours per day and 7 days per week. Crime Lab Total Building Energy Usage 210,000 190,000 170,000 kwh 150,000 130,000 110,000 90,000 70,000 50,000 Mar April May June July Aug Sept Oct Nov Before After Figure 11: Total building energy usage before and after retrofit Page 9 of 10

Crime Lab Peak Demand kw 550 500 450 400 350 300 250 200 150 100 50 0 M ar April M ay June July Aug Sept Oct Nov Before After Figure 12: Total building peak demand before and after retrofit Conclusion Benefits and points of interest include: Maintenance was greatly reduced Environmentally friendly R-134a is used in chillers (reducing environmental impact) Oil-less chillers were used (reducing our dependency on foreign oil while increasing the efficiency of the machines) Noise was greatly reduced New lab space requirements are met while reducing energy usage Building occupants are comfortable Significant portion of the central plant upgrade was covered by utility incentives For more information about this retrofit please contact Ben Erpelding, P.E. (SDREO s Engineering Manager) at 858-244-1177. References 1. Hartman, T. December 2001. Ultra-efficient Cooling with Demand Based Control. Heating/Piping/Air Conditioning Engineering. 2. Hartman, T. 2003. Presenting Intelligent Iterative Control: PID Replacement for Setpoint Control. (Part 1, 2, and 3) Heating/Piping/Air Conditioning Engineering. 3. Hartman, T. December 1993. Terminal Regulated Air Volume (TRAV) Systems ASHRAE Transactions: Symposia 1993 791-800. Page 10 of 10