Variable Refrigerant Flow Systems
|
|
|
- Dominic Campbell
- 10 years ago
- Views:
Transcription
1 The following article was published in ASHRAE Journal, April Copyright 2007 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. Variable Refrigerant Flow Systems By William Goetzler, Member ASHRAE Variable refrigerant flow (VRF) systems, which were introduced in Japan more than 20 years ago, have become popular in many countries, yet they are relatively unknown in the United States. The technology has gradually expanded its market presence, reaching European markets in 1987, and steadily gaining market share throughout the world. In Japan, VRF systems are used in approximately 50% of medium-sized commercial buildings (up to 70,000 ft 2 [6500 m 2 ]) and one-third of large commercial buildings (more than 70,000 ft 2 [6500 m 2 ]). 1 Although vigorous marketing of VRF systems in the U.S. began only two to three years ago, several thousand systems likely will be sold in the U.S. this year, amounting to tens of thousands of tons of capacity. Of course, the market is still very small compared to the chiller market, but VRF systems are marketed in the U.S. by at least five manufacturers. The success of the VRF in other countries, and its historically limited market presence in the U.S., has several sources, including: Differences in construction practices; Figure 1: Typical VRF configuration in an office building. The long history and large installed base of ducted direct exchange (DX) systems and chillers in the U.S. compared, for example, to Europe, where many buildings did not have air conditioning until recent decades; Differences in regulatory environment (e.g., regulations that discourage electric chiller installations in Japan); and VRF technology has been developed and promoted by Asian companies, which had limited market presence in the U.S. until recently. Also, building owners are wary of HVAC suppliers whose parts availability, service and technical support infrastructure is uncertain. What is VRF? Many HVAC professionals are familiar with ductless minisplit products. A varia- About the Author William Goetzler is an associate director at Navigant Consulting, Burlington, Mass. He has performed consulting services for VRF manufacturers. 2 4 A S H R A E J o u r n a l a s h r a e. o r g A p r i l
2 tion of this product, often referred to as a multisplit, includes multiple indoor evaporators connected to a single condensing unit. Ductless products are fundamentally different from ducted systems in that heat is transferred to or from the space directly by circulating refrigerant to evaporators located near or within the conditioned space. In contrast, conventional systems transfer heat from the space to the refrigerant by circulating air (in ducted systems) or water (in chillers) throughout the building. VRF systems are larger capacity, more complex versions of the ductless multisplit systems, with the additional capability of connecting ducted style fan coil units. They are inherently more sophisticated than multisplits, with multiple compressors, many evaporators, and complex oil and refrigerant management and control systems. They do not provide ventilation, so a separate ventilation system is necessary. The term variable refrigerant flow refers to the ability of the system to control the amount of refrigerant flowing to each of the evaporators, enabling the use of many evaporators of differing capacities and configurations, individualized comfort control, simultaneous heating and cooling in different zones, and heat recovery from one zone to another. This refrigerant flow control lies at the heart of VRF systems and is the major technical challenge as well as the source of many of the system s advantages. Figure 1 illustrates a standard VRF configuration, while Figure 2 shows a heat recovery unit providing simultaneous heating and cooling. VRF Benefits VRF systems have several key benefits, including: Installation Advantages. Chillers often require cranes for installation, but VRF systems are lightweight and modular. Each module can be transported easily and fits into a standard elevator. Multiples of these modules can be used to achieve cooling capacities of hundreds of tons. Each module (or set of two) is an independent refrigerant loop, but they are controlled by a common control system. The modularity also enables staged, floor-by-floor installations, for example, if a building is only partly occupied, which is similar to currently available self-contained VAV systems. The relatively light weight of the system also may reduce requirements for structural reinforcement of roofs. Because ductwork is required only for the ventilation system, it can be smaller than the ducting in standard ducted systems, reducing building height and costs. In cases where operable windows are present and meet code requirements for ventilation, VRF systems are also particularly suitable for retrofitting historical buildings without disturbing the structure or for older buildings with no air conditioning. Finally, because the condensing units are normally placed outdoors, no need exists for a machine room. Design Flexibility. A single condensing unit can be connected to many indoor units of varying capacity (e.g., 0.5 to 4 tons [1.75 to 14 kw]) and configurations (e.g., ceiling recessed, wall-mounted, floor console). Current products enable up to 20 indoor units to be supplied by a single condensing unit. Modularity also makes it easy to adapt the HVAC system to expansion or reconfiguration of the space, which may require additional capacity or different terminal units. Maintenance and Commissioning. VRF systems with their standardized configurations and sophisticated electronic controls are aiming toward near plug-and-play commissioning. Because they are DX systems, maintenance costs for a VRF should be lower than for water-cooled chillers, so water treatment issues are avoided. Normal maintenance for a VRF, similar to that of any DX system, consists mainly of changing filters and cleaning coils. However, chillers, which often operate for 20 to 30 years, normally would be anticipated to have a longer life expectancy than a DX system such as a VRF. 2 The large number of compressors in a VRF may create a higher probability of compressor failure, although the redundancy also leads, in many cases, to a greater ability to continue to occupy the space while repairs are made. Comfort. Many zones are possible, each with individual setpoint control. Because VRF systems use variable speed compressors with wide capacity modulation capabilities, they can maintain precise temperature control, generally within ±1 F (±0.6 C), according to manufacturers literature. Energy Efficiency. The energy efficiency of VRF systems derives from several factors. The VRF essentially eliminates duct losses, which are often estimated to be between 10% to 20% of total airflow in a ducted system. 3 VRF systems typically include two to three compressors, one of which is variable speed, in each condensing unit, enabling wide capacity modulation. This approach yields high part-load efficiency, which translates into high seasonal energy efficiency, because HVAC systems typically spend most of their operating hours in the range of 40% to 80% of maximum capacity. At the present time, no ARI-certified rating system exists for measuring the efficiency of a VRF system, so simple EER comparisons to other systems can not be quoted here. A careful review of all engineering data must be performed to make accurate, quantitative comparisons. For buildings requiring simultaneous heating and cooling, heat recovery VRF systems can be used. These systems circulate refrigerant between zones, transferring heat from the indoor units of zones being cooled to those of zones being heated. Each manufacturer has its own proprietary design, but most use a three-pipe system (liquid, suction and discharge) and special valving arrangements. Typically, extra heat exchangers in distribution boxes are used to transfer some reject heat from the superheated refrigerant exiting the zone being cooled to the refrigerant that is going to the zone to be heated. A p r i l A S H R A E J o u r n a l 2 5
3 The modularity of the VRF also enables relatively simple submetering of electricity (i.e., placing an electric meter on one or a few condensing units is relatively simple, accurate and inexpensive, whereas metering chilled water or refrigerant is more complex). Though difficult to quantify, submetered VRF systems may encourage energy-saving behavior in multitenant buildings if energy costs are charged explicitly to each tenant rather than being hidden in overall leasing costs. Heat Recovery Unit First Costs As with chilled water systems, installed costs for VRF systems are highly variable, project dependent, and difficult to pin down. Total installed costs for VRF systems are estimated Figure 2: Heat recovery VRF system. by some sources to be 5% to 20% higher than for chilled water systems providing equivalent capacity, 2 but actual costs are highly project dependent. The same reference describes a 100,000 ft 2 (9300 m 2 ) office building project in Brazil where the VRF system was approximately 15% to 22% more expensive than a comparable chilled water system, but notes that the cost was skewed by the high import tariff on the VRF. Also cited is a 43,000 ft 2 (4000 m 2 ) German hotel where the VRF was approximately equivalent in price to an air-cooled screw chiller system. Equipment costs in the U.S. would probably be similar to those in Europe. However, at the present time, American contractors would likely bid a higher installation cost than their European counterparts because they are less familiar with the product and need to build in a larger contingency. As their experience and comfort level with the product increases, installation costs should converge. A comparison done by a VRF manufacturer of a 200 ton (700 kw) VRF to both air- and water-cooled chillers in a U.S. application also showed an Advertisement formerly in this space. 2 6 A S H R A E J o u r n a l a s h r a e. o r g A p r i l
4 installed cost premium of approximately 5% to 20% for the VRF, but this was based on expected, rather than actual, costs. 1 All these estimates apply to new construction. Replacing a chiller and air-handling unit with another chiller and air handler normally will be much less expensive than replacing it with a VRF and ventilation system. The major cost issue is that a VRF would need new refrigerant piping while the chiller already would have its water piping installed. In summary, it is likely that, at present, in the U.S., a VRF system would involve a cost premium over a chiller in applications where the VRF is competitive. In some cases, where chiller installations are particularly problematic (e.g., if access for installing a new chiller requires major expense or demolition, if water piping is deteriorating and difficult to access for repair) the VRF may have the lowest installed cost. In many others, the VRF will not be suitable at all. Energy Efficiency As with installed costs, the energy efficiency of VRF systems is application dependent. Both field tests and simulations can be skewed by factors such as climate or the choice of baseline systems for comparison. For example, one article cited an installation in a government building where much of the space is unoccupied during much of the day when workers are out in the field. 4 A rooftop VAV was used on one side of the building and a VRF on the other. The energy consumption of the VRF was approximately 38% lower than for the VAV. However, other project details, including the baseline system efficiency, were not published. The general applicability of simulations also can be questionable, due to the many different scenarios encountered in the real world, and the limitations of current simulation tools. A full year, hourly simulation, using standard spreadsheet software, of a 538 ton (1892 kw) VRF compared to both screw and centrifugal chillers yielded high energy savings for the VRF relative to the other options. 5 The cooling energy savings of about 30% may be explained by the relatively temperate Brazilian climate. Another recent simulation compared a state-of-the-art 200 ton (700 kw) VRF system to both an air-cooled screw chiller and a water-cooled chiller. 1 The highest efficiency, newest R-410a VRF system achieved energy savings of 30% to 40% compared to the chillers, but an older R-22 VRF system showed little or no savings compared to the chillers. The VRF system savings are due to their high part-load efficiency. The improved efficiency of the newest VRF systems compared to older generations is due to component changes such as variable speed fan motors and compressors that use ECM motors. The chiller efficiency is higher than that of the VRF only at >90% load, but 80% of the chiller operating hours occurred at 45% to 80% load. Variable speed compressors in chillers are now common, but other components such as pumps are often single speed. Applications VRF systems are generally best suited to buildings with diverse, multiple zones requiring individual control, such as office buildings, hospitals, or hotels. A VRF system does not compete well with rooftop systems in a large low-rise building such as a big box retail store. Although VRF heat pumps operate at ambient temperatures as low as 0 F ( 18 C), as in all heat pumps, their efficiency drops off considerably at low temperatures, so they are less cost effective compared to gas heating in very cold climates. Market Acceptance Issues* Previous studies, 2 recent experience in marketing the VRF, as well as focus groups conducted with engineers, contractors, and facility managers, have revealed several important concerns regarding the application of VRF systems in the U.S. As manufacturers have intensified their education and training efforts to address these concerns, and have explained some of the technical features of the VRF that address these issues, many of these concerns have been alleviated. Lack of Awareness of Energy Efficiency Advantages. Most industry professionals refer only to EER or kw/ton ratings when considering efficiency. The more subtle energy efficiency advantages of VRF systems, such as the reduction in duct losses, the ease of electrical submetering, and even the higher part load efficiency, frequently are overlooked. Engineers rarely have the time and inclination to undertake complex building energy simulations, and current non-proprietary tools such as Energy Plus cannot address VRF systems. Furthermore, ARI has not yet established a certification program for VRF system performance, although it is expected by First Cost. In many cases, the initial cost of a VRF system is higher than that of a chilled water system, water source heat pump, or rooftop DX system. Building owners often have no incentive to accept higher first costs even if the payback period is short, and they can be skeptical of energy savings predictions. While a VRF may be cost competitive for new construction, in a chiller replacement situation with existing water piping, replacing the chiller would normally be less expensive than installing a VRF. Gas Heating for Cold Climates. Currently available VRF systems have no integrated gas heating option. This factor hampers their acceptance in cold climates for buildings with substantial heating loads. Integration of the VRF with hydronic heating works well and is sometimes done when such systems already exist. However, using gas or oil heating with a VRF requires a separate furnace or boiler, which is more expensive than a gas-fired rooftop system or a chiller/boiler system. Refrigerant Piping. Contractors are concerned about long refrigerant piping runs for several reasons. They believe that compliance with ANSI/ASHRAE Standard , Safety Standard for Refrigeration Systems, is difficult. Long refrigerant lines also raise the specter of refrigerant leaks, which can be difficult to find and repair, particularly in inaccessible spaces. These are legitimate concerns, but they can be overcome. *Some of the information in this section is derived from Reference A S H R A E J o u r n a l a s h r a e. o r g A p r i l
5 Compliance with Standard is accomplished in the same manner as with any DX system. The total refrigerant charge in the refrigerant loop must be within the limits prescribed by Standard for the smallest zone served by the system to ensure the safety of occupants if the entire charge is released. In practice, the charge in a single system s refrigerant loop (condensing unit and multiple fan coil units) is usually not problematic, except when serving relatively small spaces. In those cases, one solution is to use a single fan coil unit for multiple rooms, with ducting to each room. In that case, the space to be considered in the safety calculation is the total space of the multiple rooms served by the fan coil unit. Other suitable design approaches also exist. Compliance with Standard can be achieved through careful system design. Minimization of leaks is also critical. VRF manufacturers have developed products and protocols to address this concern. Typically, all joints are brazed joints with no flared fittings. Headers and splitters are specifically designed for the product and do not require flaring or changing wall thicknesses. Contractor training includes protocols that require pressure testing of each refrigerant circuit during commissioning. Long refrigerant piping loops also raise concerns about oil return, and VRF products are designed to ensure proper oil return. Typically, each compressor has its own oil separator, which is optimized for the VRF system. Periodically, the VRF goes into oil retrieval mode, during which time the thermostatic expansion valve opens, and the compressor cycles at high pressure to flush oil out of any locations where it has accumulated. Manufacturer Support. VRF systems were introduced by Japanese companies with limited presence in the U.S., particularly in the large commercial HVAC market. In the past, they have had limited sales and support for these products in the U.S. Today, however, at least five manufacturers offer VRF systems in the U.S., and several acquisitions involving U.S. and Japanese manufacturers in recent years also should reduce this concern. Code Compliance Issues Specific to the U.S. Europe and Japan, where VRF systems are widespread, have code requirements analogous to Standard and ANSI/ASHRAE Standard , Ventilation for Acceptable Indoor Air Quality, and VRF installations are engineered to meet those requirements. Advertisement formerly in this space. Future Directions VRF manufacturers will target several additional challenges over the next few years. ARI Rating Standard. Currently, no approved ARI standard exists for a performance rating of VRF systems. Consequently, manufacturers need to apply for waivers from the Department of Energy to market their products in the U.S. Although these waivers have been granted, new applications need to be submitted for new product groups. Furthermore, an ARI standard will en- A p r i l A S H R A E J o u r n a l 2 9
6 able stakeholders to compare different manufacturers products more accurately and will provide them with a greater comfort level with the products. A draft provisional standard is under review with final publication expected in Energy Modeling Tools. Current, non-proprietary building energy simulation tools like Energy Plus and DOE-2 cannot model VRF systems. Manufacturers are working to resolve this issue. In the meantime, only proprietary tools are available, which some stakeholders view with skepticism. Integration of Outside Air. Currently, ventilation systems used in conjunction with VRF systems are engineered separately on a caseby-case basis. Manufacturers are evaluating potential approaches for an integrated solution, incorporating controls to ensure adequate outside air and economizing, while optimizing overall performance. Broaden Installer Base. The shortage of skilled installers is problematic for the HVAC industry as a whole, but expanding the number of installers who are comfortable with extensive refrigerant piping work is particularly critical for the VRF market. Conclusions VRF systems are not suitable for all commercial building applications. However, they are an excellent option for certain projects, and one more tool for engineers to consider. As more VRF units are installed and we gain further operating experience in the U.S., many of the concerns expressed by industry professionals are likely to diminish. 4. Air Conditioning, Heating, & Refrigeration News. January 14, Digital variable multi A/C technology passes test. 5. Interact Ltda. of Brazil for DK Systemas De Ar Condicionado Ltda Estudo comparativo de alternativas de climatizacao para o predio Cardoso de Mello (Comparative Study of Alternative Air Conditioning Systems for Predio Cardoso de Mello). February. Acknowledgments Figures 1 and 2 are from Daikin Industries, Ltd. Advertisement formerly in this space. References 1. Smith, L A Daikin Perspective on VRF. Daikin Air Conditioning U.K. 2. Roth, K.W., et al Energy Consumption Characteristics of Commercial Building HVAC Systems Volume III: Energy Savings Potential. Report prepared by TIAX LLC for DOE Building Technologies Program. 3. Fisk, W.J., et al Duct Systems in Large Commercial Buildings: Physical Characterization, Air Leakage, and Heat Conduction Gains. LBNL Report, LBNL A p r i l A S H R A E J o u r n a l 3 1
Variable Refrigerant Flow: An Emerging Air Conditioner and Heat Pump Technology
Variable Refrigerant Flow: An Emerging Air Conditioner and Heat Pump Technology Ammi Amarnath, Electric Power Research Institute Morton Blatt, Energy Utilization Consultant ABSTRACT This paper reviews
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution. Presented by: Fujitsu General America, Inc.
The ABC s of VRF: A Green HVAC Technology An Ideal Green School Solution Presented by: Fujitsu General America, Inc. What to look for in a Green HVAC solution? What if your HVAC system could provide Individual
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
HVAC Variable Refrigerant Flow Systems
HVAC Variable Refrigerant Flow Systems Course No: M03-014 Credit: 3 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
HEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
MEETING AGENDA. Project Administrator:
MEETING AGENDA Project Administrator: To: Ann Green M. Baker, SLCS C. Bullinger, SLCS R. Clark, SLCS Board C. Cox, SLCS S. Dotinga, Granger J. Graham, SLCS J. Gusick, SLCS, Board C. Hanshaw, SLCS Board
Ductless Heat Pumps. Gary Nordeen January 2009. www.nwbuildings.org/dhp.aspx [email protected]
Ductless Heat Pumps Gary Nordeen January 2009 www.nwbuildings.org/dhp.aspx [email protected] Outline Heat Pump Basics Ductless Heat Pumps Efficiency Advantages Commercial installations Planning (applications,
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction What is DNSS EcoSave? The Daikin Network Service System (DNSS EcoSave) is a Daikin developed internet based remote
ULTRA-EFFICIENT HVAC DESIGN AND CONTROL
CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego,
B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation
B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1
Air-Conditioning Buying Guide
Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS
SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
Heat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
DIABLO VALLEY COLLEGE CATALOG 2015-2016
HEATING, VENTILATION, AIR CONDITIONING, REFRIGERATION - HVACR Tish Young, Dean Physical Sciences and Engineering Division Physical Sciences Building, Room 263 Possible career opportunities Upon successful
Nordic Heat Pump Product Guide
Nordic Heat Pump Product Guide About Maritime Geothermal Maritime Geothermal is a privately owned, Canadian based manufacturer of geothermal heat pumps. We began manufacturing the Nordic line of heat pumps
Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)
UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
EarthCents (DSM) Program Summary
EarthCents (DSM) Program Summary Renewable Energy EarthCents Programs Solar Water Heating This program is available to residential customers for the installation of a qualifying solar thermal water heater.
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances
Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL
Why Daikin? 2015 Houston, Texas USA www.daikincomfort.com
Why Daikin? Daikin: The Premium Brand industry leader Daikin is recognized as the world s number one leader in the manufacture of HVAC equipment and refrigerants. For over 90 years, Daikin has grown consistently
RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.
1. There is verbiage in the hazardous material report referring to a state licensed abatement contractor. Within the recommendations part of the report (page 64 of 111 of the specification pdf) is the
Selection Tips For Air-Conditioning Cooling Systems
PDHonline Course M117 (2 PDH) Selection Tips For -Conditioning Cooling Systems Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Section 2: Estimating Energy Savings and Incentives
Section 2: Estimating Energy Savings and Incentives 2.1 Estimating Energy Savings and Incentives... 2 2.2 Customized Measures - Estimation Software... 2 2.2.1 AC&R I - High Efficiency Chiller... 3 2.2.2
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
air conditioners how to choose a cooling system
air conditioners how to choose a cooling system taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced
Introduction To VRF: System Overview, Applications, & Savings Opportunities
Introduction To VRF: System Overview, Applications, & Savings Opportunities System Overview What is VRF? Zoning System Two-Pipe / Three Pipe System Packaged DDC Control Operates as a Heat Pump Simultaneous
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
2015 HVAC Excellence Educator Conference Variable Refrigerant Flow & Variable Refrigerant Temperature
2015 HVAC Excellence Educator Conference Variable Refrigerant Flow & Variable Refrigerant Temperature Slide 1 Residential Market Push for more efficiency Green Building Initiative R-22 & High Efficiency
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact
ASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
Reducing the Cost of Keeping Office Data Centers Cool
Reducing the Cost of Keeping Office Data Centers Cool Portable Spot Air Conditioners as Permanent Cooling Solutions A Guide for Facility Managers, IT Managers and Mechanical Contractors Today s office
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
Centralized Vs Decentralized Air Conditioning Systems
Centralized Vs Decentralized Air Conditioning Systems Course No: M05-012 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Preliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
Air Conditioning Clinic
Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations
ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations MECHANICAL SYSTEMS DESIGN STANDARDS Appendix A RECOMMENDED HVAC SYSTEMS BY TYPE OF SPACE Matt Higgins Valentin Lucero
POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System)
Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V Water II Heat VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BL-001-US 011M05 Executive Summary Contents
Daikin VRV Retrofit Provides Comfortable, Quiet Rooms for Residents
Daikin VRV Retrofit Provides Comfortable, Quiet Rooms for Residents The Challenge An assisted living center needed a cost efficient HVAC system replacement which could be installed without disrupting the
Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
Tim Sisson - Trane HVAC OVERVIEW
Tim Sisson - Trane HVAC OVERVIEW HVAC Systems System Types Acoustics Controls Modernization more than one Down to the Studs Opportunity for new System Type Renovation Possible opportunity for new System
The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
Appendix C. Minimum Equipment Efficiency Standards
Appendix C Minimum Equipment Efficiency Standards Appendix C: Minimum Equipment Efficiency Standards This Appendix is an overview of building and equipment standards in the State of California that have
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
Heating, ventilation and air conditioning (HVAC) equipment. A guide to equipment eligible for Enhanced Capital Allowances
Heating, ventilation and air conditioning (HVAC) equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Boost Introduction your cash flow 03 1. Background Check it s on the
Todd M. Rossi, Ph.D. President
Residential Air Conditioning Fault Detection and Diagnostics (FDD) and Protocols to Support Efficient Operation DOE - Building America Program Residential Buildings Integration Meeting - July 20-22, 2010
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
FTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29
Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Xcel Business Customers: Program and Rebate Summary
Xcel Business Customers: Program and Rebate Summary Rebates for New Energy-Efficient Equipment Xcel offers prescriptive rebates to its business customers. What s a prescriptive rebate? It simply means
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
The Benefits Really Add Up
Unico, Inc. 7401 Alabama Ave. St. Louis, MO 63111 Unico, Inc. manufacturing plant and sub-assembly plant +1 800 527 0896 +1 314 481 9000 www.unicosystem.com Unico, Inc. is the leader in Small Duct High
Condensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
Printing and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand