Laser-Optimized Fiber



Similar documents
With the advent of Gigabit Ethernet

The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper

Will Your Fiber Optic Cable Plant Support Gigabit Ethernet?

WHITE PAPER. 50 versus 62.5 micron multimode fiber

Overcoming OM3 Performance Challenges

Cabling & Test Considerations for 10 Gigabit Ethernet LAN

Fiber Selection and Standards Guide for Premises Networks

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

MINIMIZING PMD IN CABLED FIBERS. Critical for Current and Future Network Applications

Attaching the PA-A1-ATM Interface Cables

Installation Guide for GigaBit Fiber Media Converter

CISCO 10GBASE X2 MODULES

Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces

Fibre Channel Fiber Cabling

HP Multimode OM3 LC/LC Optical Cables Overview. Models HP 50 m Multimode OM3 LC/LC Optical Cable

Introduction to Optical Link Design

Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network

Designing Fiber Optic Systems David Strachan

How To Get A Better Signal From A Fiber To A Coax Cable

Cisco Small Form-Factor Pluggable Modules for Gigabit Ethernet Applications

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

OFS AllWave Zero Water Peak (ZWP) single-mode

Present State-of-the-art of Plastic Optical Fiber (POF) Components and Systems

The Conversion Technology Experts. Fiber Optics Basics

High-Reliability Diode Lasers for Gesture Recognition. Applying Telecommunications Reliability Design to Consumer Electronics

Data Center Design for 40/100G

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Bandwidth analysis of multimode fiber passive optical networks (PONs)

Upgrading Path to High Speed Fiber Optic Networks

Intel Ethernet SFP+ Optics

Cisco SFP Optics for Gigabit Ethernet Applications

Obsolete Fiber Technology? Not in my Data Center!

Accurately Testing fibre Optic Cables

Module 13 : Measurements on Fiber Optic Systems

Fibre Channel Fiber-to-Fiber Media Converters

10 Gigabit Ethernet Cabling

SFP Transceiver Specifications

Optimizing Infrastructure Support For Storage Area Networks

Wavelength Division Multiplexing

Trends In Data Rate And Link Length In Evolving Optical Standards

CWDM: lower cost for more capacity in the short-haul

The 50G Silicon Photonics Link

Simulation and Best Design of an Optical Single Channel in Optical Communication Network

Different Types of Dispersions in an Optical Fiber

Fibre Optic Indoor/Outdoor Cable

Gigabit Ethernet Copper-to-Fiber Converters

100BASE-FX Technical Brief

What to do about Fiber Skew?

Local Area Networks. Guest Instructor Elaine Wong. Elaine_06_I-1

Fiber Optics: Fiber Basics

Troubleshooting and Auto-Negotiation Features for IMC Networks Media Conversion Products

TransPacket white paper. CWDM and DWDM networking. Increasing fibre-optical network utilization and saving on switches/routers

Optical Fibers Fiber Optic Cables Indoor/Outdoor

INTRODUCTION FIGURE 1 1. Cosmic Rays. Gamma Rays. X-Rays. Ultraviolet Violet Blue Green Yellow Orange Red Infrared. Ultraviolet.

Improving Chromatic Dispersion and PMD Measurement Accuracy

CISCO DWDM XENPAK. Main features of the Cisco DWDM XENPAK include:

Upgrading Data Center Network Architecture to 10 Gigabit Ethernet

FIBER OPTIC COMMUNICATIONS. Optical Fibers

The Three Principles of Data Center Infrastructure Design WHITE PAPER

What are Fibre Optics?

Plug & Play Gigabit Ethernet Media Conversion Module. Application Note

Preparing Infrastructure for 10 Gigabit Ethernet Applications

Optical Fibres. Introduction. Safety precautions. For your safety. For the safety of the apparatus

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center

Fiber Distributed Data Interface

EE4367 Telecom. Switching & Transmission. Prof. Murat Torlak

10G CWDM Conversion Technology

Fiber Optics and Liquid Level Sensors Line Guide

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method

Sustaining the Cloud with a Faster, Greener and Uptime-Optimized Data Center

Industry solutions: Broad cast

QuickSpecs. Models HP X131 10G X2 CX4 Transceiver. HP X131 10G X2 Transceivers (SR, LRM, LR, ER and CX4) Overview. HP X131 10G X2 SC LRM Transceiver

Measuring of optical output and attenuation

Introduction to Ethernet

Simulation of Gaussian Pulses Propagation Through Single Mode Optical Fiber Using MATLAB . MATLAB

SummitStack in the Data Center

QuickSpecs. Models. ProCurve Mini-GBICs Overview. ProCurve Gigabit-LX-LC Mini-GBIC. ProCurve Gigabit-LH-LC Mini-GBIC

10G and Beyond in the Data Center with OM3 Fiber

Recession-Proof Consulting Services with CWDM Network Design

Introduction to Optical Networks

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

How To Make A Data Center More Efficient

CISCO WDM SERIES OF CWDM PASSIVE DEVICES

Compatibility of Bend Optimized Multimode Fibers White Paper. Issued September 2009

USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION

WDM-PON: A VIABLE ALTERNATIVE FOR NEXT GENERATION FTTP

Upon completing this chapter, you will be able to: Describe the primary types and uses of twisted-pair cables Describe the primary types and uses of

Fiber Optics: Engineering from Global to Nanometer Dimensions

CHAPTER 6 NETWORK DESIGN

Loss & Continuity Testing with MPO/ MTP Connectors

New Installation and Maintenance Tools for CWDM Networks

Dispersion penalty test 1550 Serial

Implementation of Short Reach (SR) and Very Short Reach (VSR) data links using POET DOES (Digital Opto- electronic Switch)

Transcription:

FIBER FAQs Laser-Optimized Fiber Technical Resource: Tony Irujo Manager, Customer Technical Support

FIBER FAQs Laser-Optimized Fiber As transmission speeds over optical fiber networks in the enterprise increase to 1 and even 10 Gigabits per second (Gb/s) and beyond, a relatively new term "laser-optimized fiber" has crept into the industry s vocabulary. What is laser-optimized fiber? What do you need to know about it? And what exactly does the term "laseroptimized" mean? Understanding the answers to these questions will help you prepare for the latest wave in optical communications for enterprise networks. Why have optical fibers been "optimized" for use with lasers? Older "legacy" optical fiber systems (Token Ring, Ethernet, FDDI, ATM) used in premises applications operated at relatively slow speeds in the range of 4 to 155 Megabits per second (Mb/s). These systems utilized inexpensive light sources called Light Emitting Diodes (LEDs), which were perfectly adequate for these slower speeds. Multimode fibers used in these systems were rated to certain minimum bandwidths, typically: 160 MHz/km over 62.5/125 µm fiber at 850 nm 500 MHz/km over 50/125 µm fiber at 850 nm 500 MHz/km over both products at 1300 nm These fibers were tested for bandwidth using an Overfilled Launch (OFL) test method, which accurately replicated real-life performance with an LED. As the demand for bandwidth and higher throughput increased, especially in building and campus backbones, LEDs could not keep pace. With a maximum modulation rate of 622 Mb/s, LEDs would not support the 1 Gb/s and greater transmission rates required. One could make use of traditional lasers (Fabry-Perot, Distributed 1

Laser-Optimized Fiber Feedback) typically used over single-mode fiber, but these are considerably more expensive due to the higher performance characteristics required for long-distance transmission on single-mode fiber. In response, the industry developed a new high-speed laser light source called a Vertical Cavity Surface Emitting Laser (VCSEL). These VCSELs are inexpensive and well suited for low-cost 850 nm multimode transmission systems, allowing for data rates of 1 Gb/s and 10 Gb/s in the enterprise. With the emergence of these VCSELs, multimode fiber had to be "optimized" for operation with lasers. What s the difference between a VCSEL and an LED? VCSELs provide higher power, narrower spectral width, smaller spot size, and faster data rates than LEDs. All of these advantages add up to a significant performance boost. This assumes, of course, the fiber itself does not hinder performance. To understand why this could occur, we need to understand the differences between VCSELs and LEDs and how they transmit signals along a multimode fiber. All LEDs produce a smooth, uniform output that consistently fills the entire fiber core and excites the many hundreds of modes in the fiber. The bandwidth of the fiber is determined by the aggregate performance of all the modes in the fiber. If a few modes lag behind or get ahead due to modal dispersion, they have little impact on bandwidth because many other modes are carrying the bulk of the signal. The energy output of a VCSEL is smaller and more concentrated than that of an LED. As a result, VCSELs do not excite all the modes in a multimode fiber, but rather a restricted set of modes. The bandwidth of the fiber is dictated by this restricted set of modes, and any modes that lag or get ahead have a much greater influence on bandwidth. Typically, a VCSEL s power would be concentrated in the center of the fiber, where older fibers were prone to defects or variations in the refractive index profile (the critical light-guiding property in the core of the fiber), resulting in poor transmission of the signal. That is why some fibers may actually perform poorly with a VCSEL compared to an LED. To complicate matters, the power profile of a VCSEL is non-uniform and fluctuates constantly. It changes sharply across its face, varies from VCSEL to VCSEL, and varies with temperature and vibrational fluctuations. Consequently, individual VCSELs will excite different modes in a given fiber at any given time. And because different modes carry varying amounts of power, the fiber s bandwidth can vary in an unpredictable manner. 2 FIBER FAQs

FIBER FAQs Laser-Optimized Fiber Why are laser-optimized fibers the best choice for use with VCSELs? With the advent of VCSELs, it became apparent that the traditional multimode fiber deployed for LED systems did not take full advantage of the performance benefits of VCSELs. To fully capitalize on the benefits that VCSELs offered, fiber manufacturers developed laser-optimized multimode fiber (LOMMF). LOMMF is specifically designed, fabricated, and tested for efficient and reliable use with VCSELs. LOMMFs should have a well-designed and carefully controlled refractive index profile to ensure optimum light transmission with a VCSEL. Precise control of the refractive index profile minimizes modal dispersion, also known as Differential Mode Delay (DMD). This ensures that all modes, or light paths, in the fiber arrive at the receiver at about the same time, minimizing pulse spreading and, therefore, maximizing bandwidth. A good refractive index profile is best achieved through DMD testing. VCSELs and LOMMF provide tremendous flexibility and cost efficiency in "freeing up" bandwidth bottlenecks in the enterprise today and well into the future. LOMMF is completely compatible with LEDs and other fiberoptic applications (there are no special connectors or termination required and no effect on attenuation). LOMMF can be installed now and utilized at slower data rates until the need arises to increase network speed to 1 or even 10 Gb/s. At that point, you only need to upgrade the optics modules to VCSEL-based transceivers. There is no need to pull new cable. 3

Laser-Optimized Fiber Can you use any laser-optimized fiber for 10 Gb/s? No -- it is important to note that not all laser-optimized fiber is 10 Gb/s-capable. If 10 Gb/s capacity is in your future, you must make sure that the LOMMF you re installing now is 10 Gb/s-capable. The first laser-optimized fibers, introduced to the market in the mid-1990s, were designed for 1 Gb/s applications. Available in both 62.5/125 µm and 50/125 µm designs, these fibers extended the reach capability of 1 Gb/s systems beyond what the industry standards stated. For instance, OFS 1 Gb/s Laser Optimized 62.5 Fiber can go 300 meters in cost-effective, 1 Gb/s 850 nm (1000BASE-SX) systems. 50/125 fibers offer even greater performance, with a reach of 600 meters or more. These 1 Gb/s LOMMFs, coupled with 850 nm VCSELs, allow for the lowest systems cost for building backbones and short- to medium-length campus backbones. As attention turned to 10 Gb/s data rates, existing LOMMF (designed for 1 Gb/s speeds) did not provide the support needed for 300-meter backbone distances. Laser-optimized 62.5/125 fibers were limited to about 35 meters at 10 Gb/s, and laser-optimized 50/125 fibers to about 90 meters. Further refinement of the fiber s refractive index profile was necessary to achieve 10 Gb/s data rates on multimode fiber to distances of 300 meters and beyond. Fortunately, advancements in DMD testing developed by OFS enabled the necessary improvements to the fiber manufacturing process that would produce fiber with accurate, defect-free refractive index profiles. (During this development process, it became apparent that 62.5/125 fiber would not be capable of meeting the high performance demand for 10 Gb/s capability. 62.5/125 has inherently lower bandwidth than 50/125 fiber, because its larger core carries many more modes. More modes mean more modal dispersion and less bandwidth. As such, LOMMF for 10 Gb/s applications is only available with 50/125 µm fiber.) In 1999, the first laser-optimized fiber to support 10 Gb/s speeds up to 300 meters was introduced by OFS (part of Lucent Technologies at the time). Called LaserWave 300 Fiber, this fiber has a DMD controlled core and very high bandwidth at 850 nm (> 2000 MHz-km of Effective Modal Bandwidth, or "laser bandwidth"). * 4 FIBER FAQs

FIBER FAQs Laser-Optimized Fiber LaserWave 300 or LaserWave 550 fiber can be installed today and used with slower, LED-based systems. When 1 Gb/s capability is needed, the optical modules can be easily replaced and the same fibers will support 1 Gb/s transmission to 1000 meters or more. Finally, on the same fiber, the system can be upgraded to 10 Gb/s by again "swapping out" the optical modules. At each step, the advantages of lower cost 850 nm VCSEL technology can be realized. With an eye to the future, LaserWave fibers will even support 40 Gb/s, anticipated to be the next Ethernet speed. Coarse Wavelength Division Multiplexing (CWDM) will allow for this ultimate upgrade path by transmitting four different wavelengths at 10 Gb/s each. Reach at 40 Gb/s will be at least the same as today s 10 Gb/s reach. * These fibers are referred to as Laser-Optimized 50 µm Multimode Fiber in the TIA-568 standard and as OM3 in the ISO 11801-2nd Edition standards. We encourage the use of the term OM3 since it is simple and does not confuse this fiber with the 1 Gb/s Laser Optimized fibers. How do you measure bandwidth for laser-optimized fiber? Since LEDs have a uniform and consistent power profile that excites all the modes in a multimode fiber, the traditional OFL method of bandwidth measurement accurately predicts bandwidth of fiber for LED applications. But because VCSELs only excite some of the modes in a fiber, and in a varying manner, the OFL bandwidth measurement cannot predict what the fiber s bandwidth would be if the fiber were to be used in a VCSEL application. In an attempt to overcome this uncertainty, a Restricted Mode Launch (RML) method of measuring bandwidth was developed. This measurement technique is the same as OFL, but as the name suggests, a restricted (smaller) launch is used to light only some of the modes in the fiber. This restricted launch is intended to replicate a VCSEL, but test results can vary depending on exactly how the light source is coupled with the fiber. In other words, the actual bandwidth achieved in an installed system may differ from the RML tested bandwidth. For these reasons, RML is simply not a reliable predictor of a fiber s bandwidth. It should become clear now why fiber manufacturers developed laser-optimized fiber, and why DMD testing is so important. The refractive index has to be well designed and controlled to ensure that all modes exhibit minimal DMD and all arrive at the other end of the fiber at the same time. No matter which modes in the fiber are actually guiding the light, those modes will have minimal DMD and provide high bandwidth. 5

Laser-Optimized Fiber What should you look for in DMD testing? DMD testing provides such a clear picture of how individual mode groups carry light down the fiber, and which mode groups are causing DMD, that the standards require fiber to be DMD-tested to ensure adequate bandwidth to the rated distances for 10 Gb/s applications. Pioneered by Lucent s Bell Labs and perfected by OFS Labs (formerly part of Bell Labs), DMD testing involves transmitting short-duration, high-powered laser pulses in small steps across the entire core of the fiber. Each pulse excites only a few modes at each step, and the individual pulse shapes and arrival times are captured at the other end of the fiber. The DMD of the fiber is the difference between the earliest and latest arrival times of all pulses at all steps. From this information, adjustments can be made to the fiber manufacturing process to produce low DMD (high bandwidth) fiber. With a highly advanced process for making fiber, such as OFS patented MCVD process, DMD testing serves as a powerful process control tool to maintain a precise refractive index profile; so much so that OFS is able to specify tighter DMD in the center region of its fiber, where fiber manufactured by other processes can be prone to defects. 6 FIBER FAQs

For additional information please contact your sales representatives. You can also visit our website at www.ofsoptics.com/ofs-fiber or call 1.888.fiberhelp. For regional assistance, contact: North America Phone: 508.347.8590 Toll Free: 800.799.7732 Fax: 508.347.1211 Email: fibersalesnar@ofsoptics.com Caribbean, Latin America Phone: 508.347.8590 Fax: 508.347.1211 Email: fibersalescala@ofsoptics.com Europe, Middle East, Africa Phone: +45-43 48 3736 Fax: +45 4348 3444 Email: fibersalesmea@ofsoptics.com Asia Pacific Phone: +852 2836 7102 Fax: +852 2836 7101 Email: fibersalesap@ofsoptics.com Japan Phone: +81-3-3286-3424 Fax: +81-3-3286-3708 or 3190 Email: fibersalesjapan@ofsoptics.com China Phone: +86 10 6505 3660 Fax: +86 10 65059515 Email: fibersaleschina@ofsoptics.com LaserWave is a trademark of Furukawa Electric North America. OFS reserves the right to make changes to the prices and product(s) described in this document in the interest of improving internal design, operational function, and/or reliability. OFS does not assume any liability that may occur due to the use or application of the product(s) and/or circuit layout(s) described herein. This document is for informational purposes only and is not intended to modify or supplement any OFS warranties or specifications relating to any of its products or services. Copyright 2005 Furukawa Electric North America All rights reserved, printed in USA. OFS Marketing Communications