Power Separation Guidelines for SYSTIMAX Installations



Similar documents
Screened cable and data cable segregation

EN and EN : 2008 Integrated standards for telecommunications cabling installation

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

800 Communications Circuits

Specifying an IT Cabling System

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

Separation of power and information technology cabling

Chapter 9. Bonding and Grounding

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Article 10 - ADMINISTRATIVE SECTION

ELECTRICAL INSPECTION BULLETIN (Effective )

Standards. 5 ANSI/TIA/EIA-569-A (CSA T530)

Introduction to Data Centre Design

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

Session 14 Cable Support Systems

Minimum Standards for Data/Voice Infrastructure in New Building Construction

TC Grounding and Bonding for Telecommunications Systems

Code Compliance for Spring Steel Fasteners Based on the 2005 NEC

CommScope Intelligent Building Infrastructure Solutions (IBIS)

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

MASTER ELECTRICIAN CODE EXAMINATION EXAMINATION REFERENCE MATERIAL AND CONTENT OUTLINE. Answers to sample questions: CONTENT OUTLINE

Unified requirements for systems with voltages above 1 kv up to 15 kv

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

Excerpts from the Canadian National Building Code (NBC)

Electrical Grounding. Appendix C

BASIC NEC CODE RULES AND DESIGN PRACTICE

No Phone Line II-48 System

PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION

CHAPTER 2 EXAMPLES AND TABLES

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

Installation Guide Content for P250xV-240 microinverters

AC Module Installation Guide Content

Errata NFPA 70. Proposed 2014 Edition

CURRENT RATINGS MORE THAN A CABLE

Grounding & Bonding Why it is done And How to Install Properly

Top Commercial / Residential Electrical Requirements *

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND

The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022.

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

AC and DC Drive System Installation Information

Electrical Code (NEC) Snake Tray Cable Management Solutions

MOBILE HOME SERVICE REQUIREMENTS GAS

Structured Cabling, Earthing & Equipotential Bonding

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

Cabinets 101: Configuring A Network Or Server Cabinet

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Lightning Arresters P KVA P KVA. Description & Installation

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

Canopy Surge. User Manual

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

Voltage Drop. Voltage Drop 1

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

Shunt lock function 3066

Enphase Engage Cable and Accessories

Fundamentals of Power

WHITE PAPER Fire & safety performance standards

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

IRRIGATION PUMPING Table of Contents - Section 900

Power Distribution Considerations for Data Center Racks

Questions and Answers for Heating and A/C Contractors

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

Short Circuit Current Calculations

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Protect your home and family with Advanced Technology from Cutler-Hammer

No Phone Line System. Quick Start Guide NPL II. 1.0 Installation

Voltage Drop (Single-Phase)

2012 Electrical Code Changes Module 2 Sections 6-16

5SV Residual Current Protective Devices

LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

Model Number Electrical Compatibility Module Connector Type. M LL-S22 60 cell PV module MC-4 Type 2 Locking

Definition AC Power Distribution

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

Electrical Drawings - Table of Contents

Project files. Customer copy Legrand copy

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

Electrical Code Regulation

Transcription:

SYSTIMAX Solutions Power Separation Guidelines for SYSTIMAX Installations Design and installation guidelines August 2011 www.commscope.com

1.0 General These guidelines are based on extensive testing and modeling performed by CommScope Labs and by standards committees (especially by TIA in the US). The guidelines outline the minimum requirements for registration of SYSTIMAX installations for the 20-Year Extended Product Warranty and Applications Assurance Program. The exception is for installations with SYSTIMAX x297/x298 cables where the guidelines outline in Section 4.0 shall apply. Unless otherwise stated, the power cables are assumed to be non-armored. Applicable local or national safety regulations take precedence whenever their required separation distances are larger than those specified in this document. For example: In the UK, if no mechanical divider is present between the data and power cables, BS 6701 requires a minimum separation distance of 50 mm (2 in) for voltages less than 600 Va.c. In the USA, Article 800.52 of NEC Ed 2002 states the following for Class 1 circuits: o o Communications wires and cables shall be separated at least 50 mm (2 in) from conductors of any electric light, power, Class 1, non-power-limited fire alarm, or medium power network-powered broadband communications circuits. -- Exception No. 1: Where either (1) all of the conductors of the electric light, power, Class 1, non-power-limited fire alarm, and medium power network-powered broadband communications circuits are in a raceway or in metal-sheathed, metal-clad, nonmetallicsheathed, Type AC, or Type UF cables, or (2) all of the conductors of communications circuits are encased in raceway. -- Exception No. 2: Where the communications wires and cables are permanently separated from the conductors of electric light, power, Class 1, non-power-limited fire alarm, and medium power network-powered broadband communications circuits by a continuous and firmly fixed non-conductor, such as porcelain tubes or flexible tubing, in addition to the insulation on the wire. In the US, ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers and ANSI/TIA-1005 Telecommunications Infrastructure Standard for Industrial Premises provide power separation requirements in Clause 7.3 and Clause 5.2 respectively. These requirements are fully in alignment with SYSTIMAX guidelines and can be adhered to except for 1 to 15 power cables where SYSTIMAX guidelines will apply. In Europe, EN 50174-2:2000 has been revised and the new published standard (EN 50174-2:2009) specifies separation requirements in Clause 6 that are similar to SYSTIMAX guidelines. Section 4.0 of this document will correlate SYSTIMAX guidelines with EN 50174-2:2009 requirements. www.commscope.com 2

2.0 Power Cables Rating: Va.c 415V and I 100A The following guidelines are applicable to power cables rated 415 volts (Va.c) or less and 100 amperes (A) maximum. Unless otherwise stated, the power cables are assumed to be non-armored. For SYSTIMAX installations of cable lengths of up to 90 meters (295 ft), zero separation distance is required for branch/radial circuits that meet all the following conditions: Limited to one power cable rated at 110/240V, 20A, single-phase (phase-to-neutral or earth). The power cable or cord must have Live (L), Neutral (N) and Earth (E) conductors contained within a common sheath (that is, sheathed power cables). If loose (individual) conductors are used as power cables, these conductors must be bunched or maintained close together to minimise inductive coupling. A ring circuit can be considered to be equivalent to two branch circuits, e.g. a ring circuit of 40A is considered to be equivalent to two branch circuits of 20A each. In this case, the guidelines for 20A apply. Powering typical office equipment. The main electrical service entrance is protected with surge arresters (transient voltage surge suppressor) according to the applicable local/national codes (for equipment safety). In addition, all the following requirements shall also be met: The building itself shall be suitably protected from direct lightning strikes according to the applicable local or national codes. Multi-channel outlet boxes or compartments where individual power conductors and Category 5 or higher cabling are introduced to serve a workstation require 6 mm (0.25 in) separation. If loose, open (spaced) power conductors are used and not bunched or maintained close together, a minimum separation of 50 mm (2 in) is required. For all fluorescent light fixtures and associated power cables (in the vicinity of the light fixtures see Figure 1), the separation distance is 50 mm (2 in). Power and SYSTIMAX cables shall cross over at right angles. However, a bridge may be required to meet national/local safety codes. Figure 1: Example of fluorescent lighting fixtures www.commscope.com 3

The following considerations should also be given: If multi-channel plastic raceways (i.e. compartmentized plastic trunking) are used, the power cables should be installed in the bottom compartment and the data cables in the top or vice versa (as per IEC/EN 60364-5-52 guidelines). If loose (individual) power conductors are used, they must be bunched or maintained close together within the trunking. The use of surge suppressors in branch circuits can further limit the propagation of electrical surges. These must be installed according to the applicable local/national codes (for equipment safety). Table 1 provides additional separation requirements beyond those given above. This table is normally applicable to cabling in the horizontal and work area subsystems. The following points should be noted: The power conductor cross-sectional area is the minimum requirement for use. S is the required separation distance between the power and data cables. L is the total data cable horizontal length and NOT just the coupled length (i.e. length parallel to the power cable). Testing carried out by TIA in the US indicated that coupled length beyond 10 meter (33 ft) has little effect on frame errors. Normal power operating condition is assumed. If the power cables are armoured, then the separation distances provided in Table 1 can be halved. However, the armouring must completely surround the cable (except at the socket) and must be properly bonded and earthed in accordance with the applicable local or national regulations. If Table 1 is not applicable, the following requirements shall apply: Feeder power circuits (i.e. supply for branch circuits, etc.) or large groupings (> 30 power cables) of branch circuits shall maintain a minimum of 600 mm (2 ft) separation from data cables and patch panels in open frames (Figure 2). This situation typically arises in the communication/equipment rooms where the power distribution units (PDUs) are located as shown in Figure 3. The 600 mm (2 ft) separation distance can be halved, i.e. 300 mm (1 ft) if the power cables are armoured. These power cables can be loose-laid or installed on cable baskets (Figure 2). Alternatively, the 300 mm (1 ft) separation is also applicable if the power cables and/ or data cables are installed on separate cable trays. These trays can have slots for easy attachment of the cables. These slots must be small, i.e. 50 mm (2 in) x 10 mm (0.4 in), and parallel to the axis of the tray as shown in Figure 4. Cable baskets shall not be used. Figure 5 provides an example of a typical installation requirement. The various separation distances are derived as follow: In the vicinity of the equipment room subsystem, there are 72 and 36 power cables. Hence 600 mm (2 ft) separation distance is required. In the horizontal subsystem, there are 9 power cables. Hence, from Table 1, the separation distance is 100 mm (4 in). In the work area subsystem, there are 2 power cables. Hence, from Table 1, the separation distance is 4 mm (0.16 in). At the multi-channel outlet boxes, the separation distance is 6 mm (0.25 in). www.commscope.com 4

Table 1: Additional Separation Guidelines for 110/240V, Single-Phase (Phase-to-Neutral or Earth) Power Cables. Total Data Cable Total Number Power Conductor Maximum Current Horizontal of Power Separation Cross-sectional Area Rating, I (A) Length, L Cables, N Distance, S 1 mm 2 (0.0016 in 2 ) 20 90 m (295 ft) 1 0 1 mm 2 (0.0016 in 2 ) 20 90 m (295 ft) 2 0.004 m (0.16 in) 1 mm 2 (0.0016 in 2 ) 20 90 m (295 ft) 30 0.1 m (4 in) Figure 2: Separation requirements between power cables and data cables www.commscope.com 5

Note 1: If armoured power circuits are used, the separation distance can be reduced to 300 mm (1ft). Figure 3: Separation requirements between PDU power cables and data cables/patch panels Note 1: If armoured power circuits are used, the separation distance can be reduced to 300 mm (1ft). In this situation, cable baskets can be used. Figure 4: Separation requirements when using cable trays

Figure 5: Example of an installation requirement 3.0 Power Cables Rating: Va.c > 415V and/or I > 100A If the conditions and/or separation distances provided in Section 2 cannot be achieved, then zero separation distance is permitted when the data cables and/or the power cables are enclosed in metallic trunking or conduit. All the following conditions then apply: The metallic trunking/conduit must completely enclose the cables and be continuous. The metallic trunking/conduit must be properly bonded and earthed in accordance with the applicable local or national regulations, for example, IEE Wiring Regulations (BS 7671) in the UK or NEC in the USA. The trunking/conduit must be at least 1 mm (0.04 in) thick if made of galvanised (low carbon) steel or 2 mm (0.08 in) thick if made of aluminium. However, if the above conduit/trunking thickness cannot be achieved, then Table 2 shall apply. www.commscope.com 7

Table 2: Trunking/conduit material and thickness requirements Separation Distance, mm (inches) Galvanised Steel Thickness, mm (inches) Aluminium 600 (24) 0.05 (0.002) 0.1 (0.004) 300 (12) 0.1 (0.004) 0.2 (0.008) 150 (6) 0.2 (0.008) 0.5 (0.02) Table 75 (3) 2: Trunking/conduit 0.5 (0.02) material and thickness requirements 1 (0.04) 0 (0) 1 (0.04) 2 (0.08) Fibre cabling is recommended if none of the above conditions can be achieved. 4.0 EN 50174-2:2009 Standard and SYSTIMAX Guidelines The EN 50174-2:2009 standard provides power separation requirements in Clause 6. In this standard, the minimum separation requirement A is calculated by multiplying the minimum separation S (obtained from Table 4) by the power cabling factor P (obtained from Table 5). The value of S depends upon the segregation classification of the IT cable of Table 3. This segregation classification depends on the transverse conversion loss (TCL) for unscreened balanced (U/UTP) cables or coupling attenuation for screened balanced (F/UTP, F/FTP, S/FTP) cables. The segregation classification of SYSTIMAX cables is given in Table 3. Table 3: EN 50174-2 segregation classification for SYSTIMAX cables SYSTIMAX Cables x061 (U/UTP) x071 (U/UTP) x091 (U/UTP) x291 (F/UTP) x297 (S/FTP) x298 (S/FTP) EN 50174-2 Segregation Classification b c c c d d Table 4 provides the minimum separation requirement A, according to EN 50714-2 and compares it with the minimum separation guidelines from SYSTIMAX. Hence for 230V, 1-phase and 20A electrical circuits, the power separation requirements of EN 50174-2 can be adhered to. www.commscope.com 8

Table 4: Comparing EN 50174-2 and SYSTIMAX minimum separation requirements Minimum Separation Requirement, A (mm) for 230V, 1-phase, 20A electrical circuits Quantity of circuits b (x061) c (x071, x091, x291) SYSTIMAX 1 to 3 20 10 10 4 to 6 40 20 20 7 to 9 60 30 30 10 to 12 80 40 40 13 to 15 100 50 50 16 to 30 200 100 100 31 to 45 300 150 150 46 to 60 400 200 200 61 to 75 500 250 250 > 75 600 300 300 www.commscope.com 2012 CommScope, Inc. All rights reserved. Visit our website at www.commscope.com or contact your local CommScope representative or BusinessPartner for more information. All trademarks identified by or TM are registered trademarks or trademarks, respectively, of CommScope, Inc. TP-106296-EN 11/12