80UHG. Service Literature



Similar documents
G26 Corp L11 Revised LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS


PRODUCT DESIGN. 5. Furnace awaits call from thermostat.

Commercial Gas Furnace Upflow

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Inch PowerVent LED Indicator Explanations & Troubleshooting Table

Fossil fuel heating equipment

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE

Revised G24M SERIES UNITS

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

Cooling Capacity CFM in. w.c. (125 Pa)

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard


SL280UHV SERIES GAS FURNACE WARNING

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Communicating Controls Service Manual

37E73A-903 & 906 INTELLI-VENT

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Cooling Capacity CFM in. w.c. (125 Pa)

Model Description / Applications. Intermittent Pilot Gas Ignition Control

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

G670 Intermittent Pilot Ignition Controls

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

Cooling Capacity CFM in. w.c. (125 Pa)

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

WARNING CAUTION 21V51U-843 DESCRIPTION PRECAUTIONS

TECHNICAL MANUAL GDS8 & GHS8

12288 Side Road 22, Wainfleet, Ontario Canada L0S 1V0 Phone: Fax:

G9MXE. Product Specifications

F9MXE. Product Specifications

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

ECM. Service Guide.

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08

, User s Manual

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

Air Conditioning Sign-Off Sheet

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

INSTALLER S SYSTEM SETUP GUIDE

DVI 980/982 (Honeywell Nr. S4865) Gas Burner Safety Control

OPERATIONAL CHECKS & SAFETY CIRCUIT DESCRIPTION

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND

Flame Conductivity VS Flame Rectification Systems

CONTROLS KITS AND ACCESSORIES /2014 Supersedes10/2014

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

TB-A A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

Heating Basics Gas Valve Systems

Commercial Gas Water Heater

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual

EFFECTIVE OCTOBER Atwood Furnaces. and Digital Thermostats

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book

Commercial Gas Water Heaters

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

User s Information/Installation Instructions

INTELLI-VENT CONTROL INFORMATION When Used On Gas, Residential, Power Vented Water Heaters

Certification Information. Qualifications. Test Specifications. Gas Furnaces Industry References

Eclipse Veri-Flame Single Burner Monitoring System Model 5600 Version 1

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

ELITE SERIES Up Flow / Horizontal Precision Speed Blower

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Veri-Flame Single Burner Monitoring System

Installation Instructions

E2 Series Electric Furnaces

WHITE-RODGERS COMFORT-SET 90 SERIES

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

HEAT HEAT COOL HEAT PUMP COOL

PANASONIC TROUBLE SHOOTING GUIDE

For installation guide see reverse of book

MODEL 2202IQ (1991-MSRP $549.00)

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function

LOBOY 16 AIR CONDITIONERS

SERVICE INSTRUCTIONS

How To Control A Thermostat

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

M1 Series. M1G and M1M Furnaces. Service Manual

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

ICM1 / ICM2 CAUTION CAUTION. Service Literature Variable Speed Motors. I Introduction

Factory owners must ensure the boiler is:

Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement.

How To Buy A Lennox Power System

INSTALLER'S GUIDE. Supplementary Electric Heaters 18-GJ08D1-1. Table of Contents

ARMSTRONG AIR HEAT PUMPS


USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

Annual Service Agreement

DKG 972 Gas Burner Safety Control

EP A2 (19) (11) EP A2 (12) EUROPEAN PATENT APPLICATION. (43) Date of publication: Bulletin 2011/32

G6 Series. 90+ High Efficiency Upflow/Downflow Models. Service Manual

LANDFILL GAS ENCLOSED FLARE SYSTEM

Evaluate, Clean, and Tune Guidance

USER S INFORMATION MANUAL

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

How to Measure HVAC System Airflow

Local Dealer:

Transcription:

Service Literature Corp. 9728 L12 Revised 01 2002 80UHG 80UHG series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with tubular heat exchangers formed of aluminized steel. 80UHG units are available in heating capacities of 45,000 to 120,000 Btuh and cooling applications up to 5 tons. Refer to Engineering Handbook for proper sizing. Units are factory equipped for use with natural gas. Kits are available for conversion to LPG operation. 80UHG 1 model units use electronic (direct spark) ignition. 80UHG 2 and 3 model units are equipped with the Lennox SureLight silicon nitride ignition system. The 80UHGX unit meets the Califor nia Nitrogen Oxides (NO x ) Standards and California Sea sonal Efficiency requirements. All units use a redundant gas valve to assure safety shut off as required by A.G.A. or C.G.A. Units may be installed in upflow or horizontal posi tion. All specifications in this manual are subject to change. Pro cedures outlined in this manual are presented as a recom mendation only and do not supersede or replace local or state codes. In the absence of local or state codes, the guidelines and procedures outlined in this manual (except where noted) are recommended only and do not constitute code. TABLE OF CONTENTS Introduction.................................... 1 Specifications.................................. 2 Blower Data................................. 3 4 High Altitude................................... 4 Parts Identification............................ 5 6 I Unit Components........................... 6 15 II Installation.................................. 15 III Start Up.................................... 15 IV Heating System Service Checks........... 16 17 V Typical Operating Characteristics.............. 18 VI Maintenance............................ 19 20 VII Wiring and Sequence of Operation......... 21 28 VIII SureLight Troubleshooting Guide.......... 29 34 Page 1 1999 Lennox Industries Inc. Litho U.S.A.

Page 2

Page 3

Page 4

3 Furnace Control (A3) 80UHG 2, 3 Models 80UHG 2 and 3 model units are equipped with the Len nox SureLight ignition system. The system consists of ignition control board (figure 6 with control terminal desig nations in table 4) and ignitor (figure 7). The board and ig nitor work in combination to ensure furnace ignition and ignitor durability. The SureLight integrated board controls all major furnace operations. The board also features two LED lights for troubleshooting and two accessory termi nals rated at (4) four amps. See table 3 for troubleshoot ing diagnostic codes. Table 1 and 2 show jack plug termi nal designations. Units equipped with the SureLight board can be used with either electronic or electro me chanical thermostats without modification. The Sur elight ignitor is made of durable silicon nitride. Ignitor longevity is also enhanced by voltage ramping by the control board. The board finds the lowest ignitor tempera ture which will successfully light the burner, thus increas ing the life of the ignitor. Each time power is applied to the furnace, the SureLight board performs a selfcheck in cluding energizing the combustion air blower for a period of 1 second. PIN # TABLE 1 SureLight BOARD J156 (J2) TERMINAL DESIGNATIONS FUNCTION 1 Combustion Air Inducer Line 2 Ignitor Line 3 Combustion Air Inducer Neutral 4 Ignitor Neutral PIN # TABLE 2 SureLight BOARD J58 (J1) TERMINAL DESIGNATIONS FUNCTION 1 Primary Limit / Pressure Switch Out 2 Secondary Limit 3 24V 4 Not Used 5 Rollout Switch In 6 24V 7 Primary Limit In 8 Ground 9 Gas Valve In 10 Pressure Switch In 11 Rollout Switch Out 12 Gas Valve Out a Electronic Ignition (See Figure 5) On a call for heat the SureLight control monitors the com bustion air inducer pressure switch. The control will not be gin the heating cycle if the prove switch is closed (by passed). Once the prove switch is determined to be open, the combustion air inducer is energized. When the differ ential in the prove switch is great enough, the prove switch closes and a 15 second pre purge begins. If the prove switch is not proven within 2 1/2 minutes, the control goes into Watchguard Pressure Switch mode for a 5 minute re set period. After the 15 second pre purge period, the SureLight igni tor warms up for 20 seconds during which the gas valve opens at 19 seconds for a 4 second trial for ignition. The ignitor stays energized for the first second of the 4 second trial. 80UHG units equipped with control 10M9301: ignitor remains energized during the 4 second trial until flame is sensed. If ignition is not proved during the 4 second peri od, the control will try four more times with an inter purge and warm up time between trials of 35 seconds. After a to tal of five trials for ignition (including the initial trial), the control goes into Watchguard Flame Failure mode. After a 60 minute reset period, the control will begin the ignition sequence again. The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ig nitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the low est power is determined and the cycle begins again. b Fan Time Control The fan on time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. See figure 4. FANOFF TIME ADJUSTMENT 60sec. 90sec. 120sec. 180sec. To adjust fan off timing, flip dip switch to desired setting. FIGURE 4 Page 7

The SureLight board is equipped with two LED lights for troubleshooting. The diagnostic codes are listed below in table 3. TABLE 3 DIAGNOSTIC CODES MAKE SURE TO ID LED S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT. LED #1 LED #2 DESCRIPTION SIMULTANEOUS SLOW FLASH SIMULTANEOUS FAST FLASH SLOW FLASH OFF ALTERNATING SLOW FLASH SIMULTANEOUS SLOW FLASH SIMULTANEOUS FAST FLASH ON SLOW FLASH ALTERNATING SLOW FLASH Power Normal operation Also signaled during cooling and continues fan. Normal operation signaled when heating demand initiated at thermostat. Primary or Secondary limit open. Units with board 12L69: Limit must close within 5 trials for ignition or board goes into one hour limit Watchguard. Units with board 56L84: Limit must close within 3 minutes or board goes into one hour limit Watch guard. Pressure switch open or has opened 5 times during a single call for heat; OR: Blocked inlet/exhaust vent; OR: Condensate line blocked; OR: Pressure switch closed prior to activation of combustion air blower. Watchguard burners fail to ignite. SLOW FLASH OFF Flame sensed without gas valve energized. ON SLOW FLASH Rollout switch open. OR: 9 pin connector improperly attached. ON ON OFF ON OFF ON Circuit board failure or control wired incorrectly. FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral. SLOW FLASH FAST FLASH Low flame signal. Measures below 0.2 microamps. Replace flame sense rod. ALTERNATING FAST FLASH ALTERNATING FAST FLASH Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR: Open ignitor circuit. NOTE Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.15 microamps SureLight Control Ignition Sequence (Control 56L8401 ONLY) ÉÉ ÉÉ ON OFF DEMAND CA BIGNITOR GAS VALVE INDOOR BLOWER 1 15 3435 38 80 5 SEC Pre Purge Ignitor Warmup Trial for Ignition Delay Purge ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉ *Blower on time will be 45 seconds after ignition. Blower off time will depend on OFF TIME" Setting. FIGURE 5 Blower On" Post Page 8

180 60 120 90

NOTE When unit is initially started, steps 1 through 11 may need to be repeated to purge air from pilot line.

NORMAL HEATING MODE HEATING SEQUENCE CONTINUED ABNORMAL HEATING MODE 15SECOND COMBUSTION AIR INDUCER PREPURGE INITIATED BY CLOSED PRESSURE SWITCH. IGNITOR WARMUP 20 SECONDS. 4SECOND TRIAL FOR IGNITION. GAS VALVE OPENS. IGNITOR ENERGIZED FOR 1 SECOND AFTER VALVE OPENS. CONTROL 10M9301: IGNITOR ENERGIZED DURING TRIAL UNTIL FLAME SENSED. FLAME STABILIZATION PERIOD. 4 SECONDS FLAME RECTIFICATION CURRENT CHECK. CAN FLAME BE PROVEN WITHIN 4 SECONDS AFTER GAS VALVE OPENS? (0.15 microamps) FLAME PRESENT? NO NO NO IS VOLTAGE ABOVE 75 VOLTS? NO NO IS THERE A PROPER GROUND? NO IS IGNITOR INTACT AND CONNECTED? GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER OFF. HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND? WATCHGUARD MODE. GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WATCHGUARD FAILURE CODE. IS 60MINUTE RESET PERIOD COMPLETE? HAS CONTROL RESET IGNITION SEQUENCE FOUR TIMES? LEDS SIGNAL ALTERNATING FAST FLASH NO NO FLAME SIGNAL ABOVE 0.2 MICROAMPS? INDOOR BLOWER ON DELAY BEGINS (45 seconds.) PRIMARY AND SECONDARY LIMIT SWITCHES CLOSED? NO NO LOW FLAME SIGNAL (Does not affect operation of control) LED #1 SLOW FLASH LED #2 FAST FLASH GAS VALVE DE ENERGIZED. COMBUSTION AIR INDUCER DE ENERGIZED. INDOOR BLOWER ON UNTIL SWITCH CLOSES. LED #1 SLOW FLASH. LED #2 ON. IS LIMIT SWITCH CLOSED? HAS PRIMARY SECONDARY LIMIT RESET (CLOSED) WITHIN 3 MINUTES? LIMIT SWITCH WATCHGUARD MODE. GAS VALVE OFF. COMB. AIR INDUCER OFF. INDOOR BLOWER OFF WITH DELAY. LED#1 SLOW FLASH LED#2 ON. IS 60 MINUTE RESET PERIOD COMPLETE? NO ROLLOUT SWITCH CLOSED? COMBUSTION AIR PRESSURE SWITCH CLOSED? THERMOSTAT DEMAND SATISFIED. LED #1 & #2 SIMULTANEOUS SLOW FLASHES. COMB. AIR INDUCER CONTINUES 5SECOND POST PURGE AFTER T STAT DEMAND IS SATISFIED. INDOOR AIR BLOWER COMPLETES SELECTED OFF" DELAY BEFORE SHUTTING OFF. NO NO GAS VALVE POWER OFF. COMBUSTION AIR INDUCER POWER ON. INDOOR BLOWER ON LED #1 ON. LED #2 SLOW FLASH. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERUPTED OR THERMOSTAT IS CYCLED OFF/ON FOR 1 TO 20 SEC. GAS VALVE DE ENERGIZED. COMBUSTION AIR INDUCER ON. INDOOR BLOWER OFF WITH DELAY LED #1 OFF. LED #2 SLOW FLASH. HAS CAB SWITCH CLOSED IN 2.5 MINUTES? NO 5MINUTE PRESSURE SWITCH WATCHGUARD MODE. Page 26