Veri-Flame Single Burner Monitoring System
|
|
|
- Mark Sanders
- 10 years ago
- Views:
Transcription
1 Instruction Manual 88 6//06 Veri-Flame Single Burner Monitoring System Model 5600 Version.2 Modulation Model No Purge Model Purge Model
2 Copyright Disclaimer notice Copyright 2006 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by federal regulation and shall not be copied, distributed, transmitted, transcribed or translated into any human or computer language, in any form or by any means, to any third parties, without the express written consent of Eclipse, Inc., Rockford, Illinois, U.S.A. In accordance with the manufacturer s policy of continual product improvement, the product presented in this brochure is subject to change without notice or obligation. The material in this manual is believed adequate for the intended use of the product. If the product is used for purposes other than those specified herein, confirmation of validity and suitability must be obtained. Eclipse, Inc. warrants that the product itself does not infringe upon any United States patents. No further warranty is expressed or implied. We have made every effort to make this manual as accurate and complete as possible. Should you find errors or omissions, please bring them to our attention so that we may correct them. In this way we hope to improve our product documentation for the benefit of our customers. Please send your corrections and comments to our Marketing Communications Manager. Liability and Warranty It must be understood that Eclipse s liability for its products, whether due to breach of warranty, negligence, strict liability, or otherwise, is limited to the furnishing of burner monitoring system replacement parts and Eclipse will not be liable for any other injury, loss, damage or expenses, whether direct or consequential, including but not limited to loss of use, income of, or damage to material arising in connection with the sale, installation, use of, inability to use or the repair or replacement of Eclipse products. Eclipse, Inc., for a period of one year from shipment, warrants each Veri-Flame burner monitoring system to the original purchaser to be free from defects in material and workmanship under normal use as defined hereafter. Any operation expressly prohibited in this Guide, any adjustment or assembly procedures not recommended or authorized in these instructions, shall void the warranty.
3 About this manual Audience Scope Document Conventions This manual has been written for the people who select and install the product and the technicians who work on it. They are expected to have previous experience with this kind of equipment. This manual contains essential information for the proper installation and operation of the Eclipse Veri-Flame Burner Monitoring System. Following the instructions in this manual should assure trouble-free installation and operation of the monitoring system. Read this manual carefully. Make sure that you understand its structure and contents. Obey all the safety instructions. Do not deviate from any instructions or application limits in this manual without written consent from Eclipse Combustion, Inc. If you do not understand any part of the information in this manual, do not continue. Contact your Eclipse sales office or Eclipse Combustion, Inc., Rockford, Illinois. There are several special symbols in this document. You must know their meaning and importance. The explanation of these symbols follows. Please read it thoroughly. Danger: Indicates hazards or unsafe practices which WILL result in severe personal injury or even death. Only qualified and well trained personnel are allowed to carry out these instructions or procedures. Act with great care and follow the instructions. Warning: Indicates hazards or unsafe practices which could result in severe personal injury or damage. Act with great care and follow the instructions. Caution: Indicates hazards or unsafe practices which could result in damage to the machine or minor personal injury. Act carefully. Note: Indicates an important part of the text. Read the text thoroughly.
4 How to get help If you need help, you can contact your local Eclipse Combustion sales office. You can also contact Eclipse Combustion, Inc. at: 665 Elmwood Road Rockford, Illinois 603 USA Phone: Fax:
5 Table of Contents About this manual... 3 Table of contents Introduction... 8 Product Description... 8 Specifications... 9 Introduction... 9 Specifications... 9 Dimensions... 9 DIP Switch Selection... 2 Introduction... 2 DIP Switch Location... 2 DIP Switch Access... 2 No Purge DIP Switch Settings... 2 Modulation & Purge DIP Switch Settings... 3 Function Summary... Introduction... Standard Features... Combustion Air Flow Check... Main Fuel Valve Closed switch... Low Fire Start... High Fire/High Fire Purge Check... Recycle Mode... Pilot Test Mode... Interrupted or Intermittent Pilot... 5 Post Purge... 5 Spark, Pilot Flame & Main Flame Separation... 5 System Error & Lockout Conditions... 5 High to Low Fire Purge Modulation Capability with High to Low Fire Position Switch Interlocks... 6
6 5 6 7 Optional Features... 6 Pilot Test Mode Sequence... 6 Air Switch Input Hold... 6 Remote Display & Power Supply... 6 Status Lights & Push-buttons... 7 Interlocks Closed... 7 Air Failure... 7 System Error... 7 Burner On... 7 Flame Failure... 7 Low Fire... 7 High Fire... 7 Auto... 7 Test/Reset... 7 System Installation... 8 Introduction... 8 Interlocks and Limit Switch Input... 8 Combustion Air Switch Input... 8 Ignition Wiring... 8 Low Fire Input... 9 Main Valve Closed switch... 9 High Fire Input... 9 Remote Reset... 9 Remote Display & Power Supply... 9 Purge and No Purge Wiring Diagram (Figure 5.) Modulation Wiring Diagram (Figure 5.2) Typical Connections for all Models (Figure 5.3)... 2 Sensor Installation... 2 Introduction... 2 Sensor Wiring... 2 Flame Rods Scanners Scanner Sighting Considerations Test Procedures Introduction Flame Signal Strength Minimum Pilot Test Pilot Flame Failure Test Main Flame Failure Test Spark Sighting Test Limits & Interlock Tests
7 8 9 Maintenance & Troubleshooting Introduction Maintenance Monthly Checklist Yearly Checklist Troubleshooting LED Status LED Status & Conditions for No Purge Models (Table 8.) LED Status & Conditions for Purge Models (Table 8.2)... 3 LED Status & Conditions for Modulation Models (Table 8.3) Remote Display Messages Introduction Veri-Flame Operating Sequence (Table 9.)... 3 Remote Display Diagnostic Messages (Table 9.2) Appendix... Conversion Factors... Illustrated Parts List
8 Introduction Product Description The Eclipse Combustion Veri-Flame Single Burner Monitoring System controls the start-up sequence and monitors the flame of single gas, oil, or combination gas/oil burners. There are three different models to the Veri-Flame line: the no purge, the purge and the modulation models. Each model features field selectable trial for ignition (TFI). Each model is also available for use with four types of flame sensor: ultraviolet (UV), self-check UV, solid state UV/IR and flame rod. Required components are the Veri-Flame, matching wiring base and a flame sensor. Optional components include a remote display and cable, tester, and various scannner accessories. The Veri-Flame No Purge and Purge models are available in three different series 5602, 5603 and The 5602 Series is UL listed, CSA certified, FM approved and GE GAP acceptable; the 5605 Series is UL listed, FM approved and GE GAP acceptable. The 5603 Series is for 20VAC applications and is FM approved. Please see instruction manual 88-2 for European CE marked versions. The Veri-Flame Modulation model is available in two different series: 5602 and Both series are capable of modulation (high and low fire purging). The 5602 Series is UL listed, CSA certified, FM approved and GE GAP acceptable. The 5603 Series is for 20VAC and is FM approved. Figure. Veri-Flame Single Burner Monitoring System (Purge Unit Shown) 8
9 Specifications 2 Introduction Specifications This section gives a detailed overview of Veri-Flame specifications and dimensions. PARAMETER DESCRIPTION Supply Series 5602 & 5605: 20 VAC (+0%, -5%), 50/60 Hz standard. Series 5603: 20 VAC (+0%, -5%), 50/60 Hz standard. Internal power consumption: 2 VA (excluding external connected loads). Temperature Ranges Unit Model Nos. Temperature Range Veri-Flame All Models -0 to +60 C (-0 to +0 F) 90 U.V. Scanner A -20 to +60 C (0 to 0 F) U.V. Scanner to +25 C (0 to +257 F) NEMA UV Scanner N -20 to +25 C (0 to +257 F) UV/IR Scanner SC -20 to +80 C (0 to +76 F) Self-Check U.V to +60 C (0 to +0 F) Remote Display 5602DBP 0 to 50 C (32 to 22 F) Flame Failure Response 3 seconds ±0.5 seconds. Trial For Ignition (TFI) Pilot Interrupt (if selected) 0 seconds. No Purge & Purge Models: Series 5602 & 5603: 5 or 0 seconds selectable. Series 5605: 0 or 5 seconds selectable. Modulating Model: 5 or 0 seconds selectable Purge Time Selectable from seconds in 5 second increments. Output Ratings for 20 VAC (maximum total connected load not to exceed 5 amps)* Output Ratings for 20 VAC (maximum total connected load not to exceed 5 amps)* UL, CSA Relay Contact Rating Function Terminals Inductive Load Resistive Load Gas Valve 3, 5 75VA, /0 HP 0 amps Ignition 375 VA 0 amps Motor or Contactor 8 70 VA, /2 HP 6 amps Control Signal A, 0,, 2, 3 75VA 0 amps Relay Contact Rating Function Terminals Resistive Load Valves, Ignition 3,, 5, 5 amps Motors or Contactor 8 6 amps Alarm A 5 amps Control 0,, 2, 3 5 amps *Resistive loads have inrush currents approximately the same as steady state operation. The inductive inrush current must be less than 0 timesthe rating. The inrush current must not be applied more than once every 5 seconds. (continued onto next page) 9
10 Specifications (continued) Parameter Approvals (See chart below.) Shipping Weight Description No Purge & Purge Models: Series 5602: UL listed, CSA certified, FM approved and GE GAP acceptable. Series 5603: FM approved. Series 5605: UL listed, FM approved and GE GAP acceptable. Modulating Models: Series 5602: UL recognized (must be mounted in panel), CSA certified, FM approved and GE GAP acceptable. Series 5603: FM Approved.. kilograms (3 lbs.) for all Veri-Flame models. 0.9 kilograms (2 lbs.) for Models & bases..2 kilograms (2.6 lbs.) for Model base. Approval Information UL Listed, File MP537 UL Recognized, File MP537 CSA Certified, File FM Approved, File Dimensions Veri-Flame Unit/All Models 76mm (3") 33mm (5-/") Square Veri-Flame Bases/Purge & No Purge Models Model Number Model Number mm (5") Square 5.5mm (7/32") Dia. Mounting Holes () Knockouts (0) for 3mm (/2" Conduit 27mm (5") Square 38mm (-/2") 02mm (") Square 3mm (/2") 02mm (") Square 9mm (3/") 2mm (-7/8") 38mm (-/2") 0
11 Dimensions (continued) Veri-Flame/Modulating Model with Base Model Number mm (5/6") 25mm (") 7mm (6-3/") 6mm (-9/6") A D S2 S mm (-9/6") 0mm (3/8") 5mm (3/6") 23mm (8-3/8") Remote Display Model Number 5602-DBP 02mm (") Square * 5mm (2-/8") 89mm (3-/2") Square * = Alternate Mounting Locations * Mounting Bracket & Screw (2) Wiring Terminals (2) Ground Screw Contrast Adjustment Screw
12 DIP Switch Selection 3 Introduction This section details the location, selection and description of the Veri-Flame DIP switches, which allow for sequence and timing functions as well as system configuration. Caution To avoid electric shock, shut off the power supply when installing or removing any control device. Flame monitoring systems must be installed by a qualified, licensed technician. DIP Switch Location DIP Switch Access No Purge DIP Switch Settings Modulation & Purge DIP Switch Settings All of the DIP switches are located in the back of each Veri-Flame unit (see Figure 3. on page 3, or the photograph on page 8). To gain access to the DIP switches, the Veri-Flame must be separated from the back box (for visual reference, please refer to Dimensions on page 0). This separation will expose the DIP switches on the back of the Veri-Flame unit. No Purge models of the Veri-Flame only use three of the eight DIP switches, as shown in the labels in Figure 3.2 on page 3. They are as follows: SW: Recycling mode selection (On = Recycling; Off = Non-recycling) SW2: Pilot selection (On=Intermittent, where pilot remains on during burner cycle; Off =Interrupted, where pilot valve closes after main burner is established). SW3: Trial-for-ignition (TFI) range selection (For 5602/5603 units: On =0 seconds; Off =5 seconds. For 5605 units: On =0 seconds; Off =5 seconds). Modulation and purge models of the Veri-Flame use all of the eight DIP switches, as illustrated in Figure 3.2 on page 3. They are as follows: SW: Recycling mode selection (On = Recycling; Off = Non-recycling) SW2: Pilot selection (On=Intermittent, where pilot remains on during burner cycle; Off =Interrupted, where pilot valve closes after main burner is established). SW3: Trial-for-ignition (TFI) range selection (For 5602/5603 units: On=0 seconds; Off =5 seconds. For 5605 units: On =0 seconds; Off =5 seconds). SW through 7: Purge time selection. Total purge time is the sum of each switch selected. If all are set off, the trial for ignition starts when the air switch input comes on. SW8: Post purge selection. (On=5 second post purge). 2
13 Figure 3. DIP Switch Location Close-up of DIP switches on back side of all Veri-Flame models. Figure 3. 2 DIP Switch Labels with Selections No Purge Models Purge Models Modulation Models 3
14 Function Summary Introduction Standard features Interlocks and Limit Switch Input (Terminal 7) Combustion Air Switch Input (Terminal 6) Main Fuel Valve Closed Switch (Terminal V) Low Fire Start This section describes the features of the Veri-Flame. It is divided into three categories: Standard features, Optional features and the LED Indicator Lights on the front cover. Refer to Figure 5.5 for sequence diagrams. The following function features are standard on the Veri-Flame models as noted: This input is considered the normal operation control or run input to the Veri-Flame system. Interlocks are generally pressure or temperature switches which, when activated, start the burner. Limit switches are generally pressure, temperature and other switches which, when activated, stop the burner. The interlocks and limit switches are wired in series. A break in this circuit will shut the burner down, but will not produce an alarm. For purge and modulation models: This input is for monitoring the combustion air switch separately from other interlocks and limits. The Veri- Flame checks the air flow switch input is open before start-up, closed during operation, and open again at burner shutdown, thus preventing operation with an air switch that is defective, maladjusted or jumped. This input has about a 2 second delay to filter out and ignore a momentary interruption. The input will be proven open before start-up and after shutdown. If the input is improperly powered before the fan output is energized, the system error light will blink. The input must de-energize within 30 seconds or the Veri-Flame will lockout. After the fan output has energized, the air switch input must be made within 0 seconds. If not proven, then the system will lockout, the alarm output and the air failure light will come on. However, if the unit has the optional air switch input hold feature, the sequence is held indefinitely without causing a lockout. When the air switch input is made, then the sequence continues. If the air switch opens during the main firing cycle, the system will either lockout or recycle, depending on the DIP switch recycle selection. Purge and No-Purge models: the Veri-Flame can be interlocked with the main valve closed switch. This feature checks the switch position before startup and after shutdown to insure proper valve operation when the jumper on the base is cut. For modulation models: when wired, the system checks for the low fire start position prior to light-off.
15 Main Fuel Valve Closed/ High Fire Purge Check (Terminal D) Recycle Mode Pilot Test Mode Test Mode (Button In) Run Mode (Button Out) Interrupted or Intermittent Pilot Post Purge Spark, Pilot Flame & Main Flame Separation System Errors & Lockout Conditions For modulation models: This feature is enabled when the jumper on the base is cut. The system checks that the high fire position switch and the main valve closed switch are both made at the end of the high fire purge. For all models: when selected, the Veri-Flame will restart the sequence after flame or air failure. The recycle mode allows the system to re-initiate the start-up sequence automatically provided the main burner has been operating for at least 35 seconds. If the pilot flame fails to light during recycling, the system will lock out and annunciate a pilot flame fail. If the recycle is successful and the main burner is operational for at least 35 seconds, the system is ready for another recycle. At no time will the system recycle in the event of pilot flame fail. For all models: this mode is entered by depressing the TEST/RESET button on the front cover. In the pilot test mode, the Veri-Flame will hold the sequence once the pilot flame is established (i.e., the main valve is not energized). When in the pilot test mode, the green Interlocks Closed light blinks. To exit the pilot test mode, push the TEST/RESET button again and the Veri- Flame will exit the pilot test mode (the green Interlocks Closed light stops blinking but remains lit) and you must restart the sequence. For all models: pilot mode is selected using the DIP switch SW2. An interrupted pilot shuts off 0 seconds after the main valve opens. An intermittent pilot continues during the entire main flame firing cycle. For purge and modulation models: post purge is enabled by DIP switch SW8. A post purge maintains the combustion air fan output for 5 seconds after the interlocks and limit switch input have opened. For all models: during the trial for ignition period (TFI), the pilot valve and ignition coil remains energized. If a flame signal is present at the end of the TFI, the pilot output remains on and the ignition coil is de-energized. After a five second delay to prove the pilot flame, the main gas valve is energized. A system error (illuminated by the red System Error LED on the front cover) prevents gas ignition. The unit will continue its sequence after the error is cleared. A lockout condition energizes the alarm output and de-energizes the gas valve and ignition outputs. The unit must be reset to clear the alarm and start the sequence. To reset, the button must be pressed twice so that the button is in the out position. The following system errors result in immediate lockout conditions: ) Wiring error which puts external voltage on the output terminals (for all models). 2) Welded internal contacts or other malfunctions in the Veri-Flame (for all models). 3) Main fuel valve (for all models) open after cycle shutdown or before start-up. The system error light blinks twice and then remains on. The fan output terminal 8 will energize. 5
16 System Errors & Lockout Conditions (Continued) ) Low fire fail (for modulating model) low fire switch open prior to trial for ignition. 5) High fire fail (for modulating model) high fire switch is not closed at the end of high fire purge. The following situations will result in a lockout condition: 6) Air failure (for purge and modulation models) loss of combustion air anytime during the operational cycle. The Air Failure LED will be on for this condition. (See Recycle Mode on page ) 7) Pilot flame fail (for all models) loss of flame during the trial for pilot ignition period. The Flame Failure LED will be on for this condition. 8) Main flame fail (for all models) loss of flame during the main burner trial for ignition or run period (recycling not selected). The Flame Failure LED will be on for this condition. The following result in lockout conditions after 30 seconds, the system error light blinks about times and then remains on: 9) If a flame is detected out of sequence, which may be caused by: a) a faulty scanner (for all models); b) electrical interference on the sensor wiring (for all models); c) a flame exists in the burner or in the line of sight of a scanner, due to a gas leak, product fire or other condition (for all models). 0) Air flow switch closed before start-up (for purge and modulation models). High to Low Fire Purge Modulation Capability with High to Low Fire Position Switch Interlocks For modulation models: the modulation feature incorporates a high fire purge time and a low fire purge time into the purge sequence. This feature allows the Veri-Flame to sequence internal dry contacts which can be used by the customer requiring a high fire purge of the combustion chamber before ignition. The high fire and low fire purge times are selectable by means of DIP switches (see Section 3, DIP Switch Settings on page 2): SW...5 seconds SW seconds SW seconds SW seconds The selected times are additive and apply to both the high fire and low fire purge times (that is, high and low fire times are always identical). The modulation terminals will sequence as follows: Sequence Step Internal Contact Connections Power Off Terminal 0 (Common) Terminal 2 (Low Fire) Power On, Limits Open Terminal 0 (Common) Terminal 2 (Low Fire) Purge To High Fire Terminal 0 (Common) Terminal 3 (High Fire) Purge To Low Fire Terminal 0 (Common) Terminal 2 (Low Fire) Automatic Modulation Terminal 0 (Common) Terminal (Auto) Alarm and Lockout Terminal 0 (Common) Terminal 2 (Low Fire) The purge to high fire sequence does not start until the air switch input is on. The Automatic step occurs when the burners are operating and allows the burner firing rate to be controlled by an automatic temperature controller. 6
17 Optional features Air Switch Input Hold Remote Display & Power Supply Manual Reset on Power Outage Status Lights & Push-button Interlocks Closed Air Failure System Error Flame Failure Low Fire High Fire Auto Test/Reset Flame Signal The following features are available on select models, or when optional equipment is purchased. For purge/modulation models: holds the sequence indefinitely until air switch input is confirmed without affecting the air failure function and causing a lockout. The model 5602DBP operates on 20VAC and has a keypad for reset function. The display is door panel mounted and features a liquid crystal display in a ¼ DIN housing. The unit connects to the Veri-Flame by a cable to the flame signal test jack, and receives a serial communication on each sequence state change. The display incorporates the following functions: ) Provides status messages for the Veri-Flame sequence (see section 9). 2) Indicates lockout conditions when they occur, as well as the amount of time into the sequence when the lockout occurred (see section 9). 3) Provides continuous monitoring of the burner s flame signal strength and run time during main burner operation. This optional feature requires a reset on initial application of power or after an interuption of power. The system error light blinks rapidly (about times per second) and a remote display will show PUSH RESET TO START. The reset button must be pressed in and out to start. Do not order this option if the Veri-Flame is mounted inside an enclosure. All of the status lights and the TEST/RESET push-button are located on the front cover of the Veri-Flame. This section describes their respective functions. For all models: this green LED illuminates when the operation limits are made. These limits are wired in series to terminal 7. This input becomes energized to begin the burner sequence. When in the test mode, this LED blinks (see Pilot Test Mode on page 5). For purge and modulation models: this red LED illuminates whenever combustion air is lost during the operational cycle of the Veri-Flame. For all models: this red LED illuminates when a system error is detected (see System Errors & Lockout Conditions on pages 5-6). For all models: this red LED illuminates when a pilot or main flame fails. For modulation models: this yellow LED illuminates during the low fire period of the purge cycle. For modulation models: this red LED illuminates during the high fire period of the purge cycle. For modulation models: this green LED illuminates during the automatic period which occurs 20 seconds after the main valve is energized. For all models: this push-button is used to activate the pilot test mode or to reset the Veri-Flame unit. For all models: this red LED is located behind the signal test port and illuminates when a flame signal is present. 7
18 System Installation 5 Introduction In this section, the necessary procedures are detailed to integrate a Veri-Flame into a burner system; Figures 5. and 5.2 illustrate the various terminal strips mentioned. Note: Shut off the power supply before the Veri-Flame is removed or replaced from the base. Caution: Installation and maintenance must conform with the National Electrical Code and all other national and local codes and authorities having jurisdiction. Flame monitoring systems must be installed by a qualified, licensed technician. Interlocks and Limit Switch Input Combustion Air Switch Input To Fan Output Terminal FAN 3-Way Solenoid Valve De-energized To Fan Output Terminal FAN Air Switch Open To Burner Air Switch Closed 3-Way Solenoid Valve Energized To Burner Wire external interlock, control, and limit switches in series to this input. Guard against induced voltage levels to wiring connected to this input. In some extreme wiring runs, reduction of induced voltages may require a load (relay or light) connected to terminal 7 to avoid system error lockouts. This input is the power source for the valve and ignition output terminals. Be sure all switches wired to this input can handle the current required by the total of all loads connected to terminals 3,, and 5. For purge and modulation models: Wire any switches and contacts in series to this terminal for proving air flow function and relating to the air failure light. Power must not be immediately present at terminal 6 when power is first applied to terminals or 7. If this terminal is not used, place a jumper between the combustion blower output (terminal 8) and the air switch input (terminal 6). If the combustion air blower is controlled outside of the Veri-Flame system, then a three way solenoid valve must be connected between the air switch port and the blower sensing port. The valve de-energized state should vent the switch to ambient pressure. The energized state then connects the air switch to the blower sensing port. Power the valve from the blower ouput terminal 8. If accepted by local codes, the air switch could be wired between the combustion blower output and the air switch input. Connecting the air switch in this manner will satisfy the open contact (air short) check on the switch. 8
19 Ignition Wiring Low Fire Input Main Valve Closed Switch High Purge Input Remote Reset Remote Display & Power Supply Route ignition wiring a sufficient distance from all sensors and other low voltage wiring to avoid electrical interference, which may cause erratic operation of the Veri-Flame system. Keep the high voltage wire run from the ignition transformer as short as possible. The best condition is to mount the ignition transformer close to the burner and keep a low impedance path from the burner ground to the case of the transformer. Make sure the high voltage lead and ground return paths do not create a loop antenna around the Veri-Flame and sensor wiring. For modulation models: it is possible to wire the system for checking low fire start position prior to pilot ignition. To use this feature, the low fire start switch must be connected between terminal 3 and the pilot valve (see Figure 5.2). On direct spark burners, a by-pass contact must be wired around the low fire switch, see relay and contact CR in Figure 5.3. The system can be wired to check for the main valve closed switch on the main gas valve prior to start-up and after the end of the burner cycle. For purge and no purge models: the main valve closed switch must be connected to Terminal V and the jumper in the base must be cut (see Figure 5. on page 22). For modulation models: the main valve closed switch must be wired in series between the air flow switch and the high purge damper switch (see Figure 5. on page 20). To use this feature, the jumper in the base must be cut. For modulation models: the system can be wired to check for high purge position during the high fire purge portion of the sequence. To use this feature, the red jumper in the base must be cut and the high purge position switch must be connected from terminal 6 to D. If this feature is not used, the jumper in the base remains intact or a jumper must be installed between terminals and D. Please note that the yellow jumper on the base has no effect whether cut or intact. This feature permits remote mounting of a switch to reset the Veri-Flame. To use this feature, a normally closed remote reset switch must be wired so power is interrupted to terminal. When it is depressed or actuated, the connection to terminal is momentarily interrupted and resets the Veri-Flame. Wire the display according to figure 5.3. Mount through a ¼ DIN cutout using the two supplied brackets in either the top and bottom or the side slots. Locate the display and wiring to minimize electrical interference. Applying and disconnecting the display power supply should coincide with power to terminal of the Veri-Flame. Use the appropriate cable (Eclipse part #2038) to connect to the test jack and to the S2 terminal of the Veri-Flame wiring base. Do not attempt to parallel the test jack signal to other devices when using a remote display. The LCD display contrast can be adjusted on the back with a small blade screwdriver. Note: power for terminal 7 of the VeriFlame should not flow through the R-R2 contact when load currents exceed 5 amps. 9
20 No Purge Models Figure 5. No Purge and Purge Wiring Diagrams Purge Models 5602/5605: 20 VAC 50/60 HZ 5603: 20 VAC 50/60 HZ 5602/5605: 20 VAC 50/60 HZ 5603: 20 VAC 50/60 HZ 5 A Fuse On/Off 2 Piloted Burner 5 A Fuse On/Off 2 Piloted Burner 3 Pilot 3 Pilot Interlocks & Limits 5 7 Ignition Main Air Flow Switch 5 6 Ignition Main Proof of Closure A V S S2 Alarm Interlocks & Limits Proof of Closure 7 8 A V Fan Alarm S G S2 G Figure 5.2 Modulation Wiring Diagram 5602/5605: 20 VAC 50/60 HZ 5603: 20 VAC 50/60 HZ 5 A. Fuse On/Off Air Flow Cut Red Jumper To Activate Terminal D Low Fire Proving Pilot Ignition Main 6 Interlocks & Limits 7 8 Fan Proof of Closure High Purge Damper Switch A D S2 S Flame Sensor Terminals Common Automatic Low Fire High Fire Alarm See the High to Low Fire Purge Modulation Capability section on page 6 for contact connections. G 20
21 Figure 5.3 Typical Connections For All Models 2 S S2 Self Check U.V (Requires cable) A B C D Model 5602 DBP 20 VAC Remote Display 2V + 2V - Tx Rx 20V 20V N L Cable #2038 to 20 VAC R R2 G PLUG To Flame Signal Test Jack To S2 Veri-Flame 2 S S2 Self-Check U.V (Requires cable) for 20 VAC Veri-Flame 20V T 20V A B C D Solid State U.V. / I.R. White S Black Scanner S2 G Shield S S2 Blue Flame Rod Flame Rod T Third party transformer required. Must be at least 25 VA. S S2 U.V. Blue (Signal) Yellow (Neutral) U.V or I.R. No Purge & Purge Direct Spark 3 5 MAIN IGNITION Note: Intermittent pilot must be selected, DIP-SW2 = ON Neutral 3 5 Modulation Direct Spark with Low Fire Start Low Fire Proving CR CR MAIN IGNITION Neutral Note: Intermittent pilot must be selected, DIP-SW2 = ON CR is a control relay used to bypass the low fire switch after the burner is lit. Notes for Figures 5., 5.2 & 5.3:. Ground, shielding and conduit must not be connected to terminal S2. 2. Control circuit wires must meet 90 C (9 F) specification minimum and must be No. 6 AWG or larger and in accordance with all applicable codes. 3. Flame sensor wires must be individually run in their own separate conduit; flame sensor wires CANNOT be run together in a common conduit or wireway (See Section 6).. Flame signal should read between and 0 VDC with a digital volt meter. Drop off is approximately.0 VDC. Positive test jack point is on the cover marked Flame Signal with negative point being the S2 or ground. 5. Purge time, TFI, intermittent/interrupted pilot, and recycle/non-recycle selections are made with a DIP switch located on the rear plate of the control unit. 6. Neutral must be grounded. 2
22 Figure 5. Purge and No Purge Bases Model Number Model Number P2 5 6 S2 S 7 8 P3 P Gnd 3 V 2 A Jumper Gnd NOTE: Ground Terminal n not present in plastic base P3 P2 P Jumper 5 6 S2 S 7 8 A 2 V V 6 2 S2 S Internal Diagram Purge & No-purge P 5 6 P3 P2 P2 Fan P 2 Alarm P P Fault Pilot P3 3 6 Ign P3 J 5 Main P3 P3 3 Supervisor Flame Signal Amplifier Jack Note: No purge models do not use 6 & 8. 8 A 3 5 Modulating Base Model Number Internal Diagram Modulation Model P P 5 Fan Red P3 P2 P J J2 7 D 6 2 Alarm P P Fault Pilot P3 3 6 Ign P3 5 22K Main P3 22K P3 3 P3 2 P2 2 Supervisor A 3 5 Gnd Jumper A D S2 S S2 S 0 P2 J2 Flame Signal Amplifier J2 2 J2 J2 3 Jack Auto Low High
23 Outputs Inputs Terminal V Function Control Power Pilot Valve Ignition Main Valve Interlocks POVC Figure 5.5 Sequence Diagrams Start TFI Pilot Trial Flame Check Pilot Off 35 Seconds Main Trial 0 Sec (Interrupted) Recycle Permitted Firing Cycle Pilot Off End (Intermittent) Outputs Inputs Terminal V Function Control Power Pilot Valve Ignition Main Valve Fan Air Switch Interlocks POVC Start 0 Sec Air Proven Purge Flame TFI Check 5 Sec Pilot Trial Pilot Off 35 Seconds Main Trial 0 Sec (Interrupted) Firing Cycle Pilot Off Recycle Permitted (Intermittent) Post Purge 5 Sec End Outputs Inputs Continuity Between Modulation Terminals Terminal D 3 0 to 2 0 to 3 0 to Function Control Power Pilot Valve Ignition Main Valve Fan Air Switch Interlocks High Fire & POVC Low Fire Switch Low Fire Purge High Fire Purge Automatic Start 0 Sec Air Proven High Fire Purge Low Fire Purge Flame TFI Check 5 Sec Pilot Trial Pilot Off Main Trial 0 Sec 20 Seconds 35 Seconds (Interrupted) Firing Cycle Pilot Off Recycle Permitted (Intermittent) End Post Purge 5 Sec 23
24 Sensor Installation 6 Introduction This section describes the proper wiring, installation and sighting considerations for all sensors that can be used with a Veri-Flame. Warning Incorrect sensor installation may cause the sensor to generate a false flame signal, possibly resulting in the collection of unburned fuel in the combustion chamber. This unburned fuel creates the potential for explosions which can result in injuries, death and property damage. Be certain that the flame sensor detects acceptable pilot and main flames only. Sensor Wiring Flame Rods Route sensor wiring a sufficient distance from ignition and other high voltage or high current wiring to avoid electrical interference. Interference from ground currents, nearby conductors, radio-frequency emitters (wireless divices), and inverter drives can induce false flame signals. Shielded cables can help reduce interference with the shield connected to ground at the control end only. The wire type and its capacitance (picofarads or microfarads) to ground may cause low signal problems, so a grounded shield may decrease the signal due to the cable s internal capacitance. Multiple U.V. tube-type sensor leads run together without shielding may interfere or cross talk, so the shield or flexible armor must be grounded to prevent this situation. For flame rod sensor runs approximately 00 feet (30 meters) or greater, use Eclipse part number 27 coax cable. To achieve the maximum wiring distance, the shield should not be grounded (keep in mind that an ungrounded shield provides less protection against electrical interference). Note: Unshielded sensor wiring must not be run in common with other wires; it must be run in separate conduit. Multiple unshielded flame sensor wiring must not be run together for long lengths in a common conduit or wireway. Use # to #8 AWG wire suitable for 90 C (9 F) and 600 volt insulation, or a better grade if required by the application. Multiple shielded flame sensor cables can be run in a common conduit. Flame rods should be used only on gas burners. They accumulate soot from oil burners, causing nuisance shutdowns and unsafe operating conditions. See the burner manufacturer s literature for flame rod mounting location. When installing flame rods, please consider the following: 2
25 Figure 6. Flame Rod Position WRONG Rod Detects Weak Pilot PILOT Scanners CORRECT Rod Detects Only Strong Pilot Flame ) Keep the flame rod as short as possible and at least 3 mm (/2 ) away from any refractory. 2) Position the rod into the side of both the pilot and main flames, preferably at a descending angle to minimize drooping of the flame rod against burner parts, as shown in Figure 6.. Flame rod position must adequately detect the pilot flame at all burner draft conditions. Extend the rod 3 mm (/2 ) into nonluminous flames, such as blue flames from burning an air/gas mixture. For partially luminous flames, such as atmospheric air/gas mixtures, place the rod at the edge of the flame. 3) Provide a burner/flame grounding area that is at least four times greater than the flame rod area contacting the flame. The flame rod/burner ground ratio and position of the rod in the flame may need adjustment to yield maximum flame signal strength. ) Ignition interference from the spark plug may increase or decrease the flame signal strength. Reversing the ignition transformer primary leads may reduce this effect. Changing the spark gap or adding grounding area between the flame rod and spark plug may eliminate the interference. Warning Use only Eclipse scanner models as listed in the Illustrated Parts List at the end of this document. When installing scanners, please consider the following: ) Position the scanner within 57 mm (8 ) of the flame. Consult factory for longer distances. 2) Bushing threads are /2 inch F.N.P.T. for all scanner models except which has inch F.N.P.T. bushing threads. 3) The ambient temperature limits of each scanner varies; check the literature for the specific scanner model. For higher temperatures, use Eclipse heat block seal 23HBS for ½ N.P.T. scanners and if necessary, add cooling purge air. ) An optional magnifying lens may also be used to increase the flame signal strength in difficult sighting situations. Scanner Sighting Considerations Figure 6.2 U.V. Scanner Sighting MAIN BURNER Scanner Sight Line SCANNER /3 of Flame Length Aim scanners at the third of the flame closest to the burner nozzle, as shown in Figure 6.2 (oil flames typically have less UV radiation in the outer flame). The scanner should view the intersection of the pilot and main flames. When sighting scanners, please consider the following: ) If possible, sight the scanner away from the ignition spark. Sighting the spark or its reflections from burner internals may lead to a misdiagnosis of shutdowns during burner ignition. If necessary, use a scanner orifice to reduce spark pickup. 2) Do not allow the scanner to detect a pilot flame that is too small to ignite the main burner. 3) Perform a minimum pilot test when installing or adjusting any pilot or main burner system; see Minimum Pilot Test on page 26. ) Solid State UV/IR scanner model SC may better detect oil flames. When used, aim the scanner at the outer oil flame for flicker detection. 25
26 Test Procedures 7 Introduction This section describes the test procedures that must be performed after installation to insure that the Veri-Flame is operating properly; these procedures are mandatory. Flame Signal Strength Minimum Pilot Test Insert the positive probe of a 0-5 VDC, digital volt meter into the test point on the front cover of the Veri-Flame; connect the negative probe to S2 or ground. A good flame signal strength will read between 6 and VDC; anything below VDC is inadequate. Also, the red LED inside the test point illuminates when a flame signal is indicated. Run the following test procedures to ensure that the sensor will not detect a pilot flame too small to reliably light the main flame: ) Manually shut off the fuel supply to the burner, but not to the pilot. 2) Start the system normally. 3) To enter the pilot test mode, depress the test/reset button located in the lower right corner on the front cover. ) The control will hold the operating sequence at the pilot flame step. Measure signal strength as described above. 5) Reduce pilot fuel until the flame relay drops out. Increase pilot fuel until the flame signal is greater than VDC, and flame relay just manages to pull in. This is the minimum pilot. If you don t think this flame will be able to safely light the main burner, realign the sensor so that it requires a larger pilot flame and repeat steps 2 through 5. 6) Push the test/reset button located in the lower right corner on the front cover to exit the test mode (reset) and begin the normal start-up sequence again. 7) When the sequence reaches the main flame trial for ignition, smoothly restore the fuel supply to the burner. If the main burner does not light within five seconds, immediately shut off the burner supply to shut down the system. Realign the sensor so that it requires a larger pilot flame. Repeat steps through 6 until the main burner lights off smoothly and reliably. 26
27 Pilot Flame Failure Test Main Flame Failure Test (For Interrupted Pilot Systems) Spark Sighting Test Limits & Interlock Tests ) Manually shut off the fuel supply to the pilot and the main burner. 2) Place system in pilot test mode (please refer to page 5). 3) Start the system normally. The controller should lock out*; if it doesn t, then the controller is detecting a false flame signal (see Section 6). Find the problem and correct it before resuming normal operation. ) Manually shut off the fuel supply to the main burner but not to the pilot. 2) Start the system normally. This should ignite the pilot and lock out* after pilot interruption. If the system does not lock out, the controller is detecting a false flame signal (see Section 6). Find the problem and correct it before resuming normal operation. ) Manually shut off the fuel supply to the pilot and the main burner. 2) Start the system normally. 3) Measure the flame signal as described in Flame Signal Strength in this section. ) If a flame signal greater than VDC is measured for more than three seconds during the trial for ignition, then the sensor is picking up a signal from the spark plug; see Sensor Wiring on page 2. It is not necessary to correct a spark sighting condition for a Veri-Flame when the ignition transformer is connected to terminal. Periodically check all interlock and limit switches by manually tripping them during burner operation to make sure they cause the system to shut down. Warning Never operate a system that is improperly adjusted or has faulty interlocks or limit switches. Always replace faulty equip ment with new equipment before resuming operation. Oper ating a system with defective safety equipment can cause ex plosions, injuries, and property damage. * Indicated by the illuminated red Flame Failure LED on the Veri-Flame front cover. 27
28 Maintenance & Troubleshoot- 8 Introduction Maintenance This section is divided into two parts: The first part describes the maintenance procedures. The second part describes troubleshooting procedures, from identifying problems to interpreting the operating conditions by the lit LEDs on the front cover. Preventative maintenance is the key to a reliable, safe and efficient system. The core of any preventive maintenance program is a list of periodic tasks. In the paragraphs that follow are suggestions for a monthly list and a yearly list. Note: The monthly list and the yearly list are an average interval. If your environment is dirty, then the intervals may need to be shorter. Caution: Turn off power before disconnecting or installing sensors, controls or modules. Monthly Checklist Yearly Checklist. Inspect flame-sensing devices for good condition and cleanliness. Keep scanner lenses clean with a soft, damp cloth, since small amounts of dust will measurably reduce the flame signal strength. Wash the flame rod electrode and insulator with soap and water, then rinse and dry thoroughly. 2. Test all the alarm systems for proper signals. 3. Check ignition spark electrodes and check proper gap.. Test interlock sequence of all safety equipment as described on page 27: manually make each interlock fail, noting what related equipment closes or stops as specified by the manufacturer. Test flame safeguard by manually shutting off gas to the burner.. Test (leak test) safety shut-off valves for tightness of closure. 2. Test pressure switch settings by checking switch movements against pressure setting and comparing with actual impulse pressure. 3. Visually check ignition cable and connectors.. Make sure that the following components are not damaged or distorted: the burner nozzle the spark plugs the flame sensors the flame tube or combustion block of the burner 28
29 Troubleshooting PROBLEM POSSIBLE CAUSE SOLUTION Cannot initiate start sequence Main valve is not closed. Air pressure switch has not made contact. Check main valve closed switch. No voltage on V (or D). Check air pressure switch adjustment. Check air filter. Check blower rotation. Check outlet pressure from blower. No voltage on 6 after 8 is on. High gas pressure switch has tripped. Check incomming gas pressure; adjust gas pressure if necessary. Check pressure switch setting and operation. No voltage to 7. Scrambled messages on remote display. UNSAFE AIR SHORT message appears on display. Burner flame fails but no flame failure indication occurs. Voltage reading greater than 5VDC at Test Point on Veri-Flame faceplate. Low gas pressure switch has tripped. Malfunction of flame safeguard system such as a shorted-out flame sensor or electrical noise in the sensor line. Purge cycle not completed. Main power is off. No power to control unit. Electrical interference. Improperly adjusted air switch. Air switch either shorted or wired wrong. A faulty scanner. Improperly connected sensor wires. Electrical interference from other current carrying wires. Improper grounding. Check incomming gas pressure; adjust gas pressure if necessary. Check pressure switch setting and operation. No voltage to 7. Have qualified electrician investigate and rectify. Check switch settings. Check air switch. Make sure power is on to control system. Call qualified electrician to investigate. Check grounding in system. Separate communication cable. Move ignition circuit. Check air switch settings. Check wiring to air switch. Check scanner as explained in checklists in Maintenance portion of this Section. Check wiring diagram on page 20 or 2 as well as appropriate sensor information in Section 6. Check Note information on page 2 regarding sensor wiring. Check grounding of neutral at control power transformer. 29
30 LED Status This section describes the status of operating conditions based on the LED or combination of LEDs which are lit on the front cover of each Veri-Flame model. Table 8. LED Status & Conditions for Veri-Flame No Purge Models LED(s) Lit INTERLOCKS CLOSED SYSTEM ERROR FLAME FAILURE Possible Causes ) The interlocks are closed (normal operation), power on terminal 7. ) The flame detected is out of sequence, flame signal light is on. 2) The sensor is runaway, flame signal light is on. 3) Inductance is detected on sensor wires, flame signal light is on. ) Voltage wired into terminals 3,, or 5. 5) Internal relay contacts welded. 6) Internal controller failure. 7) Main valve closed switch defective, no power to V. ) Pilot flame is not established in selected TFI. 2) Main flame is not established in selected TFI. 3) Main flame fails within 35 seconds of TFI. ) Flame failed during operation in non-recycle mode. 5) Flame failed 35 seconds after TFI and was not established after try in recycle mode. No Purge Model 30
31 Table 8.2 LED Status & Conditions for Veri-Flame Purge Models LED(s) Lit INTERLOCKS CLOSED SYSTEM ERROR FLAME FAILURE AIR FAILURE Possible Causes ) The interlocks are closed (normal operation), power on terminal 7. ) The flame detected is out of sequence, flame signal light is on. 2) The sensor is runaway, flame signal light is on. 3) Inductance is detected on sensor wires, flame signal light is on. ) Voltage wired into terminals 3, or 5. 5) Internal relay contacts welded. 6) Internal controller failure. 7) Air flow switch closed before start-up. 8) Main fuel valve switch opens after shutdown or before start-up, no power to V. ) Pilot flame is not established in selected TFI. 2) Main flame is not established in selected TFI. 3) Main flame fails within 35 seconds of TFI. ) Flame failed during operation in non-recycle mode. 5) Flame failed 35 seconds after TFI and was not established after one try in recycle mode. ) Air flow switch not closed within ten seconds of start-up. 2) Air flow switch is open during timing cycle. 3) Air flow switch is open during firing cycle. Purge Model 3
32 Table 8.3 LED Status & Conditions for Veri-Flame Modulation Models LED(s) Lit Possible Causes INTERLOCKS CLOSED ) The interlocks are closed (normal operation), power on terminal 7. SYSTEM ERROR FLAME FAILURE AIR FAILURE INTERLOCKS CLOSED and AUTO INTERLOCKS CLOSED and HIGH FIRE ) The flame detected is out of sequence, flame signal light is on. 2) The sensor is runaway, flame signal light is on. 3) Inductance is detected on sensor wires, flame signal light is on. ) Voltage wired into terminals 3, or 5. 5) Internal relay contacts welded. 6) Internal controller failure. 7) Air flow switch closed before start-up. 8) High purge damper switch and/or main fuel valve switch opens during start-up. 9) Low fire switch not made before TFI. ) Pilot flame is not established in selected TFI. 2) Main flame is not established in selected TFI. 3) Main flame fails within 35 seconds of TFI. ) Flame failed during operation in non-recycle mode. 5) Flame failed 35 seconds after TFI and was not established after try in recycle mode. ) Air flow switch not closed within ten seconds of start-up. 2) Air flow switch is open during timing cycle. 3) Air flow switch is open during firing cycle. ) Burner in run mode, firing rate determined by automatic controller (normal operation). ) Purge high sequence (normal operation). INTERLOCKS CLOSED and LOW FIRE ) Purge low sequence (normal operation). Modulation Model 32
33 Remote Display Messages 9 Introduction This section covers how the optional remote display is used with the Veri-Flame. The remote display provides LCD messages which monitor the status of the Veri-Flame s functions as well as any lockout conditions. This section is divided into two parts or tables: The first table describes the start-up and shutdown monitoring sequences of the Veri-Flame and how the progress (or halt) of the sequence can be monitored by the messages on the remote display. The second table alphabetically lists and explains the diagnostic messages which can appear on the remote display. 33
34 Table 9. Veri-Flame Operating Sequence NORMAL MESSAGE REMOTE DISPLAY REVISION X.X ERROR MESSAGE # UNSAFE FLAME ON POWER ON Was internal safe start check successful? YES NO EXTERNAL INTERLOCK CHECKS Is flame signal present? YES NO Various lockout messages Is main valve closed switch made?* Fan is energized. If signal is elimi-nated within 30 seconds, FOR PURGE & MODULATING Is voltage present at air flow switch? YES NO ERROR MESSAGE #2 30 SECONDS AFTER # UNSAFE FLAME ON Alarm energized. ERROR MESSAGE # UNSAFE AIR SHORT If switch is opened within 30 seconds, sequence continues. If YES NO ERROR MESSAGE MAIN VALVE FAIL ERROR MESSAGE #2 30 SECONDS AFTER # UNSAFE AIR SHORT Alarm energized. Is voltage present at interlock switch? NORMAL MESSAGE SAFE START OK Check_Sum = XX NORMAL MESSAGE FAN ENERGIZED YES NO ERROR MESSAGE LIMITS OPEN TIME = XXXX:XX:XX Holds until answer is yes. Fan output is energized; modu-lator is sent to low fire. BURNER START-UP (see next page) * Applies to purge and no purge models only. 3
35 Table 9. Veri-Flame Operating Sequence (continued) BURNER START-UP Is voltage present at air flow switch within ten seconds? NORMAL MESSAGE AIR PROVEN Purge based on selected time. NO PURGE MODELS PURGE MODELS Is voltage present at air switch... YES NO ERROR MESSAGE AIR NOT PROVEN NORMAL MESSAGE AIR PROVEN NORMAL MESSAGE PURGE TO HIGH FIRE Modulator sent to high fire for selected purge time. MODULATION MODELS Is voltage present at air switch... YES NO ERROR MESSAGE AIR NOT PROVEN Is voltage present at high purge switch? NORMAL MESSAGE PURGE TO LOW FIRE YES NO Modulator sent to low fire for selected purge time. NORMAL MESSAGE PILOT TRIAL FOR IGNITION Spark and pilot valve energized for selected trial for ignition. ERROR MESSAGE HI DAMPER FAIL Is low fire switch closed? YES NO ERROR MESSAGE LOW FIRE FAIL NORMAL MESSAGE PILOT FLAME ON Flame signal detected YES NO ERROR MESSAGE PILOT FLAME FAIL NORMAL MESSAGE PILOT FLAME XX.XV TIME = XXXX:XX:XX Spark turns off at end of TFI; sequence delayed 5 seconds. NORMAL MESSAGE MAIN FLAME ON YES NO ERROR MESSAGE MAIN FLAME FAIL Is flame signal present? (see next page) 35
36 Table 9. Veri-Flame Operating Sequence (continued) BURNER START-UP (continued) Is flame signal present? YES NO ERROR MESSAGE MAIN FLAME FAIL NORMAL MESSAGE MAIN FLAME ON NORMAL MESSAGE MAIN FLAME ON PILOT OFF Pilot will shut off 0 seconds after main flame is energized. IF Interrupted Pilot is selected IF Intermittent Pilot Is Selected NORMAL MESSAGE MAIN FLAME ON MODULATION MODELS NORMAL MESSAGE AUTOMATIC MODULATION Modulator sent to automatic 20 seconds after main valve is energized. MODULATION MODELS PURGE & NO PURGE MODELS NORMAL MESSAGE BURNER ON XX.XV TIME = XXXX:XX:XX Main flame of burner is proven. Flame signal = XX.XVolts DC; elapsed time is shown in hours: minutes:seconds. PURGE & NO PURGE MODELS Is flame signal present? NO YES Is air switch signal on? NO YES Is recycle selected? YES NO Is recycle selected? YES NO Was the main flame on more than 35 seconds? NO YES Was the main flame on more than 35 seconds? NO YES ERROR MESSAGE MAIN FLAME FAIL RECYCLING Unit returns to beginning sequence. ERROR MESSAGE MAIN FLAME FAIL ERROR MESSAGE AIR FAILURE RECYCLING Unit returns to beginning sequence. ERROR MESSAGE AIR FAILURE 36
37 Table 9. Veri-Flame Operating Sequence (continued) BURNER SHUTDOWN Shutdown is started by opening the operating interlock circuit. Continued operation. YES NO YES NO NORMAL MESSAGE POST PURGE XX Fuel valves de-energized; fan energized for 5 seconds. YES NO ERROR MESSAGE MAIN VALVE FAIL Fan energized; alarm sounds. FOR PURGE & MODULATING ERROR MESSAGE # UNSAFE AIR SHORT YES NO Is flame signal present? If switch is opened within 30 seconds, sequence continues. If ERROR MESSAGE # UNSAFE FLAME ON YES NO ERROR MESSAGE #2 30 SECONDS AFTER # UNSAFE AIR SHORT Alarm energized. Fan is energized. If signal is elimi-nated within 30 seconds, ERROR MESSAGE #2 30 SECONDS AFTER # UNSAFE FLAME ON Alarm energized. NORMAL MESSAGE LIMITS OPEN TIME = XXXX:XX:XX * Applies to purge and no purge models only. 37
38 Table 9.2 Remote Display Diagnostic Messages (Listed Alphabetically) Message Type explanation AIR FAILURE AIR FAILURE RECYCLING AIR NOT PROVEN AIR PROVEN AUTOMATIC MODULATION Lockout Status Lockout Status Status For purge & modulation models: Combustion air flow limit switch opened for more than two seconds once initially proven. For purge & modulation models: Combustion air flow limit switch opened; if recycle has been selected, the Veri-Flame will restart the sequence after air failure (see Recycle Mode on page ). For purge & modulation models: Combustion air flow limit switch did not make within ten seconds of fan being energized. For purge & modulation models: Combustion air flow limit switch closed within ten seconds of fan being energized. For modulation models only: Modulating motor is sent to automatic operation. BURNER ON xx.xv time=xxxx:xx:xx D-INTERNAL FAIL XX: FAN ENERGIZED FLAME failure HI DAMPER/POVC K-INTERNAL FAIL L-INTERNAL FAIL Status Lockout Status Lockout Lockout Lockout Lockout Main flame of burner is proven in the automatic modulation mode; flame strength is XX.XV (volts DC). Elapsed time is shown in hours: minutes:seconds. For modulation models only: Internal control failure; replace controller. For purge & modulation models: Blower motor is energized at the start of pre-purge. Main flame lost during operation in the automatic modulation mode. Burner number (X) given of failed unit. For modulation models only: High damper or high purge rate switch did not make at the end of pre-purge to high fire. Internal control failure; replace controller. Internal control failure; replace controller. LIMITS OPEN time=xxxx:xx:xx LOW FIRE FAIL MAIN FLAME fail MAIN FLAME FAIL RECYCLING Status Lockout Lockout Status The controller has completed its internal checks and is standing by for the interlocks to close. For modulation models only: Low fire switch is open just prior to pilot trial for ignition. Main flame was not established during the main burner trial for ignition. Main flame lost during automatic modulation; control will recycle once if recycle has been selected. 38
39 Table 9.2 Remote Display Diagnostic Messages (continued) Message Type explanation MAIN FLAME ON MAIN FLAME ON PILOT OFF MAIN VALVE FAIL NO PURGE SELECT PILOT FLAME FAIL PILOT ON PILOT TRIAL FOR IGNITION POST PURGE PROGM SWITCH ERR Lockout Status Lockout Lockout Lockout Status Status Status Lockout Main valve has been energized and main flame proven during trial for ignition. Pilot valve is de-energized and main flame is on. For purge and no purge models: Main valve closed switch is open before start-up or after burner shutdown. For purge & modulation models: No purge time was selected; lockout prior to purge to high fire. Pilot flame was not established during the pilot trial for ignition. Pilot flame is proven; transformer is de-energized; remaining countdown for pilot trial for ignition is. Pilot valve and ignition transformer are energized; countdown for pilot trial for ignition begins. For purge & modulation models: 5 second post purge is started on burner shutdown. DIP switch improperly set or changed during cycle. Purge TO HIGH FIRE Purge TO LOW FIRE RELAY FAIL SAFE START OK UNSAFE AIR SHORT UNSAFE AIR SHORT Status Status Lockout Status Status Lockout For modulation models only: Modulating motor is sent to high fire. For modulation models only: Modulating motor is sent to low fire. Internal relay(s) fail initial check. Check ratings. If lockout still occurs after overload is eliminated, replace control. Control has completed internal safe-start check. For purge & modulation models: Combustion air switch is closed before start-up or after shutdown; control holds start-up until switch reopens; if interlocks close before switch opens, alarm is energized. For purge & modulation models: Same conditions as above, except the interlocks close before the switch reopens, causing a lockout and the alarm being energized. 39
40 Table 9.2 Remote Display Diagnostic Messages (continued) Message Type explanation UNSAFE FLAME ON UNSAFE FLAME ON Hold Lockout Flame signal actual, induced, or runaway scanner is detected before start-up or after shutdown. The fan is energized. If the cause is corrected within 30 seconds, as in afterburn, the control will turn off the fan and continue the sequence. Same conditions as above, except the cause has not been corrected within 30 seconds, resulting in a lockout and the alarm being energized. UNSAFE FLM PURGE UNSAFE FLM PURGE V INTERNAL FAULT WATCHDOG FAIL XXXXXXX XXXXXTESTXX Hold Lockout Lockout Lockout Status For purge & modulation models: Flame signal actual, induced, or runaway scanner is detected during the selected purge time period. The fan is energized. If the cause is corrected within 30 seconds, as in afterburn, the control will turn off the fan and continue the sequence. For purge & modulation models: Same conditions as above, except the cause has not been corrected within 30 seconds, resulting in a lockout and the alarm being energized. Internal control failure; replace controller. Internal control failure; replace controller. In combination with other messages, shows the control is in the minimum pilot test mode. 0
41 Appendix Conversion Factors Metric to English. From to multiply by cubic meter (m 3 ) cubic foot (ft 3 ) 35.3 cubic meter/hour (m 3 /h) cubic foot/hour (cfh) 35.3 degrees Celsius ( C) degrees Fahrenheit ( F) ( C x.8) + 32 kilogram (kg) pound (lb) kilowatt (kw) Btu/hr 3 meter (m) foot (ft) 3.28 millibar (mbar) inches water column ( wc) 0.0 millibar (mbar) pounds/sq in (psi).5 x 0-3 millimeter (mm) inch (in) 3.9 x 0-2 Metric to Metric. From to multiply by kilopascals (kpa) millibar (mbar) 0 meter (m) millimeter (mm) 000 millibar (mbar) kilopascals (kpa) 0. millimeter (mm) meter (m) 0.00 English to Metric. From to multiply by Btu/hr kilowatt (kw) x 0-3 cubic foot (ft 3 ) cubic meter (m 3 ) x 0-2 cubic foot/hour (cfh) cubic meter/hour (m 3 /h) x 0-2 degrees Fahrenheit ( F) degrees Celsius ( C) ( F 32).8 foot (ft) meter (m) inches (in) millimeter (mm) 25. inches water column ( wc) millibar (mbar) 2.9 pound (lb) kilogram (kg) 0.5 pounds/sq in (psi) millibar (mbar) 68.95
42 Illustrated Parts List 2 Category Sensors Bases Pos. No Description Model Number Part Number Straight U.V. scanner NEMA U.V. scanner N U.V. scanner A Self-check scanner Solid-state U.V./I.R. scanner SC foot cable for self-check scanner Scanner support () A SS Magnifying lens assembly Lens, magnifying Lens, non-magnifying (2) 865 Insulated coupling Cable, coax, RG62A/U for flame rod 27 Heat block seal 23HBS 000 Internal terminal base, metal Exposed terminal base, metal Internal terminal base, plastic P 229 Exposed terminal base, plastic P 2295 Modulation base Screw, mounting to plastic base 220 Screw, mounting to metal base Test Display Tester for Veri-Flame units Relay module (3) Remote display, 20VAC with keypad 5602 DBP Cable for remote display () For 90º U.V. scanner (Model No A), NEMA U.V. scanner (5600-9N) and solid state U.V./I.R. scanner ( SC) (2) For magnifying lens assembly (Model No ), self-check scanner (5602-9), and heat block seal (23HBS) (3) Used to test modulation controls on tester (Model No 5602) above Instruction Manual 88 6/06 Litho in USA
Eclipse Veri-Flame Single Burner Monitoring System Model 5600 Version 1
Instruction Manual 88 9/5/008 Eclipse Veri-Flame Single Burner Monitoring System Model 5600 Version Modulation Model No Purge Model Purge Model Co p y r i g h t Copyright 008 by Eclipse, Inc. All rights
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control
PARTS & ACCESSORIES GeniSys 12V Model 7556 Advanced 12 Vdc Burner Control Description / Applications The Beckett GeniSys TM 12V Advanced Burner Control is a 12 Vdc primary safety control for oil burners
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual
QUALITY STEAM SPECIALTIES SINCE ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual Section: C500 Bulletin: C500.40 Date: 06-26-01 Supersedes: New PRODUCT DESCRIPTION: The Clark-Reliance
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:
Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do
prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10
prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
Electric Panel Pump Control System. Operation, Maintenance and Installation Manual
Manual No. 5EP-OM1-1 Electric Panel Pump Control System Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 SEQUENCE
TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table
New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control
PARTS & ACCESSORIES Model 7586 Intermittent Pilot Gas Ignition Control Description / Applications The Beckett GeniSys Intermittent Pilot Gas Ignition Control is a 24 Vac gas ignition and safety control.
E110 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES
E-11 OCTOBER 30, 2015 E1 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES E1 with ED5 Display Module APPROVED DESCRIPTION The Fireye
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for
USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
DC400 Dispensing Cutoff System
DC400 Dispensing Cutoff System DC404 and DC406 Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com
TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output
133-683 JUNE 28, 2006 TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output DESCRIPTION APPLICATION The Fireye 65UV5-1004 flame scanner is a microprocessor based flame
Automatic Phone-Out Home Monitoring Systems
Automatic Phone-Out Home Monitoring Systems Power Outage and Freeze Alarm Model Number: THP202 Power Outage, Freeze and Flood Alarm Product Description Model Number: THP201 These monitoring systems are
Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
INSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE
SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function
SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function Document No. 155-751 SKP15U.. Description Only when assembled to Series VGU Gas valves SKP15 electro-hydraulic actuators combine with
Leak Detection System
Instructions - Parts List Leak Detection System 311200A For detecting leaks in your diaphragm pump system. Not for use in explosive atmospheres. Part No. 234576 120 psi (0.8 MPa, 8 bar) Maximum Air Input
Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)
Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) VPS 504 S06 (120 VAC) is: CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter R-15 (Canada) UL
SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND
Honeywell Electronic Ignition Troubleshooting Tech Tip April 2007 The Honeywell S8610H Intermittent Pilot Module provides the ignition sequencing, pilot spark, pilot flame monitoring, Pilot Valve (PV)
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
LDG DTS-4/4R Desktop Coaxial Switch / Remote
LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 [email protected] www.ldgelectronics.com
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Installation and Operation Guide for PD5100 Automatic Transfer Switch
Installation and Operation Guide for PD5100 Automatic Transfer Switch Member P r o gr e ssive Dynamics, Inc. 507 Industrial Rd Marshall, MI 49068 www.progressivedyn.com 2012 Progressive Dynamics, Inc.
How To Use A Cdm250 Digital Multimeter
User Manual CDM250 Digital Multimeter 070-6736-03 Copyright Tektronix, Inc. 1987. All rights reserved. Tektronix products are covered by U.S. and foreign patents, issued and pending. Information in this
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity
6 & 12 Volt Battery and Systems Tester with 100 Amp Load
6 & 12 Volt Battery and Systems Tester with 100 Amp Load Form No. 841-731 -000 DESCRIPTION This Load Tester tests 6 or 12 volt automotive-size lead-acid batteries under load. It will also test 6 or 12
7800 SERIES Relay Modules
7800 SERIES Relay Modules This publication provides general checkout and troubleshooting procedures for the 7800 SERIES Relay Modules. CHECKOUT AND TEST SYSTEM CHECKOUT IMPORTANT Perform all Static Checkout
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Thermo Top - Troubleshooting Tree
Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may
FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON
FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON SERIAL NUMBER Flash Technology, 332 Nichol Mill Lane, Franklin, TN 37067 (615) 261-2000 Front Matter Abstract This
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
10000HXL31/15000HXL31/20000HXL31
Table of Contents www.eaton.com/dxups USER MANUAL ON LINE UPS 10000HXL31/15000HXL31/20000HXL31 Uninterruptible Power Supply Table of Contents 1. Brief introduction 1.1 System and model description---------------------------------------------------------------------1
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control
On/Off Relay Switch and 3-Way Switch Kit
45637/45638 Wireless Lighting Control On/Off Relay Switch and 3-Way Switch Kit marthome Control the On/Off status of permanently installed lighting, fans and more! www.lowes.com/iris 2012 JASCO Made in
Owner's Manual [ S/N LABEL HERE ] Document # BW-BCU5DOC
Owner's Manual [ S/N LABEL HERE ] Document # BW-BCU5DOC BAYweb Remote Model BW-BCU5 Owner's Manual Copyright 2009-2010 Bay Controls, LLC Part Number: BW-BCU5DOC Revision: 0.2 April 18, 2010 BAYweb is a
AGS. Owner's Manual. Xantrex Automatic Generator Start Control System
AGS Owner's Manual Xantrex Automatic Generator Start Control System TABLE OF CONTENTS INTRODUCTION...3 Main Features...3 Safety Summary...3 THINGS YOU SHOULD KNOW...4 THEORY OF OPERATION...5 System...5
USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book
USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
BroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0
Form No. 74-00-4001 S168-195-001 Revision E DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 INTRODUCTION Allied Healthcare Products, Inc. s Digital Alarm
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed
OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS
Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN
Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Power Max Level 2 Charging Station en Installation and Operating Instructions This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center
FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS
MC-5000 JUNE 9, 2015 FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS APPROVED WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state
VLT Series 300 Watt True Sine Wave Inverter
VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
ITC-BTTN Cellular Bluetooth Gateway. Owner s Manual 1
ITC-BTTN Cellular Bluetooth Gateway Owner s Manual 1 2 Table of Contents Introduction...3 Package Contents...3 XLink Connections Diagram...4 Setup...5 Pairing your Bluetooth Cell Phone to the XLink...6
Pro Logic Version 4.10. Diagnostics Manual
Pro Logic Version 4.10 Diagnostics Manual Turbo Cell & Control Electronics 2009 Hayward Industries Table of Contents Important safety instructions Pg. 1 No Cell Power 1 & No Cell Power 2 Pg. 2 No Cell
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
ABLOY DA60 SWING DOOR OPERATOR Installation and commissioning manual Abloy Oy An ASSA ABLOY Group company APPROVALS / STANDARDS Low Voltage directive 7//EEC as amended by the directive 9/68/EEC EMC directive
Instructions & Safety Information Models A220-20D and A220-20L Version 2
Quick 220 Voltage Converting Power Supply Instructions & Safety Information Models A220-20D and A220-20L Version 2 Quick 220 Systems LLC PO Box 47489 Phoenix, Arizona 85068-7489 800-347-0394 602-938-6057
Model 800 Residential Steam Humidifier Owner s Manual. Includes Safety & Operating Instructions and Warranty Information
Steam Humidifier Model 800 Residential Steam Humidifier Owner s Manual Includes Safety & Operating Instructions and Warranty Information READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS Safety Cautions...
USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE. AeroVironment EV Solutions
USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE AeroVironment EV Solutions 2013 AeroVironment, Inc. All rights reserved. AeroVironment, EV Solutions, and the AeroVironment logo are trademarks
Short Range Wireless Switch System Handheld 8 Installation and Operations Guide
Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
i ChatterBox! Motorcycle Security
i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence
Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)
TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the
APOLLO Gate Operators, Inc.
APOLLO Gate Operators, Inc. Model 7200ETL Post Mounted Residential & Heavy Duty Commercial Slide Gate Operator INSTALLATION MANUAL 04/11 CONTENTS IMPORTANT SAFETY INSTRUCTIONS... 3 Applications... 4 Pre-Installation
GNOME PELLET E.I. Pellet Heater Owner's Manual Installation and Operating Instructions. Please read this entire manual before installation.
Pellet Heater Owner's Manual Installation and Operating Instructions Please read this entire manual before installation. Save these instructions. SAFETY NOTICE HEATER MUST BE PROPERLY INSTALLED AND MAINTAINED
STC 3S012-020-A Series Solenoid Valves
STC 3S012-020-A Series Solenoid Valves 3S012-020-A Series Solenoid Valve Specifications Valve Model 3S012-1/8-A 3S012-1/4-A 3S020-1/8-A 3S020-1/4-A Port Size (NPT) 1/8 1/4 1/8 1/4 Valve Type Action 3 Way,
