Controlling a 2-phase CO 2 loop using a 2-phase accumulator



Similar documents
Thermal Modeling Issues Concerning the Mechanically Pumped Two-Phase CO 2 Cooling for the AMS-2 2 Tracker

UNIT 2 REFRIGERATION CYCLE

How To Calculate The Performance Of A Refrigerator And Heat Pump

16. Heat Pipes in Electronics Cooling (2)

Why and How we Use Capacity Control

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Chapter 3.4: HVAC & Refrigeration System

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

How To Clean Up A Reactor Water Cleanup

Waste Heat Recovery through Air Conditioning System

Two-Phase Evaporative Precision Cooling Systems

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

How To Design A Refrigeration System

Refrigeration Basics 101. By: Eric Nelson

How To Understand Evaporator

Testing methods applicable to refrigeration components and systems

Heat. Investigating the function of the expansion valve of the heat pump. LD Physics Leaflets P Thermodynamic cycle Heat pump

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

How Ground/Water Source Heat Pumps Work

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

A/C refrigerant system, overview

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

Fundamentals of Mass Flow Control

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Low GWP Replacements for R404A in Commercial Refrigeration Applications

How To Know If A Refrigeration System Is Efficient

C. starting positive displacement pumps with the discharge valve closed.

Characteristics of Evaporators

FEDSM Flow Boiling Heat Transfer Enhancement in Subcooled and Saturated Refrigerants in Minichannel Heat Sinks

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

CGC s Hybrid System Loop Control

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

Heat Pipe Cooling of Concentrating Photovoltaic (CPV) Systems

Energy savings in commercial refrigeration. Low pressure control

BB-18 Black Body High Vacuum System Technical Description

RESULTS OF ICARUS 9 EXPERIMENTS RUN AT IMRA EUROPE

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

Optimization of Natural Gas Processing Plants Including Business Aspects

Energy Efficient Ammonia Heat Pump. Energy and Climate Refrigeration and Heat Pump Technology

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.

How To Clean Water From An Ammonia Refrigeration System

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

New Trends in the Field of Automobile Air Conditioning

Advances in Gas Cooler Design and the New Gas Cooler Product Selector

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

APPLICATIONS AND DEFINITIONS

WHITE PAPER #: CLIMATEMASTER KNOWLEDGE SERIES: HEAT PUMP DESIGN FOR 100% OUTSIDE AIR SYSTEMS THE SMART SOLUTION FOR ENERGY EFFICIENCY

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

2A.1 Features of Chiller Control Components A.3 Chilled-Water Supply Temperature Control A.4 Cooling-Water Supply Control...

5.2. Vaporizers - Types and Usage

HEATER, AIR CONDITIONING AND VENTILATION

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

جامعة البلقاء التطبيقية

How does solar air conditioning work?

A Design and Performance Test of the Visualization within a Capillary Pumped Loop (*).

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

Automobile Air Conditioning Primer

MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

TOPIC: KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?

Thermodynamics - Example Problems Problems and Solutions

Thermo Siphon Solar Systems

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Alcatel-Lucent Modular Cooling Solution

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

Open Cycle Refrigeration System

SOLVING REACTOR WATER CLEAN-UP SYSTEM ANOMALIES USING RELAP5 MOD3.3

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

HOW HVAC WORKS. How HVAC. Works PAGE 1

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

HVAC Processes. Lecture 7

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Soil Suction. Total Suction

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

HVAC Systems: Overview

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No , March-April 2015

How To Save Energy With High Pressure Control

GEOTHERMAL HEATING AND COOLING INTRODUCTION

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Improving Data Center Efficiency with Rack or Row Cooling Devices:

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Tankless Electric (RTE) Troubleshooting

Engineering Recommendation on: Accumulators Revised Issued January 10, 1979 Page 1 of 7

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

Transcription:

ICR07-B2-6 Controlling a CO 2 loop using a accumulator Bart VERLAAT National Institute for Nuclear Physics and High Energy Physics (NIKHEF) P.O. Box 42, 009 DB, Amsterdam, the Netherlands Email: bverlaat@nikhef.nl Telephone: + 20 92 209/ Fax: + 20 92 ABSTRACT Mechanically pumped fluid loops often have the problem of insufficient sub-cooling to operate the pumps without cavitation. This paper describes the use of accumulators for controlling CO 2 loops to obtain forced sub-cooling and accurate evaporator control. The technique of using accumulators for loop control was first applied in satellite cooling. Two accumulator controlled loops have been successfully developed at NIKHEF. One CO 2 loop for cooling the AMS particle detector which will study cosmic radiation onboard the International Space Station and a second CO 2 loop is developed for cooling the LHCb-VELO particle detector which will study CP-violation at the CERN laboratory in Geneva (Switzerland). A accumulator has the advantage of controlling the evaporator and condenser pressures independent of the primary cooler temperature. It is therefore possible to create as much sub-cooling for the pump as desired. It is even possible to operate the loop in single phase, a feature which turns out to be very convenient during start-up and cooling-down procedures. A accumulator for evaporator pressure control in combination with an internal heat exchanger between the liquid feed and the return line creates a very stable evaporator with a guaranteed evaporation at low vapor qualities. In this way the evaporator heat transfer can be tuned and evaporator dry-out is prevented.. INTRODUCTION The semiconductor silicon tracking detectors of the Alpha Magnetic Spectrometer (AMS) (Borgia, 200) on the International Space Station (ISS) and the LHCb-VErtex LOcator Experiment (VELO) (LHCb collaboration, 200) at the CERN s Large Hadron Collider (LHC) require accurate thermal control of the silicon sensors. The readout electronics of the sensors produce the heat which a cooling system should remove. Construction material used inside silicon detectors must be of low mass and tolerant to ionizing radiation. To suppress radiation damage of the silicon detectors, the silicon must be kept cold to sub-zero temperatures at all times (Rose collaboration, 999). A silicon tracking detector consists of multiple silicon sensors which are uniformly spread over the detector volume. All the silicon sensors need to have equal temperatures within or 2 degrees to avoid thermal stresses. The discussed requirements for a silicon detector cooling system such as: low mass, multiple heat sources, small temperature gradients and radiation resistance, give design constraints to the cooling system which are different from conventional cooling systems.

The requirements of the cooling system for the Figure.: The AMS experiment on the ISS LHCb VELO detector have led to the use of CO 2 as evaporative cooling fluid (Boer Rookhuizen et al. 999). CO 2 was selected as coolant because of the radiation hardness and the proper temperature range. Feasibility tests have shown excellent thermal performance of CO 2 in small diameter evaporators, which is a welcome feature for a cooling system were low mass is required. The development of CO 2 evaporative cooling at NIKHEF was simultaneous to the developments of CO 2 cooling in the commercial refrigeration industry. The AMS Silicon Tracker required a cooling system which can keep the evaporator section at a constant temperature. In space the background temperature is around 4 Kelvin, heat can be rejected to space from radiator panels. These radiators have a fluctuating temperature due to the changing exposure to the sun and earth. At NIKHEF a mechanically pumped CO 2 loop was developed for the cooling of the AMS Silicon Tracker. This cooling system is named AMS-Tracker Thermal Control System (AMS-TTCS), (Verlaat et al., 2002). The temperature in the evaporator is controlled by a accumulator control mechanism which is used in capillary pumped loop systems, which were under development for satellite cooling (TPX Space Shuttle experiment), (Delil, et al. 997). The accumulator keeps the pumped loop at a constant system pressure. The evaporator temperature is therefore fixed, as long as saturated liquid is flowing through it. The temperature variation in the sub-cooled liquid from the condenser is heated by the internal heat exchanger. In this way it is possible to keep the evaporator constant at a fluctuating heat sink, without additional heating or mechanical control. This is important in space, because power is limited and mechanical actuators have a too large risk of failure. The method of controlling a loop with a accumulator as it was done in the AMS-TTCS is well suited for the use in the cooling cycle of the LHCb-VELO detector. This cooling system is named VELO Thermal Control System (VTCS) (Verlaat, 200). The cold radiator of the AMS-TTCS is replaced by a conventional refrigeration system. This combination allows temperature control of the VELO detector at a large distance (~0m), without any control actuators in the radiation area, resulting in a complete passive evaporator system. This paper describes the design and testing of a accumulator controlled loop (2PACL) developed for the VELO Thermal Control System. Evaporator with 27 parallel connections Figure.2: The LHCb VErtex LOcator Beam-pipe 27 VELO modules

2. THE 2-PHASE ACCUMULATOR CONTROLLED LOOP FOR THE VTCS 2. PRINCIPLE OF A 2-PHASE ACCUMULATOR CONTROLLED LOOP (2PACL) 4 Heater Accumulator gas R404a chiller gas Condenser Transfer lines Cooling plant area (Ca. 0m) VELO area Inside VELO 0 Pump 2 2 liquid 4 6 Concentric tube Restriction Evaporator 9 7 liquid Figure 2.: Schematic of the VELO Thermal Control System Figure 2. shows the schematic diagram of the 2PACL as it is applied in the VELO. A mechanically pumped CO 2 loop is cooling the VELO detector by evaporating low quality CO 2 (9-0). The vapor is condensed by a chiller with R404a as refrigerant (-). The condensed liquid is pumped by a liquid pump back towards the detector (2--). The evaporator and condenser work at the same pressure, because the pressure drop of the vapor return line is low. The CO 2 pressure is controlled by the accumulator (4) which is parallel connected between the condenser and the pump (). The accumulator contains a saturated CO 2 liquid-vapor mixture. The temperature of the saturated mixture in the accumulator is regulated, controlling the accumulator pressure hence the condenser and evaporator pressure. The pressure regulation of the accumulator is a combination of heating and cooling. An electrical heater is evaporating liquid CO 2 causing the pressure to increase, an evaporator branch of the primary R404a chiller is condensing CO 2 vapor causing the pressure to decrease. 2x 0 4 Internal heat exchanger brings evaporator pre-expansion 0 4 per definition right above saturation (-)=-(0-) P [kpa] Accumulator pressure = detector temperature Pump is sub cooled Capillary expansion brings evaporator in saturation Te rtia ry VTCS in P-H dia gr am Saturation line 0 C 2 0 C -0 C 4-20 C 7 0 6 9-0 C 0-40 C Detector load (9-0) 0.2 0.4 0.6 x 0 2-40 -400-0 -00-20 -200-0 h [kj/kg] Figure 2.2: Operation of a 2PACL in the P-h diagram of CO 2 In order to ensure sub-cooling of the CO 2 before the liquid pump, the accumulator temperature must be above the condenser temperature. The sub-cooled state will prevent the pump from cavitation, a common problem in mechanically pumped loops. The sub-cooled liquid is however too cold to be injected into the evaporator, because evaporators require saturated liquid. To heat the liquid up to saturation, a heat exchanger between the liquid inlet (4-) and vapor outlet (-2) of the evaporator is used. The absorbed heat in the evaporator is used to heat the sub-cooled flow so no extra heat is needed. Figure 2.2 shows the schematic of figure

2. in the P-h diagram of CO 2. The indices of the diagram correspond to the nodes in figure 2.. The exchanged heat in the internal heat exchanger is the enthalpy difference of node and. As a minimum this heat must have been absorbed in the evaporator (9-0). If the evaporated heat is sufficient to overcome the sub-cooling, the evaporator inlet (Node 9) is and close to the saturated liquid curve, otherwise the inlet of evaporator remains sub-cooled causing degraded heat transfer. A 2PACL does only require a controlled accumulator. The 2PACL condenser temperature may vary, as long as the maximum temperature is lower than the accumulator set-point. The chiller may therefore run maximal cold, without any chiller evaporator regulation. The 2PACL pump flow may be constant as well; a sufficient overflow of the pump will make the system heat load independent and prevent the 2PACL against evaporator dry-out. A useful feature of the 2PACL is the ability of turning the loop into a single phase loop. Significantly increasing the accumulator s pressure will suppress any formation of vapor anywhere in the loop. This feature is very useful at start-up. It is used as start-up procedure in both the AMS-TTCS and the LHCb-VTCS systems. 2.2 VELO THERMAL CONTROL SYSTEM DESIGN. The cooling plant contains the chillers, the pumps, the accumulators and valves. The detector with evaporator is away from the cooling plant and situated in a hostile radiation environment which makes it inaccessible. The transfer of cooling fluid from the plant to the evaporator is via a concentric transfer tube. The liquid feed line is inside the vapor return line and bridges the 0 meter distance from the plant to the evaporator. The transfer tube is concentric so the environmental heat will only affect the return flow. The concentric tube is the necessary internal heat exchanger to overcome liquid sub-cooling. The silicon wafers in the detector need to be kept cold at all times. This is also required even if the detector is switched off. In paragraph 2. it was discussed that a heat load is needed in the evaporator to overcome the sub-cooling. If no sufficient heat load is available, sub-cooled liquid will enter the evaporator and the accumulator is no longer able to control the temperature of evaporator. The evaporator can become colder than the Figure 2.:VTCS CO 2 plant accumulator set-point leading to an uncontrolled and too cold detector. The transfer tube s isolation is tuned such that enough heat from the environment is entering the loop at all time to overcome the sub-cooling, the evaporator does not need a heat load in this case. The concept of environmental heat leak is chosen over electrical heating, because of reliability issues. Figure 2.4: VTCS Evaporator Assembly The evaporator has flow restrictions to distribute the flow evenly over the 27 parallel cooling connections. At start-up these restrictions can cause large pressure drops in the system when vapor has to pass through. At start-up it is also not guaranteed that the pumps are primed with liquid. The pumps are not self priming and they will not start up if there is no

liquid inside. A nice feature of the accumulator control is that the loop can be turned into a single phase liquid loop by heating-up the accumulator. The VTCS-accumulator will be heated to 27ºC prior to start-up. The pressure in the loop is above the saturation pressure of the environment, causing the CO 2 in the loop to be liquefied. The pump can now start-up without problems and the restrictors are fed with liquid, keeping the pump head pressure low. 2. VTCS SIMULATION RESULTS. A simulation model of the VTCS loop has been made to study the thermal equilibriums of the different operational states in transient modes. Figure 2. shows the simulation results of several situations from start-up to cold operation. The model calculates the energy and pressure balance of the nodes of figure 2.. Environmental heat leak is included and calculated between each node. Prior to start-up, the whole loop is at room temperature. It is not defined where the liquid or vapor is situated. The start-up situation (A) in the P-h diagram is somewhere along the 20ºC isotherm in the region. At start up the accumulator is heated to 27ºC and the system pressure increases to the corresponding saturation pressure of 67 bar. The loop is still at room temperature and will be filled with liquid. Once the loop is filled, the pump can be switched on. Sub-cooled liquid of 20ºC is now circulated and cooling from the primary R404a chiller is not yet needed. The loop operates as situation B in the P-h diagram. Once liquid circulation is achieved the primary chiller can be switched on. The accumulator is kept at high pressure so all the liquid will stay sub-cooled. In paragraph 2. it was discussed that the primary R404a chiller does not need any temperature regulation, therefore it will cool the liquid flow to its minimum temperature. After cooling down in liquid mode the situation of C has been reached. The pump flow will be about -40ºC, the evaporator (with liquid only!) is about -22ºC. The thermal gradient is due to the heat leak of the transfer tube. After having cooled down the loop in liquid mode, the accumulator can be cooled down by the primary chiller to the desired set-point of -0ºC. The system is now at situation D, which is indicated by the small squares in figure 2.. The unloaded evaporator (node 9-0) is now in the region, so its temperature is now controlled by the accumulator. P [bar] 2 x0 2 0 2 0 C 9,0, D E 9 0 9,0 VTCS start -up and operating cycles 40 C 20 C 0.2 0.4 0.6 0. x0 0 0 00 0 200 20 00 0 400 h [kj/kg] Figure 2.: Simulation results of the VTCS model in the P-h diagram, B 0, A 0 C -20 C -40 C Once the situation of D is stabilized, the detector power is switched on. In the diagram this means that node 0 is moved away from node 9, ending up in situation E. The circuit of E also shows a change of the sub-cooled temperature of node with respect to situation D. This increase is due to the behavior of the primary R404a chiller. An increased heat load causes the compressor suction pressure to increase, and hence the primary evaporator pressure and temperature. The simulation clearly shows the independence of a varying sub-cooling. As long as node is on the left of the saturation line, the system works properly. The inlet of the evaporator (node 9) is controlled to stay and near the saturation line, assuring the evaporator being fed with a low quality flow.

2.4 VTCS ACCUMULATOR DESIGN The accumulator must be partially filled with liquid at all operational situations. Figure 2.6 show the simulation results of different liquid fillings in the accumulator as a function of accumulator volume for several fill ratios of the accumulator and loop together. It shows that the 2 extreme accumulator liquid levels appear at the single phase cold (C) for the minimum level and the loaded evaporator (E) for the maximum level (C and E are the situations of figure 2.). The chosen VTCS design parameters are indicated in the 2 nd graph by a vertical dashed line; for a VTCS loop volume of. liter a fill ratio of 7 gram per liter with an accumulator volume of.6 liter are sufficient to comply with all the operational scenarios. Liquid level (%). Liquid level (%). Loop fill ratio: 00 gram/liter 00% 90% 0% 70% 60% 0% 40% 0% 20% 0% 0%.0 0.0 2.0 4.0 6.0.0 20.0 22.0 24.0 Accumulator Volume (L) Loop fill ratio: 60 gram/liter 00% 90% 0% 70% 60% 0% 40% 0% 20% 0% 0%.0 0.0 2.0 4.0 6.0.0 20.0 22.0 24.0 Accumulator Volume (L) Liquid level (%). Liquid level (%). Loop fill ratio: 7 gram/liter 00% 90% VTCS Design 0% 70% 60% 0% 40% 0% 20% 0% 0%.0 0.0 2.0 4.0 6.0.0 20.0 22.0 24.0 Accumulator Volume (L) Loop fill ratio: 72 gram/liter 00% 90% 0% 70% 60% 0% 40% 0% 20% 0% 0%.0 0.0 2.0 4.0 6.0.0 20.0 22.0 24.0 Accumulator Volume (L) Figure 2.6: Accumulator liquid levels as a function of accumulator volume and fill ratios for a loop volume of. liter. Figure 2.7: Accumulators in the VTCS plant Figure 2.: Thermo siphon heater Figure 2.9: Accumulator cooling coils

Figure 2.0 shows the mechanical design of the VTCS accumulator. The heater must be submerged in the liquid to avoid partial dry-out. In practice this means that the heater needs to stay below the minimum level of situation C at the design parameter line of figure 2.6. The capacity of the heater is driven by the required speed of pressurizing. A rod element heater of kw was chosen. The heater is at the bottom of the accumulator in a concentric thermo-siphon lay-out. The evaporated CO 2 on the heater surface is going up, sucking new liquid via the outer annulus to the heater. Care must be taken at heating near the critical point of CO 2. The difference in the density of liquid and vapor becomes small, decreasing the liquid flow. The decreased liquid flow causes a dry-out with high heater temperatures as a result. Figure 2.0: VTCS Accumulator mechanical design A lowering of the system pressure is achieved by condensing the vapor content in the accumulator. In the VTCS accumulator this is achieved with a coiled tube inside the accumulator volume (figure 2.9). The coil is cooled with R404a by the primary chiller. This coil is situated at the upper part of the accumulator. A large part of the coil needs to be above the maximum level of situation E at the design parameter line of figure 2.6. A submerged part of the spiral is no problem, it only decreases the condensation surface and hence the cooling down speed. At the VTCS the liquid level is monitored using a dielectric probe. 2. VTCS TEST RESULTS. Figure 2. shows some test results of the VTCS test system. The loop was started up from stand still to cold operation. Time A was the start-up time. The loop was still cold from earlier tests. The saturation temperature of the loop was 0ºC, while the pump was at room temperature. The pump was filled with vapor only and could not start-up. The accumulator was heated to pressurize the system such that the saturation temperature of the system became above room temperature. At time B the accumulator heater was reduced to avoid heater dry-out; pressurization is now going slower. At time C the system was sufficiently filled with Temperature (ºC), Pump flow (g/s). 60 0 40 0 20 0 0 6:2:6 6:0:24 7:9:2 7:4:00 :6:4 :4:6 9:4:24-0 A B C -20-0 -40 Figure 2.: VTCS Test results Pump liquid (ºC) Evaporator Saturation Temperature (ºC) Evaporator Temperature (ºC) Massflow (g/s) Accu Pressure (Bar) Evaporator Pressure (Bar) F G H D E Time (hh:mm:ss) 70 60 0 40 0 20 0 Pressure (Bar) 0-0 -20-0

liquid so the pump could start-up. The pump was rapidly cooling down while the evaporator temperature was staying behind. The accumulator was maintained on pressure making the system cooling down in sub-cooled liquid state. At time D the accumulator cooling started at a set-point of -2ºC. At time E, the evaporator was no longer sub-cooled; the accumulator had taken over control of the evaporator s temperature. At time F, the evaporator had reached the set-point temperature of -2ºC and the detector power was switched on. At time G the accumulator set-point was lowered to -0ºC, reaching the -0ºC evaporator temperature at time H. This was the minimum reachable evaporator temperature with the VTCS test system, because the pump sub-cooling had become marginal. Note that the accumulator and evaporator pressures were the same during the entire test.. CONCLUSION AND DISCUSSION The accumulator controlled loop (2PACL) method is a good solution for controlling mechanically pumped loops. It can operate at a large dynamic evaporator pressure range and is virtually independent of heat load and condenser temperature. The accumulator pressure is the only accurate controlled parameter in the system. This makes the system robust, stable and easy to operate. The 2PACL method is a good alternative for controlling the current secondary pumped loops. The accumulator method can also be used for loop systems which do not need controlled evaporators but only need to transfer heat from A to B. One can think of an accumulator maintaining a slight over-pressure with respect to the pump sub-cooling, just enough to avoid pump cavitation. Different types of accumulators can be considered, such as a spring acted bellow accumulator with secondary loading at the loop temperature, or an accumulator with a secondary fluid mixture having slight over pressure properties to the loops working fluid. An active pneumatic controlled accumulator is also an option. The LHCb-VTCS and the AMS-TTCS both use CO 2 as working fluid, but the principle is expected to work for any fluid pumped systems. 4. REFERENCES. B.Borgia, 200, The Alpha Magnetic Spectrometer on the International Space Station, IEEE Transactions on Nuclear Science, Vol. 2, No. 6, p. 276-2792 2. The LHCb Collaboration, 200, The LHCb VELO Technical Design Report, CERN/LHCC note, 200-00. The ROSE Collaboration, 999, R&D On Silicon for future Experiments, CERN/LHCC note, 2000-009 4. Boer Rookhuizen H. et al, 999, Preliminary Studies for the LHCb Vertex Detector Cooling System, LHCb note, 99-046/VELO. Verlaat, B., Krijger, E., 200, Performance Testing of the AMS TTCS CO 2 Evaporator., NIKHEF note, ASR-T- 00/MT 0-02. 6. Verlaat, B. et al. 2002, Feasibility Demonstration of a Mechanically Pumped Two-Phase CO 2 Cooling Loop for the AMS-2 Tracker Experiment, Conference on Thermophysics in Microgravity, in the Space Technology & Applications International Forum (STAIF-2002), Albuquerque, NM, USA 7. Delil, A.A.M. et al., 997, In-orbit demonstration of two-phase heat transport technology - TPX II reflight, European Space Agency, SP-400, p.. Verlaat, B., Woering, A., Pauw, A., Delil, A.A.M., 200, AMS-2 Tracker Thermal Control System: design and thermal modeling of the mechanically pumped two-phase CO 2 loop, AIAA Aerospace Sciences Meeting & Exhibit, Reno, NV, USA, (AIAA-200-04) 9. Verlaat, B., 200, Thermal Performance Testing of the VTCS Evaporator and VELO Module, NIKHEF note, MT 0-0.